Technibel CAFP 164 R, SPAFP 124 R, MAFP 165 R, SPAFP 164 R, DSAFP 164 R Installation Instructions Manual

...
Page 1
CAFP
MAFP
SPAFP
DSAFP
GRFP
K
85464359728000 2005
– PACKAGE Air Conditioner –
INSTALLATION INSTRUCTIONS
R410A Models Indoor Units
Outdoor Units
Indoor Unit Type 12 16 18 25 36 48
CAFP* 4-Way Air Discharge
Semi-Concealed
CAFP 124 R CAFP 164 R CAFP 184 R CAFP 254 R CAFP 364 R CAFP 484 R
MAFP Wall-Mounted MAFP 125 R MAFP 165 R MAFP 185 R MAFP 255 R
SPAFP Ceiling-Mounted SPAFP 124 R SPAFP 164 R SPAFP 184 R SPAFP 255 R SPAFP 365 R SPAFP 485 R
DSAFP Concealed-Duct DSAFP 124 R DSAFP 164 R DSAFP 184 R DSAFP 255 R DSAFP 365 R DSAFP 485 R
Refrigerant R410A is used in the outdoor units.
GRFP 255 R, GRFP 365 R, GRFP 485 R
GRFP Outdoor Units
GRFP 255 L, GRFP 365 L, GRFP 485 L
Optional Controllers
Remote Controller K70D036Z
Wireless Remote Controller (For CAFP type) K70D037Z
Wireless Remote Controller (For SPAFP type) K70D040Z
Wireless Remote Controller+rceiver (for all types) K70D039Z
K Wireless Remote Controller (For MAFP type) K70D041Z
Simplified Remote Controller K70D042Z
Remote Sensor K70D050Z
System Controller K70D043Z
Schedule Timer K70D046Z
DC Inverter R410A
04-393 DC INV Tech p a-44 12/15/04 3:04 PM Page a
Indoor Unit Type 12 16 18 25 36 48
CAFP
* 4-Way Air Discharge
* For this type of Indoor unit (CAFP), please see the Installation Instructions accompanying the unit
Page 2
2
IMPORTANT! Please Read Before Starting
This air conditioning system meets strict safety and operat­ing standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
Carefully read this instruction booklet before beginning.
Follow each installation or repair step exactly as shown.
Observe all local, state, and national electrical codes.
Pay close attention to all warning and caution notices given in this manual.
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.
If Necessary, Get Help
These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tub­ing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental
injury or death.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause over­heating at connection points and a possible fire hazard.
When Transporting
Be careful when picking up and moving the indoor and out­door units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin alu­minum fins on the air conditioner can cut your fingers.
When Installing…
…In a Room
Properly insulate any tubing run inside a room to prevent “sweating” that can cause dripping and water damage to walls and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This pre­vents water damage and abnormal vibration.
…In an area with High Winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
• Ventilate the room well, in the event that is refrigerant gas leaks during the installation. Be careful not to allow contact of the refrigerant gas with a flame as this will cause the generation of poisonous gas.
• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak-free connection.
• Check carefully for leaks before starting the test run.
Depending on the system type, liquid and gas lines may be either narrow or wide. Therefore, to avoid confusion the refrigerant tubing for your particular model is speci­fied as either “narrow” or “wide” than as “liquid” or “gas.”
When Servicing
• Turn the power OFF at the main power box (mains) before opening the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.
• Ventilate any enclosed areas when installing or testing the refrigeration system. Escaped refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas.
• Confirm after installation that no refrigerant gas is leak­ing. If the gas comes in contact with a burning stove, gas water heater, electric room heater or other heat source, it can cause the generation of poisonous gas.
NOTE
WARNING
WARNING
CAUTION
CAUTION
04-393 DC INV Tech p a-44 12/15/04 3:04 PM Page 2
Page 3
3
2. The standards for minimum room volume are as follows.
(1) No partition (shaded portion)
(2) When there is an effective opening with the adja-
cent room for ventilation of leaking refrigerant gas (opening without a door, or an opening 0.15% or larger than the respective floor spaces at the top or bottom of the door).
(3) If an indoor unit is installed in each partitioned
room and the refrigerant tubing is interconnected, the smallest room of course becomes the object. But when mechanical ventilation is installed inter­locked with a gas leakage detector in the smallest room where the density limit is exceeded, the vol­ume of the next smallest room becomes the object.
3. The minimum indoor floor space compared with the amount of refrigerant is roughly as follows (for room with 2.7 m high ceiling):
Check of Density Limit
The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its density will not exceed a set limit.
The refrigerant (R410A), which is used in the air condi­tioner, is safe, without the toxicity or combustibility of ammonia, and is not restricted by laws imposed to pro­tect the ozone layer. However, since it contains more than air, it poses the risk of suffocation if its density should rise excessively. Suffocation from leakage of refrigerant is almost non-existent. With the recent increase in the number of high density buildings, how­ever, the installation of multi air conditioner systems is on the increase because of the need for effective use of floor space, individual control, energy conservation by curtailing heat and carrying power, etc. Most importantly, the multi air conditioner system is able to replenish a large amount of refrigerant com­pared to conventional individual air conditioners. If a single unit of the multi air conditioner system is to be installed in a small room, select a suitable model and installation procedure so that if the refrigerant acci­dentally leaks out, its density does not reach the limit (and in the event of an emergency, measures can be made before injury can occur). In a room where the density may exceed the limit, create an opening with adjacent rooms, or install mechanical ventilation combined with a gas leak detection device. The density is as given below.
Total amount of refrigerant (kg)
Min. volume of the indoor unit installed room (m3)
Density limit (kg/m
3
)
The density limit of refrigerant which is used in multi air con­ditioners is 0.3 kg/m
3
(ISO 5149).
1. If there are 2 or more refrigerating systems in a sin­gle refrigerating device, the amount of refrigerant should be as charged in each independent device.
For the amount of charge in this example:
The possible amount of leaked refrigerant gas in rooms A, B and C is 10 kg. The possible amount of leaked refrigerant gas in rooms D, E and F is 15 kg.
NOTE
Outdoor unit
Refrigerant tubing
Indoor unit
e.g., charged amount (10 kg)
Outdoor unit
Indoor unit
Room A Room B Room C Room D Room E Room F
e.g., charged amount (15 kg)
Refrigerant tubing
Outdoor unit
Very small room
Indoor unit
Small room
Medium room
Large room
Mechanical ventilation device – Gas leak detector
40
35
30
25
20
15
10
5
0
10 20 30
Total amount of refrigerant
Min. indoor floor space
m
2
kg
Range below the density limit of 0.3 kg/m
3
(countermeasures not needed)
Range above the density limit of 0.3 kg/m
3
(countermeasures needed)
04-393 DC INV Tech p a-44 12/15/04 3:04 PM Page 3
Page 4
4
1-2. Prevent impurities including water, dust and oxide from entering the tubing. Impurities can cause R410A
refrigerant deterioration and compressor defects. Due to the features of the refrigerant and refrigerating machine oil, the prevention of water and other impurities becomes more important than ever.
2. Be sure to recharge the refrigerant only in liquid form.
2-1. Since R410A is a non-azeotrope, recharging the refrigerant in gas form can lower performance and cause
defects of the unit.
2-2. Since refrigerant composition changes and performance decreases when gas leaks, collect the remaining
refrigerant and recharge the required total amount of new refrigerant after fixing the leak.
3. Different tools required
3-1. Tool specifications have been changed due to the characteristics of R410A.
Some tools for R22- and R407C-type refrigerant systems cannot be used.
Unit: mm
Material 0
Copper tube
Outer diameter 6.35 9.52 12.7 15.88
Wall thickness 0.8 0.8 0.8 1.0
Item New R407C tools Remarks
tool compatible
with R410A
Manifold gauge Yes No Types of refrigerant, refrigerating machine
oil, and pressure gauge are different.
Charge hose Yes No To resist higher pressure, material must be changed.
Vacuum pump Yes Yes Use a conventional vacuum pump if it is equipped
with a check valve. If it has no check valve, purchase and attach a vacuum pump adapter.
Leak detector Yes No Leak detectors for CFC and HCFC that
react to chlorine do not function because R410A contains no chlorine. Leak detectors for HFC134a can be used for R410A.
Flaring oil Yes No For systems that use R22, apply mineral oil (Suniso oil)
to the flare nuts on the tubing to prevent refrigerant leakage. For machines that use R407C or R410A, apply synthetic oil (ether oil) to the flare nuts.
Precautions for Installation Using New Refrigerant
1. Care regarding tubing
1-1. Process tubing
Material: Use C1220 phosphorous deoxidized copper specified in JIS H3300 Copper and Copper Alloy Seam-
less Pipes and Tubes.
Tubing size: Be sure to use the sizes indicated in the table below.
Use a tube cutter when cutting the tubing, and be sure to remove any flash. This also applies to distribution
joints (optional).
When bending tubing
φ
15.88 or smaller, use a bending radius that is 4 times the outer diameter of the tubing or larger.
* Using tools for R22 and R407C and new tools for R410A together can cause defects.
Manifold gauge
Vacuum pump
Outlet Inlet
CAUTION
Use sufficient care in handling the tubing. Seal the tubing ends with caps or tape to prevent dirt, moisture, or other foreign substances from entering. These contaminants can result in system malfunction.
04-393 DC INV Tech p a-44 12/15/04 3:04 PM Page 4
Page 5
5
Valve
Liquid
3-2. Use R410A exclusive cylinder only.
Single-outlet valve
(with siphon tube) Liquid refrigerant should be recharged with the cylinder standing on end as shown.
04-393 DC INV Tech p a-44 12/15/04 3:04 PM Page 5
Page 6
6
IMPORTANT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Please Read Before Starting Check of Density Limit Precautions for Installation Using New Refrigerant
1. GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1-1. Tools Required for Installation (not supplied) 1-2. Accessories Supplied with Unit 1-3. Type of Copper Tube and Insulation Material 1-4. Additional Materials Required for Installation 1-5. Tubing Size 1-6. Optional Distribution Joint Kits 1-7. Installing Distribution Joint Kit (for Twin &
Double-Twin) (K70A056Z)
1-8. Installing Distribution Joint Kit (for Triple)
(K70A061Z)
2. SELECTING THE INSTALLATION SITE . . . . .17
2-1. Indoor Unit 2-2. Outdoor Unit 2-3. Air Discharge Chamber for Top Discharge 2-4. Installing the Unit in Heavy Snow Areas 2-5. Precautions for Installation in Heavy Snow
Areas
2-6. Dimensions of Snow / Wind-proof Ducting
and Refrigerant Tubing Space of Installation
3. HOW TO INSTALL THE INDOOR UNIT . . . . .20
4-Way Air Discharge Semi-Concealed Type
(CAFP Type) . . . . . . . . . . . . . . . . . . . . . . . . . . .20
3-1. Preparation for Suspending 3-2. Suspending the Indoor Unit 3-3. Placing the Unit Inside the Ceiling 3-4. Installing the Drain Piping 3-5. Checking the Drainage
Wall-Mounted Type (MAFP Type) . . . . . . . . . . .24
3-6. Removing the Rear Panel from the Unit 3-7. Selecting and Making a Hole 3-8. Installing the Rear Panel onto the Wall 3-9. Removing the Grille to Install the Indoor Unit 3-10. Preparing the Tubing 3-11. Shaping the Tubing 3-12. Installing the Drain Hose
Ceiling-Mounted Type (SPAFP Type) . . . . . . . .28
3-13. Required Minimum Space for Installation and
Service 3-14. Suspending the Indoor Unit 3-15. Duct for Fresh Air 3-16. Shaping the Tubing 3-17. Installing the Drain Piping
Concealed-Duct Type (DSAFP Type) . . . . . . .35
3-18. Required Minimum Space for Installation and
Service
3-19. Suspending the Indoor Unit 3-20. Installing the Drain Piping 3-21. Checking the Drainage 3-22. Increasing the Fan Speed
4. HOW TO INSTALL THE OUTDOOR UNIT . . .40
4-1. Installing the Outdoor Unit 4-2. Drainage Work 4-3. Routing the Tubing and Wiring
5. ELECTRICAL WIRING . . . . . . . . . . . . . . . . . . .41
5-1. General Precautions on Wiring 5-2. Recommended Wire Length and Wire Diam-
eter for Power Supply System
5-3. Wiring System Diagrams
6. HOW TO INSTALL THE REMOTE CONTROLLER
(OPTIONAL PART) . . . . . . . . . . . . . . . . . . . . . .45
6-1. When Using a Wall Box for Flush Mounting 6-2. Basic Wiring Diagram (Twin, Triple, Double-
Twin) 6-3. Wiring System Diagram for Group Control 6-4. Switching the Room Temperature Sensors 6-5. Connecting to a Ventilation Fan 6-6. Wiring the Remote Controller 6-7. Trouble Diagnostics
7. HOW TO PROCESS TUBING . . . . . . . . . . . . .53
7-1. Connecting the Refrigerant Tubing 7-2. Connecting Tubing Between Indoor and
Outdoor Units 7-3. Insulating the Refrigerant Tubing 7-4. Taping the Tubes 7-5. Finishing the Installation
8. LEAK TEST, EVACUATION AND ADDITIONAL
REFRIGERANT CHARGE . . . . . . . . . . . . . . . .57
Air Purging with a Vacuum Pump (for Test Run)
Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
8-1. Leak Test 8-2. Evacuation 8-3. Charging Additional Refrigerant 8-4. Finishing the Job
9. HOW TO INSTALL THE CEILING PANEL . . . .60
4-Way Air Discharge Semi-Concealed Type
(CAFP Type) . . . . . . . . . . . . . . . . . . . . . . . . . . 60
9-1. Before Installing the Ceiling Panel 9-2. Installing the Ceiling Panel 9-3. Wiring the Ceiling Panel 9-4. How to Attach the Corner & Air Intake Grille 9-5. Checking After Installation 9-6.
When Removing the Ceiling Panel for Servicing
9-7. Adjusting the Auto Flap
CONTENTS
Page
Page
04-393 DC INV Tech p a-44 12/15/04 3:04 PM Page 6
Page 7
7
10.TEST RUN . . . . . . . . . . . . . . . . . . . . . . . . . . . .64
10-1. Preparing for Test Run
CAFP, SPAFP, DSAFP Type . . . . . . . . . . . . . . 65
10-2. Caution 10-3. Test Run Procedure 10-4. Items to Check Before the Test Run 10-5. Test Run Using the Remote Controller 10-6. Precautions 10-7. Table of Self-Diagnostic Functions and
Corrections (CAFP, SPAFP, DSAFP, MAFP Type)
10-8. System Control
MAFP Type . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
10-9. Caution 10-10. Test Run Procedure 10-11. Items to Check Before the Test Run 10-12. Preparation for Test Run 10-13. Test Run 10-14. Precautions 10-15. Table of Self-Diagnostic Functions and
Corrections
10-16. System Control
CAFP, SPAFP, DSAFP Type (for Link Wiring) . 81 10-17. Caution 10-18. Test Run Procedure 10-19. Items to Check Before the Test Run 10-20. Test Run Using the Remote Controller 10-21. Table of Self-Diagnostic Functions and
Corrections CAFP, SPAFP, DSAFP, MAFP Type
10-22. Automatic Address Setting
MAFP Type (for Link Wiring) . . . . . . . . . . . . . . 90
10-23. Caution 10-24. Test Run Procedure 10-25. Table of Self-Diagnostic Functions and
Corrections CAFP, SPAFP, DSAFP, MAFP
Type 10-26. Automatic Address Setting 10-27. Caution for Pump Down
11. HOW TO INSTALL THE WIRELESS REMOTE
CONTROLLER RECEIVER . . . . . . . . . . . . . . 99
K70D037Z for 4-Way Cassette (CAFP Type) . . 99
11-1. Installing the Receiver Unit 11-2. Accessories 11-3. Wiring the Receiver Unit 11-4. Precautions on Simultaneous Installation of
Wired Remote Controller and Wireless Remote Controller
11-5. How to Use the Test Run Setting
K70D040Z for Ceiling Mounted (SPAFP Type) 102
11-6. Installing the Receiver Unit
11-7. Accessories Supplied with Unit 11-8. Wiring the Receiver Unit 11-9. Precautions on Simultaneous Installation of
Wired Remote Controller and Wireless Remote Controller
11-10. How to Use the Test Run Setting
K70D039Z for DSAFP Type . . . . . . . . . . . . . . 105
11-11. Accessories Supplied with Separate
Receiver Unit
11-12. Important Information for Installation of
1 Separate Receiver Unit 11-13. How to Install the Separate Receiver Unit 11-14. W iring the Separate Receiver Unit 11-15. Important Information for Installation of
2 Separate Receiver Units 11-16. Test Run Setting
Page
04-393 DC INV Tech p a-44 12/15/04 3:04 PM Page 7
Page 8
8
1. GENERAL
This booklet briefly outlines where and how to install the air conditioning system. Please read over the entire set of instructions for the indoor and outdoor units and make sure all accessory parts listed are with the system before beginning.
