Water ow (1)l/h213 368 404 445 291 600 687 789 422 653 758 869
Pressure drop (1)kPa3891131114177141823
Heating capacity (2)kW1,55 2,83 3,11 3,49 1,87 4,35 4,85 5,70 3,35 5,33 6,14 6,75
Pressure drop (2)kPa3781031013176141823
Heating capacity (3)kW2,02 3,72 4,09 4,61 2,42 5,7 6,32 7,46 4,46 7,11 8,17 8,91
Water ow (3)l/h175 323 355 400 210 495 549 648 387 617 710 774
Pressure drop (3)kPa2678279125121618
Water contentdm30,430,860,86
Air owm3/h180 400 460 520 200 530 630 750 370 630 760 880
Power input W5101215824283612344046
Sound power level (4)dB/A304144463248515541535761
Sound pressure level (5)dB/A253639412743465036485256
Water connectionsinches 1 / 2 1 / 2 1 / 2
Unit dimensions H x L x Pmm273 x 575 x 575273 x 575 x 575273 x 575 x 575
Grille dimensions H x L x Pmm64 x 730 x 73064 x 730 x 73064 x 730 x 730
Model3P24P25P2
Ratings and technical data of CAW fan coil units with 1 heat exchanger
Speed123412341234
Total cooling capacity (1)kW4,20 5,00 5,40 6,00 5,50 6,50 8,00 9,10 6,23 8,09 8,90 9,92
Sensible cooling capacity (1) kW3,13 3,70 3,99 4,40 4,11 5,08 6,10 6,84 4,69 6,17 6,87 7,71
Water ow (1)l/h720 859 930
Pressure drop (1)kPa162225302128415127425060
Heating capacity (2)kW5,40 6,40 7,10 7,70 6,28 8,52 9,42
Pressure drop (2)kPa152125302129394826424960
Heating capacity (3)kW7,08 8,39 9,33
Water ow (3)l/h615 729 810 875 707 976
Pressure drop (3)kPa121619221221242716263137
Water contentdm31,001,501,50
Air owm3/h850
Power input W132025411522415522364364
Sound power level (4)dB/A434849513746505343495357
Sound pressure level (5)dB/A384344463241454838444852
Water connectionsinches 3 / 4 3 / 4 3 / 4
Unit dimensions H x L x Pmm273 x 776 x 776290 x 1066 x 776290 x 1066 x 776
Grille dimensions H x L x Pmm64 x 860 x 86064 x 1150 x 86064 x 1150 x 860
Model6P28P210P2
1.029
944
1.116 1.373 1.561 1.070 1.389 1.529 1.702
10,19
7,34 9,53
10,08
8,14
1.060 1.160 1.300
11,24 12,26 13,18
830 1190
1.065 1.145
1.270 1.400 1.200 1.700 1.980 2.300
9,52
12,34 13,73 15,11
827
1.072 1.192 1.312
10,59 11,69
Ratings and technical data of CAW fan coil units with 2 heat exchangers
Speed1234123412341234
Total cooling capacity (1)kW 1,03 1,72 1,88 2,05 1,52 2,88 3,28 3,76 2,60 3,90 4,50 4,97 4,25 5,10 5,60 6,20
Sensible cooling capacity (1)kW 0,81 1,51 1,66 1,82 1,07 2,27 2,60 3,00 1,85 2,90 3,36 3,75 3,15 3,73 4,02 4,45
Water ow (1)l/h 177 295 323 351 295 494 563 645 445 678 781 863 735 890 970 1.075
Pressure drop (1)kP a38911811 13 17 15 25 32 37 13 19 22 28
Heating capacity (3)kW 1, 1 1,78 1,95 2,2 1,48 2,87 3,14 3,76 2,55 3,86 4,43 4,92 4,80 5,58 6,20 6,80
Water ow (3)l/h96 155 169 191 129 249 273 327 218 330 380 422 410 477 531 580
Pressure drop (3)kP a 1 1 25 2 9 36722 2 6 3 6 1 2 2 5 3 5 4 1 2 8 3 7 4 2 50
Water contentdm30,430,860,991,47
Air owm3/h 180 400 460 520 200 530 630 750 370 630 760 880 850 1.0601.1601.300
Power input W512 14 17824 28 36 12 34 40 46 1 3 2 0 25 4 1
Sound power level (4)dB/A 30 41 44 46 32 48 51 55 41 53 57 61 43 48 49 51
Sound pressure level (5)dB/A 25 36 39 41 27 43 46 50 36 48 52 56 38 43 44 46
Cooling heat exchanger water connections
Heating heat exchanger water connections
Unit dimensions H x L x Pmm273 x 575 x 575273 x 575 x 575273 x 575 x 575273 x 776 x 776
Grille dimensions H x L x Pmm64 x 730 x 73064 x 730 x 73064 x 730 x 73064 x 860 x 860
