Technibel GR360M4R5TAA, MCA90MR5TAA Technical Data & Service Manual

TECHNICAL DATA & SERVICE MANUAL
Outdoor Unit Indoor Unit
GR360M4R5TAA MCA90MR5TAA (x4)
0.8180.212.4 06/2002
MCA90MR5TAA
GR360M4R5TAA
Important! Please Read Before Starting
This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
Carefully read this instruction booklet before beginning.
Follow each installation or repair step exactly as shown.
Observe all local, state, and national electrical codes.
Pay close attention to all warning and caution notices
given in this manual.
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.
If Necessary, Get Help
These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.
Special Precautions
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or death.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.
WARNING
CAUTION
WARNING
When Transporting
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.
When Installing…
…In a Ceiling or Wall
Make sure the ceiling/wall is strong enough to hold the unit’s weight. It may be necessary to construct a strong wood or metal frame to provide added support.
…In a Room
Properly insulate any tubing run inside a room to prevent “sweating” that can cause dripping and water damage to walls and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak­free connection.
• Check carefully for leaks before starting the test run.
When Servicing
• Turn the power off at the main power box (mains) before opening the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.
Others
• Ventilate any enclosed areas when installing or testing the refrigeration system. Escaped refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas.
• Confirm upon completing installation that no refrigerant gas is leaking. If escaped gas comes in contact with a stove, gas water heater, electric room heater or other heat source, it can produce dangerously toxic gas.
CAUTION
i
Table of Contents
Page
Unit combination iv 1 OPERATING RANGE 1
2 SPECIFICATIONS
2-1 Unit Specification 2 2-2 Major Component Specifications 5
2-3 Other Component Specifications 7 3 DIMENSIONAL DATA 8 4 COOLING CAPACITY 10 5 HEATING CAPACITY 11 6 AIR THROW DISTANCE CHART 12
7 REFRIGERANT FLOW DIAGRAM 13 8 ELECTRICAL DATA
8-1 Electrical Characteristic 15
8-2 Electric Wiring Diagrams 16
10 TROUBLESHOOTING
10-1 Check before and after troubleshooting 33
10-2 Air Conditioner Does not operate 34
10-3 Some Part of Air Conditioner does not operate 38
10-4 Air Conditioner operates, but abnormalities are observed 40 10-5 If a sensor is defective 42
9 FUNCTION
9-1 Cool Mode Operation 17 9-2 Heat Mode Operation 18 9-3 Dry mode operation 19 9-4 Fan Operation 20 9-5 Protection Operations in Cool and Dry Mode 21 9-6 Protection Operation in Heat Mode 23 9-7 Cool Draft Prevention (Heating) 26 9-8 Others Features 27
11 ARRANGEMENT OF ELECTRICAL COMPONENTS 43
13 CHECKING ELECTRICAL COMPONENTS
13-1 Measurement of insulation Resistance 50
13-2 Checking Continuity of Fuse on PCB Ass’y 51 13-3 Checking Motor Capacitor 51
ii
12 SPECIAL PRECAUTIONS WHEN SERVICING THE UNIT
12-1 Solenoid valves opening for servicing 45
12-2 Refrigerant recovery 46
12-3 Service on outdoor unit 46
12-4 Evacuation using vacuum pump 46
12-5 Refrigerant charging 47
12-6 Reset the unit for normal operation 48
Unit Combination
Combine indoor and outdoor units only as listed below.
Symbol of
Indoor Unit
Outdoor Unit Indoor Unit
AE036QH
Refer to
MCA90MR5 A1
Fig.1
A2 B1
B2
Fig.1
SYSTEM
A
B
iii
MCA90MR5
MCA90MR5
MCA90MR5
1. OPERATING RANGE
Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp.
Cooling
Maximum 32°C DB / 23°C WB 46°C DB
Minimum 19°C DB / 14°C WB 19°C DB
Heating
Maximum 27°C DB 24°C DB / 18°C WB
Minimum - –5°C DB / –6°C WB
1
2. SPECIFICATIONS
2-1. Unit Specifications
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 27°C DB/19°C WB
Outdoor air temperature 35°C DB/24°C WB
Heating: Indoor air temperature 20°C DB
Outdoor air temperature 7°C DB/6°C WB
No. of indoor units. 1 indoor unit (A1 or A2, B1 or B2)
Power Source 220 – 240 V ~ 50 Hz
Cooling Heating
Capacity
kW 2.55 3.05
BTU/h 8,700 10,400
Air circulation (High) m
3
/h 470 Moisture removal (High) Liters/h 0.91 — Voltage rating V 230 Available voltage range V 198 to 264 Running amperes A 9.8 10.2 Power input W 2200 2300 Power factor % 98 98 C.O.P. W/W 1.16 1.33 Compressor locked rotor amperes A 54 Controls / Temperature control Microprocessor / I.C. thermostat Control unit Wireless remote control unit Timer 24 hr ON / OFF Fan speeds Indoor / Outdoor 3 and Auto / 1
Airflow direction (Indoor)
Horizontal Manual
Vertical Auto Air filter Washable, Anti–Mold Compressor Rotary (Hermetic) Refrigerant / Amount charged at shipment g R22 / 1900 (each system) Refrigerant control Capillary tube
Power sound level
Indoor – Hi dB-A 51
Outdoor – Hi dB-A 70 Refrigerant tubing connections Flare type Max. allowable tubing length at shipment m 7.5
Refrigerant tube
Narrow tube mm (in.) 6.35 (1/4) diameter
Wide tube mm (in.) 9.52 (3/8)
Indoor Unit Outdoor Unit
Unit dimensions Height mm
Width mm see page 8 see page 9
Depth mm package dimensions Height mm 243 1390
Width mm 855 1141
Depth mm 332 418 Weight
Net kg 8.0 128
Shipping kg 10.0 138 Shipping volume m
3
0.07 0.59
Dimensions & Weight Features Electrical Rating Performance
Indoor Unit MCA90MR5TAA Outdoor Unit GR360M4R5TAA
2
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 27°C DB/19°C WB
Outdoor air temperature 35°C DB/24°C WB
Heating: Indoor air temperature 20°C DB
Outdoor air temperature 7°C DB/6°C WB
No. of indoor units. 1 SYSTEM (A or B)
Power Source 220 – 240 V ~ 50 Hz
Cooling Heating
