Technibel GRF244MR5IAA, GRF194MR5IAA, MCAF124MR5IAA, MCAF94MR5IAA, MCAF184MR5IAA Installation Instructions Manual

...
85264189906000
Model Combinations
Indoor Units
Outdoor Units
MCAF94MR5IAA GRF194MR5IAA MCAF124MR5IAA GRF244MR5IAA MCAF184MR5IAA
Power Source: 50 Hz, single-phase, 220 – 240 V / 60 Hz, single-phase, 220 V
COOL/DRY/HEAT Model
Indoor unit B
Indoor unit A
Outdoor unit
Indoor unit C
Combination example
This air conditioner uses the new refrigerant R410A.
Contents
Page
IMPORTANT!
Please Read Before Starting .................................. 1
1. GENERAL.......................................................... 2
1-1. Tools Required for Installation (not supplied) 1-2. Accessories Supplied with Unit 1-3. Optional Copper Tubing Kit 1-4. Type of Copper Tube and Insulation Material 1-5. Additional Materials Required for Installation
2. INSTALLATION SITE SELECTION ................... 3
2-1. Indoor Unit 2-2. Outdoor Unit 2-3. Outer Dimensions of Outdoor Unit 2-4. Diagram of Outdoor Unit Installation
3. INSTALLATION PROCESS ................................ 8
3-1. Embedding the Tubing and Wiring 3-2. Installing Outdoor Unit 3-3. Use of the Flaring Method 3-4. Flaring Procedure with a Flare Tool 3-5. Caution before Connecting Tubes Tightly 3-6. Tubing Connections 3-7. Insulation of Refrigerant Tubing 3-8. Taping the Tubes 3-9. Finishing the Installation 3-10. Refrigerant Operation System
4. AIR PURGING................................................... 12
Air Purging with a Vacuum Pump (for Test Run)
Pump Down
5. WIRING INSTRUCTIONS ................................ 15
5-1. General Precautions on Wiring 5-2. Recommended Wire Length and Diameter 5-3. Wiring System Diagram 5-4. Electric Wiring Diagram 5-5. How to Connect Wiring to the Terminal 5-6. Wiring Instructions for the Outdoor Unit
6. TEST RUN......................................................... 22
7. INSTALLATION CHECK SHEET ...................... 23
02/2004
INSTALLATION INSTRUCTIONS
- Multi Split system air conditioner -
1
IMPORTANT! Please Read Before Starting
This air conditioning system meets strict safety and oper­ating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently .
For safe installation and trouble-free operation, you must:
Carefully read this instruction booklet before beginning.
Follow each installation or repair step exactly as shown.
Observe all local, state, and national electrical codes.
Pay close attention to all warning and caution notices given in this manual.
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.
If Necessary, Get Help
These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tub-
ing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this
system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental
injury or death.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause
overheating at connection points and a possible fire hazard.
When Transporting
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.
When Installing…
…In a Ceiling or Wall
Make sure the ceiling/wall is strong enough to hold the unit’s weight. It may be necessary to construct a strong wood or metal frame to provide added support.
…In a Room
Properly insulate any tubing run inside a room to prevent “sweating” that can cause dripping and water damage to walls and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This pre­vents water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak­free connection.
• Check carefully for leaks before starting the test run.
When Servicing
• Turn the power OFF at the main power box (mains) before opening the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.
Others
• Ventilate any enclosed areas when installing or testing the refrigeration system. Escaped refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas.
• Confirm upon completing installation that no refriger­ant gas is leaking. If escaped gas comes in contact with a stove, gas water heater, electric room heater or other heat source, it can produce dangerously toxic gas.
• Do not install only a single indoor unit.
WARNING
WARNING
CAUTION
CAUTION
2
1. General
This booklet briefly outlines where and how to install the air conditioning system. Please read over the entire set of instructions for the indoor and outdoor units and make sure all accessory parts listed are with the system before beginning.
1-1. Tools Required for Installation (not supplied)
1. Standard screwdriver
2. Phillips head screwdriver
3. Knife or wire stripper
4. Tape measure
5. Carpenter’s level
6. Sabre saw or key hole saw
7. Hacksaw
8. Core bits
9. Hammer
10. Drill
11. Tube cutter
12. Tube flaring tool
13. Torque wrench
14. Adjustable wrench
15. Reamer (for deburring)
16. Vacuum pump (For R410A)
17. Manifold valve
1-2. Accessories Supplied with Unit Table 1
1-3. Optional Copper Tubing Kit
Copper tubing for connecting the outdoor unit to the indoor unit is available in kits which contain the narrow and wide tubing, fittings and insulation. Consult your nearest sales outlet or A/C workshop.
1-4. Type of Copper Tube and Insulation Material
If you wish to purchase these materials separately from a local source, you will need:
(1) Deoxidized annealed copper tube for refrigerant
tubing as detailed in Table 2. Cut each tube to the appropriate lengths +30 cm
to 40 cm to dampen vibration between units.
Table 2
(2) Foamed polyethylene insulation for the specified
copper tubes as required to precise length of tub­ing. Wall thickness of the insulation should be not less than 8 mm.
(3) Use insulated copper wire for field wiring.
Wire size varies with the total length of wiring. Refer to 5. Wiring Instructions for details.
CAUTION
Check local electrical codes and regulations before obtaining wire. Also, check any specified instructions or limitations.
Model
Narrow Tube Wide Tube
Outer Dia. Thickness Outer Dia. Thickness
MCAF94MR5IAA 6.35 mm 0.8 mm 9.52 mm 0.8 mm MCAF124MR5IAA 6.35 mm 0.8 mm 9.52 mm 0.8 mm MCAF184MR5IAA 6.35 mm 0.8 mm 9.52 mm 0.8 mm
Parts Figure Qty
Labels for inter-unit A B (for GRF194MR5IAA) 4 each cable and tube
A B C (for GRF244MR5IAA) 4 each
3
1-5. Additional Materials Required for Installation
(1) Refrigeration (armored) tape (2) Insulated staples or clamps for connecting wire
(See local codes) (3) Putty (4) Refrigeration lubricant (5) Clamps or saddles to secure refrigerant tubing
2. Installation Site Selection
2-1. Indoor Unit
AVOID:
direct sunlight.
nearby heat sources that may affect performance of the
unit.
areas where leakage of flammable gas may be expected.
places where large amounts of oil mist exist.
