Technibel KAF97R5IAA, KAF98MR5IAA, KPAF127R5IAA, KPAF128MR5IAA, KPAF187R5IAA Technical Data & Service Manual

...
TECHNICAL DATA & SERVICE MANUAL
INDOOR UNIT:
KAF97R5IAA KAF98MR5IAA KPAF127R5IA
A
A
KPAF187R5IA
A
KPAF247R5IA
A
KAF97R5IA
A
KAF98MR5IA
A
KPAF127/187/247R5IA
A
KPAF128MR5IA
A
0.8180.532.1 06/2008
KPAF128MR5IAA
KPAF127R5IAA
38.7105.973
38.7105.974
38.7105.978
38.7105.976
38.7105.977
KPAF187R5IAA 38.7105.975 KPAF247R5IAA
KAF98MR5IAA
SPLIT SYSTEM AIR CONDITIONER
Model No. Product Code No.
KAF97R5IAA
IMPORTANT! Please read before installation
This air conditioning system meets strict safety and operating standards. For the installer or service person, it is important to install or service the system so that it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
• Carefully read this instruction booklet before beginning.
• Follow each installation or repair step exactly as shown.
• Observe all local, state and national electrical codes.
• Pay close attention to all warning and caution notices given in this manual.
•The unit must be supplied with a dedicated electrical line.
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.
If necessary, get help
These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sale/service outlet or your certified dealer for additional instructions.
In case of improper installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
• During installation, connect before the refrigerant system and then the wiring one; proceed in the reverse orden when removing the units.
When wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY QUALIFIED, EXPERIENCED ELECTRICIANS SHOULD ATTEMPT TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked, to ensure the grounding.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury and death.
Ground the unit following local electrical codes.
• The Yellow/Green wire cannot be used for any connection different from the ground connection.
• Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.
• Do not allow wiring to touch the refrigerant tubing, compressor, or any moving parts of the fan.
• Do not use multi-core cable when wiring the power supply and control lines. Use separate cables for each type of line.
When transporting
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminium fins on the air conditioner can cut your fingers.
When installing...
• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them; screw by hand and then tighten the nut with a torque wrench for a leak-free connection.
• Check carefully for leaks before starting the test run.
NOTE:
Depending on the system type, liquid and gas lines may be either narrow or wide. Therefore, to avoid confusion, the refrigerant tubing for your particular model is specified as narrow tube for liquid, wide tube for gas.
When servicing
• Turn the power OFF at the main power board before opening the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after the work, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.
• Ventilate the room during the installation or test
ing the refrigeration system; make sure that, after the installation, no gas leaks are present, because this could produce toxic gas and dangerous if in contact with flames or heat-sources.
WARNING
CAUTION
WARNING
… In a ceiling
Make sure the ceiling is strong enough to hold the unit-weight. It may be necessary to build a strong wooden or metal frame to provide added support.
… In a room
Properly insulate any tubing run inside a room to prevent "sweating", which can cause dripping and water damage to walls and floors.
... In moist or uneven locations
Use a raised concrete base to provide a solid level foundation for the outdoor unit. This prevents damage and abnormal vibrations.
... In area with strong winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
... In a snowy area (for heat pump-type systems)
Install the outdoor unit on a raised platform that is higher then drifting snow. Provide snow vents.
