Technibel GRF98L5TAA, GRF128L5TAA, GRF188L5TAA, GRF258L7TAA, GRF188L7TAA Technical Data & Service Manual

...
TECHNICAL DATA & SERVICE MANUAL
OUTDOOR UNIT:
GRF98L5TAA GRF188L5TAA GRF258L7TA
A
GRF128L5TAA GRF188L7TAA GRF368L7TA
A
A
0.8180.556.0 10/2008
387007182
GRF228L7TAA 387007179
Product Code No. Model No.
GRF98L5TAA 387007174 GRF258L7TAA
GRF128L5TAA 387007175 GRF368L7TAA
SPLIT SYSTEM AIR CONDITIONER
Model No.
GRF188L7TAA 387007178
Product Code No.
387007180 387007181
GRF188L5TAA 387007177 GRF488L7TAA
IMPORTANT! Please read before installation
This air conditioning system meets strict safety and operating standards. For the installer or service person, it is important to install or service the system so that it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
• Carefully read this instruction booklet before beginning.
• Follow each installation or repair step exactly as shown.
• Observe all local, state and national electrical codes.
• Pay close attention to all warning and caution notices given in this manual.
•The unit must be supplied with a dedicated electrical line.
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.
If necessary, get help
These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sale/service outlet or your certified dealer for additional instructions.
In case of improper installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
• During installation, connect before the refrigerant system and then the wiring one; proceed in the reverse orden when removing the units.
When wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIANS SHOULD ATTEMPT TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked, to ensure the grounding.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury and death.
Ground the unit following local electrical codes.
• The Yellow/Green wire cannot be used for any connection different from the ground connection.
• Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.
• Do not allow wiring to touch the refrigerant tubing, compressor, or any moving parts of the fan.
• Do not use multi-core cable when wiring the power supply and control lines. Use separate cables for each type of line.
When transporting
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminium fins on the air conditioner can cut your fingers.
When installing... ... In a ceiling or wall
Make sure the ceiling/wall is strong enough to hold the unit-weight. It may be necessary to build a strong wooden or metal frame to provide added support.
... In a room
Properly insulate any tubing run inside a room to prevent "sweating", which can cause dripping and water damage to walls and floors.
... In moist or uneven locations
Use a raised concrete base to provide a solid level foundation for the outdoor unit. This prevents damage and abnormal vibrations.
... In area with strong winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
... In a snowy area (for heat pump-type systems)
Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.
When connecting refrigerant tubing
• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them; screw by hand and then tighten the nut with a torque wrench for a leak-free connection.
• Check carefully for leaks before starting the test run.
NOTE:
Depending on the system type, liquid and gas lines may be either narrow or wide. Therefore, to avoid confusion, the refrigerant tubing for your particular model is specified as narrow tube for liquid, wide tube for gas.
When servicing
• Turn the power OFF at the main power board before opening the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after the work, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.
• Ventilate the room during the installation or testng the refrigeration system; make sure that, after the installation, no gas leaks are present, because this could produce toxic gas and dangerous if in contact with flames or heat-sources.
WARNING
CAUTION
WARNING
2
Page
1. OPERATING RANGE
4
2. SPECIFICATIONS
5
2-1 Unit specifications 5 2-2 Major Component specifications 13 2-3 Other Component specifications 21
3. DIMENSIONAL DATA
22
4. REFRIGERANT FLOW DIAGRAM
25
5. PERFORMANCE DATA
27
5-1 Performance Charts 27 5-2 Cooling Capacity 35
6. ELECTRICAL DATA
43
6-1 Electrical characteristics 43 6-2 Electric Wiring Diagram 46 6-3 System Wiring Diagram 50
Table of Contents
3
1. OPERATING RANGE
Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp.
Cooling
Maximum
Minimum
43°C D.B.
-15°C D.B.
32°C D.B. / 23°C W.B. 19°C D.B. / 14°C W.B.
4
2. SPECIFICATIONS
2-1 Unit Specifications
GRF98L5TAA
Power source
V
oltage ratin
g
Performance * MRAF98C5T
Capacity
kW
BTU/h Air circulation (High) m³/h Moisture removal (High) Liters/h
Electrical Ratin
g
Available voltage range V Running amperes A Power input W Power factor % C.O.P. W/W Compressor locked rotor amperes A
Features
Fan speed Compressor Refrigerant / Amount charged at shipment g Refrigerant control Power noise level Hi dB-A Refrigerant tubing connections Max. allowable tubing length at shipment m Refrigerant Narrow tube mm(in.) tube diameter Wide tube mm(in.)
Dimensions & Wei
g
ht
Unit dimensions Height mm
Width mm Depth mm
Package dimensions Height mm
Width mm Depth mm
Weight Net kg
Shipping kg
Shipping volume
m
3
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Remarks:
Rating conditions are: Cooling: Indoor air temperature 27°C D.B. / 19°C W.B. Outdoor air temperature 35°C D.B. / 24°C W.B.
*
For other INDOOR UNITS' MODELS, please refer to catalogue
98
3,5
17
2,70
9214
220 - 240V ~ 50Hz
230V
Cooling
34,0
0,8
Cooling
3,40
770
450
198 ~ 264
37,0 0,16
700 265 568 815 343
57
1(Hi)
Rotary (Hermetic)
R410A / 770
Capillary tube
6,35 (1/4")
9,52 (3/8)
540
Flare type
7,5
5
GRF128L5TAA
Power source
V
oltage ratin
g
Performance * MRAF128C5T
Capacity
kW
BTU/h Air circulation (High) m³/h Moisture removal (High) Liters/h
Electrical Ratin
g
Available voltage range V Running amperes A Power input W Power factor % C.O.P. W/W Compressor locked rotor amperes A
Features
Fan speed Compressor Refrigerant / Amount charged at shipment g Refrigerant control Power noise level Hi dB-A Refrigerant tubing connections Max. allowable tubing length at shipment m Refrigerant Narrow tube mm(in.) tube diameter Wide tube mm(in.)
Dimensions & Wei
g
ht
Unit dimensions Height mm
Width mm Depth mm
Package dimensions Height mm
Width mm Depth mm
Weight Net kg
Shipping kg
Shipping volume
m
3
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Remarks:
Rating conditions are: Cooling: Indoor air temperature 27°C D.B. / 19°C W.B. Outdoor air temperature 35°C D.B. / 24°C W.B.
*
For other INDOOR UNITS' MODELS, please refer to catalogue
0,16
198 ~ 264
470
Cooling
3,40
11603
1,5
12,7(1/2")
540 700
37,0
220 - 240V ~ 50Hz
230V
265 568
Flare type
7,5
6,35 (1/4")
815 343
34,0
1(Hi)
Rotary (Hermetic)
R410A / 790
Capillary tube
60
3,2
22
Cooling
4,70
1050
97
6
GRF188L5TAA
Power source
V
oltage ratin
g
Performance * MPAF188C5T
Capacity
kW
BTU/h Air circulation (High) m³/h Moisture removal (High) Liters/h
Electrical Ratin
g
Available voltage range V Running amperes A Power input W Power factor % C.O.P. W/W Compressor locked rotor amperes A
Features
Fan speed Compressor Refrigerant / Amount charged at shipment g Refrigerant control Power noise level Hi dB-A Refrigerant tubing connections Max. allowable tubing length at shipment m Refrigerant Narrow tube mm(in.) tube diameter Wide tube mm(in.)
Dimensions & Wei
g
ht
Unit dimensions Height mm
Width mm Depth mm
Package dimensions Height mm
Width mm Depth mm
Weight Net kg
Shipping kg
Shipping volume
m
3
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Remarks:
Rating conditions are: Cooling: Indoor air temperature 27°C D.B. / 19°C W.B. Outdoor air temperature 35°C D.B. / 24°C W.B.
*
For other INDOOR UNITS' MODELS, please refer to catalogue
388 55,0 60,0 0,26
830
345
690
971
7,5
6,35 (1/4")
12,7(1/2")
630
R410A / 1260 Capillary tube
63
Flare type
3,3
26
1(Hi)
Rotary (Hermetic)
198 ~ 264
7,10
1600
98
17746
760
2
Cooling
220 - 240V ~ 50Hz
230V
Cooling
5,20
7
GRF188L7TAA
Power source
V
oltage ratin
g
Control Circuit
Performance * MPAF188C5T
Capacity
kW
BTU/h Air circulation (High) m³/h Moisture removal (High) Liters/h
Electrical Ratin
g
Available voltage range V Running amperes A Power input W Power factor % C.O.P. W/W Compressor locked rotor amperes A
Features
Fan speed Compressor Refrigerant / Amount charged at shipment g Refrigerant control Power noise level Hi dB-A Refrigerant tubing connections Max. allowable tubing length at shipment m Refrigerant Narrow tube mm(in.) tube diameter Wide tube mm(in.)