DO:
select an appropriate position from which every corner of
the room can be uniformly cooled.
select a location that will hold the weight of the unit.
select a location where tubing and drain hose have the
shortest run to the outside.
allow room for operation and maintenance as well as
unrestricted air flow around the unit.
install the unit within the maximum elevation difference
(H1, H2, H3) above or below the outdoor unit and within a total tubing length (L1+L2, L1+L2+L3) from the outdoor unit as detailed in Table 3 and Fig. 1.
Table 3
INDOOR UNIT (1)
INDOOR UNIT (3)
INDOOR UNIT (2)
Tubing length (L1)
L2
L3
Elevation difference (H1)
H2
H3
OUTDOOR UNIT
Fig. 1
WARNING
To prevent abnormal heat genera­tion and the possibility of fire, do not place obstacles, enclosures and grilles in front of or sur­rounding the air conditioner in a way that may block air flow.
Max. Allowable Tubing Limit of Total Tubing Limit of Elevation
Model Length per unit Length (L1+L2) or Difference (H1, H2, H3)
(m) (L1+L2+L3) (m) (m)
GRF194MR5IAA 25 * 35 (L1+L2) 10 GRF244MR5IAA 25 * 50 (L1+L2+L3) 10
This outdoor unit requires no refrigerant charge up to the maximum limit for total tubing length of 35 m (GRF194MR5IAA) or 50 m (GRF244MR5IAA). Therefore, no refrigerant needs to be added on-site.
NOTE
Fig. 2a
4
(1) Connecting indoor unit types (94 – 124) at B
φ6.35
φ6.35
φ9.52
φ9.52
A
B
(94 – 124 type)
Outdoor unit
Indoor unit
(94 – 124 type)
(2) Connecting indoor unit type 184 at B (Length of tube: more than 17 m)
φ6.35
φ6.35
φ9.52
Union φ12.7
φ9.52
φ9.52
A
B
(94 – 124 types)
Outdoor unit
Indoor unit
(184 type)
Flare φ9.52
Union φ12.7
φ12.7
Flare φ9.52
A joint for connecting tubes of different sizes
(More than 17 m)
Fig. 2b
(3) Connecting indoor unit type 184 at B (Length of tube: less than 17 m)
φ6.35
φ6.35
φ9.52
φ9.52
A
B
(94 – 124 types)
Outdoor unit
Indoor unit
(184 type)
φ9.52
φ9.52
(Less than 17 m)
Fig. 2c
GRF194MR5IAA
5
Fig. 2e
Fig. 2f
φ6.35
φ6.35
φ6.35
φ9.52
φ9.52
Union φ12.7
φ9.52
φ9.52
φ9.52
A
B
C
(94 – 124 types)
Outdoor unit
Indoor unit
(94 – 124 types)
(184 type)
Flare φ9.52
Union φ12.7
φ12.7
Flare φ9.52
A joint for connecting tubes of different sizes
(More than 17 m)
φ6.35
φ6.35
φ9.52
φ9.52
φ9.52
φ6.35
φ9.52
A
φ9.52
B
φ9.52
C
(94 – 124 types)
Outdoor unit
Indoor unit
(94 – 124 types)
(184 type)
(Less than 17 m)
φ6.35
φ6.35
φ9.52
φ9.52
φ9.52
φ6.35
φ9.52
A
φ9.52
B
φ9.52
C
(94 – 124 type)
Outdoor unit
Indoor unit
(94 – 124 type)
(94 – 124 type)
GRF244MR5IAA
(1) Connecting indoor unit types (94 – 124) at C
(2) Connecting indoor unit type 184 at C (Length of tube: more than 17 m)
(3) Connecting indoor unit type 184 at C (Length of tube: less than 17 m)
Fig. 2d
Note: It is not possible to connect the indoor unit type 244 to 2 or 3 room outdoor unit.
6
2-2. Outdoor Unit AVOID:
heat sources, exhaust fans, etc. (Fig. 3)
damp, humid or uneven locations.
DO:
choose a place as cool as possible.
choose a place that is well ventilated.
allow enough room around the unit for air intake/
exhaust and possible maintenance. (Fig. 4a)
provide a solid base (level concrete pad, concrete
block, 15 × 40 cm beams or equal), a minimum of 15 cm above ground level to reduce humidity and protect the unit against possible water damage and decreased service life. (Fig. 4a)
install cushion rubber under units feet to reduce
vibration and noise. (Fig. 4b)
use lug bolts or equal to bolt down unit, reducing
vibration and noise.
select a location where the operating noise and air
blowing from the outdoor unit will not disturb neigh­bors.
select a location where the clearance indicated by
in the installation diagram is ensured for the front, rear, left, and right of the main unit.
install so that the unit is level.
select a location that can fully support the weight of
the outdoor unit, and that will not magnify operating noise or vibration. (Fasten in place with the anchor bolts (M10).)
provide a base using concrete or similar material,
and ensure proper drainage.
select a location where there is no danger of
flammable gas leakage.
in snowy or rainy regions, be sure to construct a
roof to keep off the snow and rain, and inhibit freez­ing and condensation.
select a location that is at least 3 meters away from
any antennas used for television, radio transceiver, or other equipment.
for purposes of future service and repair, select a
location where the inspection panel can be removed.
select a location where the drain port will not be
obstructed.
Outdoor unit
Hot air
Heat source
Exhaust fan
NO
Fig. 3
Fig. 4a
Cushion rubber
Fig. 4b
Air intake Min. 20 cm
Air discharge
Min.
10 cm
Min. 50 cm
Valve side Min. 25 cm
2 m
2 m
Min. 20 cm Air intake
Ground
Obstacle
Obstacle above
Air discharge
Air intake
Concrete or equal
About 15 cm
Min. 15 cm
Anchor bolts (4 pcs.)
About 40 cm
Install the inter-unit cable more than 1 meter away from any antenna or power lines or connecting wires used for television, radio, telephone, security system, or intercom. Electrical noise from any of these sources may affect operation.
7
2-3. Outer Dimensions of
Outdoor Unit
2-4.