1-1. Tools Required for Installation (not supplied)
1. Standard screwdriver
2. Phillips head screwdriver
3. Knife or wire stripper
4. Tape measure
5. Carpenters level
6. Sabre saw or key hole saw
7. Hacksaw
8. Core bits
9. Hammer
10. Drill
11. Tube cutter
12. Tube flaring tool
13. Torque wrench
14. Adjustable wrench
15. Reamer (for deburring)
1-2. Accessories Supplied with Unit
See Tables 1-1 to 1-4.
1-3. Type of Copper Tube and Insulation Material
If you wish to purchase these materials separately from a local source, you will need:
1. Deoxidized annealed copper tube for refrigerant tubing.
2. Foamed polyethylene insulation for copper tubes as required to precise length of tubing. Wall thickness of the insulation should be not less than 8 mm.
3. Use insulated copper wire for field wiring. Wire size varies with the total length of wiring. Refer to
5. Electrical Wiring for details.
1-4. Additional Materials Required for Installation
1. Refrigeration (armored) tape
2. Insulated staples or clamps for connecting wire (See your local codes.)
3. Putty
4. Refrigeration tubing lubricant
5. Clamps or saddles to secure refrigerant tubing
6. Scale for weighing
CAUTION
Check local electrical codes and regulations before obtaining wire. Also, check any specified instructions or limitations.
Table Type
1-1 4-Way Air Discharge Semi-Concealed
1-2 Wall-Mounted
1-3 Ceiling-Mounted
1-4 Concealed-Duct
04-393 DC INV Tech p a-44 12/15/04 3:04 PM Page 8
Page 9
9
Table 1-1 (4-Way Air Discharge Semi-Concealed)
Part Name Figure
Qty
Remarks
Full-scale installation diagram
1
Flare insulator
2
Insulating tape
2
Hose band
1
Packing
1
Drain insulator
1
Drain hose
1
4
For wide and narrow tubes
For securing drain hose
For drain joint
For dr
ain joint
(White)
Washer
8
For suspension bolts
Screw
Printed on container box
For wide and narrow tube flare nuts
For full-scale installation diagram
For securing drain hose
Table 1-2 (Wall-Mounted)
Part Name
Figure
Qty
Remarks
Plastic cover
1
Tapping screw
10
For improved tubing appearance
For fixing the rear panel
Truss-head Phillips 4 × 16 mm
Insulator
1
For insulating flare nut (255 type only)
Table 1-3 (Ceiling-Mounted)
Part Name Figure
Qty
Remarks
Special washer
4
Drain insulator
1
Flare insulator
2 sets
Insulating tape
2
Vinyl clamp
8
Eyelet
1
Full-scale installation
diagram
1
Drain hose
1
For temporarily suspending indoor unit from ceiling
For drain hose joint
For wide and narrow tube joints
For wide and narrow flare joints
For flare and drain insulator
For pow
er supply inlet
T10
T5
T3
White (heat-resisting)
For drain hose connection
2
Hose band
L140
For main unit + PVC pipe joints
Printed on container box
04-393 DC INV Tech p a-44 12/15/04 3:04 PM Page 9
Page 10
10
Table 1-4 (Concealed-Duct)
Part Name Figure
Qty
Remarks
8
Flare insulator
2
Insulating tape
2
Drain insulator
1
Hose band
1
Packing
1
Drain hose
1
Sealing putty
1
Vinyl clamp
8
Booster cable*
1
For suspending indoor unit from ceiling
For wide and narrow tubes
For wide and narrow tubes flare nuts
For drain hose joint
For securing drain hose
For drain joint
For sealing recessed por tion of power supply
F
or flare and drain insulators
* Booster cable is housed inside the electrical component box.
Washer
Connector for changeover to HT tap.
Use 3/8" for suspension bolts.
Field supply for suspending bolts and nuts.
1-5. Tubing Size
(A) Single type
Refrigerant tubing between the indoor and outdoor units
shall be kept as short as possible.
The length of the refrigerant tubes between the indoor
and outdoor units are limited by the elevation difference between the 2 units. During tubing work, try to make both the tubing length (L) and the difference in elevation (H1) as short as possible. Refer to Table 1-5.
Table 1-5
Single
Main tubing L
H1
Outdoor unit type 25, 36 types 48 types
Maximum allowable tubing length 50 m 50 m
Charge-less tubing length (actual length) 3 – 30 m 5 – 30 m
Additional charge per 1 m 40g
04-393 DC INV Tech p a-44 12/15/04 3:04 PM Page 10
Page 11
11
(B) Simultaneous operation multi (Twin, Triple, Double-Twin)
Because the indoor units run simultaneously, install them within the same room.
NOTE
Single
Twin
Triple
Double-Twin
Actual length (m)
L
L + 1 L + 2
L + 3
L + 1, L + 2
L + L1 + 1, L + L1 + 2
L2 + 3, L2 + 4
Max.: L2 + 4 Min.: L1 + 1 (L2 + 4) – (L1+ 1)
L1 + 1, L1 + 2
1, 2
1 > 2
1 > 2 > 3
1 – 2
1 – 2 1 – 3 2 – 3
L + L2 + 3, L + L2 + 4
1, 2, 3
50
15
10
10
10
30 15 0.5
Item
Contents
Allowable tubing lengths
Maximum allowable tubing length
One-way length of tubing from outdoor unit to the most distant indoor unit
Maximum distribution tubing length
Maximum length following the first branch point (No. 1 distribution)
Maximum branch tubing length
Difference between the maximum length and minimum length in tubing following the first branch point
Maximum difference between lengths of No. 1 distribution tubing (double twin)
Maximum difference between lengths of No. 2 distribution tubing (double twin)
Maximum allowable height difference
Maximum indoor-outdoor height difference
If outdoor unit is higher
If outdoor unit is lower
Maximum height difference between indoor units
Symbol
L2 > L1
2 > 1 4 > 3 2 – 1 4 – 3
L2 – L1
H2
H2, H3, H4 H2, H3, H4, H5, H6, H7
––
––
H1 H1
Triple
Twin
Double-Twin
Main tubing L
Main tubing L
Main tubing L
Distribution joint No. 1
Distribution joint (purchase separately)
Distribution joint
Distribution tubing
A
A
A
1
2
2
A
1
1
2
3
3
4
* For connection tubing sizes, refer to table above.
B
H1
H1
H1
H2
H2
H2
H4H3
H3
H6
H7
H5
Distribution joint No. 2
L1
L2
A = K70A056Z B = K70A061Z
For refrigerant tube branches, use the optional distribution joints.
For cautions on the use of the optional distribution joints, be sure to refer to the provided instruction sheet. Also,
be careful to install them in the correct direction (orientation).
NOTE
04-393 DC INV Tech p a-44 12/15/04 3:04 PM Page 11
Page 12
12
Limit of elevation difference between the 2 units
No additional charge of compressor oil is necessary. *
1
If total tubing length becomes 30 to 50 m, charge additional refrigerant by 40 g/m.
Models
GRFP255L GRFP255R
GRFP365L GRFP365R
GRFP485L GRFP485R
Tubing Data
Tubing size Narrow tube mm (in.) 9.52 (3/8) 9.52 (3/8) 9.52 (3/8) outer diameter Wide tube mm (in.)
15.88 (5/8) 15.88 (5/8) 15.88 (5/8)
Limit of tubing length (m)
50 50 50
Outdoor unit is placed
30 30 30
higher (m) Outdoor unit is placed
15 15 15
lower (m)
Max. allowable tubing length at shipment (m)
3 – 30 3 – 30 5 – 30
Required additional refrigerant *
1
(g/m)
a) 40 b) 40 b) 40
Refrigerant charged at shipment (kg) 1.2 1.2 1.2
Table 1-6 Tubing Data for Models (Single, Twin, Triple, Double-Twin)
25 – 48
25 – 48
12 – 18
φ15.88
φ15.88
φ15.88
φ9.52
φ9.52
φ9.52 φ6.35
φ12.7
( 1, 2, 3, 4)
20 g
40 g
40 g
40 g
Wide tube
Narrow tube
Main tubing (L)
25
Double-Twin distribution tube (L1, L2)
Total type capacity of indoor units connected after the branch
Indoor unit connection tube
Type capacity of indoor units
Amount of additional charge per 1 m
Table 1-7 List of Connection Tube Sizes
Charge with an amount of additional refrigerant calculated using the formula below, based on the values in Table 1-7 and the size and length of the liquid (narrow) tubing.
Amount of additional refrigerant charge (g)
Do not remove refrigerant from the system, even if the result of the calculation is negative. (Use with the current refrigerant charge.)
(a) Actual length (m) of main tubing (φ9.52) Refrigerant charge per 1 m of actual length = 40 g/m (25, 36 and 48) (b) Total length of distribution tubing (φ9.52) Refrigerant charge per 1 m of actual length = 40 g/m (c) Total length of distribution tubing (φ6.35) Refrigerant charge per 1 m of actual length = 20 g/m
Example
Sample tubing lengths
L = 35 m 1 = 5 m L1 = 10 m 2 = 5 m L2 = 5 m 3 = 5 m
4 = 10 m
Find the liquid (narrow) tube size from Table 1-7.
L: φ9.52 (48 type) L1 : φ9.52 (Total type capacity of indoor units 25) L2 : φ9.52 (Total type capacity of indoor units 25)
1 – 4 : φ6.35
The amount of additional on-site refrigerant charge is found by subtracting the outdoor unit
charge-less refrigerant amount from the total charge amount for all tube sizes.
φ9.52 L : 35 m × 40 g / m = 1400 φ9.52 L1 + L2 : (10 + 5) m × 40 g / m = 600 φ6.35 1 4 : (5 + 5 + 5 + 10) m × 20 g / m = 500
Outdoor unit charge-less refrigerant amount –1200
Total +1300
The amount of additional on-site refrigerant charge is 1,300 g.
Outdoor unit
Indoor unit (12 type × 4)
L
L1
L2
4
3
21
Additional refrigerant amount (g) = Additional refrigerant for main tubing (g) + Additional refrigerant for distribution tubing (g)
– Outdoor unit charge-less refrigerant amount (g)
= 40X (a) + 40X (b) + 20X (c) – 1200 (25, 36 and 48)
04-393 DC INV Tech p a-44 12/15/04 3:04 PM Page 12
Page 13
13
CAUTION
CAUTION
WARNING
1. This unit requires no additional refrig­erant charge up to tubing length 30 m. In case of more than 30 m, additional refrigerant charge is required. Refer to Tables 1-6 and 1-7.
2. In case of multi type installation, indoor units should be installed within the same room. If multi type indoor units are installed in different rooms, temperature control may develop prob­lems because thermostat operation must follow the thermostat condition of 1 indoor unit only (the main unit).
Always check the gas density for the room in which the unit is installed.
Pay special attention to any location, such as a basement or recessed area, etc. where leaked refrigerant can collect, since refrigerant gas is heav­ier than air.
10
13.5
27.0
40.5
54.0
67.5
81.0
94.5
108
121.5
135
5
10
15
20
25
30
35
40
45
50
m
3
m
2
Total amount of refrigerant
Min. indoor floor area
(when the ceiling is 2.7 m high)
Min. indoor volume
20 30 40 kg
Range below the density limit of
0.3 kg/m
3
(Countermeasures not needed)
Range above the density limit of
0.3 kg/m
3
(Countermeasures needed)
Check of limit density
When installing an air conditioner in a room, it is neces­sary to ensure that even if the refrigerant gas acciden­tally escapes, its density does not exceed the limit level. If the density might exceed the limit level, it is neces­sary to set up an opening between it and the adjacent room, or to install mechanical ventilation which is inter­locked with the leak detector.
(Total refrigerant charged amount : kg)
(Min indoor volume where the indoor unit is installed : m3) Limit density 0.3 (kg/m3)
The limit density of refrigerant which is used in this unit is 0.3 kg/m
3
(ISO 5149).
The shipped outdoor unit comes charged with the amount of refrigerant fixed for each type; so add it to the amount that is charged at the field. (For the refriger­ant charge amount at shipment, refer to the unit’s nameplate.)
Minimum indoor volume & floor area relative to the amount of refrigerant is roughly as given in the following table.
04-393 DC INV Tech p a-44 12/15/04 3:04 PM Page 13
Page 14
14
1-6. Optional Distribution Joint Kits
K70A056Z : Cooling capacity after distribution is 16.0 kW (54,600 BTU/h) or less
K70A061Z : Cooling capacity after distribution is 28.0 kW (95,500 BTU/h) or less
Table 1-8 Distribution Branch Size ( 1, 2, 3, 4)
Unit: mm (in.)
Indoor Unit
12 type
16 type
18 type 25 type 36 type 48 type
Wide tube 12.7 (1/2) 15.88 (5/8)
Narrow tube 6.53 (1/4) 9.52 (3/8)
210
145
103
185
135
83
Distribution joint
Insulation material
Insulation material
Distribution joint
EEE
E
E
E
DD
D
C
C
C
GG
G
FF
F
for wide tube for narrow tube
K70A056Z
Table 1-9 Dimensions of connections (inner diameter of tubing)
Unit: mm
Position A B C D E F G
Size ø 28.58 ø 25.4 ø 19.05 ø 15.88 ø 12.7 ø 9.52 ø 6.35
100 35
80
80
(295)
φ9.52φ9.52φ9.52
1
2
1
2
3
4
5
6
BCUP-3
100 80 80
300
100
φ12.7
φ25.4
φ15.88
φ15.88
φ15.88
for narrow tube
for wide tube
(3 locations)
Dowel pin position
Narrow distribution joint
Wide distribution joint
Narrow-tube side tube connector
31
31
1112
Wide-tube side tube connector
Wide-tube side tube connector
1
1
φ9.52 φ12.7
φ12.7
φ15.88
φ15.88
φ19.05
φ19.05
φ25.4
φ25.4
φ28.58
φ9.52
φ6.35
Thermal insulation for narrow distribution joints
Thermal insulation for wide distribution joints
K70A061Z (for simultaneous Triple)
04-393 DC INV Tech p a-44 12/15/04 3:04 PM Page 14
Page 15
15
Dowel pin
Cutting location
Cut as far away as possible (to ensure proper insertion clearance for the connecting tube)
Cutting is only necessary for the welding dimensions at positions B, D, and F.
Vertical installation (directed upward or downward)
Example showing tubing directed upward
Horizontal line
Horizontal line
Indoor unit side
Outdoor unit side
Install at a positive angle. (15 – 30°)
Horizontal installation
1-7. Installing Distribution Joint Kit (for Twin &
Double-Twin) (K70A056Z)
Use a tube cutter and cut at the size position that
corresponds to the field-supply tube size selected based on the total indoor unit capacity. (If the size is the same as the tube end size, cutting is not neces­sary.)
If the reducer that was supplied in the package is
used, perform brazing on-site.
Note: Do not cut in such a way that applies exces-
sive force and causes deformation of the tube. (This will prevent insertion of the con­necting tube.) For size selection, refer to Information for the Person in Charge of Installation and other materials that were supplied with the outdoor unit.
Cut at a position that is as far away as possible
from the dowel pin.
After cutting the tube, be sure to remove any burrs
and to finish the end surface correctly. (If there is excessive crushing or indentation of the tube, use a tube expander to expand it.)
Check that there is no dirt or other foreign sub-
stance inside the distribution tubing.
Install the distribution tubing so that it is either hori-
zontal or vertical.
Use the supplied thermal insulation to insulate the
distribution tubing. (If other insulation is used, be sure to use insula­tion that can withstand temperatures of at least 120°C.)
For details, refer to Information for the Person in
Charge of Installation.
Nitrogen gas replacement required for tube brazing
If nitrogen replacement is not done when brazing is performed on the indoor unit and outdoor unit refrig­erant tubing, oxide scale will occur. This scale will clog the solenoid valves, strainers, and other parts, leading to malfunction.
Therefore be sure to replace the air in the tubing with nitrogen when performing brazing in order to prevent problems from oxide scale.
04-393 DC INV Tech p a-44 12/15/04 3:04 PM Page 15
Page 16
16
Refrigerant tubing (field supply)
Refrigerant tubing (field supply)
Seal securely with vinyl tape (4 locations)
Distribution joint insulation materials (supplied)
Use the supplied insulation materials. The supplied insulation materials include only tape for temporarily fastening them in place. Use insulation material or other material to seal the joining lines so that there are no gaps. Use vinyl tape or similar means to seal and fasten the insulation materials in place.
Tubing insulation material must be able to withstand temperatures of at least 120°C.
Tubing insulation material (field supply; thickness of more than 10 mm)
Only the distribution joints are horizontal with respect to the ground. The collective tubes are vertical with respect to the ground.
The collective tube and distribution joint are horizontal with respect to the ground.
Collective tube
Distribution joint
<Narrow tube side>
1-8. Installing Distribution Joint Kit (for Triple)
(K70A061Z)
Before installing, check the system combination.
The 3 indoor units must be installed within the
same room.