Dimensions & Wei
g
ht
Unit dimensions Height mm
Width mm Depth mm
Package dimensions Height mm
Width mm Depth mm
Weight Net kg
Shipping kg
Shipping volume
m
3
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Remarks:
Rating conditions are: Cooling: Indoor air temperature 27°C D.B. / 19°C W.B. Outdoor air temperature 35°C D.B. / 24°C W.B.
*
For other INDOOR UNITS' MODELS, please refer to catalogue
388 55,0 60,0 0,26
830
345
690
971
7,5
6,35 (1/4")
12,7(1/2")
630
R410A / 1260 Capillary tube
64
Flare type
3,2
20
1(Hi)
Rotary (Hermetic)
342 ~ 418
3,40
1650
211
18087
760
2
Cooling
380 - 415V 3N ~ 50Hz
230V ~ 50Hz
Cooling
5,30
400V
8
GRF228L7TAA
Power source
V
oltage ratin
g
Control Circuit
Performance * MPAF228C5T
Capacity
kW
BTU/h Air circulation (High) m³/h Moisture removal (High) Liters/h
Electrical Ratin
g
Available voltage range V Running amperes A Power input W Power factor % C.O.P. W/W Compressor locked rotor amperes A
Features
Fan speed Compressor Refrigerant / Amount charged at shipment g Refrigerant control Power noise level Hi dB-A Refrigerant tubing connections Max. allowable tubing length at shipment m Refrigerant Narrow tube mm(in.) tube diameter Wide tube mm(in.)
Dimensions & Wei
g
ht
Unit dimensions Height mm
Width mm Depth mm
Package dimensions Height mm
Width mm Depth mm
Weight Net kg
Shipping kg
Shipping volume
m
3
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Remarks:
Rating conditions are: Cooling: Indoor air temperature 27°C D.B. / 19°C W.B. Outdoor air temperature 35°C D.B. / 24°C W.B.
*
For other INDOOR UNITS' MODELS, please refer to catalogue
0,30
1000
400 71,0 77,0
735
942
341
755
Flare type
7,5
6,35 (1/4")
15,88 (5/8)
Rotary (Hermetic)
R410A / 1440 Capillary tube
67
215
3,1
27
1(Hi)
Cooling
342 ~ 418
4,20
2080
6,50
22182
830
2,5
380 - 415V 3N ~ 50Hz
400V
230V ~ 50Hz
Cooling
9
GRF258L7TAA
Power source
V
oltage ratin
g
Control Circuit
Performance * CAF258C5
T
Capacity
kW
BTU/h Air circulation (High) m³/h Moisture removal (High) Liters/h
Electrical Ratin
g
Available voltage range V Running amperes A Power input W Power factor % C.O.P. W/W Compressor locked rotor amperes A
Features
Fan speed Compressor Refrigerant / Amount charged at shipment g Refrigerant control Power noise level Hi dB-A Refrigerant tubing connections Max. allowable tubing length at shipment m Refrigerant Narrow tube mm(in.) tube diameter Wide tube mm(in.)
Dimensions & Wei
g
ht
Unit dimensions Height mm
Width mm Depth mm
Package dimensions Height mm
Width mm Depth mm
Weight Net kg
Shipping kg
Shipping volume
m
3
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Remarks:
Rating conditions are: Cooling: Indoor air temperature 27°C D.B. / 19°C W.B. Outdoor air temperature 35°C D.B. / 24°C W.B.
*
For other INDOOR UNITS' MODELS, please refer to catalogue
380 - 415V 3N ~ 50Hz
230V ~ 50Hz
Cooling
7,80
400V
26618
1020
3
Cooling
342 ~ 456
5,10
2580
220
3,0
27
1(Hi)
Rotary (Hermetic)
R410A / 1540 Capillary tube
68
Flare type
7,5
6,35 (1/4")
15,88(5/8")
735 942 341 755
1000
400 71,0 77,0 0,30
10
GRF368L7TAA
Power source
V
oltage ratin
g
Control Circuit
Performance * CAF368C5
T
Capacity
kW
BTU/h Air circulation (High) m³/h Moisture removal (High) Liters/h
Electrical Ratin
g
Available voltage range V Running amperes A Power input W Power factor % C.O.P. W/W Compressor locked rotor amperes A
Features
Fan speed Compressor Refrigerant / Amount charged at shipment g Power noise level Hi dB-A Refrigerant tubing connections Max. allowable tubing length at shipment m Refrigerant Narrow tube mm(in.) tube diameter Wide tube mm(in.)
Dimensions & Wei
g
ht
Unit dimensions Height mm
Width mm Depth mm
Package dimensions Height mm
Width mm Depth mm
Weight Net kg
Shipping kg
Shipping volume
m
3
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Remarks:
Rating conditions are: Cooling: Indoor air temperature 27°C D.B. / 19°C W.B. Outdoor air temperature 35°C D.B. / 24°C W.B.
*
For other INDOOR UNITS' MODELS, please refer to catalogue
380 - 415V 3N ~ 50Hz
400V
230V ~ 50Hz
Cooling
10,40
35491
1920
3,5
Cooling
342 ~ 456
6,60
3300
217
3,2
33
1(Hi)
Rotary (Hermetic)
R410A /2580
70
Flare type
7,5
9,52 (3/8")
19,05(3/4")
1235
940 340
1255
0,56
1000
400 104,0 111,0
11
GRF488L7TAA
Power source
V
oltage ratin
g
Control Circuit
Performance * CAF488C5
T
Capacity
kW
BTU/h Air circulation (High) m³/h Moisture removal (High) Liters/h
Electrical Ratin
g
Available voltage range V Running amperes A Power input W Power factor % C.O.P. W/W Compressor locked rotor amperes A
Features
Fan speed Compressor Refrigerant / Amount charged at shipment g Power noise level Hi dB-A Refrigerant tubing connections Max. allowable tubing length at shipment m Refrigerant Narrow tube mm(in.) tube diameter Wide tube mm(in.)
Dimensions & Wei
g
ht
Unit dimensions Height mm
Width mm Depth mm
Package dimensions Height mm
Width mm Depth mm
Weight Net kg
Shipping kg
Shipping volume
m
3
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Remarks:
Rating conditions are: Cooling: Indoor air temperature 27°C D.B. / 19°C W.B. Outdoor air temperature 35°C D.B. / 24°C W.B.