Diagram of Outdoor Unit Installation
Base (not provided) (concrete or similar material)
Fastened with anchor bolts (not provided) (M10, 4 locations)
Tubing panel
B
A
C
Indoor unit A
Indoor unit B
Indoor unit C
Cable fastener
Ground wire (not provided)
Over 250
Power breaker
Over 200
Inspection panel
Over 10
Over 500
Ensure 150 mm of space if a drain hose is to be used.
Service space
Be sure to connect indoor and outdoor units only in combinations that are listed in the catalog or in the combination table that was provided with the outdoor unit. (Use caution. Connecting any other model may result in operation failure and malfunction.)
The dimensions indicated by in the figure below are spaces that are required in order to maintain performance. Install in a location where the dimensions indicated by ⇔ are ensured, and where 2 or more faces of the unit are unobstructed. In principle, the top direction should be unobstructed.
Cover
Tubing panel
Two indoor units (Type 3)
(1) Place covers over positions that tubes
do not pass through, as necessary according to the number of indoor units.
(2) Adjust the tube positions and attach the
tubing panel.
Three indoor units (no covers used.)
Using the tubing panel and covers
940
13 13
13 13
1015
380
405
660
110
340
730
18
166
86
166
246
86
GRF194MR5IAA model
Service valve on narrow tube side
Service valve on wide tube side
(Outer diameter φ6.35)
Service valve on narrow tube side
(Outer diameter φ6.35)
(Outer diameter φ9.52)
Service valve on wide tube side
(Outer diameter φ9.52)
GRF244MR5IAA model
Fig. 5
Fig. 6
Never install only a single indoor unit.
Unit: mm
8
3. Installation Process
3-1. Embedding the Tubing and Wiring
Do not connect tubes to locations that are embedded.
Be sure to bind refrigerant tubing and inter-unit
cables together with vinyl tape.
The power cable must be obtained on-site.
2.0: Less than 15 m / φ2.6: Less than 20 m / φ3.5: Less than 26 m)
Be sure to apply the provided labels to both ends of
the inter-unit cables to prevent miswiring.
Securely seal the end of embedded tubing with vinyl
tape in order to prevent dirt or moisture entry.
In order to prevent insulation breakdown and
ground faults, do not allow the wire ends to contact rainwater, or be subject to dew condensation.
3-2.
Installing Outdoor Unit
(1) Select a location for installing the outdoor unit.
(Refer to 2-2. Outdoor Unit.)
(2) The connection valves are stored inside the unit.
Remove the inspection panel and remove the cable fasteners. (To remove the inspection panel, remove the 3 screws, then push the panel down and pull it toward you.) (Refer to 2-4. Diagram of Outdoor Unit Installation.)
(3) Remove the tubing panel in order to attach covers
as needed, according to the number of indoor units. (Refer to 2-4. Diagram of Outdoor Unit Installation.)
Narrow Tube Wide Tube
φ
6.35 mm (1/4")
φ
9.52 mm (3/8")
Be sure to prepare special R410A-type tubes (wall thickness
0.8 mm) as shown in the table at right.
Deburring
Before
After
Fig. 7
3-3. Use of the Flaring Method
Many conventional split system air conditioners employ the flaring method to connect refrigerant tubes which run between indoor and outdoor units. In this method, the copper tubes are flared at each end and connected with flare nuts.
3-4. Flaring Procedure with a Flare Tool
For creating the flare, use the special R410 flare tool. The
previous (R22) flare tool may also be used. (Fig. 9)
(1) Cut the copper tube to the required length with a tube
cutter. It is recommended to cut approx. 30 – 50 cm longer than the tubing length you estimate.
(2) Remove burrs at the end of the copper tube with a tube
reamer or file. This process is important and should be done carefully to make a good flare. (Fig. 7)
Table 4
9
Service valve on narrow tube side
Service valve on wide tube side
Apply the provided labels to the indoor and outdoor unit tubing connectors to prevent errors in connections.
B
A
C
Reamer
Copper tubing
Fig. 8
Fig. 9
Flare tool
Flare nut
Copper tubing
Fig. 10
Fig. 13
Apply refrigerant lubricant here and here
Fig. 11
Flare nut
Union
Fig. 12
When reaming, hold the tube end downward and be sure that no copper scraps fall into the tube. (Fig. 8)
(3) Remove the flare nut from the unit and be sure to
mount it on the copper tube.
(4) Make a flare at the end of copper tube with a flare
tool.* (Fig. 10) (*Use RIGID or equivalent.)
A good flare should have the following characteristics:
inside surface is glossy and smooth.
edge is smooth.
tapered sides are of uniform length.
3-5. Caution before Connecting Tubes Tightly
a) Be sure to apply a sealing cap or water-proof tape
to prevent dust or water from getting into the tubes before they are used.
b) Be sure to apply refrigerant lubricant to the
matching surfaces of the flare and union before connecting them together. This is effective for reducing gas leaks. (Fig. 11)
c) For proper connection, align the union tube and flare
tube straight with each other, then screw in the flare nut lightly at first to obtain a smooth match. (Fig. 12)
3-6. Tubing Connections
a) Temporary connection:
Screw in 3 – 5 rotations by hand. (Fig.13)
b) To fasten the flare nuts, apply specified torque as:
Table 5
NOTE
NOTE
0 0.5 mm
If the special R410A flare tool is used:
1.2 mm
If the previous flare tool (clutch-type) is used:
Adjust so that the amount of tube protrusion is as shown in the figure.
Tube Dia. Tightening Torque
6.35 mm 18 N·m (180 kgf·cm)
9.52 mm 42 N·m (420 kgf·cm)
12.70 mm 55 N·m (550 kgf·cm)
10
Insulation
3-7. Insulation of Refrigerant Tubing
To prevent heat loss and wet floors due to dripping of condensation, both tubes must be well insulated with a proper insulation material. The thickness of the insulation should be a minimum 8 mm. (Fig. 16)
3-8. Taping the Tubes
(1) At this time, the 2 refrigerant tubes (and electrical
wire if local codes permit) should be taped togeth­er with armoring tape. The drain hose may also be included and taped together as 1 bundle with the tubing.
(2) Wrap the armoring tape from the bottom of the
outdoor unit to the top of the tubing where it enters the wall. As you wrap the tubing, overlap half of each previous tape turn. (Fig. 17a)
(3) Clamp the tubing bundle to the wall, using 1 clamp
approx. every 120 cm.