Capacity
kW 5.6 5.8
BTU/h 19,300 19,800
Air circulation (High) m
3
/h 470 Moisture removal (High) Liters/h 2.2 — Voltage rating V 230 Available voltage range V 198 to 264 Running amperes A 9.8 10.2 Power input W 2200 2300 Power factor % 98 98 C.O.P. W/W 2.54 2.52 Compressor locked rotor amperes A 54 Controls / Temperature control Microprocessor / I.C. thermostat Control unit Wireless remote control unit Timer 24 hr ON / OFF Fan speeds Indoor / Outdoor 3 and Auto / 1
Airflow direction (Indoor)
Horizontal Manual
Vertical Auto Air filter Washable, Anti–Mold Compressor Rotary (Hermetic) Refrigerant / Amount charged at shipment g R22 / 1900 (each system) Refrigerant control Capillary tube
Power sound level
Indoor – Hi dB-A 54
Outdoor – Hi dB-A 70 Refrigerant tubing connections Flare type Max. allowable tubing length at shipment m 7.5
Refrigerant tube
Narrow tube mm (in.) 6.35 (1/4) diameter
Wide tube mm (in.) 9.52 (3/8)
Indoor Unit Outdoor Unit
Unit dimensions Height mm
Width mm see page 8 see page 9
Depth mm package dimensions Height mm 243 1390
Width mm 855 1141
Depth mm 332 418 Weight
Net kg 8.0 128
Shipping kg 10.0 138 Shipping volume m
3
0.07 0.59
Dimensions & Weight Features Electrical Rating Performance
Indoor Unit MCA90MR5TAA Outdoor Unit GR360M4R5TAA
3
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 27°C DB/19°C WB
Outdoor air temperature 35°C DB/24°C WB
Heating: Indoor air temperature 20°C DB
Outdoor air temperature 7°C DB/6°C WB
No. of indoor units. 2 SYSTEMS (A + B)
Power Source 220 – 240 V ~ 50 Hz
Cooling Heating
Capacity
kW 11.2 11.6
BTU/h 38,300 39,600
Air circulation (High) m
3
/h 470 Moisture removal (High) Liters/h 4.4 — Voltage rating V 230 Available voltage range V 198 to 264 Running amperes A 19.6 20.4 Power input W 4400 4600 Power factor % 98 98 C.O.P. W/W 2.54 2.52 Compressor locked rotor amperes A 54 Controls / Temperature control Microprocessor / I.C. thermostat Control unit Wireless remote control unit Timer 24 hr ON / OFF Fan speeds Indoor / Outdoor 3 and Auto / 1
Airflow direction (Indoor)
Horizontal Manual
Vertical Auto Air filter Washable, Anti–Mold Compressor Rotary (Hermetic) Refrigerant / Amount charged at shipment g R22 / 1900 (each system) Refrigerant control Capillary tube
Power sound level
Indoor – Hi dB-A 54
Outdoor – Hi dB-A 73 Refrigerant tubing connections Flare type Max. allowable tubing length at shipment m 7.5
Refrigerant tube
Narrow tube mm (in.) 6.35 (1/4) diameter
Wide tube mm (in.) 9.52 (3/8)
Indoor Unit Outdoor Unit
Unit dimensions Height mm
Width mm see page 8 see page 9
Depth mm package dimensions Height mm 243 1390
Width mm 855 1141
Depth mm 332 418 Weight
Net kg 8.0 128
Shipping kg 10.0 138 Shipping volume m
3
0.07 0.59
Dimensions & Weight Features Electrical Rating Performance
Indoor Unit MCA90MR5TAA Outdoor Unit GR360M4R5TAA
4
2-2. Major Component Specifications
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Part No. WSA –LTR Controls Microprocessor Control circuit fuse 250 V – 3.15 A
Remote Control Unit RC–2(WOA)
Type Cross–flow Number ... Dia. and length mm 1 ... ø95 / L617 Fan motor model ... Number KFV4Q–11H5P -S... 1 No. of poles ... rpm (230 V, High) 4 ... 1190 Nominal output W 10 Coil resistance (Ambient temp. 20°C) WHT – BRN : 561.8
WHT – VLT : 197.4 VLT – ORG : 63.4 ORG – YEL : 155.7
YEL – PNK : 115.9
Safety
Type Internal thermal fuse
devices
Operating temp.
Open °C 145 ± 2 Close
Run capacitor
µF 0.8
VAC 440 Type Stepping motor Model MP24GA1 Rating DC 12 V Coil resistance (Ambient temp. 25°C) WHT – BLU (respectively 4 wires) : 380 ± 7% Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.4 Face area m
2
0.130
Heat
Exch. Coil
Flap Motor Fan & Fan Motor
Controller
PCB
Indoor Unit MCA90MR5TAA
5
6
Controller PCB MSC1V1 (40V1-D)
Control circuit fuse 250 V– 3.15 A Type Rotary (Hermetic) Compressor model ... Number PH36VTRT ... 2 Nominal output W 1600 x 2 Compressor oil ... Amount cc DIAMOND MS32(N-1) ... 900 x 2 Coil resistance (Ambient temp. 25°C) C – R : 1.08
C – S : 6.36 Type Internal Overload relay ... Number UP3RE0302 ... 2
Safety
Operating
Open °C 155 ± 5
devices
temp.
Close °C 90 ± 10
Operating amp.(Ambient temp. 25°C) Trip in 3 to 10 sec. at 54 A
Run capacitor µF 55 ... 2
... Number VAC 450 ... 2 Type Propeller Number ... Dia. mm 2 ... ø460 Fan motor model ... Number KFC-6T-91C5P ... 2 No. of poles ... rpm (230 V,High) 6 ... 868 Nominal output W 100 Coil resistance (Ambient temp. 20°C) WHT – BRN : 61 YEL - PNK: 17.7
WHT – YEL: 64.3 Safety Type Internal protector devices
Operating
Open °C 130 ± 8
temp.
Close 79 ± 15
Run capacitor
µF 5.0
VAC 480 Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 2 Face area m
2
0.45 (each system)
External Finish Acrylic baked-on enamel finish
Heat
Exch. Coil
CompressorFan & Fan Motor
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
outdoor Unit GR360M4R5TAA
2-3. Other Component Specifications
Indoor Unit MCA90MR5TAA
Thermistor (Coil sensor ) NTC - SENSOR
Resistance k 25°C 10 ± 5%
Outdoor Unit GR360M4R5TAA
Power Relay (PRa, PRb)
DFU24D1-F (M)
Coil rating DC 24V Coil resistance Ω (at 20°C) 650 ± 10% Contact rating AC 250V, 20A
Thermistor (TOA, TCa, TCb) NTC - SENSOR
Resistance k
Solenoid Coil - 4 way Valve (RVa1/a2, RVb1/b2) CHV-01AI506B1 (Coil), CHV-0101 (Valve)
Coil rating
AC 230V, 50Hz, 6W
Coil resistance (at 20°C) 1400 ± 7%
Thermistor (Room sensor ) NTC - SENSOR
Resistance k 25°C 10 ± 5%
Solenoid Coil - Bypass (SVa3, SVb3) NEV-MOAJ503B0 (Coil), NEV-202DXF (Valve)
Coil rating
AC 230V, 50Hz, 5W
Coil resistance Ω (at 20°C) 1450 ± 7%
Solenoid Coil - Indoor units (SVa1/a2, SVb1/b2) HM2-9100/RA6 (Coil), CASTEL (Valve)