To adjust the tube sizes of the distribution joints,
use the supplied tube connectors.
How to Install Distribution Joints
Use the supplied distribution joints to complete refrig­erant tubing work. Install distribution joints so that the tubes are horizon­tal after the branch point.
Orientation of distribution joints
Only the distribution joints are horizontal with respect to the ground. The collective tubes are vertical with respect to the ground.
The collective tube and distribution joint are horizontal with respect to the ground.
Collective tube
Distribution joint
<Wide tube side>
Inclination
Inclination
Be sure to install so that the tubes are horizontal after the branch point.
INCORRECT
Length requirement for strainer on main distribution tube side
Attach a straight tube 500 mm or longer to the main tubing side of the distribution joint (for both narrow and wide tubing).
Tubing insulation
Be sure to apply thermal insulation to both the narrow and wide tubing. Depending on the conditions inside the ceiling, condensation may form on the insulation mate­rial. If high temperatures and high humidity are expected to occur inside the ceiling, add glass wool (16 – 20 kg/m
3
, with a thickness of 10 mm or more) to the below insulation materials and apply sufficient thermal insulation.
More than 500 mm
More than 500 mm
04-393 DC INV Tech p a-44 12/15/04 3:04 PM Page 16
Page 17
17
2. SELECTING THE INSTALLATION SITE
2-1. Indoor Unit
AVOID:
areas where leakage of flammable gas may be
expected.
places where large amounts of oil mist exist.
direct sunlight.
locations near heat sources which may affect the
performance of the unit.
locations where external air may enter the room
directly. This may cause sweating on the air dis­charge ports, causing them to spray or drip.
locations where the remote controller will be splashed
with water or affected by dampness or humidity.
installing the remote controller behind curtains or fur-
niture.
locations where high-frequency emissions are gener-
ated.
DO:
select an appropriate position from which every cor-
ner of the room can be uniformly cooled.
select a location where the ceiling is strong enough
to support the weight of the unit.
select a location where tubing and drain pipe have
the shortest run to the outdoor unit.
allow room for operation and maintenance as well as
unrestricted air flow around the unit.
install the unit within the maximum elevation differ-
ence above or below the outdoor unit and within a total tubing length (L) from the outdoor unit as detailed in Tables 1-5 and 1-6.
allow room for mounting the remote controller about
1m off the floor, in an area that is not in direct sun­light nor in the flow of cool air from the indoor unit.
Concealed-Duct Type
4-Way Semi-Concealed T
ype
1m
1m
1m
1m
1m
Wall-Mounted Type
min.15 cm
Front View
min. 15 cm
min. 15 cm
Ceiling-Mounted Type
Side view
min. 25 cm
The rear of the indoor unit can be installed flush against the wall.
min. 50 cm
Air intake
Air discharge
min. 25 cm
Ceiling
Wall
NOTE
Front view
Max. 25 cm
Obstacle
Fig. 2-1
Fig. 2-2
Fig. 2-3
04-393 DC INV Tech p a-44 12/15/04 3:04 PM Page 17
Page 18
18
2-2. Outdoor Unit
AVOID:
heat sources, exhaust fans, etc. (Fig. 2-4)
damp, humid or uneven locations
DO:
choose a place as cool as possible.
choose a place that is well ventilated and outside
air temperature does not exceed maximum 45°C constantly.
allow enough room around the unit for air intake/
exhaust and possible maintenance. (Fig. 2-5)
use lag bolts or equal to bolt down unit, reducing
vibration and noise.
Installation space
Distance between obstructions and the unit air inlet and outlet must be as shown below.
Fig. 2-4
Fig. 2-5
Fig. 2-6
Fig. 2-7
Out­door unit
Heat source
Hot air
Exhaust fan
Air in
Air in
Air discharge
Anchor bolts (4 pieces)
Min. 15cm
In case of multiple installations
provide a solid base (concrete block, 10 × 40 cm
beams or equal), a minimum of 15 cm above ground level to reduce humidity and protect the unit against possible water damage and decreased ser­vice life. (Fig. 2-7)
use lug bolts or equal to bolt down unit, reducing
vibration and noise.
*4
*1
*2
*3
*1
More than 1cm
More than 100cm
More than 1cm
Inlet side C
Inlet side More than 20cm
Outlet side
(field supply)
A
B
(ground)
Air direction chamber
(Obstruction above unit)
(Obstruction on inlet side)
CAUTION
Concerning inlet-side distance “C (Fig. 2-5)
The minimum for distance “C” is 15 cm if there are no obstructions on the outlet side (wall *1 side) and *2 or *4 is not present. In all other cases, the minimum for distance C is 20 cm.
If the unit is installed with the outlet side facing wall *1, then there must be no obstruc-
tions on 2 of the remaining 3 sides: *2, *3, *4.
If wall *1 is on the outlet side (Fig. 2-5), or if obstructions are present on all 3 sides *2,
*3, and *4 (Fig. 2-5), then the minimum distance for “A” and “B” is 2 m (Fig. 2-7). Even if there is no wall on the outlet side, a minimum of 100 cm is required.
04-393 DC INV Tech p a-44 12/15/04 3:04 PM Page 18
Page 19
19
Fig. 2-8
Fig. 2-9
Fig. 2-10
2-3. Air Discharge Chamber for Top Discharge
Be sure to install the air discharge chamber in the field when:
it is difficult to keep a space of min. 50 cm between
the air discharge outlet and the obstacle.
the air discharge outlet is facing to the sidewalk
and discharged hot air annoys the passers-by. Refer to Fig. 2-8.
2-4. Installing the Unit in Heavy Snow Areas
In locations with strong wind, snow-proof ducting should likewise be fitted and direct exposure to the wind should be avoided as much as possible.
Countermeasures against snow and wind
In regions with snow and strong wind, the following problems may occur when the outdoor unit is not pro­vided with a platform and snow-proof ducting:
a) The outdoor fan may not run and damage of the
unit may be caused. b) There may be no air flow. c) The tubing may freeze and burst. d) The condenser pressure may drop because of
strong wind, and the indoor unit may freeze.
2-5. Precautions for Installation in Heavy Snow
Areas
(1) The platform should be higher than the max. snow
depth. (Fig. 2-9)
(2) The 2 anchoring feet of the outdoor unit should be
used for the platform, and the platform should be installed beneath the air intake side of outdoor unit.
(3) The platform foundation must be firm and the unit
must be secured with anchor bolts.
(4) In case of installation on a roof subject to strong
wind, countermeasures must be taken to prevent the unit from being blown over.
Air discharge
In regions with significant snowfall, the outdoor unit should be provided with a platform and snow-proof duct.
Without snow­proof ducting (Low platform)
Without snow­proof ducting (Hi
g
h platform)
Air Intake
Platform (foundation)
Higher than the maximum snow depth
Duct
About 1/2 of the unit hei
g
ht
Air Intake
Duct
Outdoor Unit
Duct
Duct
Outdoor Unit
Min. 100
300
Min. 100 300 Unit: mm
Example of Installation
2-6. Dimensions of Snow / Wind-proof Ducting
and Refrigerant Tubing Space for Installation
Fig. 2-11
04-393 DC INV Tech p a-44 12/15/04 3:04 PM Page 19
Page 20
CAFP
20
3. HOW TO INSTALL THE INDOOR UNIT
4-Way Air Discharge Semi-Concealed Type (CAFP Type)
3-1. Preparation for Suspending
This unit uses a drain pump. Use a carpenters level to check that the unit is level.
3-2. Suspending the Indoor Unit
(1) Fix the suspension bolts securely to the ceiling
using the method shown in the diagrams (Figs. 3­1 and 3-2), by attaching them to the ceiling sup­port structure, or by any other method that ensures that the unit will be securely and safely suspended.
(2) Follow Fig. 3-2 and Table 3-1 to make the holes in
the ceiling.
Table 3-1
Unit: mm
(3) Determine the pitch of the suspension bolts using
the supplied full-scale installation diagram. The diagram and table (Fig. 3-3 and Table 3-2) show the relationship between the positions of the sus­pension fitting, the unit, and the panel.
Table 3-2
Unit: mm
Fig. 3-1
Fig. 3-2
Fig. 3-3
Hole-in-anchor Hole-in-plug
Concrete Insert
Suspension bolt (M10 or 3/8") (field supply)
Type
A
B
C
D
788
723
885
885
12, 16, 18, 25, 36, 48
Length
A
B
C
D
113
173
173
210
210
256
36, 48
12, 16, 18, 25
E
88
88319
113
Type
Length
D (ceilin
g
openin
g
dimension)
C (ceiling opening dimension)
A (suspension bolt pitch)
B (suspension bolt pitch)
E
A
B
C
D
35
Suspension lug
Refrigerant tubing joint (narrow side)
Refrigerant tubing joint (wide side)
(VP25)
Drain outlet
(other side)
04-393 DC INV Tech p a-44 12/15/04 3:04 PM Page 20
Page 21
CAFP
21
Fig. 3-4
Fig. 3-5
3-3. Placing the Unit Inside the Ceiling
(1) When placing the unit inside the ceiling, determine
the pitch of the suspension bolts using the sup­plied full-scale installation diagram. (Fig. 3-4)
Tubing and wiring must be laid inside the ceiling when suspending the unit. If the ceiling is already constructed, lay the tubing and wiring into position for connection to the unit before placing the unit inside the ceiling.
(2) The length of suspension bolts must be appropri-
ate for a distance between the bottom of the bolt and the bottom of the unit of more than 15 mm as shown in Fig. 3-4.
(3) Thread the 3 hexagonal nuts and 2 washers (field
supply) onto each of the 4 suspension bolts as shown in Fig. 3-5. Use 1 nut and 1 washer for the upper side, and 2 nuts and 1 washer for the lower side, so that the unit will not fall off the suspension lugs.
(4) Adjust so that the distance between the unit and
the ceiling bottom is 12 to 17 mm. Tighten the nuts on the upper side and lower side of the suspen­sion lug.
(5) Remove the protective polyethylene used to pro-
tect the fan parts during transport.
Full-scale installation diagram (printed on top of container box)
Supplied bolt
Over 15 mm
12 – 17 mm
12 – 17 (mm)
Suspension bolt
Suspension lug
Nuts and washers (use for upper and lower)
Notch
Double nut
04-393 DC INV Tech p a-44 12/15/04 3:04 PM Page 21
Page 22
CAFP
22
3-4. Installing the Drain Piping
(1) Prepare a standard hard PVC pipe (O.D. 32 mm)
for the drain and use the supplied drain hose and hose band to prevent water leaks. The PVC pipe must be purchased separately. The units transparent drain port allows you to check drainage. (Fig. 3-6)
Insert the drain pipe until it contacts the socket
as shown in Fig. 3-6, then secure it tightly with the hose band.
Do not use adhesive when connecting the sup-
plied hose.
Reasons: 1. It may cause water to leak from the
connection. Since the connection is slippery just after the adhesive has been applied, the pipe easily slips off.
2. The pipe cannot be removed when maintenance is needed.
Do not bend the supplied drain hose 90° or
more. The hose may slip off.
Align the hose bands with the end of the hose.
Tighten the hose band firmly. Make sure that the bead is not covered by the hose band. (Fig. 3-6)
(2) After checking the drainage, wrap the supplied
packing and drain pipe insulator around the pipe. (Fig. 3-7)
Make sure the drain pipe has a downward gradient (1/100 or more) and that there are no water traps.
NOTE
CAUTION
CAUTION
Tighten the hose clamps so their locking nuts face upward. (Fig. 3-6)
CAUTION
Do not install an air bleeder
as this may cause water to spray from the drain pipe outlet. (Fig. 3-8)
Fig. 3-6
Fig. 3-7
Fig. 3-8
Bead
Hose band
Supplied drain hose
Connection pipe
(drain port)
Align the hose band with the end of the pipe
(Field supply)
(Field supply)
Packing
(supplied)
VP-25
VP-25
Hard PVC socket
Hard PVC pipe
PVC adhesive
Vinyl clamps
Drain insulator (supplied)
Air bleeder prohibited
04-393 DC INV Tech p a-44 12/15/04 3:04 PM Page 22
Page 23
CAFP
23
Fig. 3-9
30 cm or less (as short as possible)
64 cm or less
Fig. 3-10
Upward gradient prohibited
Fig. 3-11
Fig. 3-12
Support pieces
Water (Approx. 1,200 cc)
Over 100 mm
Drain pan outlet
Drainage check
Plastic container for
water intake
CAUTION
If it is necessary to
increase the height of the drain pipe, the sec­tion directly after the connection port can be raised a maximum of 64 cm. Do not raise it any higher than 64 cm, as this could result in water leaks. (Fig. 3-9)
Do not install the pipe
with an upward gradient from the connection port. This will cause the drain water to flow back­ward and leak when the unit is not operating. (Fig. 3-10)
Do not apply force to the
piping on the unit side when connecting the drain pipe. The pipe should not be allowed to hang unsupported from its connection to the unit. Fasten the pipe to a wall, frame, or other sup­port as close to the unit as possible. (Fig. 3-11)
Provide insulation for
any pipes that are run indoors.
3-5. Checking the Drainage
After wiring and drain piping are completed, use the following procedure to check that the water will drain smoothly. For this, prepare a bucket and wiping cloth to catch and wipe up spilled water.
(1) Connect power to the power terminal board (R, S
terminals) inside the electrical component box.
(2) Slowly pour about 1,200 cc of water into the drain
pan to check drainage. (Fig. 3-12)
(3) Short the check pin (CHK) on the indoor control
board and operate the drain pump. Check the water flow through the transparent drain pipe and see if there is any leakage.
(4) When the check of drainage is complete, open the
check pin (CHK) and remount the tube cover.
CAUTION
Be careful since the fan will start when you short the pin on the indoor control board.
04-393 DC INV Tech p a-44 12/15/04 3:04 PM Page 23
Page 24
MAFP
24
Wall-Mounted Type (MAFP Type)
3-6. Removing the Rear Panel from the Unit
(1) Remove the set screws used to fasten the rear
panel to the indoor unit during transportation.
(2) Press up on the frame at the 2 locations shown by
the arrows in the figure at right, and remove the rear panel.
Tubing can be extended in 4 directions as shown in Fig. 3-14. Select the direction which will provide the shortest run to the outdoor unit.
3-7. Selecting and Making a Hole
(1) Remove the rear panel from the indoor unit and
place it on the wall at the location selected. Fix the rear panel and hook the unit onto it temporarily. Make sure the unit is horizontal using a carpen­ters level or tape measure to measure down from the ceiling.
(2) Determine which notch of the rear panel should be
used. (Fig. 3-15)
(3) Before drilling a hole, check that there are no
studs or pipes behind the determined location. The above precautions are also applicable if tub­ing goes through the wall in any other location.
(4) Using a sabre saw, key hole saw or hole-cutting
drill attachment, make a hole (dia. 80 mm) in the wall. (Fig. 3-16)
(5) Measure the thickness of the wall from the inside
edge to the outside edge and cut the PVC pipe at a slight angle 6 mm shorter than the thickness of the wall. (Fig. 3-17)
(6) Place the plastic cover over the end of the pipe (for
indoor side only) and insert in the wall. (Fig. 3-18)
The hole should be made at a slight downward gradi­ent to the outside.
NOTE
NOTE
Fig. 3-13
Fig. 3-14
Fig. 3-15
Fig. 3-16
Fig. 3-17Fig. 3-18
CAUTION
Avoid areas where electri­cal wiring or conduits are located.
Plastic cover
INSIDE
Wall
Slight angle
PVC pipe
OUTSIDE
Cut at slight angle
PVC pipe (locally purchased)
Indoor side
Outdoor side
Center of left rear tubing hole
Center of right rear tubing hole
Tubing hole diameter
φ80
Left tubing
Right-rear tubing (recommended)
Ri
g
ht tubin
g
Left-rear tubing
Remove the rear panel
Press
Screws used during transportation
04-393 DC INV Tech p a-44 12/15/04 3:04 PM Page 24
Page 25
MAFP
25
Fig. 3-19
3-8. Installing the Rear Panel onto the Wall
Confirm that the wall is strong enough to support the unit.
See either Item a) or b) below depending on the wall type.
a) If the Wall is Wooden
(1) Attach the rear panel to the wall with the 10 screws
provided. (Fig. 3-19) If you are not able to line up the holes in the rear panel with the beam locations marked on the wall, use Rawl plugs or toggle bolts to go through the holes on the panel or drill 5 mm dia. holes in the panel over the stud locations and then mount the rear panel.
(2) Check with a tape measure or carpenters level.
This is important so that the unit is correctly installed. (Fig. 3-20)
(3) Make sure the panel is flush against the wall. Any
space between the wall and unit will cause noise and vibration.
b) If the Wall is Brick, Concrete or Similar
Drill 4.8 mm dia. holes in the wall. Insert Rawl plugs for appropriate mounting screws. (Fig. 3-21)
3-9. Removing the Grille to Install the Indoor Unit
In principle, with this model wiring can be completed without removing the grille. However, if it is necessary to change the settings on the PCB, follow the procedure below.