*
For other INDOOR UNITS' MODELS, please refer to catalogue
380 - 415V 3N ~ 50Hz
400V
230V ~ 50Hz
Cooling
14,10
48118
1920
5
Cooling
342 ~ 456
9,70
5000
224
2,8
74
1(Hi)
Rotary (Hermetic)
R410A /2880
71
Flare type
7,5
9,52 (3/8")
19,05(3/4")
1235
940 340
1255
0,56
1000
400 128,0 135,0
12
2-2 Major Component Specifications
Outdoor Unit: GRF98L5TAA
Compresso
r
Type Compressor model Nominal input W Compressor oil…Amount cc. Coil resistance (Ambient temp. 20°C)
Overload relay Safety devices Type
Operating Temp. Open °C
Close °C
Run capacitor µF
VAC
Fan & Fan Moto
r
Type Q'ty ……. Dia. Fan motor model…Q'ty No. Of poles…rpm (230 V, High) Nominal output W Coil resistance (Ambient temp. 25 °C )
Safety devices Type
Operating temp. Open °C
Close °C
Run capacitor µF
VAC
Heat Exch. Coil
Coil Rows Fin pitch mm Face area
m
2
External Finish
DATA SUBJECT TO CHANGE WITHOUT NOTICE
30
700
MRA99901-9201
N/A N/A
RB68A / Freol Alpha 68M…350
C-R: 3,863 C-S: 3,309
External (OLR T)
Rotary (Hermetic)
5PS102EAG01
400
Propeller
1…. Ø 370
IB-966-501…1
6…865
-
1,5
450
21
BRN-WHT: 242.4
WHT-YEL: 408.1
Thermal protector
120 ± 5
Acrylic baked-on enamel finish
Aluminium plate fin / Copper tube
2
1,4
0,34
13
Outdoor Unit: GRF128L5TAA
Compresso
r
Type Compressor model Nominal output W Compressor oil…Amount cc. Coil resistance (Ambient temp. 20°C)
Overload relay Safety devices Type
Operating Temp. Open °C
Close °C
Run capacitor µF
VAC
Fan & Fan Moto
r
Type Q'ty ……. Dia. Fan motor model…Q'ty No. Of poles…rpm (230 V, High) Nominal output W Coil resistance (Ambient temp. 25 °C )
Safety devices Type
Operating temp. Open °C
Close °C
Run capacitor µF
VAC
Heat Exch. Coil
Coil Rows Fin pitch mm Face area
m
2
External Finish
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Acrylic baked-on enamel finish
Aluminium plate fin / Copper tube
2
1,4
0,34
6…865
-
1,5
450
21
BRN-WHT: 242.4
WHT-YEL: 408.1
Thermal protector
120 ± 5
400
Propeller
1…. Ø 370
IB-966-501…1
Rotary (Hermetic)
5PS132EAD01
25
900
MRA98533-9201
N/A N/A
RB68A / Freol Alpha 68M…350
C-R: 2,798 C-S: 5,432
External (OLR T)
14
Outdoor Unit: GRF188L5TAA
Compressor
Type Compressor model Nominal input W Compressor oil…Amount cc. Coil resistance (Ambient temp. 20°C)
Overload relay Safety devices Type
Operating Temp. Open °C
Close °C
Run capacitor µF
VAC
Fan & Fan Motor
Type Q'ty ……. Dia. Fan motor model…Q'ty No. Of poles…rpm (230 V, High) Nominal output W Coil resistance (Ambient temp. 25 °C )
Safety devices Type
Operating temp. Open °C
Close °C
Run capacitor µF
VAC
Heat Exch. Coil
Coil Rows Fin pitch mm Face area
m
2
External Finish
DATA SUBJECT TO CHANGE WITHOUT NOTICE
2
1,5
0,51
Acrylic baked-on enamel finish
80 ± 15
2
440
Aluminium plate fin / Copper tube
BRN-WHT: 98.5
WHT-PNK: 201.0
Thermal protector
130 ± 5
1…. Ø 400
KFG6-51SB5P…1
6…900
40
50
370
Propeller
Internal
Thermal protector
N/A N/A
1700
FV50S …670
C-R: 1,780 C-S: 2,175
Rotary (Hermetic)
5KS205EAA21
15
Outdoor Unit: GRF188L7TAA
Compressor
Type Compressor model Nominal input W Compressor oil…Amount cc. Coil resistance (Ambient temp. 20°C)
Overload relay Safety devices Type
Operating Temp. Open °C
Close °C
Run capacitor µF
VAC
Fan & Fan Motor
Type Q'ty ……. Dia. Fan motor model…Q'ty No. Of poles…rpm (230 V, High) Nominal output W Coil resistance (Ambient temp. 25 °C )
Safety devices Type
Operating temp. Open °C
Close °C
Run capacitor µF
VAC
Heat Exch. Coil
Coil Rows Fin pitch mm Face area
m
2
External Finish
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Acrylic baked-on enamel finish
Aluminium plate fin / Copper tube
2
1,5
0,51
130 ± 5 80 ± 15
2
440
40
BRN-WHT: 98.5 WHT-PNK: 201.0 Thermal protector
Propeller
1…. Ø 400
KFG6-51SB5P…1
6…900
N/A
--
--
V-W: 7,630
Internal
Thermal protector
N/A
1780
FV50S …670
U-V: 7,767
U-W: 7,943
Rotary (Hermetic)
5KS205PAA21
16
Outdoor Unit: GRF228L7TAA
Compressor
Type Compressor model Nominal input W Compressor oil…Amount cc. Coil resistance (Ambient temp. 20°C)
Overload relay Safety devices Type
Operating Temp. Open °C
Close °C
Run capacitor µF
VAC
Fan & Fan Motor
Type Q'ty ……. Dia. Fan motor model…Q'ty No. Of poles…rpm (230 V, High) Nominal output W Coil resistance (Ambient temp. 25 °C )
Safety devices Type
Operating temp. Open °C
Close °C
Run capacitor µF
VAC
Heat Exch. Coil
Coil Rows Fin pitch mm Face area
m
2
External Finish
DATA SUBJECT TO CHANGE WITHOUT NOTICE
2
1,4
0,60
Acrylic baked-on enamel finish
N/A
6
440
Aluminium plate fin / Copper tube
WHT - PNK: 50,7 WHT - BRN: 88,9 Thermal protector
130 ± 5
1…. Ø 460
Y7S623B54 … 1
4 … 760
60
N/A
--
Propeller
--
V-W: 5,562
Internal
Thermal protector
N/A
1800
FV50S … 1130
U-V: 5,786
U-W: 5,954
Rotary (Hermetic)
5JS270PAA21
17
Outdoor Unit: GRF258L7TAA
Compressor
Type Compressor model Nominal input W Compressor oil…Amount cc. Coil resistance (Ambient temp. 20°C)
Overload relay Safety devices Type
Operating Temp. Open °C
Close °C
Run capacitor µF
VAC
Fan & Fan Motor
Type Q'ty ……. Dia. Fan motor model…Q'ty No. Of poles…rpm (230 V, High) Nominal output W Coil resistance (Ambient temp. 25 °C )
Safety devices Type
Operating temp. Open °C
Close °C
Run capacitor µF
VAC
Heat Exch. Coil
Coil Rows Fin pitch mm Face area
m
2
External Finish
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Rotary (Hermetic)
5JS330PBA21
2845 / 2895
FV50S …1130
U-V: 5,786 U-W: 5,954 V-W: 5,562
Internal
Thermal protector
N/A N/A
--
--
Propeller
1…. Ø 460
Y7S623B54 … 1
4 … 760
60 WHT - PNK: 50,7 WHT - BRN: 88,9
Thermal protector
130 ± 5
N/A
6
440
Acrylic baked-on enamel finish
Aluminium plate fin / Copper tube
2
1,4
0,60
18
Outdoor Unit: GRF368L7TAA
Compressor
Type Compressor model Nominal input W Compressor oil…Amount cc. Coil resistance (Ambient temp. 20°C)
Overload relay Safety devices Type
Operating Temp. Open °C
Close °C
Run capacitor µF
VAC
Fan & Fan Motor
Type Q'ty ……. Dia. Fan motor model…Q'ty No. Of poles…rpm (230 V, High) Nominal output W Coil resistance (Ambient temp. 25 °C )
Safety devices Type
Operating temp. Open °C
Close °C
Run capacitor µF
VAC
Heat Exch. Coil
Coil Rows Fin pitch mm Face area
m
2
External Finish
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Rotary (Hermetic)
5JD420PAA02
3500
RB68A o Freol Alpha68M …1300
U-V: 3,478 U-W: 3,576 V-W: 3,344
Internal
Thermal protector
N/A N/A
--
--
Propeller
1…. Ø 460
Y7S623B54 … 1
4 … 760
60 WHT - PNK: 50,7 WHT - BRN: 88,9
Thermal protector
130 ± 5
N/A
6
440
Acrylic baked-on enamel finish
Aluminium plate fin / Copper tube
2
1,5
0,53
19
Outdoor Unit: GRF488L7TAA
Compressor
Type Compressor model Nominal input W Compressor oil…Amount cc. Coil resistance (Ambient temp. 20°C)
Overload relay Safety devices Type
Operating Temp. Open °C
Close °C
Run capacitor µF
VAC
Fan & Fan Motor
Type Q'ty ……. Dia. Fan motor model…Q'ty No. Of poles…rpm (230 V, High) Nominal output W Coil resistance (Ambient temp. 25 °C )