NOTES CAW WITH 2 PIPES:
1 = water temperature 7/12°C, air temperature dry bulb 27°C, wet
bulb 19°C
2 = inlet water temperature 50°C, water ow rate same as in cooling mode, air inlet temperature 20°C
3 = water temperature 60/50°C, air temperature 20°C
4 = sound power conforming to ISO 3741 and ISO 3742
5 = Sound pressure level measured at a distance of 1 m with a
NOTES CAW WITH 4 PIPES:
1 = water temperature 7/12°C, air temperature dry bulb 27°C, wet bulb
19°C
3 = Water temperature 70 - 60°C; air temperature 20°C
4 = sound power conforming to ISO 3741 and ISO 3742
5 = Sound pressure level measured at a distance of 1 m with a direc-
9 - Technical data ............................................................................ 22
1 - GENERAL
GB
1.1 - FOREWORD
• The equipment must be installed, started-up and
maintained by authorised and qualified personnel,
in accordance with local rules and professional
standards.
1.2 - GENERAL SUPPLY CONDITIONS
• Generally speaking, the material is transported at
the consignee’s risk.
• The consignee must immediately provide the
carrier with written reserves if he finds any damage
caused during transport.
• Do not place objects or tools on the device.
• Position the device as near as possible to its place
of installation without unpacking it.
1.3 - VOLTAGE
• Before any operation, check that the voltage and
the frequency indicated on the device corresponds
with that of the mains.
1.4 - OPERATION LIMITS
• Hydraulic circuit:
- minimum water inlet temperature: 4°C.
- maximum water inlet temperature:
main battery: 70°C
secondary battery: 80°C
Note: For reasons relating to comfort (homogeneity of
the air temperature in the room), not exceeding
a water inlet temperature of 55°C in the battery
is recommended.
- Maximum operating pressure: 16 bars.
• Ambient air:
- Minimum air recirculation temperature: 5°C
- Maximum air recirculation temperature: 32°C
Important: During installation shut-down, in
case of connection to an outside air vent or in
case of ambient temperature near 0°C, there
is a risk that the hoses may freeze. Envisage
draining the hydraulic circuit.
1.5 - USE OF EQUIPMENT
• This equipment is intented for the air-conditioning of
premises and to provide comfort for the personnel.
A Condensate opening: OD 18mm
B Main battery water inlet: 1/2” female - gas
(3/4” for CAW 5)C Main battery water outlet: 1/2” female - gas
(3/4” for CAW 5)
D Secondary battery water inlet: 1/2” female - gas
E Secondary battery water outlet: 1/2” female - gas
F Main battery air bleeder
G Secondary battery air bleeder
H New air intake: Ø 70mm
Electrical box
730
544
Fresh air intake side
730
506
Net weight
ModelCAW 3CAW 4-5
Unit18 kg20 kg
Frame / Grille Assembly2,5 kg2,5 kg
A Condensate opening : OD 32 mm
B Main battery water inlet: 3/4” female - gas
C Main battery water outlet: 3/4” female - gas
D Air vent valve (main battery)
E Electrical cable passage
F New air intake: 60 mm x 55 mm
G Secondary battery water inlet: 3/4” female - gas
H Secondary battery water outlet: 3/4” female - gas
I Air vent valve (secondary battery)
30 mini CWX 6
3 - INSTALLATION
CAW 8-10
27 kg
8 kg
F
860
Y
500
DC
760L
I
H
G
B
H
240
200
30
E
Z
A
X
125
48
3.1 - CHOOSING THE LOCATION
• This unit is designed to be installed in sheltered rooms (IP 20).