Removing the grille
(1) Lift up on both sides of the air-intake grille to open it.
(Fig. 3-22)
(2) Remove the filter. (Fig. 3-22)
(3) Adjust the flap so that it is horizontal. (Fig. 3-23)
(4) Open the installation screw covers below the grille
(3 locations). (Fig. 3-23)
(5) Remove the screws. (Fig. 3-23)
(6) Remove the grille. (Fig. 3-24)
Attaching the grille
(1) Close the flap.
(2) Keep the grille installation tabs aligned with the top
portion of the grille, and reinstall the lower portion of the grille. Fit the installation tabs into the grooves and press the lower portion of the grille back into its original position to install it.
(3) Press on the installation tabs to completely close
the grille. Check that the grille and frame are fitted tightly together.
Fig. 3-20
Fig. 3-21
Fig. 3-22
Fig. 3-23
Fig. 3-24
4.8 mm dia. hole
Rawl plug
Intake grille
Filter
Flap
Open the
g
rille
Installation screw cover
Remove the grille
04-393 DC INV Tech p a-44 12/15/04 3:04 PM Page 25
Page 26
MAFP
26
3-10. Preparing the Tubing
(1) Arrangement of tubing by directions
a) Right or left tubing
The corner of the right or left frame should be cut with a hack saw or similar. (Fig. 3-25)
b) Right-rear or left-rear tubing
In this case, the corners of the frame do not
need to be cut.
(2) Be sure to insulate the part of the drain hose that
is run indoors, and the refrigerant tubing. If these are not insulated, condensation may result in dripping and damage to walls and furniture. The flare nuts on the 25-type (only) are large; therefore, use the supplied insulation material.
(3) To mount the indoor unit on the rear panel.
1. When installing the indoor unit, position the indoor unit onto the installation tabs on the upper part of the rear panel. (Fig. 3-26)
2. Press on the air outlet to hold it in place, and press the lower part of the indoor unit until a click sound is heard and the indoor unit is securely fastened to the installation tabs on the lower side of the rear panel. (Fig. 3-27)
Raising the clamp to lift up the indoor unit will facili­tate this work. (Fig. 3-28)
To remove the indoor unit, press up on the 2 loca­tions ( ▲ marks) on the lower part of the unit frame to disconnect the installation tabs. Refer to Section 3-6. Removing the Rear Panel from the Unit (Fig. 3-13). Then lift up the indoor unit to remove it.
3-11. Shaping the Tubing
Right-rear tubing
(1) Shape the refrigerant tubing so that it can easily
go into the hole. (Fig. 3-29)
(2) After performing a leak test, wrap both the refriger-
ant tubing and drain hose together with insulating tape. The drain hose should be positioned below the refrigerant tubes, and should be given sufficient space so that no strong tension is applied to it.
(3) Push the wiring, refrigerant tubing and drain hose
through the hole in the wall. Adjust the indoor unit so it is securely seated on the rear panel.
Fig. 3-25
Frame
Right tubing outlet
When left and right side tubing
Fig. 3-26
Installation tabs
Installation tabs
Fig. 3-27
Press
Fig. 3-28
Clamp
Fig. 3-29
Insulating
tape
Refrigerant
tubing
Rear panel tab
Plastic cover
Indoor and outdoor unit connection wiring
04-393 DC INV Tech p a-44 12/15/04 3:04 PM Page 26
Page 27
MAFP
27
Fig. 3-32
Fig. 3-30
Insulation
Fig. 3-31
Insulating tape
Rear panel
Inter-unit wiring
Refrigerant tubing
Drain hose
Indoor unit
Slant
Refrigerant tubing
3-12. Installing the Drain Hose
a) The drain hose should be slanted downward to the
outside. (Fig. 3-32)
b) Never form a trap in the course of the hose.
c) If the drain hose will run in the room, insulate* the
hose so that chilled condensation will not damage furniture or floors.
* Foamed polyethylene or its equivalent is recom-
mended.
WARNING
Do not supply power to the unit or operate it until all tubing and wiring to the outdoor unit are completed.
Left or left-rear tubing
(1) Pass the tubing and drain hose into the rear of the
indoor unit. Provide sufficient length for the con­nections to be made. Next, bend the tubing with a pipe bender, and con­nect them.
(2) After performing a leak test, wrap the refrigerant
tubing and drain hose together with insulating tape, as shown in the figure at right. Then fit the tubing into the tubing storage space in the rear of the indoor unit and clamp in place.
(3) Adjust the indoor unit so that it is securely installed
onto the rear panel.
04-393 DC INV Tech p a-44 12/15/04 3:04 PM Page 27
Page 28
SPAFP
28
Ceiling Mounted Type (SPAFP Type)
3-13. Required Minimum Space for Installation and Service
(1) Dimensions of suspension bolt pitch and unit
12, 16, 18
25
36, 48
855
1125
1540
910
1180
1595
210
210
210
ABC
Length
Type
B
C
A
170
320
680
27.5
27.5
Ceiling side
(Suspension bolt pitch)
(Suspension bolt pitch)
Air intake
Air
(2) Refrigerant tubing drain hose position
(3) Unit opening position (Refrigerant tubing drain hose power inlet port remote controller wiring inlet port)
251 84 146 161
75 97 216
39
39
171
105
171
251
Wide tubing
Narrow tubing
Right side
Left side
Rear (Figure shows view from front)
Closed with rubber stopper at time of shipment.
Left drain position Right drain position
(Narrow tubing Wide tubing)
53
70
123
110 7 6
216
50130
Left-side drain hose outlet port
Right-side drain hose outlet port
Top outlet port
Remote controller wiring inlet port (φ30, knock-out)
Power inlet port (φ40, knock-out)
Power inlet port (φ40, knock-out)
Knock-out
Side panel
Position of plate inside side panel
Side panel
Left-side drain hose outlet port
Rear tubing hole
84
32
32
60
171
347
125 72
85106
90
262
Remote controller wiring inlet port (φ30, rubber grommet on right side only)
Outside air intake duct connection port (φ100, knock-out)
Rear outlet port
*3
*1
*1
*2
*3
Fig. 3-33
Fig. 3-35
Fig. 3-34
*1 Use a compass saw, jig saw or simi-
lar tool and cut along the indented portion of the side panel.
*2 If the optional drain up kit is installed,
this becomes the upper tubing outlet port. For details, refer to the manual for the optional part.
*3 If the remote controller wiring inlet
port is changed to the left side or the left top side, change the location of the rubber grommet. Use aluminum tape or similar material to seal the unused inlet port on the right side.
Unit: mm
Unit: mm
Unit: mm
04-393 DC INV Tech p a-44 12/15/04 3:04 PM Page 28
Page 29
SPAFP
29
(4) Wall and ceiling side opening position
90
145
135
125
155
90
*
Figure shows view from front Figure shows view from top
φ100 wall side opening (for left-side drain hose)
φ100 wall side opening
φ100 ceiling opening
φ100 ceiling opening
Wall
Ceiling
Full-scale installation diagram
Wall
Ceiling
Fig. 3-37
Fig. 3-36
Fig. 3-38
3-14. Suspending the Indoor Unit
(1) Place the full-scale diagram (supplied) on the ceil-
ing at the spot where you want to install the indoor unit. Use a pencil to mark the drill holes. (Fig. 3-37).
Since the diagram is made of paper, it may shrink or stretch slightly because of high temperature or humid­ity. For this reason, before drilling the holes maintain the correct dimensions between the markings.
(2) Drill holes at the 4 points indicated on the full-
scale diagram.
(3) Depending on the ceiling type:
a) Insert suspension bolts as shown in Fig. 3-38.
or
b) Use existing ceiling supports or construct a suit-
able support as shown in Fig. 3-39.
NOTE
WARNING
It is important that you use extreme care in supporting the indoor unit from the ceil­ing. Ensure that the ceiling is strong enough to support the weight of the unit. Before hanging the ceiling unit, test the strength of each attached suspension bolt.
(4) Screw in the suspension bolts, allowing them to
protrude from the ceiling as shown in Figs. 3-38 and 3-39. The distance of each exposed bolt must be of equal length within 50 mm. (Fig. 3-40)
Hole-in-anchor Hole-in-plug
Concrete Insert
Suspension bolt (M10 or 3/8") (field supply)
Fig. 3-39
Fig. 3-40
Ceiling tiles
Ceiling support
A
A
unit
Ceiling surface
Fixture
Within
50 mm
* If the optional drain up kit is installed, create a φ100 hole along the dotted line (part marked with * in figure).
Unit: mm
04-393 DC INV Tech p a-44 12/15/04 3:04 PM Page 29
Page 30
SPAFP
30
Fig. 3-41
Slide
Hinge
Air-intake grille
Pull out the air-intake grille pushing claws of the hinges
Screw
Latch
Fig. 3-42
Slide toward front side
Side panel
Fig. 3-43
Unit
Suspension bolt (field supply)
Ceiling surface
Washer (supplied)
Double nut (field supply)
Fixture
Fig. 3-44
Unit
Suspension bolt (field supply)
Washer (supplied)
Washer (field supply)
Double nut (field supply)
Fig. 3-45
Ceiling surface
Approx.
25 mm
Suspension bolt
Washer
(supplied)
Nut (field supply)
(5) Before suspending the indoor unit, remove the 2
or 3 screws on the latch of the air-intake grilles, open the grilles, and remove them by pushing the claws of the hinges as shown in Fig. 3-41. Then remove both side panels sliding them along the unit toward the front after removing the 2 attach­ment screws. (Fig. 3-42)
(6) Carry out the preparation for suspending the
indoor unit. The suspension method varies depending on whether there is a suspended ceil­ing or not. (Figs. 3-43 and 3-44)
(7) Suspend the indoor unit as follows:
a) Mount 1 washer and 2 hexagonal nuts on each
suspension bolt as shown in Fig. 3-45.
04-393 DC INV Tech p a-44 12/15/04 3:04 PM Page 30
Page 31
SPAFP
31
Fig. 3-46
Fig. 3-47
Fig. 3-48
Indoor side
Outdoor side
Fig. 3-49
Cut at slight angle
PVC pipe (locally purchased)
INSIDE
Wall
Slight angle
PVC pipe
OUTSIDE
b) Lift the indoor unit, and place it on the washers
through the notches, in order to fix it in place. (Fig. 3-46)
c) Tighten the 2 hexagonal nuts on each suspen-
sion bolt to suspend the indoor unit as shown in Fig. 3-47.
The ceiling surface is not always level. Confirm that the indoor unit is evenly suspended. For the installa­tion to be correct, leave a clearance of about 10 mm between the ceiling panel and the ceiling surface and fill the gap with an appropriate insulation or filler material.
(8) If the tubing and wiring are to go towards the rear
of the unit, make holes in the wall. (Fig. 3-48)
(9) Measure the thickness of the wall from the inside
to the outside and cut PVC pipe at a slight angle to fit. Insert the PVC pipe in the wall. (Fig. 3-49)
NOTE
The hole should be made at a slight downward slant to the outside.
NOTE
04-393 DC INV Tech p a-44 12/15/04 3:04 PM Page 31
Page 32
SPAFP
32
3-15. Duct for Fresh Air
There is a duct connection port (knock-out hole) at the right-rear of the top panel of the indoor unit for drawing in fresh air. If it is necessary to draw in fresh air, remove the cover by opening the hole and con­necting the duct to the indoor unit through the con­nection port. (Fig. 3-50)
3-16. Shaping the Tubing
The positions of the refrigerant tubing connections
are shown in the figure below. (The tubing can be routed in 3 directions.)
* When routing the tubing out through the top or right
sides, knock out the appropriate parts in the top panel and cut notches in the side panel as shown in Fig. 3-35.
* When routing the tubing out through the top, the
optional L-shape tubing kit is required.
3-17. Installing the Drain Piping
Prepare standard PVC pipe for the drain and con-
nect it to the indoor unit drain pipe with the sup­plied hose clamps to prevent water leaks.
(1) Drain hose connection
The drain hose is connected below the refrigerant
tubing.
(2) Installing the drain hose
To install the drain hose, first place 1 of the 2 hose
bands over the unit drain port and the other hose band over the hard PVC pipe (not supplied). Then connect both ends of the supplied drain hose.
On the unit drain side, grasp the hose band with
pliers and insert the drain hose all the way to the base.
Power inlet port (φ40, knock-out)
Left-side drain hose outlet port
Rear tubing hole
Remote controller wiring inlet port (φ30, rubber grommet on right side only)
Outside air intake duct connection port (φ100, knock-out)
Rear outlet port
Fig. 3-50
Rear cover
CAUTION
Attach so that the hose
band fastener is on the side of the drain port. (Fig. 3-54)
Attach the hose bands so
that each is approximately 5 to 25 mm from the end of the supplied drain hose.
If the tubing is to be routed out together, use a box cutter or similar tool to cut out the part of the rear cover indicated by the marked area in the figure below, to match the positions of the tubes. Then draw out the tubing.
Fig. 3-51
Fig. 3-52
04-393 DC INV Tech p a-44 12/15/04 3:04 PM Page 32
Page 33
SPAFP
33
140
25 25
5
5
Position to fasten hose bands
Drain hose (supplied)
Hose band (2 bands, supplied)
Unit drain pan
Unit drain port
Drain hose insulation (supplied)
Twist tie (4 ties, supplied)
Hard PVC pipe (equivalent to VP-20) (Field supply)
Fig. 3-54
Good
Min. 1/100
Not good
Fig. 3-53
If other commercially available hose bands are
used, the drain hose may become pinched or wrin­kled and there is danger of water leakage. There­fore be sure to use the supplied hose bands. When sliding the hose bands, be careful to avoid scratch­ing the drain hose.
Do not use adhesive when connecting the supplied
drain hose to the drain port (either on the main unit or the PVC pipe).
Wrap the hose with the supplied drain hose insula-
tion and use the 4 twist ties so that the hose is insulated with no gaps.
Connect the drain piping so that it slopes down-
ward from the unit to the outside. (Fig. 3-53)
Never allow traps to occur in the course of the piping.
Insulate any piping inside the room to prevent drip-
ping.
After the drain piping, pour water into the drain pan
to check that the water drains smoothly.
If the drain hose is to be raised, use the optional
drain up kit. The drain hose can be raised 60 cm above the top of the main unit. (For details, refer to the manual for the optional part.)
* If the drain hose is routed
through the left side, refer to Fig. 3-51, and follow the procedure above to install the hose. Rettach the rub­ber stopper removed earlier onto the right side. The rubber stopper can be inserted easily by using a screwdriver or similar tool to press the stopper into the drain port on the main unit. Press the stop­per into the main unit drain port as far as it will go.
Screwdriver
Rubber stopper
Drain port
CAUTION
Check local electrical codes and regulations before wiring. Also, check any specified instruction or limi­tations.
Unit: mm
04-393 DC INV Tech p a-44 12/15/04 3:05 PM Page 33
Page 34
SPAFP
34
* Insert the remote controller
wiring into the electrical component box from the inlet port as shown in the figure. This is done regardless of whether the wiring was inserted from the top, rear, or left side of the main unit.
Remote controller wiring inlet port
Power, inter-unit wiring
Power, inter-unit wiring, remote controller wiring inlet port
Clamp
How to carry out power supply wiring
(1) Wiring connection ports
The power inlet ports are located at the rear and top.
The remote controller wiring inlet ports are located at the rear and top (for use with the wired remote con­troller). For details, refer to Fig. 3-50. For the method used to insert the wiring, refer to the figure below. (Fig. 3-55)
(2) How to carry out wiring
Open the knock-out hole on the rear or top of the
main unit. Attach the supplied rubber grommet and pull the power wiring into the main unit.
Feed the wiring into the wiring inlet port on the
electrical component box. Connect the wiring to the terminal plate and fasten in place with the supplied clamp.
Perform electrical and grounding work in accor-
dance with the package A/C power specifications, and following local electrical codes and regulations.
CAUTION
When removing the fasten­ing bracket from the cover of the electrical component box, use caution to avoid dropping the bracket.
Fig. 3-55
04-393 DC INV Tech p a-44 12/15/04 3:05 PM Page 34
Page 35
DSAFP
35
Fig. 3-56
Fig. 3-57
Indoor unit
Inspection access 450 450
Air outlet duct flange
min. 250
min. 400
min. 650
580
A (Suspension bolt pitch)
Electrical component box
Refrigerant tubing
min.
250
Concealed-Duct Type (DSAFP Type)
3-18. Required Minimum Space for Installation and
Service
This air conditioner is usually installed above the ceiling
so that the indoor unit and ducts are not visible. Only the air intake and air outlet ports are visible from below.
The minimum space for installation and service is
shown in Fig. 3-56 and Table 3-3.
It is recommended that space is provided (450 × 450
mm) for checking and servicing the electrical system.
Fig. 3-57 and Table 3-4 show the detailed dimensions
of the indoor unit.