When connecting refrigerant tubing
2
Page
1. SPECIFICATIONS
4
1-1 Unit specifications 4-5 1-2 Major Component specifications 6-7 1-3 Other Component specifications 8
2. DIMENSIONAL DATA
9
3. ELECTRICAL DATA
10
3-1 Electric Wiring Diagrams 10
4. FUNCTION
11
4-1 Operation Functions 11-12 4-2 Protective Functions 13-14
5. TEST RUN
15
5-1 How to Test Run the Air Conditioner 15
6. TROUBLESHOOTING
16
6-1 Precaution before Performing Inspection or Repair 16 6-2 Method of Self-Diagnostics 16-17 6-3 Checking the Indoor and Outdoor Units 18 6-4 Noise Malfunction and Electromagnetic Interference 19
7. CHECKING ELECTRICAL COMPONENTS
20
7-1 Measurement of Insulation Resistance 20 7-2 Checking Continuity of Fuse on PCB Ass'
y
21
7-3 Checking Motor Capacitor 21
Table of Contents
3
1. SPECIFICATIONS
1-1 Unit Specifications
KAF97R5IAA - KAF98MR5IAA
Power source
V
oltage ratin
g
Performance
Capacity
A
ir circulation High/Med./Lo
w
m³/h
Features
Controls/Temperature controls Control unit Timer Fan speed Airflow direction Vertical
orizzontal Air Filter Power noise level
High/Med./Low
dB-A Refrigerant tubing connections Refrigerant Narrow tube mm(in.) tube diameter Wide tube mm(in.) Refrigerant Refrigerant tube kit / Air clean filter
Dimensions & Wei
g
ht
Unit dimensions Height mm
Width mm Depth mm
Package dimensions Height mm
Width mm Depth mm
Weight Net kg
Shipping kg
Shipping volume
m
3
0,13
620 265
18 20
700 560 200 770
9,52 (3/8)
Optional / --------------
Microprocessor/ I.C. thermostat
Wireless remote control unit
3 and Auto /1(Hi)
ON/OFF 24 hours & Daily program, 1-hour OFF
R410A
Flare type
Washable, Anti-Mold
51/48/42
220 - 240 V ~ 50 Hz
230 V
6,35 (1/4)
manual manual
See catalogue with the requested matching
425/390/320
4
KPAF127R5IAA - KPAF128MR5IAA
Power source
V
oltage ratin
g
Performance
Capacity Air circulation
High/Med./Low
m³/h
Features
Controls/Temperature controls Control unit Timer Fan speed Airflow direction Vertical
Orizzontal Air Filter Power noise level High/Med./Low dB-A Refrigerant tubing connections Refrigerant Narrow tube mm(in.) tube diameter Wide tube mm(in.) Refrigerant Refrigerant tube kit / Air clean filter
Dimensions & Wei
g
ht
Unit dimensions Height mm
Width mm Depth mm
Package dimensions Height mm
Width mm Depth mm
Weight Net kg
Shipping kg
Shipping volume
m
3
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Flare type
1011
296
23,5
R410A
Optional / --------------
680 900
31,5 0,24
220 - 240 V ~ 50 Hz
230 V
See catalogue with the requested matching
Microprocessor/ I.C. thermostat
190 813
700/590/500
6,35 (1/4) 9,52 (3/8)
ON/OFF 24 hours & Daily program, 1-hour OFF
3 and Auto /1(Hi)
Auto
Washable, Anti-Mold
55/51/46
Manual
Wireless remote control unit
5
KPAF187R5IAA
Power source
V
oltage ratin
g
Performance
Capacity Air circulation
High/Med./Low
m³/h
Features
Controls/Temperature controls Control unit Timer Fan speed Airflow direction Vertical
Orizzontal Air Filter Power noise level High/Med./Low dB-A Refrigerant tubing connections Refrigerant Narrow tube mm(in.) tube diameter Wide tube mm(in.) Refrigerant Refrigerant tube kit / Air clean filter
Dimensions & Wei
g
ht
Unit dimensions Height mm
Width mm Depth mm
Package dimensions Height mm
Width mm Depth mm
Weight Net kg
Shipping kg
Shipping volume
m
3
DATA SUBJECT TO CHANGE WITHOUT NOTICE
720/615/515
6,35 (1/4) 12,7 (1/2)
ON/OFF 24 hours & Daily program, 1-hour OFF
3 and Auto /1(Hi)
Auto
Washable, Anti-Mold
56/52/47
Manual
Wireless remote control unit
31,5 0,24
220 - 240 V ~ 50 Hz
230 V
See catalogue with the requested matching
Microprocessor/ I.C. thermostat
190 813
Flare type
1011
296
23,5
R410A
Optional / --------------
680 900
6
KPAF247R5IAA
Power source
V
oltage ratin
g
Performance
Capacity Air circulation
High/Med./Low
m³/h
Features
Controls/Temperature controls Control unit Timer Fan speed Airflow direction Vertical
Orizzontal Air Filter Power noise level High/Med./Low dB-A Refrigerant tubing connections Refrigerant Narrow tube mm(in.) tube diameter Wide tube mm(in.) Refrigerant Refrigerant tube kit / Air clean filter
Dimensions & Wei
g
ht
Unit dimensions Height mm
Width mm Depth mm
Package dimensions Height mm
Width mm Depth mm
Weight Net kg
Shipping kg
Shipping volume
m
3
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Flare type
1011
296
23,5
R410A
Optional / --------------
680 900
31,5 0,24
220 - 240 V ~ 50 Hz
230 V
See catalogue with the requested matching
Microprocessor/ I.C. thermostat
190 813
900/800/650
6,35 (1/4)
15,88 (5/8)
ON/OFF 24 hours & Daily program, 1-hour OFF
3 and Auto /1(Hi)
Auto
Washable, Anti-Mold
58/55/52
Manual
Wireless remote control unit
7
1-2 Major Component Specifications
KAF97R5IAA - KAF98MR5IAA
Controller PCB
Part No.