Safety devices Type
Operating temp. Open °C
Close °C
Run capacitor µF
VAC
Heat Exch. Coil
Coil Rows Fin pitch mm Face area
m
2
External Finish
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Rotary (Hermetic)
ZP67KCE-TFD
5200
POE …1660
U-V: 2,5
U-W: 2,5
V-W:2,5
Internal
Thermal protector
N/A N/A
--
--
Propeller
1…. Ø 460
Y7S623B54 … 1
4 … 760
60 WHT - PNK: 50,7 WHT - BRN: 88,9
Thermal protector
130 ± 5
N/A
6
440
Acrylic baked-on enamel finish
Aluminium plate fin / Copper tube
2
1,5
0,53
20
2-3 Other Component Specifications
Thermostat (fan speed control
)
Switching temperature °C Coil resistance
(
at 20°C
)
Relay H62S
Contact rating 5 A - 220 V Coil supply VAC 230 Coil resistance (20 °C) k 17,2 ± 10%
Power rela
y (
compressor
)
(PR)
FINDER 65.31
Contact rating 30 A - 250 V Coil supply 230 V ~ 50 Hz Coil resistance (20 °C) 7250 ± 10%
Ne
g
ative Phase Rela
y
Type Rating Contact Rating Operation
Fan Speed Controller
Type Factory setting Adjustable range
16 to 39bar
RGE-Z1L6-7DS
CISE131-V
AC 380 V, 3-PHASE 50 Hz
AC 250 V , 8 A
Positive phase: ON
Negative phase: OFF
HIGH…LOW 28,5°C ± 1
LOW…HIGH 31°C ± 1
YTB-S383
30bar
21
3. DIMENSIONAL DATA
Outdoor Unit: GRF98L5TAA GRF128L5TAA
700
540
15
470
4 – ø12 holes
116
320
294
Air intake
Air discharge
25510
170
103 57
Narrow tube service valve ø6.35 (1/4")
Wide tube service valve ø9.52 (3/8") ø12.7 (1/2")
7000/9000 BTU/h 12000 BTU/h
Unit : mm
22
Outdoor Unit: GRF188L5TAA GRF188L7TAA dimension mm
Outdoor Unit: GRF228L7TAA GRF258L7TAA
dimension mm
WIDE TUBE
D.15,88 (5/8")
NARROW TUBE
D.6,35 (1/4")
NARROW TUBE D.6,35 (1/4")
WIDE TUBE D.12,7 (1/2")
4 - Ø12 for anchor bolt
4 - Ø13 for anchor bolt
23
Outdoor Unit: GRF368L7TAA GRF488L7TAA dimension mm
24
4. REFRIGERANT FLOW DIAGRAM
Indoor Unit:
MRAF98C5T MRAF128C5T MPAF188C5T MPAF228C5T CAF258C5T
Outdoor Unit: GRF98L5TAA GRF128L5TAA GRF188L5TAA GRF188L7TAA
GRF228L7TAA GRF258L7TAA
Indoor Unit:
CAF368C5T CAF488C5T
Outdoor Unit: GRF368L7TAA GRF488L7TAA
Indoor Unit Outdoor Unit:
Indoor Unit Outdoor Unit:
25
IMPORTANT
Because capillary tubing is used in the outdoor unit, both the wide and narrow tubes of this air conditioner become cold. To prevent heat loss and wet floors due to dripping of condensation, both tubes must be well insulated with a proper insulation material. The thickness of the insulation should be a min. 8mm.
CAUTION
After a tube has been insulated, never try to bend it into a narrow curve because it can cause the tube to break or crack.
26
5. PERFORMANCE DATA
5-1 Performance charts
GRF98L5TAA
Coolin
g
Characteristics
0,74
0.8180.531.00 05/2007
Notes:
Points of Rating condition
Data referred to MRAF98C5T
Overload prevention operates to protect the air conditioner when outdoor ambient temperature reaches extremely high values in heating mode.
2,6
2,8
3,0
3,2
3,4
3,6
3,8
4,0
20 25 30 35 40 45
Outdoor inlet air D.B. temp. (°C)
Operating current (A)
Indoor inlet air
D.B. (°C)
0,60
0,70
0,80
0,90
1,00
1,10
1,20
20 25 30 35 40 45
Outdoor inlet air D.B. (°C)
Low pressure at wide tube service valve MP
a
Indoor inlet air
D.B. (°C)
32
27
19
32
27
19
32
27
19
27
GRF128L5TAA
Coolin
g
Characteristics
0,74
0.8180.531.00 05/2007
Notes:
Points of Rating condition
Data referred to MRAF128C5T
Overload prevention operates to protect the air conditioner when outdoor ambient temperature reaches extremely high values in heating mode.
3,2
3,7
4,2
4,7
5,2
5,7
20 25 30 35 40 45
Outdoor inlet air D.B. temp. (°C)
Operating current (A)
Indoor inlet air
D.B. (°C)
32
27
19
0,50
0,60
0,70
0,80
0,90
1,00
1,10
20 25 30 35 40 45
Outdoor inlet air D.B. (°C)
Low pressure at wide tube service valve MP
a
Indoor inlet air
D.B. (°C)
32
27
19
28
GRF188L5TAA
Coolin
g
Characteristics
0,74
0.8180.531.00 05/2007
Notes:
Overload prevention operates to protect the air conditioner when outdoor ambient temperature reaches extremely high values in heating mode.
Points of Rating condition
Data referred to:
MPAF188C5T
5,0
5,5
6,0
6,5
7,0
7,5
8,0
8,5
9,0
20 25 30 35 40 45
Outdoor inlet air D.B. temp. (°C)
Operating current (A)
Indoor inlet air
D.B. (°C)
0,60
0,70
0,80
0,90
1,00
1,10
1,20
20 25 30 35 40 45
Outdoor inlet air D.B. (°C)
Low pressure at wide tube service valve MP
a
Indoor inlet air
D.B. (°C)
32
27
19
32
27
19
29
GRF188L7TAA
Coolin
g
Characteristics
0,74
0.8180.531.00 05/2007
Notes:
Overload prevention operates to protect the air conditioner when outdoor ambient temperature reaches extremely high values in heating mode.
Points of Rating condition
Data referred to:
MPAF188C5T
2,5
3,0
3,5
4,0
4,5
20 25 30 35 40 45
Outdoor inlet air D.B. temp. (°C)
Operating current (A)
Indoor inlet air
D.B. (°C)
0,60
0,70
0,80
0,90
1,00
1,10
1,20
20 25 30 35 40 45
Outdoor inlet air D.B. (°C)
Low pressure at wide tube service valve MP
a
Indoor inlet air
D.B. (°C)
32
27
19
32
27
19
30
GRF228L7TAA
Coolin
g
Characteristics
0,74
0.8180.531.00 05/2007
Notes:
Overload prevention operates to protect the air conditioner when outdoor ambient temperature reaches extremely high values in heating mode.
Points of Rating condition
Data referred to:
MPAF228C5T
3,0
3,5
4,0
4,5
5,0
5,5
20 25 30 35 40 45
Outdoor inlet air D.B. temp. (°C)
Operating current (A)
Indoor inlet air
D.B. (°C)
32
27
19
0,50
0,60
0,70
0,80
0,90
1,00
1,10
20 25 30 35 40 45
Outdoor inlet air D.B. (°C)
Low pressure at wide tube service valve MP
a
Indoor inlet air
D.B. (°C)
32
27
19
31
GRF258L7TAA
Coolin
g
Characteristics
0,74
0.8180.531.00 05/2007
Notes:
Overload prevention operates to protect the air conditioner when outdoor ambient temperature reaches extremely high values in heating mode.
Points of Rating condition
Data referred to:
CAF258C5T
3,5
4,0
4,5
5,0
5,5
6,0
6,5
7,0
20 25 30 35 40 45
Outdoor inlet air D.B. temp. (°C)
Operating current (A)
Indoor inlet air
D.B. (°C)
32
27
19
0,50
0,60
0,70
0,80
0,90
1,00
1,10
20 25 30 35 40 45
Outdoor inlet air D.B. (°C)
Low pressure at wide tube service valve MP
a
Indoor inlet air
D.B. (°C)
32
27
19
32
GRF368L7TAA
Coolin
g
Characteristics
0,74
0.8180.531.00 05/2007
Notes:
Overload prevention operates to protect the air conditioner when outdoor ambient temperature reaches extremely high values in heating mode.
Points of Rating condition
Data referred to:
CAF368C5T
6,0
6,5
7,0
7,5
8,0
20 25 30 35 40 45
Outdoor inlet air D.B. temp. (°C)
Operating current (A)
Indoor inlet air
D.B. (°C)
32
27
19
0,50
0,60
0,70
0,80
0,90
1,00
1,10
20 25 30 35 40 45
Outdoor inlet air D.B. (°C)
Low pressure at wide tube service valve MP
a
Indoor inlet air
D.B. (°C)
32
27
19
33
GRF488L7TAA
Coolin
g
Characteristics
0,74
0.8180.531.00 05/2007
Notes:
Overload prevention operates to protect the air conditioner when outdoor ambient temperature reaches extremely high values in heating mode.