Coil rating
AC 230V, 50Hz, 8W
Coil resistance (at 20°C) 1000 ± 7%
7
25°C 10 ± 5%
3. DIMENSIONAL DATA
Indoor Unit MCA90MR5TAA
58.599.5
805 177
41.0
41.0 270
Narrow tube ø6.35 (1/4")
Wide tube ø9.52 (3/8")
Center of tubing hole (2 places)
Drain hose ø18
Remote control unit
18.5
61
172.5
Unit : mm
8
Outdoor Unit GR360M4R5TAA
9
4. COOLING CAPACITY (System A or B)
Indoor Unit MCA90MR5TAA Outdoor Unit GR360M4R5TAA
230V 50 Hz RATING CAPACITY 5,6 kW
AIR FLOW RATE 470 x 2 m³/h
EVAPORATOR CONDENSER
ENT.TEMP. °C OUTDOOR AMBIENT TEMP. °C
W.B. D.B. 25 30 35 40 43
TC 5,31 5,15 4,91 4,60 4,25
CM 1,81 1,93 2,08 2,28 2,48 21 SHC 3,64 3,57 3,45 3,30 3,13 23 SHC 4,12 4,04 3,92 3,77 3,60
15 25 SHC 4,60 4,50 4,38 4,24 4,07
27 SHC 5,08 4,98 4,86 4,60 4,25 29 SHC 5,31 5,15 4,91 4,60 4,25 31 SHC 5,31 5,15 4,91 4,60 4,25
TC 5,75 5,53 5,26 4,94 4,55
CM 1,85 1,99 2,13 2,35 2,55 21 SHC 3,18 3,09 2,97 2,82 2,64 23 SHC 3,66 3,55 3,43 3,29 3,12
17 25 SHC 4,15 4,03 3,91 3,76 3,58
27 SHC 4,62 4,49 4,37 4,22 4,05 29 SHC 5,11 4,97 4,85 4,70 4,52 31 SHC 5,59 5,43 5,26 4,94 4,55
TC 6,09 5,88 5,60 5,26 4,85
CM 1,95 2,05 2,20 2,41 2,62 21 SHC 2,67 2,58 2,46 2,31 2,14 23 SHC 3,13 3,06 2,93 2,79 2,62
19 25 SHC 3,59 3,52 3,40 3,26 3,08
27 SHC 4,05 3,99 3,87 3,73 3,55 29 SHC 4,50 4,46 4,33 4,20 4,02 31 SHC 4,98 4,93 4,81 4,66 4,49
TC 6,45 6,23 5,94 5,58 5,14
CM 1,99 2,11 2,27 2,48 2,70 23 SHC 2,63 2,54 2,42 2,28 2,11
21 25 SHC 3,08 3,01 2,90 2,75 2,58
27 SHC 3,55 3,48 3,36 3,23 3,04 29 SHC 4,00 3,94 3,83 3,69 3,52 31 SHC 4,47 4,42 4,30 4,16 3,99
TC 6,89 6,60 6,23 5,83 5,43
CM 2,03 2,16 2,32 2,54 2,76
23 25 SHC 2,58 2,47 2,34 2,19 2,05
27 SHC 3,02 2,93 2,80 2,65 2,51 29 SHC 3,48 3,41 3,27 3,13 2,98 31 SHC 3,98 3,88 3,74 3,59 3,46
TC: TOTAL COOLING CAPACITY kW SHC: SENSIBLE HEAT CAPACITY kW CM: COMPRESSOR INPUT kW
RATING CONDITIONS
OUTDOOR AMBIENT TEMPERATURE 35°C D.B. INDOOR UNIT ENTERING AIR TEMP. 27°C D.B./19°C W.B.
10
5. HEATING CAPACITY (System A, B or A+B)
Indoor Unit MCA90MR5TAA Outdoor Unit GR360M4R5TAA
Outdoor temperature (°C DB)
Heating capacity ratio (%)
NOTE
1) … Point of Rating condition Black dot in the chart indicate the following rating condition.
Indoor : 20°C DB Outdoor : 7°C DB / 6°C WB
2) Above characteristics take into consideration defrost operation.
3) Fan speed : High
11
Indoor Unit MCA90MR5TAA
0
123456789
1
2
3
4
Horizontal distance (m)
Axis air velocity (m/s)
Vertical distance (m)
Axis air velocity
Flap angle
45° 60°
Room air temp. : 20°C Fan speed : High
Heating
0
123456789
1
2
3
4
Horizontal distance (m)
Axis air velocity (m/s)
Vertical distance (m)
Axis air velocity
Flap angle
0°
30°
Room air temp. : 27°C Fan speed : High
Cooling
6. AIR THROW DISTANCE CHART
12
Wide tube service valve
Narrow tube service valve
Indoor Unit MCA90MR5TAA
Outdoor Unit GR360M4R5TAA
7. REFRIGERANT FLOW DIAGRAM
CIRCUIT A
13
Wide tube service valve
Narrow tube service valve
Indoor Unit MCA90MR5TAA
Outdoor Unit GR360M4R5TAA
CIRCUIT B
14
8. ELECTRICAL DATA
8-1. Electrical Characteristics
The values in the table below indicate the sum of indoor units which are in running condition.
NOTE
230V Single phase 50 Hz
Number of indoor unit
1 System 2 Systems
(A1+A2 or B1+B2) (A + B)
Rating Conditions
Running amp. A 9.8 19.6 Power input kW 2.2 4.4
Full Load Conditions
Running amp. A 11.2 22.5 Power input kW 2.55 5.1
230V Single phase 50 Hz
Cooling
Heating
Rating Conditions: Indoor Air Temperature 20°C DB
Outdoor Air Temperature 7°C DB / 6°C WB
Full Load Conditions: Indoor Air Temperature 27°C DB
Outdoor Air Temperature 24°C DB / 18°C WB
Cooling
Heating
Number of indoor unit
1 System 2 Systems
(A1+A2 or B1+B2) (A + B)
Rating Conditions
Running amp. A 10.2 20.4 Power input kW 2.3 4.6
Full Load Conditions
Running amp. A 11.2 22.5 Power input kW 2.55 5.1
15
Indoor Unit MCA90MR5TAA Outdoor Unit GR360M4R5TAA
Rating Conditions: Indoor Air Temperature 27°C DB / 19°C WB
Outdoor Air Temperature 35°C DB
Full Load Conditions: Indoor Air Temperature 32°C DB / 23°C WB
Outdoor Air Temperature 46°C DB
8-2. Electric Wiring Diagrams
Outdoor Unit GR360M4R5TAA
Indoor Unit MCA90MR5TAAA
16
9. FUNCTION
9-1 Cool Mode Operation
(RT - SPT) [oc]
+3
+2
+1
0
-1
ON OFF
ON OFF
H
L
M
ON OFF
COMP
OFAN
IFAN
RV
over 3 min over 5 min
over 30 sec
In Cool Mode, the operation of the Compressor (COMP), Outdoor Fan (OFAN) and Indoor Fan (IFAN) are determined by the difference between the Room Temperature (RT) and the Set Point Temperature (SPT) as in the graph above.
Notes:
1. In this graph, the IFAN is operating in the “Auto Fan Speed” setting. If the user has selected the low, medium or high fan speed, the IFAN will run constantly at that speed only.
2. In addition to the value of (RT-SPT), the operations of the relays are also controlled by protection delays. For example, (a) the minimum On/Off time of the COMP is 5 min and 3 min respectively, and (b) the IFAN can change speed only after it has operated at the same speed for 30 sec.
17
9-2 Heat Mode Operation
(RT - SPT) [oc]
+1
0
-1
-2
-3
H
OFF
L
M
ON OFF
Note 1 Note 2
COMP
IFAN
RV
ON OFF
30 sec
The Heat Mode operation is similar to the Cool Mode operation. The COMP, OFAN and IFAN are mainly controlled by the value of (RT – SPT). In the graph above, the IFAN is operating in Auto Fan speed mode. Therefore, the IFAN speed changes automatically according to the (RT - SPT).
Note 1: The 30s IFAN operation is for purging the heat from the in-coil after COMP has stopped. Note 2: The IFAN will not be turned on until the in-coil temperature is high enough (as shown in the graph
below) to prevent the unit from supplying cool air.