Do not wind the armoring tape too tightly since this will decrease the heat insulation effect. Also be sure the condensation drain hose splits away from the bundle and drips clear of the unit and the tubing.
3-9. Finishing the Installation
After finishing insulating and taping over the tubing, use sealing putty to seal off the hole in the wall to pre­vent rain and draft from entering. (Fig. 17b)
NOTE
IMPORTANT
Indoor unit
Outdoor unit
Spanner
Torque wrench
Fig. 14
Fig. 15
Insulation
Min. 8 mm
Thickness: min. 8 mm
Fig. 16
Fig. 17a
Clamp
Insulated tubes
Apply putty here
Tubing
Fig. 17b
CAUTION
After a tube has been insulated, never try to bend it into a narrow curve, as this may cause the tube to break or crack.
CAUTION
Be sure to match refrigerant tubing and electric wiring between indoor and outdoor units. For more details, refer to Tubing Check Control in the Technical & Service Manual.
11
3-10. Refrigerant Operation System
When the air conditioner is turned ON, the compressor starts to work. The compressor absorbs low-temperature and low-pressure refrigerant from the evaporator; the refrigerant is then compressed into high-temperature and high­pressure refrigerant gas and goes into the condenser (COMPRESSION). This high-temperature and high-pressure refrigerant gas is condensed into liquid refrigerant; during the CONDENSING process, heat is released to the out­doors through the condenser. High-pressure and high-temperature liquid refrigerant goes into the capillary tube to reduce the pressure and to lower the temperature (PRESSURE REDUCTION). The low-pressure liquid refrigerant passed through the capillary tube is sent to the evaporator for evaporation. In this EVAPORATION process, heat in the room is absorbed. This cycle is repeated until the room temperature is lowered to the target level. During the heating cycle, the direction of refrigerant flow is reversed by a 4-way valve. As a result, the condenser draws heat from the outdoor air and the evaporator supplies hot air to the room.
Indoor unit
Service valve on wide tube side
Service valve on narrow tube
Compressor
Strainer
Muffler
Muffler
Sub­accumulator
Four-way valve
When cooling When heating When defrosting
Outdoor heat exchanger
Solenoid valve for hot gas bypass
Electric expansion valve
Electric expansion valve
Modulator
Main accumulator
Fig. 18
When cooling When heating When defrosting
Outdoor heat exchanger
Solenoid valve for hot gas bypass
Electric expansion valve
Electric expansion valve
Main accumulator
Compressor
Muffler
Muffler
Sub­accumulator
Four-way valve
Service valve on wide tube side
Service valve on narrow tube
Strainer
Modulator
Indoor unit
Fig. 19
Unit: mm
Unit: mm
3-Room Multi Refrigerant Tubing System Diagram
2-Room Multi Refrigerant Tubing System Diagram
12
4. Air Purging
Air and moisture remaining in the refrigerant system have undesirable effects as indicated below. There­fore, they must be purged completely.
pressure in the system rises
operating current rises
cooling efficiency drops
moisture in the air may freeze and block capillary
tubing
water may lead to corrosion of parts in the refriger-
ant system
Air Purging with a Vacuum Pump (for Test Run)
In order to protect the earths environment, be sure to
use a vacuum pump to perform the air purge. (Never perform an air purge by using the refrigerant gas cylinder or other external gas, or by using the gas inside the outdoor unit.)
For GRF194MR5IAA, perform the air purge for tubes A and B. For GRF244MR5IAA, perform the air purge for tubes A, B, and C. Use the same procedures for all tubes.
(1) Check that each tube (both narrow and wide
tubes) between the indoor and outdoor units have been properly connected and all wiring for the test run has been completed. Note that both narrow and wide tube service valves on the outdoor unit are kept closed at this stage.
(2) Using an adjustable wrench or box wrench,
remove the valve caps from the service valve on both narrow and wide tubes.
(3) Connect a vacuum pump and a manifold valve
(with pressure gauges) to the service port on the
HiLo
B
A
C
Service valve on narrow tube side
Service valve on wide tube side
With push-pin
Hex wrench (nominal size 4 mm, not provided)
Manifold gauge (special for R410A)
Low­pressure valve
Open
Charging hose (special for R410A)
Leave the valve open.
Vacuum pump adapter (for preventing reverse flow) (special for R410A)
Vacuum pump
High-pressure valve
Fig. 20
Cap tightening torque: 20 25 N-m (200 250 kgf-cm) (Tighten by hand, then use a wrench to turn.)
Stopper
Spindle
Screw diameter: 1/2 UNF 20 threads
Valve core
Cap nut tightening torque: 7 11 N-m (70 110 kgf-cm) (Tighten by hand, then use a wrench to turn approximately 30 .)
<Structure of service valve on wide tube side>
Fig. 21
CAUTION
Be sure to use a manifold valve for air purging. If it is not available, use a stop valve for this purpose. The Hi knob of the manifold valve must always be kept closed.
CAUTION
CAUTION
Before using the vacuum pump adapter, read the vacuum pump adapter manual, and use the adapter correctly.
In order to prevent charging errors with A/C that uses R410A, the screw diameter at the service valve charging port has been changed. When recharging or per­forming other servicing, use the special charging hose and manifold gauge.
When using a hex wrench to open the spindle, an
extremely small amount of refrigerant may leak. This does not indicate a problem.
Use a hex wrench of a type to which force can be
easily applied.
13
(4) With the “Lo” knob of the manifold valve open, run
the vacuum pump. Run the pump until the pres­sure is –101 kPa (–76 cmHg). The operation time for the vacuum pump varies with tubing length and the capacity of the pump. The following table shows the amount of time required for evacuation:
Table 6
The required time in the above table is calculated based on the assumption that the ideal (or target) vac­uum condition is around 10 mmHg abs.
(5) With the vacuum pump still running, close the Lo
knob of the manifold valve. Then stop the vacuum pump. Fully close the low-pressure valve and stop the vacuum pump. (Wait 1 – 2 minutes and check that the manifold gauge pointer does not return. If it does return, find and repair the leak, then apply the vacuum again.)
(6) With a hex wrench, turn the valve stem on the nar-
row tube service valve counter-clockwise by 90 degrees (1/4 turn) for 10 seconds, and then turn the stem clockwise to close it again.