Points of Rating condition
Data referred to:
CAF488C5T
7,0
7,5
8,0
8,5
9,0
9,5
10,0
10,5
11,0
11,5
12,0
20 25 30 35 40 45
Outdoor inlet air D.B. temp. (°C)
Operating current (A)
Indoor inlet air
D.B. (°C)
32
27
19
0,50
0,60
0,70
0,80
0,90
1,00
1,10
20 25 30 35 40 45
Outdoor inlet air D.B. (°C)
Low pressure at wide tube service valve MP
a
Indoor inlet air
D.B. (°C)
32
27
19
34
5-2 Cooling Capacity
OUTDOOR UNIT: GRF98L5TAA INDOOR UNIT: MRAF98C5T
220 - 240V ~ 50Hz RATING CAPACITY 2,70 kW moisture removal 0,8 l/h COMP. POWER INPUT 0,68 kW max comp input 0,79 kW AIR FLOW RATE 450 m³/h
EVAPORATOR ENT.TEMP. °C
W.B. D.B. 20 25 30 35 40 43
TC 2,73 2,56 2,48 2,37 2,22 2,05
CM 0,54 0,57 0,60 0,64 0,67 0,71 21 SHC 1,89 1,75 1,72 1,66 1,59 1,51 23 SHC 2,14 1,99 1,95 1,89 1,82 1,74
15 25 SHC 2,37 2,22 2,17 2,11 2,04 1,96
27 SHC 2,62 2,45 2,40 2,34 2,22 2,05 29 SHC 2,73 2,56 2,48 2,37 2,22 2,05 31 SHC 2,73 2,56 2,48 2,37 2,22 2,05
TC 2,92 2,77 2,66 2,54 2,38 2,20
CM 0,56 0,59 0,63 0,66 0,69 0,73 21 SHC 1,63 1,53 1,49 1,43 1,36 1,27 23 SHC 1,88 1,76 1,71 1,66 1,58 1,50
17 25 SHC 2,12 2,00 1,94 1,88 1,81 1,73
27 SHC 2,37 2,23 0,74 2,11 2,04 1,95 29 SHC 2,62 2,46 2,39 2,34 2,27 2,18 31 SHC 2,85 2,69 2,62 2,54 2,38 2,20
TC 3,11 2,93 2,84 2,70 2,54 2,34
CM 0,58 0,61 0,65 0,68 0,71 0,75 21 SHC 1,37 1,29 1,24 1,19 1,12 1,03 23 SHC 1,62 1,51 1,47 1,41 1,34 1,26
19 25 SHC 1,86 1,73 1,70 1,64 1,57 1,49
27 SHC 2,10 1,95 1,93 2,14 1,80 1,71 29 SHC 2,34 2,17 2,15 2,09 2,03 1,94 31 SHC 2,59 2,40 2,38 2,32 2,25 2,17
TC 3,27 3,11 3,01 2,86 2,69 2,48
CM 0,58 0,62 0,66 0,69 0,73 0,77 23 SHC 1,34 1,27 1,23 1,17 1,10 1,02
21 25 SHC 1,59 1,49 1,45 1,40 1,33 1,24
27 SHC 1,83 1,71 1,68 1,62 1,56 1,47 29 SHC 2,08 1,93 1,90 1,85 1,78 1,70 31 SHC 2,31 2,16 2,13 2,07 2,01 1,93
TC 3,48 3,29 3,18 3,01 2,81 2,62
CM 0,59 0,63 0,67 0,71 0,75 0,79
23 25 SHC 1,31 1,23 1,19 1,13 1,06 0,99
27 SHC 1,55 1,44 1,41 1,35 1,28 1,21 29 SHC 1,80 1,66 1,64 1,58 1,51 1,44 31 SHC 2,05 1,90 1,87 1,80 1,73 1,67
TOTAL COOLING CAPACITY kW SHC: SENSIBLE HEAT CAPACITY kW CM: COMPRESSOR INPUT kW
RATING CONDITIONS
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
NOTE: Data referred to MRAF98C5T
CONDENSER
OUTDOOR AMBIENT TEMP. °C
35
OUTDOOR UNIT: GRF128L5TAA INDOOR UNIT: MRAF128C5T
220 - 240V ~ 50Hz RATING CAPACITY 3,40 kW moisture removal 1,5 l/h COMP. POWER INPUT 0,956 kW max comp input 1,156 kW AIR FLOW RATE 470 m³/h
EVAPORATOR ENT.TEMP. °C W.B. D.B. 20 25 30 35 40 43
TC 3,43 3,22 3,13 2,98 2,79 2,58
CM 0,68 0,76 0,83 0,90 0,97 1,04 21 SHC 2,38 2,21 2,17 2,09 2,00 1,90 23 SHC 2,69 2,50 2,45 2,38 2,29 2,19
15 25 SHC 2,99 2,79 2,73 2,66 2,57 2,47
27 SHC 3,30 3,08 3,02 2,95 2,79 2,58 29 SHC 3,43 3,22 3,13 2,98 2,79 2,58 31 SHC 3,43 3,22 3,13 2,98 2,79 2,58
TC 3,68 3,49 3,36 3,19 3,00 2,76
CM 0,71 0,78 0,86 0,93 1,00 1,07 21 SHC 2,05 1,93 1,88 1,80 1,71 1,60 23 SHC 2,36 2,22 2,16 2,08 2,00 1,89
17 25 SHC 2,67 2,52 2,45 2,37 2,28 2,17
27 SHC 2,98 2,81 0,74 2,65 2,56 2,46 29 SHC 3,29 3,10 3,02 2,94 2,85 2,74 31 SHC 3,59 3,39 3,30 3,19 3,00 2,76
TC 3,91 3,70 3,57 3,40 3,19 2,94
CM 0,74 0,81 0,88 0,96 1,03 1,10 21 SHC 1,73 1,62 1,57 1,49 1,40 1,30 23 SHC 2,04 1,90 1,86 1,78 1,69 1,59
19 25 SHC 2,35 2,18 2,14 2,06 1,98 1,87
27 SHC 2,64 2,46 2,42 2,35 2,26 2,16 29 SHC 2,95 2,73 2,71 2,63 2,55 2,44 31 SHC 3,26 3,02 2,99 2,92 2,83 2,73
TC 4,11 3,92 3,78 3,61 3,39 3,12
CM 0,81 0,87 0,93 1,00 1,06 1,13 23 SHC 1,69 1,60 1,54 1,47 1,38 1,28
21 25 SHC 2,00 1,87 1,83 1,76 1,67 1,57
27 SHC 2,31 2,15 2,11 2,04 1,96 1,85 29 SHC 2,62 2,43 2,39 2,33 2,24 2,14 31 SHC 2,91 2,71 2,68 2,61 2,53 2,42
TC 4,39 4,14 4,01 3,78 3,54 3,30
CM 0,87 0,93 0,98 1,04 1,10 1,16
23 25 SHC 1,65 1,55 1,50 1,42 1,33 1,24
27 SHC 1,96 1,82 1,78 1,70 1,61 1,52 29 SHC 2,27 2,09 2,07 1,99 1,90 1,81 31 SHC 2,58 2,39 2,36 2,27 2,18 2,10
TOTAL COOLING CAPACITY kW SHC: SENSIBLE HEAT CAPACITY kW CM: COMPRESSOR INPUT kW
RATING CONDITIONS
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
NOTE: Data referred to MRAF128C5T
CONDENSER
OUTDOOR AMBIENT TEMP. °C
36
OUTDOOR UNIT: GRF188L5TAA INDOOR UNIT: MPAF188C5T
220 - 240V ~ 50Hz RATING CAPACITY 5,20 kW moisture removal 2 l/h COMP. POWER INPUT 1,443 kW max comp input 1,793 kW AIR FLOW RATE 760 m³/h
EVAPORATOR ENT.TEMP. °C W.B. D.B. 20 25 30 35 40 43
TC 5,25 4,93 4,78 4,56 4,27 3,95
CM 0,96 1,09 1,22 1,36 1,49 1,62 21 SHC 3,64 3,38 3,31 3,20 3,06 2,91 23 SHC 4,12 3,83 3,75 3,64 3,50 3,35
15 25 SHC 4,57 4,27 4,18 4,07 3,93 3,78
27 SHC 5,05 4,72 4,62 4,51 4,27 3,95 29 SHC 5,25 4,93 4,78 4,56 4,27 3,95 31 SHC 5,25 4,93 4,78 4,56 4,27 3,95
TC 5,63 5,34 5,13 4,88 4,59 4,23
CM 1,00 1,14 1,27 1,40 1,53 1,66 21 SHC 3,14 2,96 2,87 2,76 2,62 2,45 23 SHC 3,62 3,40 3,30 3,19 3,05 2,89
17 25 SHC 4,09 3,85 3,74 3,63 3,49 3,32
27 SHC 4,56 4,29 0,74 4,06 3,92 3,76 29 SHC 5,04 4,75 4,61 4,50 4,36 4,19 31 SHC 5,49 5,19 5,04 4,88 4,59 4,23
TC 5,98 5,65 5,46 5,20 4,88 4,50