Table 3-3
Table 3-4
Type
A (Length)
Number of duct flanges
36, 48
1,560
4
25
1,080
3
12, 16, 18
780
2
Dimension
Type
12, 16, 18
25
36, 48
E
F
G H
I
J
K
662
600
700 780 290 262 680 715 180 340 8 12
(200 × 3)
962
900
1,000 1,080 290 272 980 1,015 130
245
250 12 16
(180 × 5) (245 ×
1)
1,442
1,380
1,480 1,560
335
310
1,460 1,495 130
490
240 16 18
(230 × 6) (245 ×
2)
No. of holes
LM
C
D
B
A
Refrigerant tubing joint (narrow tube) Refrigerant tubing joint (wide tube) Upper drain port (O.D. 32 mm) Bottom drain port (O.D. 26 mm) Suspension lug Power supply outlet (2-ø30) Fresh air intake port (ø150) Flange for the flexible air outlet duct (ø200) Tube cover Electrical component box Flange for the air intake duct (Option or field supply)
9
10
9
10
11
11
(Suspension bolt pitch)
(Suspension bolt pitch)
M-ø3.3
(Hole)
4-ø12 (Hole)
(Hole)
A (O.D.)
L-ø6
I
10 10
10
5555 200
10
IJJK
B
C D(150)
40
EEEF75
65
285
70 130
25 210
310
25
175
35
90
3131
H (Duct suspension bolt pitch)
G (Ceiling opening dimension)
25
100
185
58025
115
190
85
25
70 30
160
630 25
10
88
275
(Ceiling opening dimension)
260
(O.D.)
1919
Inspection access
(450 × 450)
(Field supply)
Inspection access panel
Ceiling
Unit: mm
Unit: mm
Unit: mm
Unit: mm
04-393 DC INV Tech p a-44 12/15/04 3:05 PM Page 35
Page 36
DSAFP
36
Fig. 3-58
3-19. Suspending the Indoor Unit
Depending on the ceiling type:
Insert suspension bolts as shown in Fig. 3-58
or
Use existing ceiling supports or construct a suit­able support as shown in Fig. 3-59.
Hole-in-anchor Hole-in-plug
Concrete Insert
Suspension bolt (M10 or 3/8") (field supply)
Fig. 3-59
Fig. 3-60
Fig. 3-61
Ceiling tiles
Ceiling support
Suspension bolt
Suspension lug
Nuts and washers (use for upper and lower)
Double nuts
Notch
Suspension bolt
Hexagonal nut
Double nuts
WARNING
It is important that you use extreme care in supporting the indoor unit inside the ceiling. Ensure that the ceil­ing is strong enough to sup­port the weight of the unit. Before hanging the unit, test the strength of each attached suspension bolt.
(1) When placing the unit inside the ceiling, determine
the pitch of the suspension bolts referring to the dimensional data on the previous page. (Fig. 3-56 and Table 3-3) Tubing must be laid and connected inside the ceil­ing when suspending the unit. If the ceiling is already constructed, lay the tubing into position for connection to the unit before placing the unit inside the ceiling.
(2) Screw in the suspension bolts allowing them to
protrude from the ceiling as shown in Fig. 3-58. (Cut the ceiling material, if necessary.)
(3) Thread the 3 hexagonal nuts and 2 washers (field
supply) onto each of the 4 suspension bolts as shown in Figs. 3-60 and 3-61. Use 1 nut and 1 washer for the upper part, and 2 nuts and 1 wash­er for the lower part, so that the unit will not fall off the suspension lugs.
04-393 DC INV Tech p a-44 12/15/04 3:05 PM Page 36
Page 37
DSAFP
37
Fig. 3-62 shows an example of installation.
Air outlet duct
Air-outlet grille
Ceiling material Indoor unit
Bolt anchor
Suspension bolt
Air-intake duct
Air-intake grille
Fig. 3-62
Fig. 3-63
Fig. 3-64
Drain hose
(supplied)
(not supplied)
(not supplied)
Packing (supplied)
VP-25
Align the hose band with end of the hose, and tighten so that it does not contact the bead.
Drainage check section on drain port (transparent)
Hard PVC socket VP-25
Hard PVC pipe
PVC adhesive
Bead
Vinyl clamps
Drain insulator (supplied)
3-20. Installing the Drain Piping
(1) Prepare standard hard PVC pipe (O.D. 32 mm) for
the drain and use the supplied hose band to pre­vent water leaks. The PVC pipe must be purchased separately. The transparent drain part on the unit allows you to check drainage. (Fig. 3-63)
CAUTION
Do not use adhesive at the
drain connection port on the indoor unit.
Insert the drain pipe until it
contacts the socket, as shown in the figure at right, then secure it tightly with the hose band.
Do not use the supplied
drain hose bent at a 90° angle. (The maximum per­missible bend is 45°.)
Tighten the hose clamps so
their locking nuts face upward. (FIg. 3-63)
(2) After connecting the drain piping securely, wrap
the supplied packing and drain pipe insulator around the pipe, then secure it with the supplied vinyl clamps. (Fig. 3-64)
Make sure the drain pipe has a downward gradient (1/100 or more) and that there are no water traps.
NOTE
04-393 DC INV Tech p a-44 12/15/04 3:05 PM Page 37
Page 38
DSAFP
38
Fig. 3-65
Fig. 3-66
Fig. 3-67
Fig. 3-68
Fig. 3-69
Air bleeder
Prohibited
Good
30 cm or less
50 cm or less
Prohibited
Upward gradient
Support pieces
Water intake
If it is necessary to increase the height of the
drain pipe, the section directly after the con­nection port can be raised a maximum of 50 cm. Do not raise it any higher than 50 cm, as this could result in water leaks. (Fig. 3-66)
Do not install the pipe with an upward gradient
from the connection port. This will cause the drain water to flow backward and leak when the unit is not operating. (Fig. 3-67)
Do not apply force to the piping on the unit side
when connecting the drain pipe. The pipe should not be allowed to hang unsupported from its con­nection to the unit. Fasten the pipe to a wall, frame, or other support as close to the unit as possible. (Fig. 3-68)
3-21. Checking the Drainage
After wiring and drain piping are completed, use the following procedure to check that the water will drain smoothly. For this, prepare a bucket and wiping cloth to catch and wipe up spilled water.
(1) Connect power to the power terminal board (R, S
terminals) inside the electrical component box.
(2) Remove the tube cover and through the opening,
slowly pour about 1,200 cc of water into the drain pan to check drainage.
(3) Short the check pin (CHK) on the indoor control
board and operate the drain pump. Check the water flow through the transparent drain port and see if there is any leakage.
(4) When the check of drainage is complete, open the
check pin (CHK) and remount the insulator and drain cap onto the drain inspection port.
CAUTION
Do not install an air bleed-
er as this may cause water to spray from the drain pipe outlet. (Fig. 3-65)
CAUTION
Be careful since the fan will start when you short the pin on the indoor control board.
04-393 DC INV Tech p a-44 12/15/04 3:05 PM Page 38
Page 39
DSAFP
39
NOTE
HT : Using the booster cable
H:
At shipment
5
Air Flow (m
3
/minute)
External Static Pressure
0
50
100
0
5
10
15150
10
(mmAq)
(Pa)
Limit line
Limit line
HT
H
M
L
20
Air Flow (m
3
/minute)
External Static Pressure
0
50
0
5
10
15150
10
Limit line
Limit line
HT
H
L
100
M
(mmAq)
(Pa)
30 40
Air Flow (m
3
/minute)
External Static Pressure
0
50
0
5
10
15
150
20
Limit line
Limit line
L
100
M
H
(mmAq)
(Pa)
HT
30
Air Flow (m
3
/minute)
External Static Pressure
0
50
0
5
10
15
150
20
Limit line
HT
L
100
M
H
Limit line
(mmAq)
(Pa)
15
Air Flow (m
3
/minute)
External Static Pressure
0
50
0
5
10
15150
10
Limit line
Limit line
HT
M
L
100
H
(mmAq)
(Pa)
16, 18 Type12 Type
Indoor Fan Performance
25 Type 36 Type 48 Type
3-22. Increasing the Fan Speed
If external static pressure is too great (due to long extension of ducts, for example), the air flow volume may drop too low at each air outlet. This problem may be solved by increasing the fan speed using the fol­lowing procedure:
(1) Remove 4 screws on the electrical component box
and remove the cover plate.
(2) Disconnect the fan motor sockets in the box.
(3) Take out the booster cable (sockets at both ends)
clamped in the box.
(4) Securely connect the booster cable sockets
between the disconnected fan motor sockets in step 2 as shown in Fig. 3-70.
(5) Place the cable neatly in the box and reinstall the
cover plate.
Fig. 3-70
Fig. 3-71
Booster cable
Booster cable
Electrical component box
(At shipment) (Booster cable installed)
Fan motor socket
Fan
motor
How to read the diagram
The vertical axis is the external static pressure (Pa) while the horizontal axis represents the air flow (m
3
/minute). The characteristic curves for HT,” “H,” “M” and “L” fan speed control are shown. The nameplate values are shown based on the “H” air flow. For the 25 type, the air flow is 18 m3/minute, while the external static pressure is 49 Pa at H position. If external static pressure is too great (due to long extension of ducts, for example), the air flow vol­ume may drop too low at each air outlet. This problem may be solved by increasing the fan speed as explained above.
04-393 DC INV Tech p a-44 12/15/04 3:05 PM Page 39
Page 40
DSAFP
40
4. HOW TO INSTALL THE OUTDOOR UNIT
4-1. Installing the Outdoor Unit
Use concrete or a similar material to create the base,
and ensure good drainage.
Ordinarily, ensure a base height of 5 cm or more. If a
drain pipe is used, or for use in cold-weather regions, ensure a height of 15 cm or more at the feet on both sides of the unit. (In this case, leave clearance below the unit for the drain pipe, and to prevent freezing of drainage water in cold-weather regions.)
Refer to the Fig. 4-1 for the anchor bolt dimensions.
Be sure to anchor the feet with the anchor bolts
(M10). In addition, use anchoring washers on the top side. (Use large square 32 ( 32 SUS washers with JIS nominal diameters of 10.) (Field supply)
4-2. Drainage Work
Follow the procedure below to ensure adequate drain­ing for the outdoor unit.
For the drain port dimensions, refer to the figure at
right.
Ensure a base height of 15 cm or more at the feet on
both sides of the unit.
When using a drain pipe, install the drain socket
(optional part STK-DS25T) onto the drain port. Seal the other drain port with the rubber cap supplied with the drain socket.
For details, refer to the instruction manual of the
drain socket (optional part STK-DS25T).
4-3. Routing the Tubing and Wiring
The tubing and wiring can be extended out in 4 direc-
tions: front, rear, right, and down.
The service valves are housed inside the unit. To
access them, remove the inspection panel. (To remove the inspection panel, remove the 3 screws, then slide the panel downward and pull it toward you.)
(1) If the routing direction is through the front, rear, or
right, use a nipper or similar tool to cut out the knockout holes for the inter-unit control wiring outlet, power wiring outlet, and tubing outlet from the appropriate covers A and B.
(2) If the routing direction is down, use a nipper or simi-
lar tool to cut out the lower flange from cover A.
Fig. 4-1
942
296
150
219
13 13
19
20
15 10380
405
341
1313
171
660 111
Drain port (2 locations)
Drain port
Anchor bolt (M10)
Fig. 4-2
Inter-unit control wiring outlet
Inspection panel
Cover A
Cover B
Power wiring outlet
Tubing outlet
Down
Front
Rear
Right
CAUTION
Route the tubing so that it does
not contact the compressor, panel, or other parts inside the unit. Increased noise will result if the tubing contacts these parts.
When routing the tubing, use a
tube bender to bend the tubes.
04-393 DC INV Tech p a-44 12/15/04 3:05 PM Page 40
Page 41
41
Control wiring
(C) Inter-unit (between outdoor and indoor units) control wiring
(D) Remote control wiring (E) Control wiring for group control
0.75 mm
2
(AWG #18)
0.75 mm
2
(AWG #18)
0.75 mm
2
(AWG #18)
Use shielded wiring* Use shielded wiring Use shielded wiring
Max. 1,000 m
Max. 500 m
Max. 500 m (Total)
5. ELECTRICAL WIRING
5-1. General Precautions on Wiring
(1) Before wiring, confirm the rated voltage of the unit
as shown on its nameplate, then carry out the wiring closely following the wiring diagram.
(2) Provide a power outlet to be used exclusively for
each unit, and a power supply disconnect and cir­cuit breaker for overcurrent protection should be provided in the exclusive line.
(3) To prevent possible hazards from insulation fail-
ure, the unit must be grounded.
(4) Each wiring connection must be done in accor-
dance with the wiring system diagram. Wrong wiring may cause the unit to misoperate or become damaged.
(5) Do not allow wiring to touch the refrigerant tubing,
compressor, or any moving parts of the fan.
(6) Unauthorized changes in the internal wiring can be
very dangerous. The manufacturer will accept no responsibility for any damage or misoperation that occurs as a result of such unauthorized changes.
(7) Regulations on wire diameters differ from locality
to locality. For field wiring rules, please refer to your LOCAL ELECTRICAL CODES before begin­ning.
You must ensure that installation complies with all relevant rules and regulations.
(8) To prevent malfunction of the air conditioner
caused by electrical noise, care must be taken when wiring as follows:
The remote control wiring and the inter-unit control
wiring should be wired apart from the inter-unit power wiring.
Use shielded wires for inter-unit control wiring
between units and ground the shield on both sides.
(9) If the power supply cord of this appliance is dam-
aged, it must be replaced by a repair shop appointed by the manufacture, because special purpose tools are required.
5-2. Recommended Wire Length and Wire Diameter for Power Supply System
Outdoor unit
(A) Power supply
Wire size
Max. length
GRFP255L, GRFP255R 24 m
30 A GRFP365L, GRFP365R 22 m 40 A GRFP485L, GRFP485R 20 m 50 A
4 mm 4 mm 4 mm
2
2
2
Time delay fuse or circuit capacity
NOTE
* With ring-type wire terminal.
Indoor unit
Time delay fuse or
circuit capacity
(B) Power supply
2.5 mm
2
MAFP
CAFP, SPAFP, DSAFP
Type
Max. 150 m
Max. 130 m
10 A
10 A
04-393 DC INV Tech p a-44 12/15/04 3:05 PM Page 41
Page 42
42
5-3. Wiring System Diagrams
U2
U1
1
2
R1
R2
U2
U1
3
R1
R2
U2
U1
R1
R2
U2
U1
R1 R2
Group control:
2
1
WHT
Remote controller
D
A
E
Indoor unit (No. n)
Indoor unit (No. 1)
Indoor unit (No. 2)
Indoor unit (No. 3)
C
B
L
N
Ground
L N
L N
L N
L N
BLK
2
1
Power supply 220-240V 50Hz
B
B
B
Ground
Ground
Ground
Power supply 200-240V 50Hz
Power supply 220-240V 50Hz
Power supply 220-240V 50Hz
Power supply 220-240V 50Hz
Ground
C
Ground
C
Ground
C
Ground
2
1
N
L
Outdoor unit INV unit
2
1
1
2
3
1
2
3
U1
NOTE
(1) Refer to Section 5-2. Recommended Wire Length
and Wire Diameter for Power Supply System for the explanation of A,” “B,” “C,” “D, and E, in the above diagrams.
(2) The basic connection diagram of the indoor unit
shows the 7P terminal board, so the terminal boards in your equipment may differ from the dia­gram.
(3) Refrigerant Circuit (R.C.) address should be set
before turning the power on.
1(L)2(N) Power
supply
U1
Inter-unit
control wiring
U2
Remote
controller
8P terminal board
R1 R2
1 2 U1 U2 R1 R2
DSAFP Type
MAFP Type
1(L)2(N)
12345
Power
supply
Inter-unit
control wiring
5P terminal board
U1 U2
1(L) 2(N) Power
supply
U1 Inter-unit
control wiring
U2
Remote
controller
R1
R2
CAFP, SPAFP Type
7P terminal board
04-393 DC INV Tech p a-44 12/15/04 3:05 PM Page 42
Page 43
43
Outdoor unit
Outdoor unit
Outdoor unit
Indoor unit Indoor unit Indoor unit Indoor unit
Indoor unit
more than 1 m
more than 1 m
Branch point
16 or fewer
Indoor unit
Indoor unit Indoor unit Indoor unit
less than 1 m
Indoor unit
Outdoor unit Indoor unit Indoor unit Indoor unit
Indoor unit Indoor unit Indoor unit
Outdoor unit
Indoor unit
NO
NO
Branch point
(1) When linking outdoor units in a network (S-net link system), disconnect the terminal extended from the
short plug (CN003, 2P Black, location: right bottom on the outdoor main control PCB) from all outdoor units except any one of the outdoor units. (When shipping: In shorted condition.)
Otherwise the communication of S-net link system is not performed. For a system without link (no con­nection wiring between outdoor units), do not remove the short plug.
