Technibel KPAFP125R5I, KPAFP185R5I, KPAFP165R5I Technical Data & Service Manual

Page 1
TECHNICAL DATA & SERVICE MANUAL
SPLIT SYSTEM AIR CONDITIONER
KPAFP165R5I 38.7105.958
0.8180.451.1 09/2006
KPAFP185R5I
Model No. Product Code No.
KPAFP125R5I 38.7105.956
Page 2
IMPORTANT! Please read before installation
This air conditioning system meets strict safety and operating standards. For the installer or service person, it is important to install or service the system so that it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
• Carefully read this instruction booklet before beginning.
• Follow each installation or repair step exactly as shown.
• Observe all local, state and national electrical codes.
• Pay close attention to all warning and caution notices given in this manual.
•The unit must be supplied with a dedicated electrical line.
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.
If necessary, get help
These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sale/service outlet or your certified dealer for additional instructions.
In case of improper installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
• During installation, connect before the refrigerant system and then the wiring one; proceed in the reverse orden when removing the units.
When wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY QUALIFIED, EXPERIENCED ELECTRICIANS SHOULD ATTEMPT TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked, to ensure the grounding.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury and death.
Ground the unit following local electrical codes.
• The Yellow/Green wire cannot be used for any connection different from the ground connection.
• Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.
• Do not allow wiring to touch the refrigerant tubing, compressor, or any moving parts of the fan.
• Do not use multi-core cable when wiring the power supply and control lines. Use separate cables for each type of line.
When transporting
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminium fins on the air conditioner can cut your fingers.
When installing...
• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them; screw by hand and then tighten the nut with a torque wrench for a leak-free connection.
• Check carefully for leaks before starting the test run.
NOTE:
Depending on the system type, liquid and gas lines may be either narrow or wide. Therefore, to avoid confusion, the refrigerant tubing for your particular model is specified as narrow tube for liquid, wide tube for gas.
When servicing
• Turn the power OFF at the main power board before opening the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after the work, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.
• Ventilate the room during the installation or test
ing the refrigeration system; make sure that, after the installation, no gas leaks are present, because this could produce toxic gas and dangerous if in contact with flames or heat-sources.
WARNING
CAUTION
WARNING
… In a ceiling
Make sure the ceiling is strong enough to hold the unit-weight. It may be necessary to build a strong wooden or metal frame to provide added support.
… In a room
Properly insulate any tubing run inside a room to prevent "sweating", which can cause dripping and water damage to walls and floors.
... In moist or uneven locations
Use a raised concrete base to provide a solid level foundation for the outdoor unit. This prevents damage and abnormal vibrations.
... In area with strong winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
... In a snowy area (for heat pump-type systems)
Install the outdoor unit on a raised platform that is higher then drifting snow. Provide snow vents.
When connecting refrigerant tubing
2
Page 3
Page
1. SPECIFICATIONS
4
1-1 Unit specifications 4 1-2 Major Component specifications 6 1-3 Other Component specifications 8
2. DIMENSIONAL DATA
9
3. ELECTRICAL DATA
10
3-1 Electric Wiring Diagram 10 3-2 Control PCB switches and functions 11
4. PROCESS AND FUNCTIONS
12
4-1 Control function 12
5. REPLACING PCB
15
5-1 Replacing PCB 15 5-2 How to replace PCB 16 5-3 How to replace EEPROM with EEPROM included in PCB service pack 17 5-4 Table of setting 19