• Do not install the device in a room containing inflammable, alkaline, acidic, greasy or very damp air, nor in one
where water is liable to be projected. The components will be irremediably damaged.
• Choose the most central position in the room.
• Check that the ceiling is sufficiently sturdy to support the unit’s weight.
• In the position chosen, check that no obstacle will impede installation and maintenance (beam, insufficient
false ceiling height, fixed false ceiling panels, access impossible for maintenance, etc.).
• Provide an access for easy maintenance, namely for the valve (and electrical box for CWX 3-5 models).
• Provide for the water pipes, electric cables and the condensate discharge outlet.
• Air must be able to circulate freely around the unit.
Note : air diffusion will be less efficient if room height is greater than 3 meters.
• Use the drilling template provided (2) to determine
the position of the suspension rods (1).
• The template must be placed between 2 “T” rails of
the false ceiling.
• Install the suspension rods (not supplied).
• Place the side where the connections are located in
the most appropriate position.
• The “T” rail (3), located on the electrical box side,
must be temporarily removed.
• Put the unit in place and check that it is level.
• Adjust the distance between the unit and the false
ceiling (5) (max. 23 mm) by using the suspension rod nuts.
• Also check the distance between the suspension flange (6) and the ceiling (7) (min. 41 mm). A lesser
distance may create noise if the unit touches the ceiling.
1
506
10
10
10
GB
3
4
CAW 6-8-10
• Use the drilling template provided (2) to determine
the position of the suspension rods (1) and the hole
to be made in the false ceiling (figure 01).
For the suspension rods, use dia. 8 or 10mm
threaded rod.
• Refer to the dimensions in the table opposite
(figure 02).
• Install the suspension rods (not supplied).
• The length of the suspension rods must be long
enough to have distance of more than 15 mm
between the bottom of the suspension rod and the
bottom of the unit (figure 01).
• Place the side where the connections are located
in the most appropriate position.
• Install the unit on the suspension rods using the
nuts and washers (figure 03).
• Check that the unit is level.
• Adjust the distance between the unit and the top
of the false ceiling (48 mm) using the nuts on the
suspension rods (figures 01 and 03).
• 1/2” (CAW 3-4-5 MODELS) 3/4” (CAW 6-8-10 MODELS) female gas connections on the unit.
- Water inlet: lower connection.
GB
- Water outlet: upper connection.
• For cold water use, a control valve must be installed, otherwise there is a risk that the condensate tank may
overflow if the unit shuts down due to a thermostat disconnection or in case of condensate pump failure (for
valve installation, refer to the “Accessories” paragraph).
Important: Securely hold the unit’s connections with a wrench while tightening in order to avoid twisting
the tubes inside the unit.
• Carefully insulate the water inlet and outlet tubes as well as the elements installed on the network (shut-off
valves, ...).
Use material that is adapted to the installation conditions and water system.
• The unit is equipped with an air bleeder above the connections. Depending on the installations, other bleeders
may be required on the hydraulic network.
4.2 - CONDENSATE CONNECTION
CAW 3-4-5 MODELS
• Connect a rigid PVC pipe (4) with OD 18 mm, on the unit’s drain
connection (2) using a piece of flexible hose (2). Secure it with clamps
(3). (figure 05)
CAW 6-8-10 MODELS
• Connect the supplied flexible hose (2) to the unit’s drain fitting (1) and
secure it with the clamp (3) provided. Do not force the drain fitting.
• Connect a rigid PVC pipe (4) on the end of the hose (2) and secure it
with the clamp (3) provided.
Note : secure the clamps while ensuring that the screws are facing
upward (figure 05).
ALL MODELS
• Carefully insulate the hose with polyethylene foam.
• Be aware of the risk of freezing in false ceilings during the winter.
• If necessary, the condensate tube can be raised immediately after the
unit’s outlet. Max. height: 25 cm (figure 06).
• Make sure that the drain line has a slight slope in the flow direction
and that it does not form a siphon (figure 06).
• The tube must be held with supports (figure 07).
• Do not install air intakes (figure 08).
• The line must not have an upward slope near the outlet.