(7) With a standard screwdriver, turn the wide tube
service valve stem counterclockwise to fully open the valve.
(8) Turn the narrow tube service valve stem counter-
clockwise to fully open the valve.
(9) Loosen the vacuum hose connected to the wide
tube service port slightly to release the pressure. Then, remove the hose.
(10) Leak test all joints at the tubing (both indoor and
outdoors) with liquid soap. Bubbles indicate a leak. Be sure to wipe off the soap with a clean cloth.
NOTE
CAUTION
Be sure to completely insert the hex wrench before attempting to turn the valve.
Required time for evacuation when capacity
of 100 liter/h vacuum pump is used
20 min. or more
CAUTION
If a CFC gas detector is used, use a special detec­tor for HFC refrigerant (such as R410 and R134a).
14
(11) Replace the flare nut on the wide tube service
port and fasten the flare nut securely with an adjustable wrench or box wrench. Next, mount the valve cap and tighten it with a torque wrench (the cap needs to be tightened with the torque of 200 kg-cm). This process is very important to pre-
vent gas from leaking from the system. (12) Test run the air conditioner. (See page 22.) (13) While the air conditioner is running, apply liquid
soap to check for any gas leaks around the ser-
vice valves or caps. (14) If there is no leakage, stop the air conditioner. (15) Wipe off the soap on the tubing. This completes air purging with a vacuum pump and
the air conditioner is ready for actual operation.
Pump Down
When relocating or disposing of the A/C, request
this service from the dealer where the unit was pur­chased, or from an appropriate agent. Perform pump-down as described below.
What is pump-down?
Pump-down refers to recovering the refrigerant gas
from the refrigerant cycle at the outdoor unit. This work must be performed during cooling operation. The refrigerant gas cannot be recovered during heating operation.
During winter, or if the temperature sensor prevents
cooling operation, perform forced cooling operation.
Pump-down procedure
(For model GRF194MR5IAA, there is no tube C.) (1) Fully close the spindles at the valves on the narrow
tube side of tubes A, B, and C. (Refer to Fig. 23.)
(2) Connect the manifold gauge to the charging port at
the valve on the wide tube side of tube C. Purge the air from the charging hose. (Refer to Fig. 24.)
In order to protect the earths environment, be sure to perform pump-down to recover refrigerant
gas without releasing it into the atmosphere.
Forced cooling operation
(The following explanation uses a wall-mounted unit as the example. Refer to each indoor units Installation Instruction for details)
1. Turn the operation knob to the ON position.
2. Use the remote control to start cooling operation.
3. Turn the operation knob from the ON position to the TEST RUN position.
* The operation knob differs to
some degree depending on the model.
Narrow tube side
Charging port
Close
Close
Close
A
B
C
Fig. 23
Fig. 22
15
(3) Perform cooling operation or forced cooling
operation. When the pressure at the low-pressure side is
0.15 – 0.2 MPa (0.5 – 1 kg/cm2G), fully close the spindles at the valves on the wide tube side of tubes A, B, and C, and immediately stop opera­tion. (Refer to Fig. 24.) In the winter, the outdoor unit may stop after 5 ­10 minutes of operation. This is in order to protect the indoor unit heat exchanger from freezing and does not indicate a problem.
(4) Disconnect the manifold gauge and the inter-unit
tubes, and attach the caps and flare nuts. At this point, pump-down is completed. (If the caps and flare nuts are not reattached, there is the danger of gas leakage.) (Refer to Fig. 25.)
If pump-down is not possible
If the A/C cannot be operated because of a malfunc­tion or other cause, use a refrigerant recovery device to recover the refrigerant.
5. Wiring Instructions
5-1. General Precautions on Wiring
(1) Before wiring, confirm the rated voltage of the unit
as shown on its nameplate, then carry out the wiring closely following the wiring diagram.
(2) Provide a power outlet to be used exclusively for
each unit, with a power supply disconnect and cir­cuit breaker for overcurrent protection provided in the exclusive line.
(3) To prevent possible hazard due to insulation fail-
ure, the unit must be grounded.
(4) Each wiring connection must be done tightly and in
accordance with the wiring system diagram. Wrong wiring may cause the unit to misoperate or become damaged.
(5) Do not allow wiring to touch the refrigerant tubing,
compressor, or any moving parts of the fan.
(6) Unauthorized changes in the internal wiring can
be very dangerous. The manufacturer will accept no responsibility for any damage or misoperation that occurs as a result of such unauthorized changes.
Manifold gauge
Wide tube side
Cap
Cap
Cap
After disconnecting the inter-unit tubes, attach the flare nuts with flare bonnets.
Fig. 24
Fig. 25
16
5-2. Recommended Wire Length and Diameter
Regulations on wiring diameter differ from locality to locality. For field wiring requirements, please refer to your local elec­trical codes. Carefully observe these regulations when carry­ing out the installation. Table 7 shows maximum wire lengths for control line and power line and fuse or circuit capacity.
Refer to the wiring system diagram (Fig. 26a and b) for the meaning of “A” and “B” in Table 7.
Table 7
NOTE
Cross-sectional Max. Control Line Length Max. Power Line Length Fuse
Area (mm2) (A) (B) or
Model 1.0 2.0 2.6 3.5
Circuit Capacity
GRF194/244MR5IAA 34 m 15 m 20 m 26 m 20 A
Indoor Unit
Outdoor Unit
Unit A
Unit A
Unit B
Unit B
(A)
Terminal plate (8P)
Terminal plate (3P)
Grounding line Power supply Single-phase
AC 220 – 240 V
(B)
CAUTION
Be sure to connect the power supply line to the outdoor unit as shown in the wiring diagram. The indoor unit draws its power from the outdoor unit.
5-3. Wiring System Diagram
WARNING
Be sure to comply with local codes on running
the wire from the indoor unit to the outdoor unit (size of wire and wiring method, etc.).
Each wire must be firmly connected.
No wire should be allowed to touch refrigerant
tubing, the compressor, or any moving part.
Be sure to connect power wires correctly match-
ing up numbers on terminals of the outdoor unit and respective indoor units A – C.
To avoid the risk of electric shock, each air conditioner unit must be grounded.