KAF97R5I
KAF98MR5I
Controls Control circuit fuse
Remote Control Unit KAF97R5I
KAF98MR5I
Fan & Fan Motor
Type Q'ty ……. Dia. and lenght mm Fan motor model…Q'ty No. of poles…rpm (230 V, Hi / Me / Lo) Running Amps A Power input W Coil resistance (Ambient temp. 20 °C )
Safety devices Type
Operating temp. Open °C
Close
Run capacitor µF
VAC
Heat Exch. Coil
Coil Rows Fin pitch mm face area m2
DATA SUBJECT TO CHANGE WITHOUT NOTICE
0,12
WHT-VLT: 92÷105
Microprocessor
250 V - 3,15 A
1…. Ø 100 / L 410
26
GRY-WHT: 545÷630
Cross - flow
K35406 M01892 …1
CB-FMRV94EH
RCS-4HVPN4EX
RCS-4MHVPNW4EX
RCS-4MHVPN4EX
0,185
CB-FRV93EH
4… 1280 / 1180 / 950
Aluminium plate fin / Copper tube
1
1,4
440
VLT-YEL: 62÷71
GRY-BRN: 78÷90
1,5
Internal thermal protector
150 ± 10
Automatic
8
KPAF127R5IAA - KPAF128MR5IAA
Controller PCB
Part No.
KPAF127R5I
KPAF128MR5I
Controls Control circuit fuse
Remote Control Unit KPAF127R5I
KPAF128MR5I
Fan & Fan Motor
Type Q'ty ……. Dia. and lenght mm Fan motor model…Q'ty No. of poles…rpm (230 V, High / 2nd / 3rd / Low) Running Amps A Power input W Coil resistance (Ambient temp. 20 °C )
Safety devices Type
Operating temp. Open °C
Close
Run capacitor µF
VAC
Flap Motor
Type Model Rating Coil resistance (Ambient temp. 25 °C )
Heat Exch. Coil
Coil Rows Fin pitch mm face area m2
DATA SUBJECT TO CHANGE WITHOUT NOTICE
RCS-4HVPN4EX
RCS-4MHVPNW4EX
RCS-4MHVPN4EX
Aluminium plate fin / Copper tube
2
440
Automatic
WHT-VLT: 93,5÷108
2
1,8
0,192
Stepping motor
MP24GA2
400±7%
DC 12 V
VLT-ORG: 93,5÷108
ORG-YEL: 211÷243
0,29
WHT-PNK: 421÷485
Internal thermal protector
145 ± 5
CB-FTRV123EH
Microprocessor
CB-FTMRV124EH
65
GRY-WHT: 298÷343
250 V - 3,15 A
4… 1160 / 970 / 810 / 580
Cross - flow
2…. Ø 130 / L 180
K48407 M01596 …1
9
KPAF187R5IAA
Controller PCB
Part No. Controls Control circuit fuse
Remote Control Unit
Fan & Fan Motor
Type Q'ty ……. Dia. and lenght mm Fan motor model…Q'ty No. of poles…rpm (230 V, High / 2nd / 3rd / Low) Running Amps A Power input W Coil resistance (Ambient temp. 20 °C )
Safety devices Type
Operating temp. Open °C
Close
Run capacitor µF
VAC
Flap Motor
Type Model Rating Coil resistance (Ambient temp. 25 °C )
Heat Exch. Coil
Coil Rows Fin pitch mm face area m2
DATA SUBJECT TO CHANGE WITHOUT NOTICE
RCS-4MHVPNW4EX
72
GRY-WHT: 194÷223
250 V - 3,15 A
Cross - flow
2…. Ø 130 / L 180
K48410 M01597 …1
4… 1280 / 1095 / 920 / 590
0,34
CB-FTRV184EH
Microprocessor
WHT-PNK: 238÷274
Internal thermal protector
145 ± 5
Automatic
WHT-VLT: 80,1÷92,2
VLT-ORG: 80,1÷92,2
ORG-YEL: 200÷230
2
440
Stepping motor
MP24GA2
400±7%
DC 12 V
Aluminium plate fin / Copper tube
2
1,8
0,192
10
KPAF247R5IAA
Controller PCB
Part No. Controls Control circuit fuse
Remote Control Unit
Fan & Fan Motor
Type Q'ty ……. Dia. and lenght mm Fan motor model…Q'ty No. of poles…rpm (230 V, High / 2nd / 3rd / Low) Running Amps A Power input W Coil resistance (Ambient temp. 20 °C )
Safety devices Type
Operating temp. Open °C
Close
Run capacitor µF
VAC
Flap Motor
Type Model Rating Coil resistance (Ambient temp. 25 °C )
Heat Exch. Coil
Coil Rows Fin pitch mm face area m2
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Aluminium plate fin / Copper tube
3
0,6
0,155
Stepping motor
MP24GA2
400±7%
DC 12 V
2
440
WHT-PNK: 255÷294
Internal thermal protector
145 ± 5
Automatic
WHT-VLT: 69,3÷79,8
VLT-ORG: 69,3÷79,8
ORG-YEL: 200÷233
CB-FTRV244EH
Microprocessor
RCS-4MHVPNW4EX
74
GRY-WHT: 124÷144
250 V - 3,15 A
Cross - flow
2…. Ø 130 / L 180
K48410 M01598 …1
4… 1370 / 1230 / 990 / 540
0,35
11
1-3 Other Component Specifications
KAF97R5IAA / KAF98MR5IAA
KPAF127R5IAA / KPAF128MR5IAA
KPAF187/247R5IAA
Trasformer (TR
)
Rating Primary
Secondary Capacity
Coil resistance
(
at 25°C
)
Thermal cut-off temp.