6. SERVICE PROCEDURE
20
6-1 Meaning of alarm message 20 6-2 Led indicator messages on outdoor control PCB 21 6-3 Symptoms and parts to inspect 22 6-4 Details of alarm messages 23 6-5 Table of thermistor characteristics 26
7. OUTDOOR UNIT MAINTENANCE REMOTE CONTROL
27
7-1 Overwiew
27
7-2 Functions
27
7-3 Normal display operations and functions
28
7-4 Monitoring operations:
Display of indoor unit and outdoor unit sensor temperatures
31
7-5 Monitoring the outdoor unit alarm history:
Display of outdoor unit alarm history 32
7-6 Setting modes: setting of outdoor unit EEPROM
32
Table of Contents
3
Page 4
1. SPECIFICATIONS
1-1 Unit Specifications
KPAFP125R5I
Power source
V
oltage ratin
g
Performance
Capacity Air circulation (High/Med./Low) m³/h
Features
Controls/Temperature controls Remote Controller (Option) wired
wireless Fan speed Airflow direction Air Filter Sound pressure level high/med/low dB(A) Refrigerant tubing connections Refrigerant Narrow tube mm(in.) tube diameter Wide tube mm(in.) Refrigerant Refrigerant control
Dimensions & Wei
g
ht
Dimensions Unit Height mm
Width mm Depth mm
Package dimensions Unit Height mm
Width mm Depth mm Volume m3
Weight Net kg
Shipping kg
DATA SUBJECT TO CHANGE WITHOUT NOTICE
680
Auto (Remote control)
Electronic expansion valve
Washable
55/51/46
Flare type
6,35 (1/4) 12,7 (1/2)
R410A
220 - 240V ~ 50Hz
230V
Cooling Heating
See catalogue with the requested matching
Microprocessor/ I.C. thermostat
3 and Auto
K70D036Z / K70D042Z K70D038Z / K70D040Z
296
23,5 31,5
900
0,24
813
1011
190
4
Page 5
KPAFP165/185R5I
Power source
V
oltage ratin
g
Performance
Capacity Air circulation (High/Med./Low) m³/h
Features
Controls/Temperature controls Remote Controller (Option) wired
wireless Fan speed Airflow direction Air Filter Sound pressure level high/med/low dB(A) Refrigerant tubing connections Refrigerant Narrow tube mm(in.) tube diameter Wide tube mm(in.) Refrigerant Refrigerant control
Dimensions & Wei
g
ht
Dimensions Unit Height mm
Width mm Depth mm
Package dimensions Unit Height mm
Width mm Depth mm Volume m3
Weight Net kg
Shipping kg
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Electronic expansion valve
Flare type
31,5
813 296
1011
0,24 23,5
190
220 - 240V ~ 50Hz
230V
Cooling Heating
See catalogue with the requested matching
Microprocessor/ I.C. thermostat
K70D038Z / K70D040Z
900
680
K70D036Z / K70D042Z
Washable
6,35 (1/4)
R410A
12,7 (1/2)
3 and Auto
Auto (Remote control)
60/57/54
5
Page 6
1-2 Major Component Specifications
KPAFP125R5I
Controller PCB
Part No. Controls
Fan & Fan Motor
Type Q'ty ……. Dia. and lenght mm Fan motor model…Q'ty No. Of poles…rpm (230 V, High) Running Amps A Power input W Coil resistance (Ambient temp. 25 °C )
GRY-WHT: 194 ÷ 223
WHT-PNK: 238 ÷ 274
WHT-VLT: 80,1 ÷ 92,2 VLT-ORG: 80,1 ÷ 92,2 ORG-YEL: 200 ÷ 230
Safety devices Type
Operating temp. Open °C
Close °C
Run capacitor µF
VAC
Flap motor
Model Rating Rpm Nominal output W Coil resistance (25°C)
k
Heat Exch. Coil
Coil Rows Fin pitch mm face area m2
DATA SUBJECT TO CHANGE WITHOUT NOTICE
450
1,5
Internal thermal protector
145 ± 5K
Automatic reclosing
Microprocessor
CR-CRP50A-B
2…. Ø 130 L 180
0,29
65
Centrifugal fan
K48407-MO1596 …1
4… 1160
M2LB24ZA12
15,62 ± 15%
2,5
0,167
Aluminium plate fin / Copper tube
3
1,8
2
240 VAC
6
Page 7
KPAFP165/185R5I
Controller PCB
Part No. Controls
Fan & Fan Motor
Type Q'ty ……. Dia. and lenght mm Fan motor model…Q'ty No. Of poles…rpm (230 V, High) Running Amps A Power input W Coil resistance (Ambient temp. 25 °C )
GRY-WHT: 124 ÷ 144
WHT-PNK: 255 ÷ 294
WHT-VLT: 69,3 ÷ 79,8 VLT-ORG: 69,3 ÷ 79,8 ORG-YEL: 200 ÷ 233
Safety devices Type
Operating temp. Open °C
Close °C
Run capacitor µF
VAC
Flap motor
Model Rating Rpm Nominal output W Coil resistance (25°C)
k
Heat Exch. Coil
Coil Rows Fin pitch mm face area m2
DATA SUBJECT TO CHANGE WITHOUT NOTICE
0,167
1,6
3
Aluminium plate fin / Copper tube
Automatic reclosing
2,5
3
M2LB24ZA12
240 VAC
2
440
CR-CRP50A-B
Centrifugal fan
15,62 ± 15%
Microprocessor
2…. Ø 130 L 180
K48410-MO1598 …1
4… 1160
0,41
88
Internal thermal protector
145 ± 5K
7
Page 8
1-3 Other Component Specifications
Trasformer
Rating Primary
Secondary 1 Secondary 2 Secondary 3
Thermal cut-off temp.