WARNING
Fig. 26a Fig. 26b
Indoor Unit
Outdoor Unit
Unit A
Unit A
Unit B
Unit C
Unit B
Unit C
(A)
Terminal plate (12P)
Terminal plate (3P)
Grounding line Power supply Single-phase AC 220 – 240 V
(B)
2 indoor units with GRF194MR5IAA
3 indoor units with GRF244MR5IAA
17
5-4. Electric Wiring Diagram
BK
W
R
GRN /Y
BK
BK BK
BK
W
BK (ORG) BK (ORG)
GY GY GY GY GY GY
W(BK) GY GY
GY GY
R W BL
Control panel
Inter-unit cables
Terminal board
Display/ receiver panel
(GRN)
Fan motor
Flap motor
To heat exchanger
(W)
(W)
(W)
(W)
(GRN)
(R)
(W)
(W)
Room temperature sensor
Heat exchanger temperature sensor
Humidity sensor
BK
BK: Black W: White R: Red GRN: Green Y: Yellow BL: Blue GY: Gray
Fig. 27a
INDOOR UNIT
BK
BK
Control panel
Terminal board
Display/ receiver panel
(GRN)
Fan motor
Flap motor
(W)
(W)
(W)
(W)
(GRN)
(R)
(W)
(W)
BK: Black W: White R: Red GRN: Green Y: Yellow BL: Blue GY: Gray
Inter-unit cables
To heat exchanger
Room temperature sensor
Heat exchanger temperature sensor
GRN /Y
BK
W R
BK
BK BK
BK
R W BL
W(BK) GY GY GY GY
BK
W GY GY GY GY GY GY
Humidity sensor
Fig. 27b
MCAF94MR5IAA
MCAF124/184MR5IAA
18
CAUTION
Fig. 28a
Electric Wiring Diagram for 2-room-multi outdoor unit (GRF194MR5IAA)
Before replacing PCBs, turn off the power and check that all lamps on the PCB are off before starting work. Electric shock will occur if work is performed while the lamps are lit.
Electric Shock
YEL
YEL
BLU
BLK
WHT
BLU
BLK BLK BLK
BLK
BLK BLK
BLK
YEL YEL
WHT
BLK BLK BLK BLK BLK
BLK
BLK BLK
BLK
YEL
PNK
(
RED
)
WHT
WHT
RED
BLK
WHT
BLK
BLK
WHT
CH
CRANKCASE HEATER
FERRITE CORE
FC1,2
31
HEATER
(
YEL
)
CN02
CH
WHT
WHT
RE1
RE2RE1
++
U
GRN
/
YEL
WHT
BLU
CM
EARTH
240V
AC220V
1
12 4
UNIT B
INDOOR
421
GRN
/
YEL
BLK
GRN
/
YEL
WHT
GRN
/
YEL
TERMINAL
BASE
(
8P
)
12
321321
OPERATION CONDENSERC0TRANSISTOR
TR
DIODE
BRIDGE DIODE
BD
D
TH7
MVA,MVB
MECHANICAL VALVE
TH6
THERMISTOR(ROOM B NARROW PIPE)
THERMISTOR(ROOM B WIDE PIPE)
RED
CONTROL PCB
VW
UNIT A
INDOOR
RE2
HIC+
W
W
HIC
-
YEL
GRY
+
+
HIC+HIC
-
2
21
1
(
WHT
)
4
43
3
CN34
HIC1
HIC1
(
WHT
)
6
65
57
7
CN01
8
8
9
9
10
10
2
21
1
(
WHT
)
5
54
4
CN30
HIC2
HIC2
(
WHT
)
8
87
7
10
10
CN02
11
11
(
WHT
)
CN18
HIC3
HIC3
(
WHT
)
CN03
BLK
1
1
BLK
2
2
FILTER PCB
HS
ORG
79
CN35
(
WHT
)
3 1
5
SI
BRN
TERMINAL BASE
(
3P
)
6
67
7
WHT
BLK
(
WHT
)
PAM
PAM
CN23
4
45
5
WHT
BLK
(
WHT
)
1
12
2
BLK
BLK
(
WHT
)
CT
CT
(
WHT
)
CN08
1
13
3
BLK
BLK
(
WHT
)
PRY
PRY
(
RED
)
CN21
WW
AC200-L2
CN29
BLK
YEL YEL
BLK
YEL YEL
YEL
TH7 TH6
(
RED
)
YEL
432
1
BTH
CN22
TH5 TH4
TH2 TH1
(
BLK
)
DEF
BLU
CN05
BLU
3 1
DEF
WHT
ORG
BLU
BRN
YEL
RED
RED
BLU ORG
WHT
YEL
BRN
BD
C0
(BLK)(
WHT
)(
BLK
)
(
WHT
)
(
WHT
)(
WHT
)
(
RED
)
3
GRY
+
MC01 MC02
ORG
GRY
6
TH3
1
BLK
WHT
L2L1
WW
G2
TR
D
HIC PCB
YEL
BLU
BRN
YEL
RED
WHT
YEL
+
5432
1
CN37
MVA
MVA
6
(
BLK
)(
RED
)
GRN
/
YEL
GRN
/
YEL
FC1
FC2
GRN
/
YEL
W
WHT
RV
6 4
FMO
MMV
32 1
ATH
CN24
MVB
BRN
GRY
BLK
FMOTH
CN16
FMO
CN09
CN06
RV
MMV
CN36 CN13 CN19
COIL
/
GAIKI
COMP
1
3
1
573
1
2345
1
3
1
234
1
2
W
G1
GRY
WHT
W
DC280
(
WHT
)
3 1
CN01
5
AC200-L1
DC280
-
AC200
W
DC280+
BLK
1
12
2
MVB
CN38
1
2345
SOLDERED TERMINAL
TERMINAL
TERMINAL BASE
CONNECTOR
REACTOR
THERMISTOR(ROOM A WIDE PIPE)
THERMISTOR(ROOM A NARROW PIPE)
THERMISTOR(COMPRESSOR TEMP)
THERMISTOR(OUTDOOR TEMP)
THERMISTOR(HEAT EXCHANGER)
W
BOARD-IN-WIRE
HEAT SINK
DEF
MAIN MOTOR OPERATED VALVE
4-WAY VALVE
FAN MOTOR
COMPRESSOR MOTOR
HS
RE1,2
TH5
TH4
TH3
TH2
TH1
DEFROST VALVE
MMV
RV
FMO
CM
DESCRIPTIONSYMBOLS
854
-
2
-
5269
-
183
-
00
-
2
ELECTRIC WIRING DIAGRAM
MULTIPLE INDOOR UNITS
HEAT-PUMP OUTDOOR UNIT FOR TWO-ROOM
19
Fig. 28b
CAUTION
Before replacing PCBs, turn off the power and check that all lamps on the PCB are off before starting work. Electric shock will occur if work is performed while the lamps are lit.