There is a risk that water may flow back when the unit is off. (figure
09).
CAW 3-4-5
4
figure 05
figure 05
2% min.
figure 06
3
2
1
CAW 6-8-10
2
12 cm max. (CAW 3-4-5)
30 cm max. (CAW 6-8-10)
as short as possible
• The unit can be connected to an outside air inlet conduit (17).
• The additional fan motor for the outside air intake is equipped with a separate electric power supply and can
be controlled by means of a two-pole On/off switch with an electrical protection device.
• To avoid operating and noise-related problems, the new air output should represent approximately 10% of the
total air output.
- Open the knock-out (18), secure a Ø70mm flange on the unit and connect the thermal insulated conduit.
- On the exterior, install a grille with filter to prevent drawing in dust and debris which could clog the unit’s
exchanger.
90°0'
18
ø 70
ø 2.9
ø 90
135
135
17
CAW 6-8-10
• The unit can be connected to an outside air inlet conduit.
- Open the knock-out (A), secure a connection sleeve (not supplied) to the unit and connect a thermal
insulated conduit.
- On the exterior, install a grille with filter to prevent drawing in dust and debris which could clog the unit’s
exchanger.
A
X
60
55
4 holes ø 3,1
ø112
Model
CAW 6
CAW 8-10
X
220
250
4.4 - ELECTRICAL CONNECTION
4.4.1 - Generals
• The electrical connection conduits must be fixed.
• Class 1 appliance.
• The electrical installation must be carried out in
compliance with the rules in force (especially NF C
15-100
CEI 364).
CAW 3-4-5
GB
4.4.2 - Detail of the connection
• Remove the cover of the electrical box.
• Cable clamps are provided to maintain the cable at
their entry point into the box.
• Connect the cables to the terminals provided.
• Make sure that the wires are correctly connected
to the terminals. Incorrect connection can cause
operating problems as well as overheating which
can cause fires.
• When replacing the box’s cover, be sure not to
pinch the cables.
• 230V / 1 + Earth / 50Hz power supply from a power supply and protection device (not included) in accordance
with the rules in force. The protection must be ensured by a two-pole circuit breaker (not supplied).
Note: The unit is designed to be connected to a power supply having a TT neutral regime (neutral to ground) or
GB
TN.S regime (to neutral) as per NF C 15-100.
For a IT neutral point connection (isolated neutral), provide ground fault protection.
• The acceptable voltage variation is ± 10% during operation.
• Wire sizes are given for informational purposes only. Wire sizes must be checked and adapted, as required,
according to the installation conditions and with regard to current standards.
Symbols of componentsColours of the wires
DP Drain pump
FLP1,2 Flap motor
FMI Indoor fan motor
PCB Controller
TH1,2 Thermistor
PR Power relay
FS Float switch
To avoid electric shock, be sure to turn the air conditioner off and disconnect the power before opening
the unit.
If you are installing more than 1 indorr unit (up to 4) in the same room, it is necessary for you to assign each unit
its own address so each can be operated by its own remote control unit.
PCB
GB
INDOOR
REMOTE CONTROLPCB
UNIT
FACTORY STATE
REMOTE CONTROL
4.6.1 CONNECTION OF EXTERNAL CONTROL
Water cassette supports external control function. In order to drive terminal control needs a 0-10V analog output
for fan speed modulating and a free potential contact for operating mode setting (Sum/Win)
Control regulating logics will keep water probes, air probes and condensate discharge pump under control.
Please follow the diagram for a correct wiring.
Data cables must not be close to electromagnetic
interference sources.
4.6.2 REMOTE CONTROL: HOW TO CHANGE FROM INFRARED TO WIRED
GB
ELIMINATE “BRIDGE” WIRE (YELLOW)
YEL
YEL/GRN
WHT
VLT
PNK
REMOVE THE BATTERIES
5, 6 OFF
1. PREPARE THE REMOTE CONTROLLER
• Detach the plastic cover of the remote controller terminal block.
• Open the batteries compartment, remove the batteries and set microswitches 5 and 6 in OFF position.
•
Close the compartment without replacing the batteries (remote controller will be powered by wire).