In Auto Mode, the unit switches between the
IFAN Speed
Any
Low
Stop
30 35 40
ICT [oc]
ICT = In-coil Temperature Any = Hi, Med or Low fan speed which is
selected by the user. In Auto Fan Speed Mode, the fan speed is selected by the
unit automatically instead.
Low = The indoor fan is forced to operate at low
speed
18
9-3 Dry Mode Operation
DRY
(RT - SPT) [oc]
+2
+1
0
-1
-2
ON OFF
LOW OFF
DRY-ON DRY-OFF
Time [min]
10
20
30
40 50
COMP
& OFAN
IFAN
5 minutes COMP
ON time
Max 15 minutes Max 15 minutes 6 min
(Note 2)
3.5 min (Note 1)
In Dry Mode, the unit operates in a mild cool mode to lower the humidity of the room. In order to maintain a high efficiency in the drying operation without over lowering the room temperature excessively, the Dry Mode is different from the Cool Mode in two ways.
1. The IFAN is forced to operate at low speed only. And, the IFAN is turned off with the COMP.
2. The unit operates in either the “Dry-on” state or the “Dry-off” state. If RT = SPT, the unit will operate in “Dry-off” state. The COMP is forced to operate for 6 min after it has stopped working for 15 min. If RT > SPT, the unit will operate in “Dry-on” state. The COMP is forced off for 3.5 min after it has been working for 15 min.
Note 1: COMP is forced off in Dry-on state. Note 2: COMP is forced to operate in Dry-off state.
19
9-4 Fan Operation
1. Indoor unit
In Fan Mode the indoor fan is turned on to improve the air circulation in the room. Compressor and outdoor fan remain OFF all the time. Note: if the user has selected the Auto Fan Speed setting, the indoor fan speed would be selected by the unit automatically according to the difference between RT and SPT, as in Cool Mode.
2. Outdoor unit
a. The speed of the Outdoor fans (OFH-A & OFL-A for system A and OFH-B & OFL-B for system B)
can be
High - OFH is ON, OFL is OFF
Low - OFH is OFF, OFL is ON
OFF - both OFH and OFL are OFF
b. The OFH and OFL will never be turned ON at the same time. c. When the compressor starts working, the speed of the corresponding OFAN is high during the
first 10 min., provided the OFAN is turned ON.
Note: This rule is not applied at the first compressor starting after an High Pressure Protection (section 9-5).
In this case, the OFAN speed will be determined by the outdoor air thermistor (OAT) as in normal operation (see below) instead of forced high for 10 minutes. This rule also does not apply when the outdoor air thermistor is < 21
o
C in cool mode.
d. When compressor is OFF, the corresponding OFAN is forced OFF except during High Pressure
Protection. The OFAN will run at high speed under High Pressure Protection.
e. In general cases, when OFAN is turned ON, its speed (High or Low) is determined by the OAT as
below.
Heat Mode
f. The output of OFAN is low (fan stopped) when -2°C<OCT<8°C provided the HP protection operates
and that the OFAN is turned on (see section 9.6).
Cool Mode
20
9-5 Protection Operations in Cool and Dry Modes
1. Indoor Coil Defrost Protection
The in-coil defrost protection can prevent the ice formation at the in-coil when the ambient temperature is low.
ICT [oc]
+2
ON OFF
ON OFF
t1 t2 t3
COMP
OFAN
+1
+5
0
-1
ON OFF
IFAN
t1 = 5 min minimum for each COMP starting t2 = OFAN cycling (alternate between ON and OFF every 30 sec) for 20 min maximum t3 = COMP and OFAN stop for 10 min minimum
21
2. Outdoor coil High Pressure Protection
The outdoor coil High Pressure protection prevents the rising of pressure in the outdoor coil during cool mode operation
Protection INPUTS (from indoor units) OUTPUTS
Condition A
Condition B
RV1
(RV3)
RV2
(RV4)
CO1
(CO3)
CO2
(CO4)
OCT-A
(OCT-B)
ORV-A
(ORV-B)
CO-A
(CO-B)
OF-A
(OF-B)
SV-A1
(SV-B1)
SV-A2
(SV-B2)
SV-A3
(SV-B3)
High Pressure
Protection
Any Any Any Any > 55 RV1
(RV3)
X Hi X X X
Off Off On On = 50 X ON Hi / Lo ON ON X
Termination of Off Off On Off = 50 X ON Hi / Lo ON X ON
HP Protection Off Off Off On = 50 X ON Hi / Lo X ON ON
Notes:
1. Protection Mode is activated when any of the condition A or condition B is satisfied.
In OCT high pressure protection, only the system that start the protection is under the control of the protection routine. The other system will continue to work in normal mode.
2. The OCT HP protection is triggered by the measured OCT-A (or OCT-B) only. The status of the RV & CO inputs from the indoor units are not checked. This way, the protection can also handle the abnormal situation caused by hardware failure, such as RV or COM output relay is defective and
3. If the OF speed is marked as “Hi/Lo”, its speed is governed by the outdoor air thermistor as explained before.
22
9-6 Protection Operations In Heat Mode
1. Outdoor coil De-ice Protection
Protection INPUTS OUTPUTS
Condition A
(Condition B)
RV1
(RV3)
RV2
(RV4)
CO1
(CO3)
CO2
(CO4)
OCT-A
(OCT-B)
ORV-A
(ORV-B)
CO-A
(CO-B)
OF-A
(OF-B)
SV-A1
(SV-B1)
SV-A2
(SV-B2)
SV-A3
(SV-B3)
On Any On On = -2 X ON X ON ON X
Any On On On = -2 X ON X ON ON X
De-icing On Off On Off = -2 X ON X ON X ON
Off On Off On = -2 X ON X X ON ON On On On On > 12 ON ON Hi / Lo ON ON X
Termination of On Off On Off > 12 ON ON Hi / Lo ON X ON
De-icing Off On Off On > 12 X ON Hi / Lo X ON ON
Notes:
1. Protection Mode is activated when any of the condition A or condition B is satisfied.
In De-icing mode, both systems (A & B) will always perform De-icing at the same time.
2. In the de-icing process: (i) The de-icing process can be triggered by any one of the OCT which is < -2
o
C with the
corresponding COMP, RV are both ON and de-icing timer counts to zero.
(ii) The de-icing timer is stopped (the count is reserved) when both COM-A and COM-B
are OFF. (iii) The de-icing timer counts down when any of the compressor turn on. (iv) The de-icing timer is reset (to maximum count) when the condition “RV output of the
IDU are all Off or all OCT > -2
o
C” .
3. If the OF speed is marked as “Hi/Lo”, its speed is governed by the outdoor air thermistor as explained before.
23
2. Outdoor Coil High Pressure Protection in Heat Mode
The outdoor coil high pressure protection prevent the rising of pressure in the circuit during heating operation at high evaporating temperatures.
24
3. Indoor Coil High Pressure Protection in Heat Mode
The in-coil high pressure protection prevent the build up of high pressure at the in-coil during heating operation.
Note:
The operation temperatures shown as A and B in the chart differ by models.
MCA90MR5
A 54 - ­B 45 - -
ICT [oc]
ANY OFF
ANY
COMP
OFAN
B
A
64
OFF
COMP is forced OFF
25
9-7 Cold Draft Prevention (Heating)
This function controls indoor fan speed so a strong draft of cold air will not blow out before the indoor heat
exchange coil have sufficiently warmed up.
When 10 minutes has elapsed, the fan speed is automatically switched to set speed regardless of indoor heat
exchange coil temperature.