Electric Shock
Electric Wiring Diagram for 3-room-multi outdoor unit (GRF244MR5IAA)
WHT
YEL
YEL
BLU
BLK
WHT
BLU
BLK BLK BLK
BLK
BLK BLK
BLK
YEL YEL
WHT
BLK BLK BLK BLK BLK
BLK
BLK BLK
BLK
YEL
PNK
(
RED
)
WHT BLU
WHT
RED
BLK
WHT
BLK
BLK
WHT
CH
CRANKCASE HEATER
FERRITE CORE
FC1,2
31
HEATER
(
YEL
)
CN02
CH
WHT
WHT
RE1
RE2RE1
TH8
THERMISTOR(ROOM C NARROW PIPE)
THERMISTOR(ROOM C WIDE PIPE)
TH9
++
U
GRN
/
YEL
WHT
BLU
CM
EARTH
240V
AC220V
1
12 4
UNIT C
INDOOR
12 4
UNIT B
INDOOR
421
GRN
/
YEL
BLK
GRN
/
YEL
WHT
BLK
GRN
/
YEL
GRN/YEL
TERMINAL
BASE
(
12P
)
12
321321321
OPERATION CONDENSERC0TRANSISTOR
TR
DIODE
BRIDGE DIODE
BD
D
TH7
MVA MVC
MECHANICAL VALVE
TH6
THERMISTOR(ROOM B NARROW PIPE)
THERMISTOR(ROOM B WIDE PIPE)
RED
CONTROL PCB
VW
UNIT A
INDOOR
RE2
HIC+
W
W
HIC
-
YEL
GRY
+
+
HIC+
HIC
-
2
21
1
(
WHT
)
4
43
3
CN34
HIC1
HIC1
(
WHT
)
6
65
57
7
CN01
8
8
9
9
10
10
2
21
1
(
WHT
)
5
54
4
CN30
HIC2
HIC2
(
WHT
)
8
87
7
10
10
CN02
11
11
(
WHT
)
CN18
HIC3
HIC3
(
WHT
)
CN03
BLK
1
1
BLK
2
2
FILTER PCB
HS
ORG
79
CN35
(
WHT
)
3
1
5
SI
BRN
TERMINAL BASE
(
3P
)
6
67
7
WHT
BLK
(
WHT
)
PAM
PAM
CN23
4
45
5
WHT
BLK
(
WHT
)
1
12
2
BLK
BLK
(
WHT
)
CT
CT
(
WHT
)
CN08
1
13
3
BLK
BLK
(
WHT
)
PRY
PRY
(
RED
)
CN21
WW
AC200-L2
CN29
BLK
YEL YEL
BLK
TH9 TH8
(
BLU
)
YEL
YEL
432
1
CTH
CN20
TH7 TH6
(
RED
)
YEL YEL
432
1
BTH
CN22
TH5 TH4
TH2 TH1
(
BLK
)
DEF
BLU
CN05
BLU
3 1
DEF
WHT
ORG
BLU
BRN
YEL
RED
(
BLU
)
6
RED
BLU ORG
WHT
YEL
BRN
MVC
MVC
CN39
1
BD
C0
(
BLK
)(
WHT
)(
BLK
)
(
WHT
)
(
WHT
)(
WHT
)
(
RED
)
3
GRY
+
MC01 MC02
ORG
GRY
6
TH3
1
BLK
WHT
L2L1
WW
G2
TR
D
HIC PCB
YEL
BLU
BRN
YEL
YEL
RED
WHT
YEL
YEL
+
5432
1
CN37
MVA
MVA
6
(
BLK
)(
RED
)
BRN
GRN
/
YEL
GRN
/
YEL
FC1
FC2
GRN
/
YEL
W
WHT
RV
6
ORG
RED
4
FMO
MMV
32 1
YEL
ATH
CN24
BLU
WHT
MVB
BRN
GRY
BLK
FMOTH
CN16
FMO
CN09
CN06
RV
MMV
CN36 CN13 CN19
COIL
/
GAIKI
COMP
1
3
1
573
1
2345
1
3
1
234
1
2
W
G1
GRY
WHT
W
DC280
(
WHT
)
3
1
CN01
5
AC200-L1
DC280
-
AC200
W
DC280+
BLK
1
12
2
MVB
CN38
1
2345 5432
SOLDERED TERMINAL
TERMINAL
TERMINAL BASE
CONNECTOR
REACTOR
THERMISTOR(ROOM A WIDE PIPE)
THERMISTOR(ROOM A NARROW PIPE)
THERMISTOR(COMPRESSOR TEMP)
THERMISTOR(OUTDOOR TEMP)
THERMISTOR(HEAT EXCHANGER)
W
BOARD-IN-WIRE
HEAT SINK
DEF
MAIN MOTOR OPERATED VALVE
4-WAY VALVE
FAN MOTOR
COMPRESSOR MOTOR
HS
RE1,2
TH5
TH4
TH3
TH2
TH1
DEFROST VALVE
MMV
RV
FMO
CM
DESCRIPTIONSYMBOLS
854
-
2
-
5269
-
184
-
00
-
2
ELECTRIC WIRING DIAGRAM
MULTIPLE INDOOR UNITS
HEAT-PUMP OUTDOOR UNIT FOR THREE-ROOM
20
When connecting each power wire to the correspond­ing terminal, follow the instructions below and fasten the wire securely tight with the fixing screw of the ter­minal plate.
a) For Indoor Unit
(1) Cut the wire end with a cutting pliers, then strip
the insulation to expose the wire about 7 mm. See the label (Fig. 29) near the terminal plate.
(2) Using a screwdriver, loosen the terminal screw on
the terminal plate.