2. CONNECTION
Use a tripolar electric shielded wir
H05VVC4V5-K (according to CEI 20-20 CENELEC HD21).
CONNECTING THE REMOTE CONTROLLER TO THE 5 POLES TERMINAL BLOCK INSIDE THE ELECTRICAL
PANEL AS FOLLOWS:
• Remove the yellow “bridge” wire.
• Connect the terminal that ends with PNK wires to the bottom terminal of remote controller terminal block (+
pole).
Connect the terminal that ends with VLT wire to the medium terminal of remote controller terminal block (IR).
•
• Connect the terminal that ends with WHT wires to the upper terminal of remote controller terminal block (- pole).
e 0.5mm, max. length 15m. The wires have not to be lighter than Mod.
Set the switch 1 of SW2 to OFF position for the MASTER
UNIT, to ON position for the SLAVE UNITS.
GB
NOTES
• Only one unit can be set as MASTER.
• When a unit is set as SLAVE the parameters from its remote control are ignored and the unit operates exactly
with the remote control settings of the MASTER UNIT.
• Use a bipolar electric shielded wire 0.5mm. The wires have not to be lighter than Mod. H05VVC4V5-K
(according to CEI 20-20 CENELEC HD21).
• Max. length (total length of wires): 250 m
Min. length between units: 0,5 m
• In case of a power failure the units will restart with the last settings of the MASTER UNIT’s remote control.
Verify that the switch 1 of SW2 is in
OFF position (factory setting).
REMOTE CONTROL
2
1 - 3
1. Press and hold the CLEAN button for 7
seconds.
2. Press the buttons + and - until the
desired address is indicated (1, 2, 3.....).
3. Press and hold again the CLEAN button
for 7 seconds, pointing the remote
control towards the unit’s receiver.
4. Three “beep” will indicate the correct
address setting.
NOTES
• Positive numbers on the remote control from 1 to 99 (except 33 38 and 77): set modbus address from 1 to 99
to the cassette (except 33 38 77).
• Number 0 on the remote control: set modbus address 100 to the cassette.
• Negative numbers (flashing) on the remote control from 1 to 28: set modbus address from 101 to 128 to the
cassette.
• The numbers 33, 38 e 77 flashing on the remote control: set the modbus addresses 33, 38 and 77 to the
cassette.
• Use a bipolar electric shielded wire 0.5mm. The wires have not to be lighter than Mod. H05VVC4V5-K
(according to CEI 20-20 CENELEC HD21).
• Max. length (total length of wires): 250m
Min. length between units: 0,5m
• The cable shielding must be connected only on one side (see diagram).
• In case of a power failure the units will restart with the last settings of the MODBUS control, but it will be
necessary that the MODBUS SUPERVISOR regain control of the units before you can set the parameters again.
• The units set as SLAVE can not be connected to the MODBUS.
• The MODBUS control is only available on units set as MASTER.
• If the MODBUS control is active, the signals coming from the units’ controls are ignored. When the MODBUS
control is deactivated the unit keeps operating with the last parameters set by MODBUS until it receives a new
signal from its remote control.
- Remove the retaining screws (1) from the locks (2) on each side
(remember to replace these screws after installation).
- To open the grille (3), turn the two locks (2) in the direction of the
arrow.
- Open the grille (3) 45°.
- Detach the safety cord (4) from the frame (remember to replace it
again after installation).
- Pull the grille inward to remove it from the frame.
• To install the facade:
- Turn the two locking clips (5) downward.
- Attach the frame of the facade (6) to the unit with the two hooks
(7) by lining them up with the locking clips (5).
Note (for CAW 6-8-10 models)
- Observe the position of the facade frame as the hooks are
not the same size. Correctly present them in front of the
corresponding locking clips.
- Check the correct position of the facade frame in relation to
the false ceiling. Adjust the position of the internal unit, as
required.
- Secure the facade frame to the unit using the special screws and
washers (8) provided.
- Fit the grille (3) making sure that the filter (9) is correctly installed.
- Hook the grille safety cord to the frame, close the grille and
replace the lock retaining screws.
34
1
GB
6
7
8
9
3
6 - ACCESSORIES
VALVE KIT - CODE 70600088 - CAW 3-4-5
• The valve kit includes:
- the valve body,
- 2 swivel couplings,
- actuator (with 230V “On/Off” heating element).