CM 1,05 1,18 1,31 1,44 1,57 1,71 21 SHC 2,64 2,48 2,40 2,28 2,15 1,99 23 SHC 3,11 2,91 2,84 2,72 2,59 2,43
19 25 SHC 3,59 3,33 3,27 3,15 3,03 2,86
27 SHC 4,04 3,76 3,71 3,80 3,46 3,30 29 SHC 4,51 4,18 4,14 4,02 3,90 3,73 31 SHC 4,99 4,62 4,58 4,47 4,33 4,17
TC 6,29 5,99 5,79 5,52 5,18 4,77
CM 1,20 1,31 1,42 1,53 1,64 1,75 23 SHC 2,58 2,44 2,36 2,25 2,11 1,96
21 25 SHC 3,06 2,86 2,79 2,69 2,55 2,40
27 SHC 3,53 3,30 3,23 3,12 3,00 2,83 29 SHC 4,00 3,71 3,66 3,56 3,43 3,27 31 SHC 4,45 4,15 4,10 3,99 3,87 3,71
TC 6,71 6,33 6,13 5,79 5,41 5,04
CM 1,36 1,45 1,53 1,62 1,71 1,79
23 25 SHC 2,52 2,37 2,29 2,17 2,03 1,90
27 SHC 2,99 2,78 2,72 2,60 2,46 2,33 29 SHC 3,47 3,20 3,17 3,04 2,91 2,77 31 SHC 3,94 3,65 3,61 3,47 3,33 3,21
TOTAL COOLING CAPACITY kW SHC: SENSIBLE HEAT CAPACITY kW CM: COMPRESSOR INPUT kW
RATING CONDITIONS
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
NOTE: Data referred to MPAF188C5T
CONDENSER
OUTDOOR AMBIENT TEMP. °C
37
OUTDOOR UNIT: GRF188L7TAA INDOOR UNIT: MPAF188C5T
380 - 415V 3N ~ 50Hz RATING CAPACITY 5,30 kW moisture removal 2 l/h COMP. POWER INPUT 1,493 kW max comp input 1,943 kW AIR FLOW RATE 760 m³/h
EVAPORATOR ENT.TEMP. °C W.B. D.B. 20 25 30 35 40 43
TC 5,35 5,02 4,87 4,64 4,36 4,02
CM 0,86 1,04 1,22 1,40 1,58 1,76 21 SHC 3,71 3,44 3,38 3,26 3,12 2,96 23 SHC 4,20 3,90 3,83 3,71 3,57 3,41
15 25 SHC 4,66 4,35 4,26 4,15 4,01 3,85
27 SHC 5,15 4,81 4,71 4,60 4,36 4,02 29 SHC 5,35 5,02 4,87 4,64 4,36 4,02 31 SHC 5,35 5,02 4,87 4,64 4,36 4,02
TC 5,73 5,44 5,23 4,98 4,68 4,31
CM 0,91 1,09 1,27 1,45 1,63 1,81 21 SHC 3,20 3,01 2,93 2,81 2,67 2,50 23 SHC 3,68 3,46 3,36 3,25 3,11 2,95
17 25 SHC 4,17 3,93 3,81 3,70 3,56 3,39
27 SHC 4,65 4,38 0,74 4,14 4,00 3,84 29 SHC 5,14 4,84 4,70 4,59 4,45 4,27 31 SHC 5,60 5,29 5,14 4,98 4,68 4,31
TC 6,10 5,76 5,57 5,30 4,98 4,59
CM 0,95 1,13 1,31 1,49 1,67 1,85 21 SHC 2,69 2,52 2,44 2,33 2,19 2,03 23 SHC 3,17 2,97 2,89 2,78 2,64 2,48
19 25 SHC 3,66 3,40 3,33 3,21 3,09 2,92
27 SHC 4,12 3,84 3,78 3,90 3,53 3,36 29 SHC 4,60 4,26 4,22 4,10 3,98 3,80 31 SHC 5,08 4,71 4,67 4,55 4,41 4,25
TC 6,41 6,11 5,90 5,62 5,28 4,86
CM 1,22 1,36 1,49 1,63 1,76 1,90 23 SHC 2,63 2,49 2,41 2,29 2,15 1,99
21 25 SHC 3,11 2,92 2,85 2,74 2,60 2,44
27 SHC 3,60 3,36 3,30 3,18 3,05 2,88 29 SHC 4,08 3,79 3,73 3,63 3,49 3,33 31 SHC 4,53 4,23 4,18 4,07 3,94 3,78
TC 6,84 6,45 6,24 5,90 5,52 5,14
CM 1,50 1,58 1,67 1,76 1,85 1,94
23 25 SHC 2,57 2,42 2,34 2,21 2,07 1,94
27 SHC 3,05 2,83 2,78 2,65 2,51 2,37 29 SHC 3,53 3,26 3,23 3,10 2,96 2,82 31 SHC 4,02 3,72 3,68 3,54 3,40 3,27
TOTAL COOLING CAPACITY kW SHC: SENSIBLE HEAT CAPACITY kW CM: COMPRESSOR INPUT kW
RATING CONDITIONS
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
NOTE: Data referred to MPAF188C5T
CONDENSER
OUTDOOR AMBIENT TEMP. °C
38
OUTDOOR UNIT: GRF228L7TAA INDOOR UNIT: MPAF228C5T
380 - 415V 3N ~ 50Hz RATING CAPACITY 6,50 kW moisture removal 2,5 l/h COMP. POWER INPUT 1,85 kW max comp input 2,37 kW AIR FLOW RATE 830 m³/h
EVAPORATOR ENT.TEMP. °C W.B. D.B. 20 25 30 35 40 43
TC 6,57 6,16 5,98 5,69 5,34 4,93
CM 1,13 1,33 1,53 1,74 1,94 2,15 21 SHC 4,56 4,22 4,14 4,00 3,83 3,63 23 SHC 5,15 4,79 4,69 4,55 4,38 4,18
15 25 SHC 5,72 5,34 5,23 5,09 4,92 4,72
27 SHC 6,31 5,90 5,78 5,64 5,34 4,93 29 SHC 6,57 6,16 5,98 5,69 5,34 4,93 31 SHC 6,57 6,16 5,98 5,69 5,34 4,93
TC 7,03 6,67 6,42 6,10 5,74 5,28
CM 1,18 1,39 1,59 1,79 2,00 2,20 21 SHC 3,93 3,69 3,59 3,45 3,28 3,07 23 SHC 4,52 4,25 4,13 3,98 3,82 3,62
17 25 SHC 5,11 4,81 4,68 4,54 4,37 4,15
27 SHC 5,71 5,37 0,74 5,07 4,90 4,71 29 SHC 6,30 5,93 5,77 5,62 5,45 5,24 31 SHC 6,86 6,49 6,30 6,10 5,74 5,28
TC 7,48 7,07 6,83 6,50 6,10 5,62
CM 1,24 1,44 1,65 1,85 2,05 2,26 21 SHC 3,30 3,09 3,00 2,85 2,68 2,49 23 SHC 3,89 3,64 3,55 3,41 3,24 3,04
19 25 SHC 4,49 4,17 4,08 3,94 3,79 3,58
27 SHC 5,05 4,71 4,63 4,75 4,32 4,13 29 SHC 5,64 5,23 5,17 5,03 4,88 4,66 31 SHC 6,23 5,78 5,72 5,58 5,41 5,21
TC 7,87 7,49 7,23 6,90 6,47 5,96
CM 1,53 1,68 1,84 2,00 2,16 2,31 23 SHC 3,23 3,06 2,95 2,81 2,64 2,44
21 25 SHC 3,82 3,58 3,49 3,36 3,19 3,00
27 SHC 4,41 4,12 4,04 3,90 3,74 3,53 29 SHC 5,00 4,64 4,58 4,45 4,28 4,08 31 SHC 5,56 5,19 5,13 4,99 4,83 4,63
TC 8,39 7,91 7,66 7,23 6,77 6,30
CM 1,82 1,93 2,04 2,15 2,26 2,37
23 25 SHC 3,15 2,97 2,87 2,71 2,54 2,37
27 SHC 3,74 3,47 3,41 3,25 3,08 2,91 29 SHC 4,33 3,99 3,96 3,80 3,63 3,46 31 SHC 4,92 4,56 4,51 4,34 4,17 4,01
TOTAL COOLING CAPACITY kW SHC: SENSIBLE HEAT CAPACITY kW CM: COMPRESSOR INPUT kW
RATING CONDITIONS
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
NOTE: Data referred to MPAF228C5T
CONDENSER
OUTDOOR AMBIENT TEMP. °C
39
OUTDOOR UNIT: GRF258L7TAA INDOOR UNIT: CAF258C5T
380 - 415V 3N ~ 50Hz RATING CAPACITY 7,80 kW moisture removal 3 l/h COMP. POWER INPUT 2,261 kW max comp input 3,081 kW AIR FLOW RATE 1020 m³/h
EVAPORATOR ENT.TEMP. °C W.B. D.B. 20 25 30 35 40 43
TC 7,88 7,39 7,17 6,83 6,41 5,92