(3) Insert the wire and tighten the terminal screw
completely using a screwdriver.
b) For Outdoor Unit
For solid core wiring (or F-cable)
(1) Cut the wire end with a cutting pliers, then strip the
insulation to expose the solid wire about 25 mm. (Fig. 30a)
(2) Using a screwdriver, remove the terminal screw(s)
on the terminal plate.
(3) Using the pliers, bend the solid wire to form a loop
suitable for the terminal screw.
(4) Shape the loop wire properly, place it on the termi-
nal plate and fix it securely with the removed ter­minal screw using a screwdriver.
For stranded wiring
(1) Cut the wire end with a cutting pliers, then strip
the insulation to expose the stranded wiring about 10 mm and tightly twist the wire ends. (Figs. 30b and 31a)
(2) Using a screwdriver, remove the terminal screw(s)
on the terminal plate.
(3) Using a ring connector fastener or pliers, securely
clamp each stripped wire end with a ring connec­tor. (Fig. 30b)
(4) Place the ring connector wire, and replace and
tighten the removed terminal screw using a screwdriver. (Fig. 31b)
Solid wire
Loop
Insulation
Strip 25 mm
Fig. 30a
STRIP SIZE
7 mm (ACTUAL
SIZE)
Fig. 29
Stranded wire
Ring connector
Strip 10 mm
Fig. 30b
Screw
Ring connector
Terminal plate
Wire
Special washer
Fig. 31b
Screw and special washer
Ring connector
Wire
WARNING
Loose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazard may also exist. Therefore, be sure all wiring is tightly connected.
Twist wire ends
Fig. 31a
5-5. How to Connect Wiring to the Terminal
21
12 312 312 3
ABC
Attach the label
1
2
Ground
1
21 3 45 6 7 89 101112
1
2
4
1
2
4
Indoor unit A
Outdoor unit A
Indoor unit B
Indoor unit C
BK
WR
R
R
1
2
4
BK
W
BK
W
BK
WR
BK
W
R
BK
WR
A
B
C
Label A
Label B
Label C
Inter-unit cables φ1.0 (not provided)
Inter-unit cables φ1.0 (not provided)
Inter-unit cables φ1.0 (not provided)
A is the indoor unit with refrigerant tubing that is connected to service valve A (top) of the outdoor unit.
B is the indoor unit with refrigerant tubing that is connected to service valve B (top) of the outdoor unit.
C is the indoor unit with refrigerant tubing that is connected to service valve C (top) of the outdoor unit.
A
BC
Fasten the cable with cable fasteners.
Power cable (not provided) (φ2.0 mm: Less than 15 m) (φ2.6 mm: Less than 20 m) (φ3.5 mm: Less than 26 m)
Power: Single-phase, 220 240 V
Power switch (not provided)
Terminal board
Terminal board
Terminal board
Terminal board
5-6. Wiring Instructions for the Outdoor Unit
The below explanation uses model (GRF244MR5IAA)
as an example. With model (GRF194MR5IAA), there is no terminal block C.
Be sure to correctly align inter-unit cables A, B, and C.
Never use φ2.6 mm VVF cable or a twisted-pair cable
for the inter-unit cable.
Be sure to perform grounding.
Attach a ground wire to either the
outdoor unit or indoor unit.
If there is a grounding terminal
inside the room, use the grounding screw inside the indoor unit.
Be sure to apply the provided labels to both ends of the inter-unit
cables to prevent miswiring. The units will not function if the wiring connections are incorrect.
Use a dedicated A/C circuit for power.
To make connections to the outdoor unit, remove
the inspection panel and tubing panel.
Do not bring the inter-unit cables or power cable
into contact with tubing or service valves.
Use outdoor unit cable fasteners and fasten the
inter-unit cables at the location where the cables are double-sheathed.
Arrange the wiring so that the inter-unit cables are
contained in the inspection panel and tubing panel, as shown in Fig. 32.
CAUTION
Fig. 32
22
6. Test Run
Performing a test run
Refer to the test run procedures in the indoor unit
installation manual.
Perform the test run separately for each connected
indoor unit. If 2 units are operated simultaneously, it is not possible to correctly check for errors in tubing and wiring.
If the room temperature is 15°C or below, it may not
be possible to check for tubing errors with cooling operation. If this occurs, perform heating operation for each unit individually, and check that warm air is discharged from each unit. If there is cold air mixed in with the warm air, check the tubing connections again.
Checking tubing and wiring
Perform the test run and check that operation is nor­mal. If there is an error in tubing or wiring, the refriger­ant may flow to indoor unit B when indoor unit A is operated (for example).
Stop operation immediately if there is an error in
tubing or wiring. Turn the power (breaker) to OFF, and check whether the inter-unit cables are con­nected incorrectly, or whether the narrow tubes A and B are connected in reverse. Correct the con­nections.
If there is an error in tubing, pump-down must be
performed. Be sure to perform pump-down. After making corrections, again purge the air from the tubes.
CAUTION
23
7. Installation Check Sheet
The strength of the installation location is sufficient to support the A/C weight.
The indoor and outdoor units are installed level and vertically.
The power and voltage are as specified. Inter-unit cables are securely fastened to the termi-
nal board. Inter-unit cables are securely fixed. The power cord and inter-unit cables are not con-
nected anywhere along their paths. The ground wire is securely connected. An air purge of the refrigerant circuit has been con-
ducted. A leak test of the tubing connections has been per-
formed. Thermal insulation has been applied to the tubing
connections. Drain connections are secure and water drains
properly. Putty has been used to close the hole in the wall. All service valves are fully open. Remote controller signals are being positively
received.
R.D. 28 Reyrieux BP 131 - 01601 Trévoux CEDEX France
Tél. 04.74.00.92.92 - Fax 04.74.00.42.00
R.C.S. Bourg-en-Bresse B 759 200 728
In order to carry on a constant improvement, our products can be modified without prior notice.
Per garantire un costante miglioramento dei nostri prodotti, ci riserviamo di modificarli senza preavviso.
Par souci damélioration constante, nos produits peuvent être modifiés sans préavis.
Unsere Produkte werden laufend verbessert und können Vorankündigung abgeändert Werden.
En el interés de mejoras constantes, nuestros productos pueden modificarse sin aviso prévio.
Loading...