Indoor heat exchange
coil temp. (°C)
Max.10 minutes
Tc
Indoor Fan OFF Set Speed
NOTE
The operation temperature shown as Tc in the chart differ by models.
MCA90MR5
Tc 32
26
9-8.1 Sleep Function
Room temperature is automatically controlled to compensate for body temperature variations while sleeping. This mode of operation is designed for maximal comfort in both COOL and HEAT modes.
SPT
Time [Hr]
432
Start
Sleep
7 - 12
RT
SPT-1 SPT-2 SPT-3
SPT+2 SPT+1
SPT+3
1
7-12 Hours Sleep operation
Unit is turned to SB
after Sleep
Cool, Dry modes
Heat mode
9-8.2 Daily Timer Function
Unit can be programmed to be ON and OFF automatically at preset time everyday, by using a remote controller. The resolutions of the ON/OFF timers are 10 min.
9-8.3 IFEEL Function
This feature is provided if the unit is used together with a remote controller with the I-FEEL function. When this function is selected, the remote controller sends the room temperature measured by its build-in thermistor to the air con for more accurate temperature control.
9-8.4 Louver Control
The airflow louver can be driven by either a 12V DC stepping motor or an AC motor. The louver can be set to operate at auto swing mode or fix position mode.
Three additional features are provided if the louver is controlled by a DC stepping motor.
Different swing positions (range) for Heat Mode and Cool Mode operation
Last louver position in fix position mode is stored in the EEPROM, and is restored when the unit is
turned on.
The louver is closed automatically when the unit is switched to standby mode.
27
The push button switch and the LED indicators on the display panel let the user to control the unit operation without a remote controller. Their operations are provided below.
STAND BY
INDICATOR
1. Lights up when the Air Conditioner is connected to power and ready to receive the R/C commands
2. Blinks continuously in case of any thermistor failure.
OPERATION
INDICATOR
1. Lights up in operation mode (Note: OFF in standby mode).
2. Blinks for 0.5 sec., to announce that a R/C infrared signal has been received and stored.
3. Blinks continuously during
OCT High Pressure Protection Mode
Deicing in Heating Mode
TIMER INDICATOR
1. Lights up during Timer and Sleep operation.
2. Active On/Off timer setting will become invalid after a power failure. When this happens, the unit is forced to restart in STBY mode, and the Timer Indicator is blinked continuously until (i) the unit is switched to OPER Mode again, or (ii) any message from the R/C is received.
Push Button switches:
MODE BUTTON (Cool, Heat, SB)
Use to cycle the operation mode of the A/C unit among COOL, HEAT and SB modes, without using the R/C. Every time this switch is pressed, the next operation mode is selected, in the order : SB => Cool Mode => Heat Mode => SB => ...
28
9-8.5 Manual Unit Control and LED indicators
1. Indoor Unit PCB
2. Outdoor Unit PCB
The status of the Multi Split Controller system (MSC) is indicated by a system Status LED and a Power LED on the control board of the outdoor unit. The Power LED will be ON whenever there is +5V supply voltage in the system, otherwise it is OFF. In addition, only the Status LED will be controlled by the microprocessor (MCU) to indicate its internal operational status. The leds’ operation details can be described by the following table.
Conditions Power LED L3 (Green) Status LED L2 (Red)
Normal Operation ON OFF
Self test in progress ON ON
Self test completed w/o
error
ON Blink at 10Hz for 3sec,
then OFF
Fault Detected
(in operation or test mode)
ON Blinking
(see note below)
Power OFF / no power OFF OFF
Notes:
1. When any fault is detected, the most significant digit of the error code is shown by using the blinking Status LED. For example, when one of the thermistors is not operating properly, the Status LED will be blinking with the pattern “Blink 5 times -> OFF for 2 sec -> Blink 5 times -> …” so as to indicate that an error code of 5 has been detected (see section related to fault detection for more information).
9-8.6. Fault Operations and Indications (Outdoor Unit PCB)
The MCU of the MSC system will monitor all input continuously. Then update the status of the inputs every second. To prevent temporary input error from interfering with normal operation, the MCU will not take immediately action when an error is detected. In general, the MCU will regard an input as defective only if four successive invalid data are received at that input. As a result, there will be a 2 seconds delay between the occurrence of an error and the MCU makes proper response to this error.
1. Fault Conditions in Operating Mode
Fault operations can be one or more of the following:
The zero crossing circuit is not working at the frequency of 90-132 Hz
The OAT thermistor is not functional (Temp < -30oC or Temp > 75oC)
Any of the OCT thermistor is not functional, that is:
measured OCT is out of operational range: Temp < -30
o
C or Temp > 95oC
Any of the +12V DC supply voltage is under 8V DC.
Any photo-coupler output of an enabled indoor unit is invalid
2. Fault Handling
Beside blinking the system Status LED, the MSC MCU will also response to the system faults by taking different preventive actions to protect the system hardware.
(1) The MSC MCU will turn OFF all outputs of both systems in case of critical fault condition, one example is:
the zero crossing circuit is not working at the frequency 90-132 Hz.
(2) The MSC MCU will turn OFF the outputs of a system in case of local fault
the +12V DC supply voltage of that system is under 8V DC Note : If the +12V DC supply voltage of both systems is under 8V DC, the MCU will turn OFF
all relays, and suspend all relay operations. When one or both DC supply voltage is back to normal, the MCU will perform a “System Reset” function.
(3) The MSC unit will disable a specific indoor unit, when
the OCT thermistor of this unit is not functional
any photo-coupler output of this unit is faulty
(4) The MSC unit will always select the High OFAN speed if the OFAN is turned ON, when
OAT failure occurs
Note: A failed input, such as thermistor or photo-coupler, can be recovered whenever 4 successive valid inputs (2 sec) are received.
29
3. Self Test
Self test is initiated by connecting J1 jumper and 3 fixed resistors of 10k 1/4W, 5% or thermistors at OCT1, OCT3 and OAT satisfying conditions in note1, then H/W reset the unit. The J1 must be connected throughout the test operations. Otherwise, the system will go back to normal operation mode. Moreover, all Indoor Units must be in STBY mode to prevent the Indoor Unit operations from interfering with the test procedure.
3.1 Self Test Procedure
No Step
Task Description / Work Element
Observations on UUT
1 Initiate the Self
Test under internal loop-back
1.1 Power up the UUT by connecting Line-In on P10 and Neutral P9
-
1.2 The following tests is proceeded automatically:
- Relay Walk Test
- Zerocrossing frequency test
- 12VDC supply test
- EEPROM test
- Watchdog Reset timing test
- Thermistors test
- Auto Input Test
Wait for 8-10 seconds. Each output of UUT is turned ON
for 2 sec with a 0.5 sec separation in the order below: CCH-A,ORV-A,COM-A,SV­A1,SV-A2,SV-A3,OFH-A,OFL-A
CCH-B, ORV-B,COM-B,SV­B1,SV-B2,SV-B3,OFH-B,OFL­B,HE
1.3 Self test completed All relays are turned OFF.
If no error is detected, the Red LED on UUT is blinked at 10 Hz frequency for 3 sec and then turned OFF.