CM 1,10 1,44 1,78 2,13 2,47 2,81 21 SHC 5,47 5,07 4,97 4,80 4,60 4,36 23 SHC 6,18 5,74 5,63 5,46 5,26 5,02
15 25 SHC 6,86 6,40 6,27 6,10 5,90 5,66
27 SHC 7,57 7,08 6,94 6,77 6,41 5,92 29 SHC 7,88 7,39 7,17 6,83 6,41 5,92 31 SHC 7,88 7,39 7,17 6,83 6,41 5,92
TC 8,44 8,00 7,70 7,33 6,88 6,34
CM 1,17 1,51 1,85 2,19 2,54 2,88 21 SHC 4,71 4,43 4,31 4,14 3,93 3,68 23 SHC 5,42 5,10 4,95 4,78 4,58 4,34
17 25 SHC 6,13 5,78 5,61 5,44 5,24 4,99
27 SHC 6,85 6,44 0,74 6,09 5,88 5,65 29 SHC 7,56 7,12 6,92 6,75 6,55 6,29 31 SHC 8,24 7,78 7,56 7,33 6,88 6,34
TC 8,97 8,48 8,19 7,80 7,33 6,75
CM 1,23 1,58 1,92 2,26 2,60 2,95 21 SHC 3,96 3,71 3,59 3,43 3,22 2,98 23 SHC 4,67 4,37 4,26 4,09 3,88 3,65
19 25 SHC 5,38 5,00 4,90 4,73 4,54 4,29
27 SHC 6,06 5,65 5,56 5,70 5,19 4,95 29 SHC 6,77 6,27 6,21 6,04 5,85 5,60 31 SHC 7,48 6,94 6,87 6,70 6,49 6,26
TC 9,44 8,99 8,68 8,27 7,77 7,16
CM 1,82 2,06 2,30 2,54 2,77 3,01 23 SHC 3,88 3,67 3,54 3,37 3,17 2,93
21 25 SHC 4,58 4,30 4,19 4,04 3,83 3,59
27 SHC 5,29 4,94 4,85 4,68 4,49 4,24 29 SHC 6,00 5,57 5,49 5,34 5,14 4,90 31 SHC 6,67 6,23 6,16 5,99 5,80 5,56
TC 10,06 9,49 9,19 8,68 8,12 7,56
CM 2,40 2,54 2,67 2,81 2,95 3,08
23 25 SHC 3,78 3,56 3,44 3,26 3,05 2,85
27 SHC 4,49 4,17 4,09 3,90 3,70 3,49 29 SHC 5,20 4,79 4,75 4,56 4,36 4,15 31 SHC 5,91 5,48 5,41 5,21 5,00 4,82
TOTAL COOLING CAPACITY kW SHC: SENSIBLE HEAT CAPACITY kW CM: COMPRESSOR INPUT kW
RATING CONDITIONS
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
NOTE: Data referred to
CAF258C5T
CONDENSER
OUTDOOR AMBIENT TEMP. °C
40
OUTDOOR UNIT: GRF368L7TAA INDOOR UNIT: CAF368C5T
380 - 415V 3N ~ 50Hz RATING CAPACITY 10,40 kW moisture removal 3,5 l/h COMP. POWER INPUT 2,802 kW max comp input 3,402 kW AIR FLOW RATE 1920 m³/h
EVAPORATOR ENT.TEMP. °C W.B. D.B. 20 25 30 35 40 43
TC 10,50 9,86 9,56 9,11 8,55 7,89
CM 1,99 2,20 2,42 2,63 2,85 3,07 21 SHC 7,29 6,76 6,62 6,40 6,13 5,81 23 SHC 8,24 7,66 7,51 7,28 7,01 6,69
15 25 SHC 9,15 8,54 8,37 8,14 7,87 7,55
27 SHC 10,10 9,44 9,25 9,02 8,55 7,89 29 SHC 10,50 9,86 9,56 9,11 8,55 7,89 31 SHC 10,50 9,86 9,56 9,11 8,55 7,89
TC 11,25 10,67 10,26 9,77 9,18 8,46
CM 2,07 2,29 2,50 2,72 2,93 3,15 21 SHC 6,28 5,91 5,74 5,52 5,25 4,91 23 SHC 7,23 6,79 6,60 6,38 6,10 5,79
17 25 SHC 8,18 7,70 7,48 7,26 6,99 6,65
27 SHC 9,13 8,59 0,74 8,12 7,85 7,53 29 SHC 10,08 9,49 9,22 9,00 8,73 8,39 31 SHC 10,98 10,38 10,08 9,77 9,18 8,46
TC 11,96 11,30 10,92 10,40 9,77 9,00
CM 2,15 2,37 2,59 2,80 3,02 3,23 21 SHC 5,28 4,95 4,79 4,57 4,30 3,98 23 SHC 6,23 5,82 5,67 5,45 5,18 4,86
19 25 SHC 7,18 6,67 6,53 6,31 6,06 5,72
27 SHC 8,08 7,53 7,42 7,95 6,92 6,60 29 SHC 9,03 8,37 8,27 8,05 7,80 7,46 31 SHC 9,97 9,25 9,16 8,93 8,66 8,34
TC 12,58 11,98 11,58 11,03 10,35 9,54
CM 2,36 2,55 2,74 2,93 3,13 3,32 23 SHC 5,17 4,89 4,73 4,50 4,23 3,91
21 25 SHC 6,11 5,73 5,58 5,38 5,11 4,79
27 SHC 7,06 6,59 6,47 6,24 5,99 5,65 29 SHC 8,00 7,43 7,33 7,12 6,85 6,53 31 SHC 8,90 8,30 8,21 7,98 7,73 7,42
TC 13,42 12,66 12,25 11,58 10,83 10,08
CM 2,56 2,73 2,90 3,07 3,23 3,40
23 25 SHC 5,04 4,75 4,59 4,34 4,07 3,80
27 SHC 5,99 5,56 5,45 5,20 4,93 4,66 29 SHC 6,93 6,39 6,33 6,08 5,81 5,54 31 SHC 7,88 7,30 7,21 6,94 6,67 6,42
TOTAL COOLING CAPACITY kW SHC: SENSIBLE HEAT CAPACITY kW CM: COMPRESSOR INPUT kW
RATING CONDITIONS
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
NOTE: Data referred to
CAF368C5T
CONDENSER
OUTDOOR AMBIENT TEMP. °C
41
OUTDOOR UNIT: GRF488L7TAA INDOOR UNIT: CAF488C5T
380 - 415V 3N ~ 50Hz RATING CAPACITY 14,10 kW moisture removal 5 l/h COMP. POWER INPUT 4,502 kW max comp input 5,902 kW AIR FLOW RATE 1920 m³/h
EVAPORATOR ENT.TEMP. °C W.B. D.B. 20 25 30 35 40 43
TC 14,24 13,36 12,97 12,35 11,59 10,70
CM 2,54 3,10 3,67 4,23 4,80 5,36 21 SHC 9,88 9,16 8,98 8,67 8,31 7,88 23 SHC 11,17 10,38 10,18 9,87 9,50 9,07
15 25 SHC 12,40 11,57 11,34 11,03 10,67 10,24
27 SHC 13,69 12,79 12,54 12,23 11,59 10,70 29 SHC 14,24 13,36 12,97 12,35 11,59 10,70 31 SHC 14,24 13,36 12,97 12,35 11,59 10,70
TC 15,26 14,47 13,92 13,24 12,44 11,46
CM 2,67 3,24 3,80 4,37 4,93 5,50 21 SHC 8,52 8,01 7,79 7,48 7,11 6,65 23 SHC 9,80 9,21 8,95 8,64 8,28 7,85
17 25 SHC 11,09 10,44 10,15 9,84 9,47 9,01
27 SHC 12,38 11,64 0,74 11,00 10,64 10,21 29 SHC 13,66 12,87 12,51 12,20 11,83 11,37 31 SHC 14,89 14,07 13,67 13,24 12,44 11,46
TC 16,22 15,33 14,81 14,10 13,24 12,20
CM 2,81 3,37 3,94 4,50 5,07 5,63 21 SHC 7,16 6,71 6,50 6,19 5,82 5,39 23 SHC 8,44 7,89 7,69 7,39 7,02 6,59
19 25 SHC 9,73 9,04 8,86 8,55 8,21 7,76
27 SHC 10,95 10,21 10,05 10,60 9,38 8,95 29 SHC 12,24 11,34 11,22 10,91 10,58 10,12 31 SHC 13,52 12,54 12,41 12,11 11,74 11,31
TC 17,06 16,25 15,69 14,96 14,04 12,94
CM 3,68 4,10 4,51 4,93 5,35 5,77 23 SHC 7,01 6,63 6,41 6,10 5,73 5,30
21 25 SHC 8,29 7,77 7,57 7,30 6,93 6,50
27 SHC 9,57 8,94 8,77 8,46 8,12 7,66 29 SHC 10,85 10,07 9,93 9,66 9,29 8,86 31 SHC 12,06 11,26 11,13 10,82 10,48 10,05
TC 18,19 17,16 16,61 15,69 14,68 13,67
CM 4,55 4,82 5,09 5,36 5,63 5,90