(2) Do not install the inter-unit control wiring in a way that forms a loop. (Fig. 5-1)
Outdoor unit Outdoor unit Outdoor unit
Prohibited
Prohibited
Indoor unit Indoor unit Indoor unit Indoor unit
Indoor unit
Fig. 5-1
Fig. 5-2
Fig. 5-3
CAUTION
(3) Do not install inter-unit control wiring such as star
branch wiring. Star branch wiring causes mis-address setting.
(4) If branching the inter-unit control wiring, the number of branch points should be 16 or fewer.
(Branches less than 1 m are not included in the total branch number.) (Fig. 5-3)
04-393 DC INV Tech p a-44 12/15/04 3:05 PM Page 43
Page 44
44
Fig. 5-4
Shielded wire
Ground
Ground
Fig. 5-5
Stranded wire
Ring pressure terminal
Strip 10 mm
Fig. 5-6
Wire
Special washer
Screw
Ring pressure terminal
Terminal plate
Screw and Special washer
Ring pressure terminal
Wire
(5) Use shielded wires for inter-unit control wiring
(c) and ground the shield on both sides, other­wise misoperation from noise may occur. (Fig. 5-4) Connect wiring as shown in Section 5-3. Wiring System Diagrams.
WARNING
Loose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazard may also exist. Therefore, ensure that all wiring is tightly connected.
When connecting each power wire to the terminal, fol­low the instructions on How to connect wiring to the terminal and fasten the wire securely with the fixing screw of the terminal plate.
How to connect wiring to the terminal
For stranded wiring
(1) Cut the wire end with cutting pliers, then strip the
insulation to expose the stranded wiring about 10 mm and tightly twist the wire ends. (Fig. 5-5)
(2) Using a Phillips head screwdriver, remove the ter-
minal screw(s) on the terminal plate.
(3) Using a ring connector fastener or pliers, securely
clamp each stripped wire end with a ring pressure terminal.
(4) Place the ring pressure terminal, and replace and
tighten the removed terminal screw using a screw­driver. (Fig. 5-6)
04-393 DC INV Tech p a-44 12/15/04 3:05 PM Page 44
Page 45
45
K
Fig. 6-2
120
120
4
2.7
16
Diagram of outer dimensions
6. HOW TO INSTALL THE REMOTE CONTROLLER (OPTIONAL PART)
Remote controller wiring can be extended to a maxi­mum of 1,000 m.
How to install the remote controller
(Optional Controller)
CAUTION
Do not twist the control
wiring with the power wiring or run it in the same metal conduit, because this may cause malfunction.
Install the remote con-
troller away from sources of electrical noise.
Install a noise filter or
take other appropriate action if electrical noise affects the power supply circuit of the unit.
The mounting position for the remote controller should be located in an accessible place for control. Never cover the remote controller or recess it into the wall.
(1) When you open the decorative cover, you will see 2
gaps under the remote controller. Insert a coin into these gaps and pry off the back case. (Fig. 6-1)
6-1. When Using a Wall Box for Flush Mounting
If local codes allow, this remote controller can be
mounted using a conventional wall box for flush mounting.
(2) Attach the back case with the 2 small screws pro-
vided. Using a screwdriver, push open the cut-outs on the back case. These holes are for screws. Use the spacers and take care not to tighten the screws excessively. If the back case will not seat well, cut the spacers to a suitable thickness. (Fig. 6-1)
(3) Connect the remote controller wiring (2 wires) cor-
rectly to the corresponding terminals in the electri­cal component box of the indoor unit.
(4) To finish, fit the back tabs of the case into the
remote controller and mount it.
CAUTION
When wiring, do not con­nect the remote controller wires to the adjacent termi­nal block for the power wiring. Otherwise, the unit will break down.
CAUTION
Do not supply power to the unit or try to operate it until the tubing and wiring to the outdoor unit is completed.
Fig. 6-1
Opening for switch box
Under case (Back case)
M4 × 25 screws (2)
Remote controller
Decorative cover
Spacer
1
2
2
3
2
Remote controller switch
(with 200 mm wire)
Small screws M4 × 25
Wood screws
4
2
5
2
Spacers
Wire joints
1
Accompanying partsAccompanying parts No.No.
Q’tyQ’ty
Accessories for remote controller switch
Unit: mm
04-393 DC INV Tech p 45-63 12/13/04 11:34 AM Page 45
Page 46
46
K
6-2. Basic Wiring Diagram (Twin, Triple, Double-Twin)
CAUTION
Install wiring correctly (incorrect wiring will dam­age the equipment).
Use shielded wires for remote control wiring and
ground the shield on one side. (Fig. 6-3) Otherwise misoperation due to noise may occur.
Fig. 6-3
Fig. 6-4
Shielded wire
Ground
6-3. Wiring System Diagram for Group Control
This diagram shows when several units (maximum of
4) are controlled by a remote controller (master unit).
In this case, a remote controller can be connected at any indoor unit.
Wiring procedure
Wire according to the right diagram:
Each successive unit will respond at 1-second
intervals following the order of the group address when the remote controller is operated.
Group control using 2 remote controllers
It does not matter which of the 2 remote controllers you set as the main controller.
When using multiple remote controllers (up to 2 can be used), one serves as the main remote controller and the other as the sub-remote controller.
1
2
1
1
2
1
2
1
1
2
1
1
2
1
Outdoor unit
Indoor unit
No. 4
Indoor unit
No. 3
Indoor unit
No. 2
Indoor unit
No. 1
1
Remote controller
Connection wiring for group control
Inter-unit control wiring
Terminal 3P
2
2
22
2
(sub)
3P terminal base for remote control wiring
Remote controller (main)
1
Indoor unit
No. 1
: Ground (earth)
Indoor unit
No. 2
Indoor unit
No. 4
Indoor unit
No. 3
Connection wiring for group control
1
1
1
2
2
2
2
1
2
1
2
Fig. 6-5
04-393 DC INV Tech p 45-63 12/13/04 11:34 AM Page 46
Page 47
47
K
Cautions on group control
Group control within the same refrigerant tub-
ing system is recommended.
[Tubing system which is NOT recommended]
<Example 1> In this system, group control extending
over tubing systems becomes impossi­ble to set, which means the indoor units cannot operate.
NOTE
1
2
3
4
Tubing system 2
Tubing system 1
Indoor units
Remote controller
TIMER TMNL.
RCU
TMNL.
RCU.ADR
RCU.Main
RCU.Sub
RCU.CK
To Service Technicians
To display the sensor temperature:
WARNING
To avoid an electric shock hazard, DO NOT touch any ter­minal on the Printed Cir­cuit Board with a metal rod, a screwdriver edge or bare hand when power is supplied.
Press both and buttons on the remote controller for more than 4 seconds together. Change the sensor address (CODE NO.) with / (SET TEMP) buttons. Select the UNIT NO. that you want to call with button. Press the button to finish service mode.
To display the trouble history:
Press both and buttons on the remote controller for more than 4 seconds together. Change the alarm message: / (SET TEMP) buttons CODE NO.
Press the button to finish service mode.
On the remote controller, press + + at the same time for more than 4 seconds. Set CODE No. with / (SET TEMP) button.
Set DATA from to with / (TIMER) button. Press Finally, Press
(New) (Old)
Changing method for room temperature sensor (from Indoor unit to RCU)
1
2
3
4
Remote Controller (Sub)
Remote controller address connector
Remote Controller (Main)
Setting the main and sub remote controllers
1. Set one of the 2 connected remote controllers as the main remote controller.
2. On the other remote controller (sub-remote controller), switch the remote controller address connector on the
rear of the remote controller PCB from Main to Sub. When the connector has been switched, the remote con­troller will function as the sub-remote controller.
Fig. 6-6
04-393 DC INV Tech p 45-63 12/13/04 11:34 AM Page 47
Page 48
48
K
6-4. Switching the Room Temperature Sensors
Room temperature sensors are contained in the indoor unit and in the remote controller. One or the other of the temperature sensors is used for operation. Normally, the indoor unit sensor is set; however, the procedure below can be used to switch to the remote controller sensor.
(1) Press and hold the + + buttons for 4 seconds or longer.
The unit No. that is initially displayed is the indoor unit address of the group control master unit.
Do not press the button.
(2) Use the temperature setting / buttons to select item code 32.
(3) Use the timer time / buttons to change the setting data from 0000 to 0001.
(4) Press the button. (The change is completed when the display stops blinking.)
(5) Press the button.
The unit returns to normal stop status. At this time, “Remote controller sensor” is displayed on the LCD.
If 2 remote controllers are used for control, this setting can be made from either the main or sub remote con-
troller. However, the temperature sensor that is used is the sensor in the main remote controller.
When group control is used, the remote controller sensor will not function unless the group address is set to the
address of the master indoor unit.
If both the remote sensor and remote controller are used, do not use the temperature sensor in the remote con-
troller.
6-5. Connecting to a Ventilation Fan
If a commercially available ventilation fan or similar device is run from the ventilation fan output terminal (FAN DRIVE: 2P (white), DC 12 V) (Note) on the indoor unit PCB, use the button to enable fan operation and change the settings.
(1) Press and hold the + + buttons for 4 seconds or longer.
The unit No. that is initially displayed is the indoor unit address of the group control master unit.
Do not press the button.
(2) Use the temperature setting / buttons to select item code 31.
(3) Use the timer time / buttons to change the setting data from 0000 to 0001.
(4) Press the button. (The change is completed when the display stops blinking.)
(5) Press the button.
The unit returns to normal stop status. Press the button and check that “Fan” is displayed on the LCD display.
(Note) A special relay is required to run the ventilating fan.
NOTE
NOTE
NOTE
11 22
Relay (DC12V, field supply)
External control input for ventilation fan
Indoor unit control PCB
FAN DRIVE
(2P white)
To terminal
NOTE: The wiring from the indoor unit control PCB to the relay must be no more than 2 m in length.
04-393 DC INV Tech p 45-63 12/13/04 11:34 AM Page 48
Page 49
49
K
6-6. Wiring the Remote Controller
<Flush Mounting>
Connection diagram
Use 0.5 mm
2
– 2 mm2wires.
(1) Strip the insulation to approximately 14 mm from
the ends of the wires that will be connected.
(2) Twist together the 2 wires and create a crimp con-
nection at the wire joint.
(3) If a special crimping tool is not used, or if the con-
nection is soldered, insulate the wires using insu­lation tape.
Use the remote controller cord (optional) for remote
controller wiring.
(1) Disconnect the lead wire that is wound around the
lead wire anchor on the remote controller unit. Dis­connect the connector and connect the remote controller cord (optional) to the connector on the remote controller unit. Insert the remote controller cord (optional) into the groove and bend it into the correct shape, then wind it around the lead wire anchor.
(2) If the remote controller cord (optional) is used,
refer to the installation manual that is provided with the cord.
Terminal board for indoor unit remote controller wiring
1 2
1 2
W
BK
Remote controller wiring (field supply)
Connector
Remote controller unit
Power wire from remote controller unit
Approx. 200 mm
Remote controller wiring
Power wire from remote controller unit
Provided wire joint (white)
Wire joint CE-1, white
Remote controller cord (optional)
Connector
Lead wire anchor
04-393 DC INV Tech p 45-63 12/13/04 11:34 AM Page 49
Page 50
50
K
6-7. Trouble Diagnostics
(1) Contents of remote controller switch alarm display
Remote controller is detecting error signal from indoor unit
E01
E02
E10
E11
E14
E03
E08
E09
E04
E05
E06
E07
E15
E16
E20
E17
E18
E31
L01
L02
L03
L04
L07
L08
L09
L010
L011
L013
Indoor unit is detecting error signal from remote controller (and system controller)
Error in receiving serial communication signal (Signal from main indoor unit in case of group control)
Auto address is not completed
Outdoor system address, indoor system address, or indoor unit individual/main/sub setting is not set (Automatic address setting is not completed)
Error in transmitting serial communication signal
Improper setting of indoor unit or remote controller
Indoor unit address setting is duplicated
Remote controller setting is duplicated
Error in transmitting serial communications signal
Error in transmitting serial communications signal
Error in receiving serial communications signal
Error in receiving serial communications signal
Indoor unit is detecting error signaled from signal option
Setting error Main unit duplication in simultaneous-operation multi control
(detected by outdoor unit)
Indoor unit is detecting error signaled from outdoor unit
Outdoor unit is detecting error signaled from indoor unit
Automatic address setting failed
An indoor unit detected trouble in the signal from another indoor unit
Communications trouble between units
Setting errorMis-setting
Continued
Error in transmitting serial communications signal
Indoor unit capacity too low
Indoor unit capacity too high
No indoor units connected
Error in receiving serial communications signal
Communications failure with MDC
Indoor unit group settings error
Indoor/outdoor unit type mismatch
Main unit duplication in group control (detected by indoor unit)
Outdoor unit address duplication (system address)
Group wiring connected for independent indoor unit
Address not set or group not set
Indoor unit capacity not set
Outdoor unit capacity not set or setting error
Miswiring in group control wiring
Indoor unit type setting error (capacity)
Error in transmitting serial communications signal
Error in receiving serial communications signal (including unit quantity verification failure)
Simultaneously
Simultaneously
Simultaneously
Simultaneously
Serial commu­nication errors Mis-setting
Wired remote control
display
Wireless
remote controller
receiver display
Operation
Timer
Standby
for heating
Possible cause of malfunction
04-393 DC INV Tech p 45-63 12/13/04 11:34 AM Page 50
Page 51
51
K
P09
P01
P10
P03
P05
P15
P19
P20
P22
P26
P29
P31
H01
F01
F02
F10
F04
F06
F07
F08
F12
F29
Ceiling panel connection failure
Indoor protection
Fan protective thermostat
Float switch
Discharge temperature trouble
Open phase detected, AC power trouble
No gas
4-way valve locked
High cooling load
Outdoor fan trouble
Inverter compressor trouble (HIC PCB)
Inverter compressor trouble (MDC)
Simultaneous-operation multi control trouble
Compressor current failure (overload)
Indoor heat exchanger temperature sensor (E1)
Indoor heat exchanger temperature sensor (E2)
Indoor temperature sensor
Discharge temperature (TD)
Outdoor heat exchanger temperature (C1)
Outdoor heat exchanger temperature (C2)
Outdoor air temperature (TO)
Intake temperature (TS)
Indoor EEPROM error
Outdoor protection
Thermistor open circuit
Short circuit (indoor)
Thermistor open circuit
Short circuit (outdoor)
Activation of protective device
Thermistor fault
Alternately
Alter.
Simul.
Alter.
Simul.
Alternately
Outdoor EEPROM error
F31
Wired remote control display
Wireless
remote controller
receiver display
ON:
Operation
Timer
Standby
for heating
Blinking: OFF:
Possible cause of malfunction
04-393 DC INV Tech p 45-63 12/13/04 11:34 AM Page 51
Page 52
52
K
(2) LED Indicator Messages on Outdoor Control PCB
Power ON sequence
1. No communication from indoor units in system
2. Communication received from 1 or more indoor units in system
3. Regular communication OK (Capacity and unit quantity match)
If it is not possible to advance to 3, repeats 1 2. At 3, changes to normal control.
P03
Normal operation
Pre-trip (insufficient gas)
Pre-trip (P20)
Pre-trip (other)
Automatic address setting in progress
Automatic address setting alarm (E15)
Automatic address setting alarm (E20)
Automatic address setting alarm (Other than E15 and E20)
Note: This table shows example alarms. Other alarms may also be displayed.
(0.25/0.75)
(0.75/0.25)
EEPROM error (F31)
Blinking alternately
Blinking simultaneously
Blinking simultaneously
Blinking simultaneously
Alarm
LED 1 blinks M times, then LED 2 blinks N times. The cycle then repeats.
M = 2: P alarm
6: L alarm N = Alarm No. * Refer to
1. Examples of alarm display below.
3: H alarm 4: E alarm 5: F alarm
Alternate blinking during alarms
Insufficient gas indicator
(0.25/0.75)
(0.75/0.25)
(0.25/0.75)
(0.75/0.25)
Refrigerant recovery mode
Automatic address setting
Displayed during automatic address setting 1 and initial communication. After these are completed, alarm F31 is displayed.
P03
P04
P05
P31
H01
H02
H03
E04
F07
L13
( Blinks 2 times )
(
"
)
(
"
)
(
"
)
(Blinks 3 times)
(
"
)
(
"
)
(Blinks 4 times)
(Blinks 5 times)
3
(Blinks 6 times)
(Blinks 3 times)
(Blinks 4 times)
(Blinks 5 times)
(Blinks 31 times)
(Blinks 1 times)
(Blinks 2 times)
(Blinks 3 times)
(Blinks 4 times)
(Blinks 7 times)
(Blinks 13 times)
Alarm / Display LED 1 Alternately
LED 2
ON
:
:
:
LED 1 LED 2 Remarks
OFF
(3) Examples of alarm display (other than E15, E16, and E20)
Blinking (0.25/0.75) indicates that the lamp illuminates for 0.25 seconds, and then is OFF for 0.75 seconds. Unless otherwise indicated, the blinking is (0.5/0.5).