If error is detected, the error code is shown in the Red LED by a flash pattern as indicated on section 7.2
2 Initiate the Self
test under external loop back
2.1 Disconnect the power to the UUT
2.2 Connect the Testplug at TP1, which is also linked to IU1, IU2, IU3 and IU4, on the UUT
2.3 Provide 220VAC signal inputs to all photo-coupler
2.4 Repeat procedure 1.1 to 1.3
Note1: 1.The 3 thermistors must be within operation range.
2.The difference among the 2 OCTs must be less than 5°C. 3
.The maximum difference between the OAT and any OCT must be less than 5°C.
30
4. Error Code Message
Display of Error Code: Indicated by the Status LED (Red color), a flash pattern consists of 1 to 6 flashes with 0.5sec separation, which is corresponding to the error code 1 to 6. The flash pattern is repeated continuously with 2sec separation.
No of Flashes (Error Code)
Error Message
1 Zero Crossing Test Fails
The frequency of the zero-crossing input is measured. To pass this test, the frequency must be in the range of [90, 132] Hz.
2 12V DC Supplies Test Fails
The output levels of the two 12V DC supplies are measured. To pass this test, the supply voltages must be over 8V.
3 EEPROM Test Fails
All locations in the EEPROM is tested by non-destructive Read, Write and Verify.
4
Watchdog Reset Timing Test Fails
The Watchdog output from the MCU is stopped. And the time taken by the external reset circuit to generate a Hardware Reset is measured.
Criteria to pass: the reset must be generated between 1 to 4 sec after the Watchdog signal is stopped.
5 Thermistors Test Fails
The temperature detected by the 2 thermistors are compared with each other.
Criteria to pass: the thermistor outputs must be within operational range and the maximum difference between the OAT and any OCT must be less than 5
o
C
6 Auto Input Test Fails
Each input from the photo-coupler is tested with Testplug or without Testplug
- With Testplug, all input should provide 220VAC
- Without Testplug, all input should have no 220VAC
5. Jumper Settings
5.1 Self-test jumper - J1 (Factory test)
The J1 is used to switch the Outdoor unit to self-test mode. To do so, J1 must be closed before switching ON the power of the unit. The J1 must be closed during the tests. Whenever J1 is disconnected, the unit will go back to normal operation mode.
Operation Mode J1 setting Self Test Closed
Normal Operation Open
31
5.2 Quick Test jumper – J2 (Assembly test)
The jumper J2 is used to speed up the operation mode by 60.
Operation Mode J2 setting Quick Test Closed
Normal Operation Open
9-8.7 Recovery from Power Failure (Indoor Unit PCB)
Last unit settings (SPT, operation mode, louver settings, etc) are saved in the EEPROM in the unit. In case of power failure, these settings are restored automatically.
32
10. TROUBLESHOOTING
10-1. Check before and after troubleshooting.
10-1-1. Check power supply wiring.
Check that power supply wires are correctly connected to terminals No. 1 and No. 2 on the 3P terminal plate in the outdoor unit.
10-1-2. Check inter-unit wiring.
Check that inter-unit wiring is correctly connected to the indoor units from the outdoor unit.
10-1-3. Check power supply.
Check that voltage is in specified range (±10% of the rating).
Check that power is being supplied.
10-1-4. Check lead wires and connectors.
Check that coating of lead wires is not damaged.
Check that lead wires and connectors are firmly connected.
Check that wiring is correct.
WARNING
Hazardous voltage can cause ELECTRIC SHOCK or DEATH. Disconnect power or turn off circuit breaker before you start checking or servicing.
33
10-2. Air conditioner does not operate.
10-2-1. Circuit breaker trips (or fuse blows).
A. When the circuit breaker is set to ON, it is tripped soon. (Resetting is not possible.)
There is a possibility of ground fault.
Check insulation resistance.
If resistance value is 1Mor less, insulation is defective (“NO”).
B. Circuit breaker trips in several minutes after turning the air conditioner on.
There is a possibility of short circuit.
Measure insulation resistance of electrical parts in outdoor unit.
NO
NO
Set circuit breaker to OFF.
*
Measure insulation resistance of electrical parts in indoor unit.
1
Remove both power supply wires and inter-unit wires from terminal plate in outdoor unit.
Measure insulation resistance of outdoor unit.
2
Remove inter-unit wires from terminal plate in indoor unit.
Measure insulation resistance of indoor unit.
Insulation of outdoor unit is defective.
Insulation of indoor unit is defective.
Check capacity of circuit breaker. Capacity of circuit breaker is
suitable.
Replace with suitable one (larger capacity).
Measure resistance of compressor motor winding. (CMa, CMb)
Measure resistance of outdoor fan motor winding. (FM)
NO
34
10 -2-2.Neither indoor nor outdoor unit runs.
A. Power is not supplied.
B. Check remote control unit.
NO
Check power supply. Power is being supplied to the
outdoor unit.
Circuit breaker is tripped.
Power failure
Reset breaker.
Wait for recovery or contact power company.
OK
Try to run with another remote control unit.
First remote control unit is defective.
Check for residue buildup on transmitter of remote control unit.
Check for residue buildup on remote control receiver on front of indoor unit.
Clean transmitter.
Clean receiver.
35
C. Check fuse on the indoor PCB Ass'y.
OK
Replace the fuse.
OK
OK
Check fuse on indoor PCB Ass'y for continuity.
Check operation lamp to see if light is ON.
Light is OFF
Measure resistance of primary and secondary winding of transformer. (TR)
Indoor PCB Ass'y or switch Ass'y is defective.
OK
Measure resistance of indoor fan motor winding. (FMI)
Measure resistance of flap motor winding. (FLP)
If fuse has been blown,
E. Check TIMER button on the remote control unit.
Timer is turned ON. Check to see if "ON" is displayed on remote control
YES
Press CLEAR button to cancel the timer mode.
D. Check fuse on the outdoor PCB Ass'y.
OK
OK
OK
Check fuse on outdoor PCB Ass'y for continuity.
Check operation led (L3 green) to see if light is ON.
Light is OFF
Measure resistance of primary and secondary winding of transformer. (TR)
Indoor PCB Ass'y is defective.
OK
Measure resistance of outdoor fan motor winding. (FMa, FMb)
Measure resistance of solenoid valves (SVa/b, RVa/b)
If fuse has been blown,
Measure resistance of crank case heaters and power relays. (CCHa, CCHb, PRa, PRb)
OK
Replace the fuse.
36
10-2-3.Only outdoor unit does not run.
A. Check setting temperature.
B. Check PCB Ass'y in either indoor or outdoor unit.
12-2-4.Only indoor unit does not run.
OK
NO
Is room temperature too low ?
Try to lower setting temperature by temperature setting button cooler.
Outdoor unit still does not run.
Remote control unit is defective.
Try to run using another remote control unit.
COOL
OK
NO
Is room temperature too high ?
Try to raise setting temperature by temperature setting button warmer.
Outdoor unit still does not run.
Remote control unit is defective.
Try to run using another remote control unit.
HEAT
Indoor PCB Ass'y is defective.
Check voltage between terminals No.1 and N at terminal plate of indoor unit. (AC 220V)
No voltage appears.
Outdoor PCB Ass'y is defective.
OK
Indoor PCB Ass'y is defective.
37
10 -3. Some part of air conditioner does not operate.
10-3-1.Only indoor fan does not run.
10-3-2.Only flap motor does not run.
10-3-3.Only outdoor fan does not run.
Fan cannot be turned.
OK
Check fan rotation. Turn fan gently once or twice by hand.
Check fan casing foreign matter on inside.