Thermistor
(
Coil sensor TH1
)
Resistance
κ
Thermistor
(
Room sensor TH2
)
Resistance
κ
Thermistor
(
Humidity sensor TH3
)
Resistance
κ
ATR-I55
AC 230 V, 50/60 Hz
13.7 V - 0.4 A
5.48 VA
C7-M3-SY
25°C - 60% RH (± 5% RH): 31,0
Primary (WHT-WHT): 307 ± 10%
Secondary (BRN-BRN): 1.8 ± 10%
150°C
DTN-C502H3T-TKS128B
25 °C: 5,0 ± 3%
0 °C: 188,0 ± 4%
DTN-C583G3U-TKS121B
0
0 10203040506070809
0
40
60
80
100
120
140
160
180
200
20
10
1
2
3
4
5
6
7
8
9
10
15 20 25 30 35 40
• Indoor air temp sensor
• Indoor heat exchanger sensor
• Humidity sensor
30 35 40 45 50 55 60 65 70 75 80 85 90
1
10
100
1000
25°C
Resistance (k)
Resistance (k)
Resistance (k)
Temperature (°C)
Temperature (°C)
Relative humidity (%)
12
2. DIMENSIONAL DATA
KAF97R5IAA
KAF98MR5IA
A
Unit: mm
7
0
0
200560
13
KPAF127R5IA
A
KPAF128MR5IA
A
KPAF187R5IA
A
KPAF247R5IA
A
Unit: mm
KPAF127R5I/KPAF128MR5I d. 9,52 (3/8) KPAF187R5I d. 12,7 (1/2) Wide Tube KPAF247R5I d. 15,88 (5/8)
14
3. ELECTRICAL DATA
3-1 Electric Wiring Diagrams
KAF97R5IAA
KAF98MR5IAA
15
KPAF127R5IAA
KPAF128MR5IAA KPAF187/247R5IAA
16
4. PERFORMANCE DATA
4-1 Air Throw Distance Chart
KPAF127R5IAA - KPAF128MR5IAA
Floor Mounted
Ceiling Mounted
17
KPAF187R5IAA
Floor Mounted
Ceiling Mounted
18
KPAF247R5IAA
Floor Mounted
Ceiling Mounted
19
5. FUNCTIONS
5-1 Operation Functions
20
21
5-2 Protective Functions
22
23
6. TEST RUN
6-1 How to Test Run the Air Conditioner
display area
HIGH POWER
button
1HR. TIMER
button
ON/OFF
operation button
24
7. TROUBLESHOOTING
7-1 Precaution before Performing Inspection or Repair
7-2 Method of Self-Diagnostics
ON/OFF button
1HR. TIMER button
A
CL (reset) button
25
(1) Self-diagnostics lamps
KAF97R5IAA - KAF98MR5IAA KPAF127/187/247R5IAA - KPAF128MR5IAA
+ Since the indications cover various units, the corresponding parts listed below may not be present in some models.
(2) If the self-diagnostics function fails to operate
TIMER lamp
OPERATION lamp
SERVICE lamp
TIMER lamp
OPERATION lamp
SERVICE lamp
26
7-3 Checking the Indoor and Outdoor Units
27
7-4 Noise Malfunction and Electromagnetic Interference
28
8. CHECKING ELECTRICAL COMPONENTS
8-1 Measurement of insulation Resistance
8-1-1
8-1-4
8-1-2
8-1-3
29
8-2 Checking Continuity of fuse on PCB Assy
8-3 Checking Motor Capacitor
30
R.D. 28 Reyrieux BP 131 - 01601 Trévoux CEDEX France
Tél. 04.74.00.92.92 - Fax 04.74.00.42.00
R.C.S. Bourg-en-Bresse B 759 200 728