04-393 DC INV Tech p 45-63 12/13/04 11:34 AM Page 52
Page 53
53
7. HOW TO PROCESS TUBING
The narrow tubing side is connected by a flare nut, and the wide tubing side is connected by brazing.
7-1. Connecting the Refrigerant Tubing
Use of the Flaring Method
Many of conventional split system air conditioners employ the flaring method to connect refrigerant tubes which run between indoor and outdoor units. In this method, the copper tubes are flared at each end and connected with flare nuts.
Flaring Procedure with a Flare Tool
(1) Cut the copper tube to the required length with a
tube cutter. It is recommended to cut approx. 30 – 50 cm longer than the tubing length you esti­mate.
(2) Remove burrs at each end of the copper tubing
with a tube reamer or file. This process is impor­tant and should be done carefully to make a good flare. Be sure to keep any contaminants (moisture, dirt, metal filings, etc.) from entering the tubing. (Figs. 7-1 and 7-2)
When reaming, hold the tube end downward and be sure that no copper scraps fall into the tube. (Fig. 7-2)
(3) Remove the flare nut from the unit and be sure to
mount it on the copper tube.
(4) Make a flare at the end of the copper tube with a
flare tool.* (Fig. 7-3)
*Use RIGID
®
or equivalent.
A good flare should have the following characteristics:
inside surface is glossy and smooth
edge is smooth
tapered sides are of uniform length
NOTE
NOTE
Deburring
Before
After
Fig. 7-1
Reamer
Copper tubing
Fig. 7-2
Flare tool
Flare nut
Copper tubing
Fig. 7-3
A
φ6.35 φ9.52
φ12.7
φ15.88
9.1
13.2
16.6
19.7
A
0
– 0.4
Copper tubing (Outer dia.)
Flare size: A (mm)
04-393 DC INV Tech p 45-63 12/13/04 11:34 AM Page 53
Page 54
54
Fig. 7-7
Caution Before Connecting Tubes Tightly
(1) Apply a sealing cap or water-proof tape to prevent
dust or water from entering the tubes before they are used.
(2) Be sure to apply refrigerant lubricant to the match-
ing surfaces of the flare and union before connect­ing them together. This is effective for reducing gas leaks. (Fig. 7-4)
(3) For proper connection, align the union tube and
flare tube straight with each other, then screw on the flare nut lightly at first to obtain a smooth match. (Fig. 7-5)
Adjust the shape of the narrow tube (liquid tube)
using a tube bender at the installation site and connect it to the narrow tubing side (liquid tubing side) valve using a flare.
Cautions During Brazing
Replace air inside the tube with nitrogen gas to
prevent copper oxide film from forming during the brazing process. (Oxygen, carbon dioxide and Freon are not acceptable.)
Do not allow the tubing to get too hot during
brazing. The nitrogen gas inside the tubing may overheat, causing refrigerant system valves to become damaged. Therefore allow the tubing to cool when brazing.
Use a reducing valve for the nitrogen cylinder.
Do not use agents intended to prevent the for-
mation of oxide film. These agents adversely affect the refrigerant and refrigerant oil, and may cause damage or malfunctions.
7-2. Connecting Tubing Between Indoor and
Outdoor Units
(1) Tightly connect the indoor-side refrigerant tubing
extended from the wall with the outdoor-side tubing.
(2) To fasten the flare nuts, apply specified torque as
at right.
When removing the flare nuts from the tubing con-
nections, or when tightening them after connecting the tubing, be sure to use 2 monkey wrenches or spanners as shown. (Fig. 7-6) If the flare nuts are over-tightened, the flare may be damaged, which could result in refrigerant leakage and cause injury or asphyxiation to room occupants.
When removing or tightening the wide tube flare
nut, use 2 monkey wrenches together: one at the wide tube flare nut, and one at part A. (Fig. 7-7)
For the flare nuts at tubing connections, be sure to
use the flare nuts that were supplied with the unit, or else flare nuts for R410A (type 2). The refriger­ant tubing that is used must be of the correct wall thickness as shown in the table at right.
Apply refrigerant lubricant here and here
Fig. 7-4
Flare nut
Union
Fig. 7-5
Fig. 7-6
Indoor unit
Outdoor unit
Spanner
Torque wrench
Tube diameter
φ
6.35 (1/4")
φ
9.52 (3/8")
φ
12.7 (1/2")
φ
15.88 (5/8")
Tightening torque
(approximate)
14 18 N
·
m
(140 – 180 kgf · cm)
34 – 42 N
·
m
(340 – 420 kgf · cm)
49 – 61 N
·
m
(490 – 610 kgf
·
cm)
68 – 82 N
·
m
(680 – 820 kgf
·
cm)
0.8 mm
0.8 mm
0.8 mm
1.0 mm
Tube thickness
Because the pressure is approximately 1.6 times higher than conventional refrigerant pressure, the use of ordinary flare nuts (type 1) or thin-walled tubes may result in tube rupture, injury, or asphyxi­ation caused by refrigerant leakage.
In order to prevent damage to the flare caused by
over-tightening of the flare nuts, use the table above as a guide when tightening.
When tightening the flare nut on the narrow tube,
use a monkey wrench with a nominal handle length of 200 mm.
A
04-393 DC INV Tech p 45-63 12/13/04 11:34 AM Page 54
Page 55
55
Fig. 7-10
Fig. 7-9
Fig. 7-8
Fig. 7-11
Do not use a spanner to tighten the valve stem
caps. Doing so may damage the valves.
Depending on the installation conditions, applying
excessive torque may cause the nuts to crack.
Precautions for Packed Valve Operation
If the packed valve is left for a long time with the
valve stem cap removed, refrigerant will leak from the valve. Therefore, do not leave the valve stem cap removed.
Use a torque wrench to securely tighten the valve
stem cap.
Valve stem cap tightening torque:
7-3. Insulating the Refrigerant Tubing
Tubing Insulation
Thermal insulation must be applied to all unit tub-
ing, including distribution joint (purchased sepa­rately).
* For gas tubing, the insulation material must be
heat resistant to 120°C or above. For other tubing, it must be heat resistant to 80°C or above.
Insulation material thickness must be 10 mm or greater.
If the conditions inside the ceiling exceed DB 30°C and RH 70%, increase the thickness of the gas tubing insulation material by 1 step.
Taping the flare nuts
Wind the white insulation tape around the flare nuts at the wide tube connections. Then cover up the tubing connections with the flare insulator, and fill the gap at the union with the supplied black insulation tape. Finally, fasten the insulator at both ends with the sup­plied vinyl clamps. (Fig. 7-10)
Insulation material
The material used for insulation must have good insu­lation characteristics, be easy to use, be age resis­tant, and must not easily absorb moisture.
After a tube has been insu­lated, never try to bend it into a narrow curve because it can cause the tube to break or crack.
CAUTION
CAUTION
Never grasp the drain or refrigerant connecting outlets when moving the unit.
Unit side insulator
Insulation tape (white)
(supplied)
Sealer (supplied)
Flare insulator (supplied)
Tube insulator (not supplied) Heat resistant 120°C or above
Vin
y
l clamps (supplied)
Flare nut
The procedure used for installing the insulator for both wide and narrow tubes is the same.
Seal
Flare insulator
Vinyl clamp
Insulation tape
Refrigerant tubing and insulator (not supplied)
Drain pipe and insulator (not supplied)
Drain insulator and clamp. Large (supplied)
Packing clamp. Small hose band (supplied)
Two tubes arranged together
If the exterior of the outdoor unit valves has been finished with a square duct covering, make sure you allow sufficient space to access the valves and to allow the panels to be attached and removed.
Charging port 8 – 10 N • m (80 – 100 kgf • cm)
φ9.52 (Narrow side) 19 21 N m (190 210 kgf cm) φ15.88 (Wide side) 28 32 N m (280 320 kgf cm)
Inter-unit control wiring
Wide tube
Narrow tube
Armoring tape
Insulation
Charging port
Valve stem cap
Valve stem
Main valve
Packed valve
04-393 DC INV Tech p 45-63 12/13/04 11:34 AM Page 55
Page 56
56
GRFP
Fig. 7-12
Fig. 7-13
7-4. Taping the Tubes
(1) At this time, the refrigerant tubes (and electrical
wiring if local codes permit) should be taped together with armoring tape in 1 bundle. To pre­vent condensation from overflowing the drain pan, keep the drain hose separate from the refrigerant tubing.
(2) Wrap the armoring tape from the bottom of the
outdoor unit to the top of the tubing where it enters the wall. As you wrap the tubing, overlap half of each previous tape turn.
(3) Clamp the tubing bundle to the wall, using 1
clamp approx. each meter. (Fig. 7-12)
Do not wind the armoring tape too tightly since this will decrease the heat insulation effect. Also ensure that the condensation drain hose splits away from the bundle and drips clear of the unit and the tubing.
7-5. Finishing the Installation
After finishing insulating and taping over the tubing, use sealing putty to seal off the hole in the wall to pre­vent rain and draft from entering. (Fig. 7-13)
NOTE
Inter-unit control wiring
Wide tube
Narrow tube
Armoring tape
Insulation
Tubin
g
Apply putty here
04-393 DC INV Tech p 45-63 12/13/04 11:34 AM Page 56
Page 57
57
GRFP
Fig. 8-1
Fig. 8-2
Fig. 8-3
8. LEAK TEST, EVACUATION AND ADDITIONAL REFRIGERANT CHARGE
Perform an air-tightness test for this package A/C.
Check that there is no leakage from any of the con­nections. Air and moisture in the refrigerant system may have undesirable effects as indicated below.
pressure in the system rises
operating current rises
cooling (or heating) efficiency drops
moisture in the refrigerant circuit may freeze and
block capillary tubing
water may lead to corrosion of parts in the refriger-
ant system
Therefore, the indoor unit and tubing between the indoor and outdoor unit must be leak tested and evacuated to remove any noncondensables and moisture from the system.
Air Purging with a Vacuum Pump (for Test Run)
Preparation
Check that each tube (both narrow and wide tubes) between the indoor and outdoor units has been prop­erly connected and all wiring for the test run has been completed. Remove the valve caps from both the wide and narrow service valves on the outdoor unit. Note that both narrow and wide tube service valves on the outdoor unit are kept closed at this stage.
The refrigerant charge at the time of shipment is
only guaranteed sufficient for a tubing length of up to 30 m. The tubing may exceed this length, up to the maximum permitted length; however, an addi­tional charge is necessary for the amount that the tubing exceeds 30 m. (No additional refrigerating machine oil is needed.)
8-1. Leak Test
(1) With the service valves on the outdoor unit closed,
remove the 1/4 in. flare nut and its bonnet on the wide tube service valve. (Save for reuse.)
(2) Attach a manifold valve (with pressure gauges)
and dry nitrogen gas cylinder to this service port with charge hoses.
Manifold gauge
Outlet Inlet
Vacuum pump
Manifold valve
Pressure gauge
Lo Hi
Charge hose
Outdoor unit Narrow tube
Wide tube
Nitrogen gas cylinder (In vertical standing position)
Close
Close
Open
Cylinder valve
CAUTION
Use a manifold valve for air purging. If it is not available, use a stop valve for this purpose. The Hi knob of the manifold valve must always be kept closed.
04-393 DC INV Tech p 45-63 12/13/04 11:34 AM Page 57
Page 58
58
GRFP
Fig. 8-4
(3) Pressurize the system up to 4.15 MPa (42
kgf/cm2G) with dry nitrogen gas and close the cylin­der valve when the gauge reading reaches 4.15 MPa (42 kgf/cm2G). Then, test for leaks with liquid soap.
(4) Do a leak test of all joints of the tubing (both
indoor and outdoor) and both wide and narrow service valves. Bubbles indicate a leak. Wipe off the soap with a clean cloth after a leak test.
(5) After the system is found to be free of leaks,
relieve the nitrogen pressure by loosening the charge hose connector at the nitrogen cylinder. When the system pressure is reduced to normal, disconnect the hose from the cylinder.
8-2. Evacuation
Be sure to use a vacuum pump that includes a func­tion for prevention of back-flow, in order to prevent back-flow of pump oil into the unit tubing when the pump is stopped.
Perform vacuuming of the indoor unit and tubing.
Connect the vacuum pump to the wide tube valve and apply vacuum at a pressure of –755 mmHg (5 torr) or below. Continue vacuum application for a minimum of 1 hour after the pressure reaches –755 mmHg.)
(1) Attach the charge hose end described in the pre-
ceding steps to the vacuum pump to evacuate the tubing and indoor unit. Confirm that the Lo knob of the manifold valve is open. Then, run the vacu­um pump.
(2) When the desired vacuum is reached, close the
Lo knob of the manifold valve and turn off the vacuum pump. Confirm that the gauge pressure is under 667 Pa (–755 mmHg, 5 Torr) after 4 to 5 minutes of vacuum pump operation.
Manifold valve
Pressure gauge
Lo
Hi
Vacuum pump
Outdoor unit Narrow tube
Wide tube
Close
Close
Open
CAUTION
To avoid nitrogen entering the refrigerant system in a liquid state, the top of the cylinder must be higher than the bottom when you pres­surize the system. Usually, the cylinder is used in a ver­tical standing position.
CAUTION
Use a cylinder specifically designed for use with R410A.
04-393 DC INV Tech p 45-63 12/13/04 11:34 AM Page 58
Page 59
59
GRFP
Fig. 8-5
Fig. 8-6
8-3. Charging Additional Refrigerant
Charging additional refrigerant (calculated from the
narrow tube length as shown in P. 12, Amount of additional refrigerant charge) using the narrow tube service valve. (Fig. 8-5)
Use a balance to measure the refrigerant accurately.
If the additional refrigerant charge amount cannot
be charged at once, charge the remaining refriger­ant in liquid form by using the wide tube service valve with the system in Cooling mode at the time of test run. (Fig. 8-6)
* If an additional refrigerant charge has been per-
formed, list the refrigerant tubing length and amount of additional refrigerant charge on the product label (inside the panel).
8-4. Finishing the Job
(1) With a hex wrench, turn the narrow tube service
valve stem counter-clockwise to fully open the valve.
(2) Turn the wide tube service valve stem counter-
clockwise to fully open the valve.
(3) Loosen the charge hose connected to the wide
tube service port (5/16 in.) slightly to release the pressure, then remove the hose.
(4) Replace the 5/16 in. flare nut and its bonnet on the
wide tube service port and fasten the flare nut securely with an adjustable wrench or box wrench. This process is very important to prevent gas from leaking from the system.
(5) Replace the valve caps at both wide and narrow
service valves and fasten them securely.
CAUTION
To avoid gas from leaking when removing the charge hose, make sure the stem of the wide tube is turned all the way out (BACK SEAT position.
Valve
Liquid
Manifold valve
Pressure gauge
Lo Hi
Outdoor unit Narrow tube
Wide tube
Close
Close
Close
R410A
Outdoor unit Narrow tube
Wide tube
Open
Open
Open
04-393 DC INV Tech p 45-63 12/13/04 11:34 AM Page 59
Page 60
60
CAFP
9. HOW TO INSTALL THE CEILING PANEL
4-Way Air Discharge Semi-Concealed Type (CAFP Type)
Checking the unit position
(1) Check that the ceiling hole is within this range:
860 × 860 to 910 × 910 mm
(2) Use the full-scale installation diagram (from the
packaging) that was supplied with the unit to deter­mine the positioning of the unit on the ceiling sur­face. If the positions of the ceiling surface and unit do not match, air leakage, water leakage, flap operation failure, or other problems may result.
CAUTION
Never place the panel
face-down. Either hang it vertically or place it on top of a projecting object. Placing it face­down will damage the surface.
Do not touch the flap or
apply force to it. (This may cause flap malfunction.)
must be within the range of 12 – 17 mm.
If not within this range, malfunction or other trouble may result.
A
Ceiling side
Main unit
Ceiling opening dimension
A
Fig. 9-1
Wing
Fig. 9-2
Fig. 9-3
2
Fig. 9-5
9-1. Before Installing the Ceiling Panel
(1) Remove the air-intake grille and air filter from the
ceiling panel. (Figs. 9-3, 9-4 and 9-5)
a) Remove the 2 screws on the latch of the air-
intake grille. (Fig. 9-3)
b) Slide the air-intake grille catches in the direc-
tion shown by the arrows to open the grille. (Fig. 9-4)
c) With the air-intake grille opened, remove the
grille hinge from the ceiling panel by sliding it in the direction shown by the arrow . (Fig. 9-5)
(2) Removing the corner cover
a) Slide the corner cover to the direction shown
by the arrow to remove the corner cover. (Fig. 9-6).
1
2
1
Corner cover
Ceiling panel
Strap
Push
1
Corner cover
Fig. 9-6
Air-intake grille
Ceiling panel
Air-intake grille hinge
1
1
Fig. 9-4
Latch
Screw
04-393 DC INV Tech p 45-63 12/13/04 11:34 AM Page 60
Page 61
61
CAFP
CAUTION
9-2. Installing the Ceiling Panel
The power must be turned ON in order to change the flap angle. (Do not attempt to move the flap by hand. Doing so may damage the flap.)