Fan motor burnout or foreign matter in bearings.
Remove foreign matter or repair.
Repair or replace.
Measure resistance of indoor fan motor winding.
Check fan motor capacitor.
Fan cannot be turned.
Check fan casing for foreign matter on inside.
Check fan rotation. Turn fan gently once or twice by hand.
Measure resistance of outdoor fan motor winding.
OK
Fan motor burnout or foreign matter in bearings.
Repair or replace.
Remove foreign matter or repair.
Check fan motor capacitor.
Measure resistance of flap motor winding.
38
10-3-4.Only compressor does not run.
Measure resistance of compressor motor winding.
NO
Check compressor motor capacitor.
YES
YES
YES
Overload relay is working.
Refrigerant gas shortage. Charge refrigerant gas (R22).
Temperature of compressor is abnormally high.
Rotor may be locked up.
(OLR)(C3a,C3b)
Measure coil resistance of power relay. (PRa,PRb)
39
10 -4. Air conditioner operates, but abnormalities are observed.
12-4-1.Operation does not switch from HEAT to COOL (or COOL to HEAT).
Indoor PCB Ass'y is defective.
Check voltage between terminals No. 2 and N at terminal plate.
(AC 220V)
No voltage appears.
Outdoor PCB Ass'y is defective.
OK
Remote control unit may be defective.
Measure resistance of 4–way valve's winding.
Receiver in switch Ass'y may be defective.
COOL HEAT
Check voltage between terminals No. 2 and N at terminal plate.
(0V)
HEAT COOL
When unit a1 stops unit a2 will switch to cooling or drying operation.
Unit a1 in heating mode (first unit switched)
Unit a2 in cooling or drying mode
Unit a1 in heating mode. Heating operation has precedence so unit a2 is
in stand-by mode.
• If, in one system ( A for example), the units tried to be operated in different modes (unit a1 in heating while unit a2 in cooling), the results are as follows:
Units of one system (A or B) cannot operate in different modes simultaneously (for example unit a1 operating in the heating mode while unit a2 is in the cooling one). When operating two units of the same system, set them both to the same mode. Different system instead, can operate in different mode that is system A can be in cooling mode while B in the heating one.
CAUTION
40
10-4-2.Poor cooling or heating.
10-4-3.Excessive cooling or heating.
Air filter is clogged.
NO
YES
Temperature difference is small.
YES
Temperature difference between suction and discharge air is large enough (approx. 10 deg. or more).
Possibility of gas shortage.
YES
Check position of remote control unit. Cool or warm air from air conditioner reaches position directly.
Change position of remote control unit.
Wide and narrow tubes between indoor unit and outdoor unit are insulated.
Insulate both wide and narrow tubes separately and then tape together.
Measure temperature of suction and discharge air of air conditioner.
Charge refrigerant gas (R22).
Check for clogging of air filter.
Fan speed is set to LOW.
Clean filter.
Set fan speed to either HIGH or MEDIUM.
Review cooling load estimate, if performance of air conditioner is normal.
Reduce cooling or heating load or replace the air conditioner with larger capacity.
NOTE
NO
NO
Set temperature is suitable.
Set temperature to higher or lower value using temperature setting buttons of the remote control unit.
Remote control unit is placed where it can detect room temperature properly.
Change position of remote control unit.
41
10-5. If a sensor is defective.
10-5-1.Indoor coil / room temperature thermistor is defective.
Stand-by lamp on front side of indoor unit is flashing on and off.
YES
Replace thermistor(s).
At least one of the thermistors is defective (that is, SHORT or OPEN.)
Temperature sensor
Lead wires
Thermistor Structure
10-5-2.Outdoor coil / outdoor air temperature thermistor is defective.
Status led (RED) on outdoor PCB
blinks 5 times then off (repeat)
YES
Replace thermistor(s).
At least one of the thermistors is defective (that is, SHORT or OPEN.)
Definition of Open or Short Circuit of Sensor (Thermistor)
Open...A lead wire is broken or disconnected or the circuit inside the temperature sensor is open . Short...The protective cover of a lead wire has been damaged, and the exposed wire is touching another metal
part, or both lead wires have become exposed and are touching each other. Alternatively, the circuit inside the temperature sensor is closed.
NOTE
42
11.ARRANGEMENT OF ELECTRICAL COMPONENTS
Terminal Plate
Outdoor Unit GR360M4R5TAA
43
Outdoor Unit GR360M4R5TAA
Parts Layout in Unit
44
IMPORTANT!
For your personal safety, be sure to read and understand the following precautions before servicing.
To avoid risk of injury when servicing the outdoor unit (for instance, when replacing the compressor or repairing a refrigerant leak), follow the procedure
12-1-1. Confirm mains power is switched OFF, then
open the electrical box in order to access to the Power Control Board (PCB).
IMPORTANT!
Always check for fan running during the servicing. This ensure you that the solenoid valves SVa1 and SVa3 are open.
12. SPECIAL PRECAUTIONS WHEN SERVICING THE UNIT
Injuries can occur from burns or inhalation of toxic gas if servicing is performed while refrigerant remains in the refrigeration circuit. This servicing includes disassembling brazed tubing connections and removing any refrigeration parts or components.
WARNING
Fig.12-1
Fig.12-2
The following procedures are outlined as if SYSTEM A has to be serviced. The same steps, obviously, applies in case of SYSTEM B servicing.
NOTE
12-1-2. Disconnect the brown wire from the terminal
of PCB's compressor relay. (Fig.12-1)
12-1-3. Connect two wires between poles L, 1, and 3
of the terminal plate (Fig.12-2) Supply power to the outdoor unit. After 3 minutes the outdoor fan A will start running and the solenoid valves SVa1 and Sva3 will open.
In some cases it is required to have solenoid valves opened
during servicing. When so, perform the following steps:
45
12-2. Refrigerant recovery
12-2-1. Open the service valve to recover refrigerant into
refrigerant recovery unit.
12-3. Service on outdoor unit
12-3-1. After making sure that the refrigerant in the
circuit has been completely discharged, perform the required servicing, such as replacing the compressor or repairing refrigerant leaks.
12-3-2. Before going on to the next step, leak test all
joints where welding has been done.
Nitrogen gas is best when pressurizing the system for a leak test. However, if it is necessary to instead test with refrigerant gas, be sure to recover all gas into the refrigerant recovery unit after completing the leak test.
12-4. Evacuation using vacuum pump
12-4-1. Using a hex wrench, set the valve stems of both
the narrow and wide tube service valves as indicated in table below.
Refer to " Service Valve Construction "shown later
12-4-2. Connect the vacuum pump and a manifold valve
as shown in Fig.12-3.
Confirm that all connections are correctly made.
In order to withstand negative suction pressure during evacuation, the manifold valve should be equipped with a Hi/ Lo compound gauge with a
minimum scale reading of -76
cmHg.
NOTE
NOTE
NOTE
Refrigerant released into the air contributes to destruction of our planet's ozone layer. You should always use the refrigerant recovery unit to help protect the environment.
CAUTION
Service Valve Valve Position
Unit A 1
Narrow
Wide
Unit A2
Narrow
position -a-
Wide
IMPORTANT!
This procedure requires solenoid valves opening during the operation. Follow the steps of 12.1 before starting.
position -c-
IMPORTANT!
This procedure requires solenoid valves opening during the operation. Follow the steps of 12.1 before starting.