• Assembly
A - Valve directly on the unit’s hydraulic
connections
• Screw the “2 part” portion of the swivel
coupling on the female coupling of the unit.
Use a stepped spanner or a hex wrench. Put
sealing compound or Teflon tape on the threads.
Important: Hold the unit’s couplings with a
wrench while tightening to avoid twisting
the tubes inside the unit.
• Screw the “1 part” portion of the swivel coupling
onto the valve threads.
A - Valve directly on the unit’s hydraulic connections
• Fit the 3/4” male - 1/2” female adapter couplings
on the unit’s female connectors, then screw the “2
part” portion of the swivel couplings onto the adapter
couplings. Use a stepped spanner or a hex wrench.
Put sealing compound or Teflon tape on the threads.
Important: Hold the unit’s couplings with a wrench
while tightening to avoid twisting the tubes inside
the unit.
• Fit the 3/4” female - 1/2” male adapter couplings
on the valve, then screw the “1 part” portion of the
swivel couplings onto the adapter couplings. Use
sealing compound or Teflon on the threads.
• Fit the valve on the unit at the level of the swivel
couplings. The valve is installed at the unit’s water
outlet.
• Install the thermal actuator on the valve and
connect the cable in the electrical box as shown
in the electric wiring diagram.
• Mount the auxiliary tank (supplied with the unit) on the
side, below the valve. House the tank’s fitting in the
hole underneath the valve. Secure the tank with the
two screws provided.
B - Valve distant from the unit’s hydraulic
connections
• The valve can be installed on a pipe (not supplied)
enabling it to be offset from the unit’s hydraulic
connections.
In this case, place the valve along the unit, on the side
Before doing any work on the air conditioner, make sure it is switched off and put out of bounds.
Any work must be carried out by personnel qualified and authorised to work on this type of air conditioner.
7.1 - PRELIMINARY CHECKS
• Make sure:
- that the air handler is well fixed,
- that the power cables are well fixed to their connection terminals,
- that the electric cables are properly insulated from any pieces of sheet or metal parts which could damage
them,
- that the unit is connected to earth,
- that no tools or any other objects have been left in the unit,
- that the filter is correctly fitted,
- that the coil is clean,
- the hydraulic couplings are correctly tightened,
- that the condensate discharge outlet is correctly connected,
- that the condensate drain pan is clean,
- that the condensate discharge outlet pipes are securely fastened.
7.2 - SWITCH ON THE UNIT
• Using the isolation and protection device.
• Start the device using the control box.
• Check that the fan operates correctly at the three
ventilation speeds, without abnormal mechanical
noise.
• Check that all the connections are watertight.
• Check that the condensate pump operates correctly
by pouring a little water into the auxiliary drain pan
under the valve.
• Check that there is no water backflow when the
pump is stopped.
• Purge the cassette.
7.3 - FILLING THE HYDRAULIC CIRCUIT
WITH WATER
• If a control valve is assembled, make sure that it
operates correctly, activating it by using the remote
control.
7.4 - STARTING
• See Operation Instruction manual.
8 - MAINTENANCE
Before doing any work on the installation, make sure it is switched off and put out of bounds.
All operations must be carried out by personnel that are approved and qualified for this type of equipment.
GENERAL MAINTENANCE
All equipment must be properly maintained in order to provide optimum performance over time. Faulty maintenance
can result in the cancellation of the product guaranty. Depending on the products, maintenance operations consist
in the cleaning of filters (air, water), internal and external exchangers, casings, and the cleaning and protection
of condensate tanks. Treating odours and the disinfection of room surfaces and volumes also contributes to the
cleanliness of the air breathed by users.
IMPORTANT
GB
• Air filter:
- Clean at least once a month or more
frequently (see Operating instructions).
• Electric connections :
- Once a year, check that the electric wires
are well fastened to their terminals.
• Electric box :
- Dusting is recommended once a year.
• Condensate drainage system :
- This requires regular specific maintenance.
- The maintenance cycle is determined by
the conditions of operation (minimum operations
to be performed each time the installation
is restarted in cooling mode).