Thermistor
(
Coil sensor E1, E2
)
Resistance
k
Thermistor
(
Room sensor TA
)
Resistance
k
ATR-IIJ225A
VAC 230V, 50Hz
AC 20V - 0.2A AC 14V - 0.3A
PBC-41E-S26
AC 10,2V - 1.4A
136°C
0 °C 15,0 ± 5%
25 °C 5,0 ± 4%
DHKTEC-35-S85N
8
Page 9
2. DIMENSIONAL DATA
Units: mm
9
Page 10
3. ELECTRICAL DATA
3-1 Electric Wiring Diagram
7P terminal board
1(L) 2(N) U1 U2 R1 R2
w
iri
ng
remote
con
troller
power
supp
ly
inter-unit
con
trol
10
Page 11
3-2 Control PCB switches and functions
CR-TRP50A-B OC (CN040)
EMG (CN044)
VARISTOR (VA041)
JP1 DISP (CN072)
EXCT (CN073) FILTER (JP001)
(CN070) CHK (CN071)
FAN DRIVE GRL
(CN032) (CN020) T10 (CN061)
POWER LED
(D002) EEPROM
(IC010)
T10: 6 plug (yellow): used for remote control. (Refer to the remote control section) (CN061) 1- start/stop input 2- COM
3- remote control prohibit/release input 4- start signal output 5- COM (+DC12v) 6- alarm signal output T10
EXCT: 2P plug (red): Can be used for demand control. When imput is present, forces the unit to operate
(CN073) with the termostat OFF.
DISP: 2P plug (white): Short-circuiting this plug allows the unit to be operated by the remote controller, even if it is not (CN072) connected to an outdoor unit. (In this case, alarm "E04", which indicates trouble in the serial communication
between the indoor and outdoor unit, does not occur.)
CHK: 2P plug (white): Test pin. Short-circuiting this pin allows the indoor FM (H fan speed), drain pump, (CN071) flap motor (F1 position), and electronic expansion valve full-open position to checked. However this function
turns OFF if the indoor unit protection mechanism is activated. The unit can be operated even if the remote controller and outdoor unit are not connected. However even if the remote controller cannot is connected, it cannot be used to operate the unit. This function can be used for short-term tests.
JP1: Jumper wire: Allows selection of the T10 terminal (JP001)
11
Page 12
4. PROCESS AND FUNCTIONS
4-1 control functions
12
Page 13
13
Page 14
14
Page 15
5. REPLACING PCB
5-1 Replacing PCB
About EEPROM
(Erasable Programmable Read-Only Memory) EEPROM is a component in which the various information necessary for functionning can be electronically written or erased. This component holds informations that is essential for the running of the unit, and must be handled with care.
D002
led lamp (red)
15
Page 16
5-2 How to replace PCB
16
Page 17
5-3 How to replace EEPROM with EEPROM included in PCB service pack
17
Page 18
18
Page 19
5-4 Table of settings
19
Page 20
6. SERVICE PROCEDURE
6-1 Meaning of alarm message
20
Page 21
6-2 Led indicator messages on outdoor control PCB
21
Page 22
6-3 Symtoms and parts to inspect
22
Page 23
6-4 Details of alarm messages
resistance
23
Page 24
24
Page 25
25
Page 26
26
Page 27
7. OUTDOOR UNIT MAINTENANCE REMOTE CONTROL
27
Page 28
28
Page 29
29
Page 30
30
Page 31
31
Page 32
32
Page 33
33
Page 34
34
Page 35