46
12-4-3. Install (first by hand-tightening, then securely with
a wrench) flare nuts and bonnets at all service valves in the refrigeration circuit where evacuation will take place. This process is highly important
to completely evacuate the system.
12-4-4. With the " Lo " and "Hi" knobs of the manifold valve
open run the vacuum pump. The operation time varies with the capacity of the pump.
Evacuation is successful if the vacuum gauge reading remains –75 cmHg or more for at least 10 seconds after closing the " Lo " and "Hi" knobs of the manifold valve.
12-4-5. With the vacuum pump still running, turn the wide
and narrow service valves all the way in order to close them (position -a-). Stop the pump.
12-4-6. After removing the vacuum hoses from the service
valves, replace the flare nuts and bonnets on the valves. The refrigerant circuit is now ready for charging.
12-5. Refrigerant charging
12-5-1. After evacuation is completed, charge the circuit
with the proper amount of refrigerant.
The proper amount of refrigerant is specified on the nameplate of the outdoor unit and in Section "2-1. Unit Specifications" in the service manual.
12-5-2. Use a hose to connect the narrow tube service
valve to the liquid port of the charging cylinder. (Fig.12-4 )
12-5-3. Purge air from the hose. Do this by opening the
charging cylinder valve, then slightly loosening the connection to the narrow tube service valve. Wait a few moments, then retighten the connection.
NOTE
Fig. 12-3
Fig. 12-4
47
12-5-4. With a hex wrench, open the service valve little
by little to let refrigerant enter the circuit. (Figs.12-4 )
Write down the gradation levels on the charging cylinder before and after the charging. This allows you to calculate the charging volume.
12-5-5. If it is not possible to completely charge the unit
with the proper amount of refrigerant, an additional charging can be made after installing the units. In this case after re-setting the outdoor unit to the normal state (see 12-6), the charge is done using the wide valve port with the system running in COOLING
12-6. Reset the unit for normal operation
12-6-1. Turn off the power source. 12-6-2. Connect the brown wire to the relay terminal as
it was before servicing. (Fig.12-5 )
NOTE
Charging volume
Gradation level before charging
Gradation level after charging
=
NOTE
Reset always the unit as it was before servicing. Otherwise the system will not perform correctly and damage may occur.
CAUTION
12-6-3. Remove the servicing wires from the terminal
plate. (Fig.12-6 )
Fig.12-5
Fig.12-6
When servicing has finished, the outdoor unit must be set to the normal operation state. In this case do the following:
mode.
Charging the unit with a large amount of refrigerant at once may damage the compressor. Always charge the unit at a constant charging rate of about 100g.
48
Service Valve Construction
Valve Position -a-
The valve stems of both the wide and narrow tubes are turned all the way in. The unit is shipped from the factory in this position. (Fig.12-7a)
Valve Position -b-
The valve stems of both the wide and narrow tubes are turned all the way out ("BACK SEAT" position). This is the normal operating position. (Fig.12-7b)
Valve Position -c-
With the narrow tube valve kept at BACK SEAT, only the wide tube valve stem is turned to the halfway­down position. This position is used when refrigerant circuit evacuation is required from both narrow and wide tube valves at the same time. This position is also used when additional refrigerant charging is required in the field with both the indoor and outdoor units installed.(Fig.12-7c)
Valve Position -d-
With the valve stem of the wide tube turned all the way in, only the narrow tube valve stem is turned to the halfway-down position. This position is used for refrigerant charging for only the outdoor unit. (Fig.12-7d).
When opening or closing the service valve stem, use the supplied accessory hex wrench. Be sure to fully seat the wrench before turning the valve.
CAUTION
• Condition at Evacuation
• Condition at Charging in the Field.(-c-)
• Condition at Charging with Only Outdoor Unit (-d-)
• Condition at Operation (-b-)
• Condition at Shipping (-a-)
Valve cap
Stem
O-ring
Fig.12-7d
Fig.12-7c
Fig.12-7b
Fig.12-7a
Wide Tube Narrow Tube
Close
Hex wrench
Open
49
13-1. Measurement of Insulation
Resistance
The insulation is in good condition if the resistance exceeds 2M.
13-1-1. Power Supply Wires
Clamp the ground wire of the power supply wires with the lead clip of the insulation resistance tester and mea­sure the resistance by placing a probe on either of the power wires. (Fig. 1)
Then measure the resistance between the ground wire and the other power wire. (Fig. 1)
13-1-2. Indoor Unit
Clamp an aluminum plate fin or copper tube with the lead clip of the insulation resistance tester and measure the resistance by placing a probe on each terminal screw except where the ground line is connected on the termi­nal plate. (Fig. 2)
13-1-3. Outdoor Unit
Clamp a metallic part of the unit with the lead clip of the insulation resistance tester and measure the resistance by placing a probe on each terminal screw where power supply lines are connected on the terminal plate. (Fig. 2)
13-1-4. Measurement of Insulation
Resistance for Electrical Parts
Disconnect the lead wires of the desired electric part from terminal plate, capacitor, etc. Similarly disconnect the connector. Then measure the insulation resistance. (Figs. 1 to 4)
Refer to Electric Wiring Diagram.
If the probe cannot enter the poles because the hole is too narrow then use a probe with a thinner pin.
Insulation tester
Probe
Clip
Ground wire
Fig. 1
Terminal plate
Copper tube or metallic part
Clip
Insulation tester
Probe
Fig. 2
Copper tube or metallic part
Clip
Insulation tester
Probe
Fig. 3
Clip
Insulation tester
Probe
Metallic part
From fan motor, compressor and other parts
Fig. 4
13. CHECKING ELECTRICAL COMPONENTS
NOTE
50
13-2. Checking continuity of Fuse on
PCB Ass'y
Check for continuity using a multimeter as shown in Fig. 6.
Method Used to Replace Fuse on PCB Ass'y
— Indoor PCB Ass'y —
1. Remove the PCB Ass'y from the electrical compo nent box
2. Then pull out the fuse from the PCB Ass'y.(Fig.5a)
— Outdoor PCB Ass'y —
1. Remove the PCB Ass’y from the electrical component box.
2. Pull out the fuse at the metal clasp using pliers while heating the soldered leads on the back side of the PCB Ass'y with a soldering iron (30W or 60W).(Fig.5b)
3. Remove the fuse ends one by one. For replacement insert a fuse of the same rating and solder it. (Allow time to radiate heat during soldering so that the fuse does not melt.)
13-3. Checking Motor Capacitor
Remove the lead wires from the capacitor terminals, and then place a probe on the capacitor terminals as shown in Fig. 7. Observe the deflection of the pointer, setting the resistance measuring range of the multimeter to the maximum value.
The capacitor is “good” if the pointer bounces to a great extent and then gradually returns to its original position.
The range of deflection and deflection time differ accord­ing to the capacity of the capacitor.
Multimeter
Compressor motor capacitor
Fan motor capacitor
Fuse
PCB Ass’y
Indoor
Fig. 5a
Fuse
Fig. 6
Fig. 7
Soldering iron
PCB Ass’y
Outdoor
Fuse
Pliers
Fig. 5b
NOTE
51
S.A.C. - olgiate olona - printed in italy
R.D. 28 Reyrieux BP 131 - 01601 Trévoux CEDEX France
Tél. 04.74.00.92.92 - Fax 04.74.00.42.00
R.C.S. Bourg-en-Bresse B 759 200 728
Loading...