23 25 SHC 6,84 6,43 6,22 5,89 5,52 5,15
27 SHC 8,12 7,53 7,39 7,05 6,68 6,31 29 SHC 9,40 8,67 8,58 8,25 7,88 7,51 31 SHC 10,68 9,90 9,78 9,41 9,04 8,71
TOTAL COOLING CAPACITY kW SHC: SENSIBLE HEAT CAPACITY kW CM: COMPRESSOR INPUT kW
RATING CONDITIONS
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
NOTE: Data referred to
CAF488C5T
CONDENSER
OUTDOOR AMBIENT TEMP. °C
42
6. ELECTRICAL DATA
6-1 Electrical characteristics
OUTDOOR UNIT: GRF98L5TAA
COOLING
Indoor Unit Complete Unit
Fan Motor Fan Motor Compressor performance at Rating conditions Running Amps. A 0,12 0,28 3,00 3,40
Power input Kw 0,027 0,063 0,680 0,770
Full load conditions Running Amps. A 0,12 0,28 3,60 4,00
Power input Kw 0,027 0,063 0,790 0,880
NOTE: Data referred to indoor unit MRAF98C5T model.
For other indoor unit models there could be some differences.
OUTDOOR UNIT: GRF128L5TAA
COOLING
Indoor Unit Complete Unit
Fan Motor Fan Motor Compressor performance at Rating conditions Running Amps. A 0,13 0,28 4,29 4,70
Power input Kw 0,031 0,063 0,956 1,050
Full load conditions Running Amps. A 0,13 0,28 5,09 5,50
Power input Kw 0,031 0,063 1,156 1,250
NOTE: Data referred to indoor unit MRAF128C5T model.
For other indoor unit models there could be some differences.
OUTDOOR UNIT: GRF188L5TAA
COOLING
Indoor Unit Complete Unit
Fan Motor Fan Motor Compressor performance at Rating conditions Running Amps. A 0,37 0,41 6,32 7,10
Power input Kw 0,070 0,087 1,443 1,600
Full load conditions Running Amps. A 0,37 0,41 7,72 8,50
Power input Kw 0,070 0,087 1,793 1,950
NOTE: Data referred to indoor unit MPAF188C5T model.
For other indoor unit models there could be some differences.
Rating Conditions: Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions: Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.
Outdoor unit
230V 1-Phase 50 Hz
Outdoor unit
230V 1-Phase 50 Hz
Outdoor unit
230V 1-Phase 50 Hz
43
OUTDOOR UNIT: GRF188L7TAA
COOLING
Indoor Unit Complete Unit
Fan Motor Fan Motor Compressor performance at Rating conditions Running Amps. A 0,37 0,41 2,62 3,40
Power input Kw 0,070 0,087 1,493 1,650
Full load conditions Running Amps. A 0,37 0,41 3,32 4,10
Power input Kw 0,070 0,087 1,943 2,100
NOTE: Data referred to indoor unit MPAF188C5T model.
For other indoor unit models there could be some differences.
OUTDOOR UNIT: GRF228L7TAA
COOLING
Indoor Unit Complete Unit
Fan Motor Fan Motor Compressor performance at Rating conditions Running Amps. A 0,40 0,67 3,13 4,20
Power input Kw 0,086 0,144 1,850 2,080
Full load conditions Running Amps. A 0,40 0,67 3,93 5,00
Power input Kw 0,086 0,144 2,370 2,600
NOTE: Data referred to indoor unit MPAF228C5T model.
For other indoor unit models there could be some differences.
OUTDOOR UNIT: GRF258L7TAA
COOLING
Indoor Unit Complete Unit
Fan Motor Fan Motor Compressor performance at Rating conditions Running Amps. A 0,77 0,67 3,66 5,10
Power input Kw 0,175 0,144 2,261 2,580
Full load conditions Running Amps. A 0,77 0,67 4,76 6,20
Power input Kw 0,175 0,144 3,081 3,400
NOTE: Data referred to indoor unit CAF258C5
T
model.
For other indoor unit models there could be some differences.
Rating Conditions: Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions: Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.
Outdoor unit
230V 1-Phase 50 Hz
Outdoor unit
230V 1-Phase 50 Hz
Outdoor unit
230V 1-Phase 50 Hz
44
OUTDOOR UNIT: GRF368L7TAA
COOLING
Indoor Unit Complete Unit
Fan Motor Fan Motor Compressor performance at Rating conditions Running Amps. A 0,92 1,34 4,34 6,60
Power input Kw 0,210 0,29 2,802 3,300
Full load conditions Running Amps. A 0,92 1,34 5,14 7,40
Power input Kw 0,210 0,29 3,402 3,900
NOTE: Data referred to indoor unit CAF368C5
T
model.
For other indoor unit models there could be some differences.
OUTDOOR UNIT: GRF488L7TAA
COOLING
Indoor Unit Complete Unit
Fan Motor Fan Motor Compressor performance at Rating conditions Running Amps. A 0,92 1,34 7,44 9,70
Power input Kw 0,210 0,29 4,502 5,000
Full load conditions Running Amps. A 0,92 1,34 9,34 11,60
Power input Kw 0,210 0,29 5,902 6,400
NOTE: Data referred to indoor unit CAF488C5
T
model.
For other indoor unit models there could be some differences.
Rating Conditions: Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions: Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.
Outdoor unit
230V 1-Phase 50 Hz
Outdoor unit
230V 1-Phase 50 Hz
45
6-2 Electric Wiring Diagram
GRF98L5TA
A
GRF128L5TA
A
GRF188L5TAA
46
GRF188L7TAA
GRF228L7TAA
47
GRF258L7TAA
GRF368L7TAA
48
GRF488L7TAA
49
6-3 System Wiring Diagram
MRAF98C5T MRAF128C5T GRF98L5TAA GRF128L5TAA
MPAF188C5T GRF188L5TAA
MPAF188C5T CAF258C5T GRF188L7TAA GRF258L7TAA MPAF228C5T CAF368C5T GRF228L7TAA GRF368L7TAA
CAF488C5T GRF488L7TAA
50
0.8180.557.00 06/2008
R.D. 28 Reyrieux BP 131 - 01601 Trévoux CEDEX France
Tél. 04.74.00.92.92 - Fax 04.74.00.42.00
R.C.S. Bourg-en-Bresse B 759 200 728
Loading...