(1) Insert the temporary fasteners (stainless steel) on
the inside of the ceiling panel into the square holes on the unit to temporarily fasten the ceiling panel in place. (Fig. 9-7)
The ceiling panel must be installed in the correct
direction relative to the unit. Align the REF. PIPE and DRAIN marks on the ceiling panel corner with the correct positions on the unit.
To remove the ceiling panel, support the ceiling
panel while pressing the temporary fasteners toward the outside. (Fig. 9-7)
(2) Align the panel installation holes and the unit
screw holes.
(3) Tighten the supplied washer head screws at the 4
panel installation locations so that the panel is attached tightly to the unit. (Fig. 9-8)
(4) Check that the panel is attached tightly to the ceil-
ing.
At this time, make sure that there are no gaps
between the unit and the ceiling panel, or between the ceiling panel and the ceiling surface. (Fig. 9-9)
Square hole in unit
Temporary fastener
Push when you remove
Temporary fastener
Fig. 9-7
Drain tubing corner
Refrigerant tubing corner
Panel installation hole (4 locations)
Ceiling panel
Washer head screws
DRAIN mark
REF. PIPE mark
Fig. 9-8
Do not allow
gaps
Ceilin
g
panel
Main unit
Ceiling surface
Fig. 9-9
Insert a wrench or other tool into the corner cover installation hole and make fine adjustments to the unit nut.
Air leakage
Air leakage from ceiling surface
Staining
Condensation, water leakage
Adjust so that there are no gaps.
Fig. 9-10
Fig. 9-11
If there is a gap between the panel and the ceiling,
leave the ceiling panel attached and make fine adjustments to the installation height of the unit to eliminate the gap with the ceiling. (Fig. 9-10)
If the screws are not sufficiently
tightened, trouble such as that shown in the figure below may occur. Be sure to tighten the screws securely.
If a gap remains between the
ceiling surface and the ceiling panel even after the screws are tightened, adjust the height of the unit again.
The height of the unit can be adjusted from the ceiling panel corner hole, with the ceil­ing panel attached, to an extent that does not affect the unit levelness, the drain hose, or other elements.
04-393 DC INV Tech p 45-63 12/13/04 11:34 AM Page 61
Page 62
62
CAFP
9-3. Wiring the Ceiling Panel
(1) Open the cover of the electrical component box.
(2) Connect the 7P wiring connector (red) from the
ceiling panel to the connector in the unit electrical component box.
If the connectors are not connected, Auto flap will
not operate. Be sure to connect them securely.
Check that the wiring connector is not caught
between the electrical component box and the cover.
Check that the wiring connector is not caught
between the unit and the ceiling panel.
9-4. How to Attach the Corner & Air Intake Grille
Attaching the corner cover and air-intake grille
A. Attaching the corner cover
(1) Check that the safety cord from the corner cover is
fastened to the ceiling panel pin, as shown in the figure.
(2) Use the supplied screws to attach the corner
cover to the ceiling panel.
B. Attaching the air-intake grille
To install the air-intake grille, follow the steps for
Removing the grille in the reverse order. By rotat­ing the air-intake grille, it is possible to attach the grille onto the ceiling panel from any of 4 direc­tions. Coordinate the directions of the air-intake grilles when installing multiple units, and change the directions according to customer requests.
When attaching the air-intake grille, be careful
that the flap lead wire does not become caught.
Be sure to attach the safety cord to the ceiling
panel unit as shown in the figure at right. This keeps the air intake grille from accidentally dropping
(Direction that the unit faces has been changed to facilitate explanation.)
Ceiling panel wiring connector
Ceiling panel side
Screws (3 locations)
Mains side
Clamp
Electrical component box cover
* Pass the wiring connector through the clamp to fasten it in place,
as shown in the figure.
Place the corner cover so that the 3 tabs fit into the holes in the ceiling panel. Then fasten it in place with the supplied screws.
Pin
With this ceiling panel, the directions of the air-intake grille lattices when installing multiple units, and the position
of the label showing the company name on the corner panel, can be changed according to customer requests, as shown in the figure below. However, the optional wireless receiver kit can only be installed at the refrigerant­tubing corner of the ceiling unit.
Unit electrical component box
Unit drain hose side
Unit refrigerant tube side
Optional wireless receiver kit * Can only be installed in this position.
Can be installed rotated 90˚
Locations of the air-intake grille catches at the time the product is shipped. * The grille can be installed with these
catches facing in any of 4 directions.
Fig. 9-12
Fig. 9-13
Hole for ceiling panel hook
Hook that prevents the
g
rille from droppin
g
Fig. 9-14
Fig. 9-15
04-393 DC INV Tech p 45-63 12/13/04 11:34 AM Page 62
Page 63
63
CAFP
9-5. Checking After Installation
Check that there are no gaps between the unit and
the ceiling panel, or between the ceiling panel and the ceiling surface. Gaps may cause water leakage and condensation.
Check that the wiring is securely connected.
If it is not securely connected, the auto flap will not operate. (P09 is displayed on the remote con­troller.) In addition, water leakage and condensa­tion may occur.
9-6. When Removing the Ceiling Panel for
Servicing
When removing the ceiling panel for servicing, remove the air-intake grille and air filter, disconnect the wiring connector inside the electrical component box, and then remove the 4 mounting screws.
9-7. Adjusting the Auto Flap
The air-direction louver on the ceiling panel outlet can be adjusted as follows.
Adjust the louver to the desired angle using the
remote controller. The louver also has an automatic air-sweeping mechanism.
Never attempt to move the louver by hand.
Proper air flow depends on the location of the air
conditioner, the layout of the room and furniture, etc. If cooling or heating seems inadequate, try changing the direction of the air flow.
NOTE
04-393 DC INV Tech p 45-63 12/13/04 11:34 AM Page 63
Page 64
64
10. TEST RUN
10-1. Preparing for Test Run
Before attempting to start the air conditioner,
check the following:
(1) All loose matter is removed from the cabinet espe-
cially steel filings, bits of wire, and clips.
(2) The control wiring is correctly connected and all
electrical connections are tight.
(3) The protective spacers for the compressor used
for transportation have been removed. If not, remove them now.
(4) The transportation pads for the indoor fan have
been removed. If not, remove them now.
(5) The power has been supplied to the unit for at
least 5 hours before starting the compressor. The bottom of the compressor should be warm to the touch and the crankcase heater around the feet of the compressor should be hot to the touch. (Fig. 10-1)
(6) Both the wide and narrow tube service valves are
open. If not, open them now. (Fig. 10-2)
(7) Request that the customer be present for the trial
run. Explain the contents of the instruction manual, then have the customer actually operate the system.
(8) Be sure to give the instruction manual and warran-
ty certificate to the customer.
(9) When replacing the control PCB, be sure to make
all the same settings on the new PCB as were in use before replacement. The existing EEPROM is not changed, and is con­nected to the new control PCB.
Fig. 10-1
Fig. 10-2
Power mains switch
(Power must be turned ON at least 5 hours before attempting test run)
ON
Narrow tube
Wide tube
04-393 DC INV Tech p 64-110 12/13/04 11:35 AM Page 64
Page 65
65
CAFP, SPAFP, DSAFP Type
10-2. Caution
This unit may be used in a single-type refrigerant system where 1 outdoor unit is connected to 1 indoor
unit, and also in a system where 1 outdoor unit is connected to multiple indoor units (maximum 4).
* If multiple indoor units are used, also refer to 10-8. System Control.
The indoor and outdoor unit control PCBs utilize a semiconductor memory element (EEPROM). The set-
tings required for operation were made at the time of shipment. Only the correct combinations of indoor and outdoor units can be used.
This test run manual describes primarily the procedure when using the wired remote controller.
10-3. Test Run Procedure
Recheck the items to check before the test run.
Indicate (mark) the combination number.
Turn ON the indoor and outdoor power.
Set the remote controller to “test run.”
Turn ON the indoor and outdoor power.
Return the remote controller to normal control.
YES
YES
YES
NO
NO
NO
Automatic
address
(See 10-4)
(See 10-8-1 ~ 5)
(See 10-8-3)
(See 10-8-4)
(See 10-8-5)
(See 10-5)
(* 1)
Check the combination (wiring) of indoor and outdoor units.
Is system single-type?
(1 indoor unit is connected to 1 outdoor
unit and remote controller)
Is group control with
multiple outdoor units used?
Can
operation be
started?
Setting the Outdoor Unit System Address
Automatic Address Setting
Set the outdoor unit system address.
Use the remote controller to perform automatic address setting.
Refer to Table of Self-Diagnostic Functions to check the system. In addition, refer to 10-8-1 ~ 5 and correct any items that need to be corrected.
Note: Check the indoor-side drainage. (*1) Required for simultaneous-operation multi systems and for group control.
(Automatic Address)
Fig. 10-3
04-393 DC INV Tech p 64-110 12/13/04 11:35 AM Page 65
Page 66
66
10-4. Items to Check Before the Test Run
(1) Turn the remote power switch ON at least 12 hours in advance in order to energize the crank case heater.
(2) Fully open the closed valves on the narrow-tube and wide-tube sides.
10-5. Test Run Using the Remote Controller
(1) Press and hold the remote controller button for 4 seconds or longer. Then press the button.
TEST appears in the LCD display during the test run.
Temperature control is not possible when test run mode is engaged.
(This mode places a large load on the devices. Use it only when performing the test run.)
(2) Use either Heating or Cooling mode to perform the test run.
Note: The outdoor unit will not operate for approximately 3 minutes after the power is turned ON or after it stops
operating.
(3) If normal operation is not possible, a code appears on the remote controller LCD display.
Refer to the Table of Self-Diagnostic Functions and Corrections on the next page, and correct the problem.
(4) After the test run is completed, press the button again. Check that TEST disappears from the LCD display.
(This remote controller includes a function that cancels test run mode after a 60-minute timer has elapsed, in order to prevent continuous test run operation.)
(5) For the test run of an inverter outdoor unit, operate the compressors for a minimum of 10 minutes (in order to
check for open phase).
* When performing a test run using a wired remote controller, operation is possible without attaching the cas-
sette-type ceiling panel. (P09 will not be displayed.)
10-6. Precautions
Request that the customer be present when the test run is performed. At this time, explain the operation manual
and have the customer perform the actual steps.
Be sure to pass the manuals and warranty certificate to the customer.
Check that the AC 220 – 240 V power is not connected to the inter-unit control wiring connector terminal.
* If AC 220 – 240 V is accidentally applied, the indoor or outdoor unit control PCB fuse (0.5 A for both indoor
and outdoor units) will blow in order to protect the PCB. Correct the wiring connections, then disconnect the 2P connectors (indoor: blue, DC) (outdoor: blue, serial 1) that are connected to the PCB, and replace them with 2P connectors (indoor: brown, EMG) (outdoor: brown, serial 2). (Refer to the figure below.) If operation is still not possible after changing the brown connectors, try cutting the varistor (black) (both indoor and out­door). (Be sure to turn the power OFF before performing this work.)
Indoor unit control PCB
Outdoor unit control PCB
Varistor (black)
Varistor (black)
Fuse 0.5A
SG41
Fuse
VA002
2P connector (brown)
2P connector (blue)
CHK (2P plug)
Serial 1 (blue) connector
0.5A
Terminal plug (black)
3 ~ 5 HP
Serial 2 (brown) connector
Fig. 10-4
04-393 DC INV Tech p 64-110 12/13/04 11:35 AM Page 66
Page 67
67
Wired remote
controller display
Cause
Correction
Nothing is
displayed
Nothing is
displayed
E 0 1
displayed
E 0 2
displayed
E 0 9
displayed
E 1 4
displayed
E 0 4
displayed
E 0 5
displayed
E 1 5
displayed
E 1 6
displayed
E 2 0
displayed
P 0 5
displayed
L 0 2
displayed
L 1 3
displayed
P 0 9
displayed
L 0 7
displayed
P 1 2
displayed
Indoor unit
receiver lamp
Operating lamp
is blinking.
Standby lamp
is blinking.
Both the Operation
lamp and Standby
lamp are blinking
together.
Operation lamp and
Standby lamp are
blinking alternately.
Timer lamp and
Standby lamp are
blinking alternately.
1:1 connection (single type)
Remote controller is not connected correctly.
Indoor unit power is not ON.
Automatic address setting has not been
completed.
Inter-unit control wiring is cut or is not
connected correctly.
Remote controller is not connected correctly
(remote controller receiving failure).
Remote controller is not connected correctly
(failure in transmission from remote controller
to indoor unit).
Indoor-outdoor inter-unit wiring is not
connected correctly.
Indoor unit capacity is too low.
Indoor unit capacity is too high.
No serial signal is being received at all from
the indoor units.
Reversed phase or open phase in the outdoor
unit 3-phase power
Insufficient gas
Indoor-outdoor unit type mismatch
The indoor unit ceiling panel connector is not
connected correctly.
Indoor unit DC fan trouble
Remote controller is not connected with
indoor unit correctly
Indoor unit power is not ON.
Automatic address setting has not been
completed.
Inter-unit control wiring is cut or is not
connected correctly.
Remote controller is not connected with
indoor unit correctly
Remote controller is not connected with
indoor unit correctly
Same as in the left
Indoor-outdoor inter-unit wiring is cut or
is not connected correctly.
Same as in the left
Reversed phase or open phase in the 3-
phase power at one of the outdoor units
in the group
Same as in the left
Same as in the left
Same as in the left
Simultaneous-operation multi system
(flexible combination)
Same as in the left
Same as in the left
Same as in the left
Same as in the left
Same as in the left
Same as in the left
Same as in the left
Same as in the left
Same as in the left
Same as in the left
Same as in the left
Same as in the left
Same as in the left
Same as in the left
Same as in the left
Same as in the left
Remote controller crossover wiring is cut
or is not connected correctly.
Indoor unit ceiling panel connector is not
connected correctly.
Indoor unit fan trouble
Remote controller crossover wiring is
connected to the indoor unit, however it is set
for individual operation.
Connect the remote controller correctly.
Turn ON the indoor unit power.
2 remote controllers are
set as the main remote
controller.
Control by main-sub
remote controllers
Check the remote controller and inter-unit
control wiring.
Perform automatic address setting
(See 10-8-4).
Connect the remote controller correctly.
Refer to 10-8-6 Main-sub remote Control,
and make the correct settings.
Check the remote controller crossover wiring.
Perform automatic address setting again.
Connect the wiring correctly.
Refer to 10-8 System Control, and make the
correct settings.
Check that the total capacities of the indoor
and outdoor units are appropriate.
Check whether the fan holder is loose.
Check the wiring between the DC fan and
the PCB.
Check that the indoor unit power is ON, and that
the inter-unit control wiring is connected correctly.
Reverse 2 phases of the outdoor unit 3-phase
power and connect them correctly.
Check that the indoor and outdoor unit types
are correct.
Perform automatic address setting (See 10-8).
Connect the indoor unit ceiling panel
connector correctly.
DC fan trouble at one of the indoor units
in the group
Ceiling panel connector at one of the
indoor units in the group is not
connected correctly.
Group connection
Reversed phase or open phase in
the outdoor unit 3-phase power
10-7. Table of Self-Diagnostic Functions and Corrections (CAFP, SPAFP, DSAFP, MAFP Type)
04-393 DC INV Tech p 64-110 12/13/04 11:35 AM Page 67
Page 68
68
10-8. System Control
System control refers to connecting link wiring for control, for simultaneous-operation multi systems, group control, and main-sub remote controller control.
10-8-1. Basic wiring diagram 1
Single type and simultaneous-operation multi system
Simultaneous-operation multi system
Up to 4 (Double-Twin) indoor units can be connected to 1 outdoor unit for operation. (However, coordinate the outdoor unit capacity and the total capacity of the indoor units.) (It is not possible to connect individual remote controllers for independent operation.)
Be careful to avoid miswiring when connecting the wires. (Miswiring will damage the units.)
1
2
12
1 2
U2
U1
0
L N
N
U1 U2
1 2
L
L N
1 2
U2
U1
L N
Remote controller crossover wiring for group control
System address rotary switch (Set to 0 at the time of shipment.)
Inter-unit control wiring
Outdoor unit
Indoor
unit
Indoor
unit
Indoor
unit
For a simultaneous-operation multi system, a maximum of 4 indoor units can be connected to 1 outdoor unit.
Ground
Wired remote controller
Remote controller wiring
WHT
BLK
(Optional)
Ground
Ground
Ground
Leakage breaker
Leakage breaker
Fig. 10-5
04-393 DC INV Tech p 64-110 12/13/04 11:35 AM Page 68
Page 69
69
10-8-2. Basic wiring diagram 2
Group control (when a central control device is not used)
Simultaneous-operation multi system
Up to 4 (Double-Twin) indoor units can be connected to 1 outdoor unit for operation. (However, coordinate the outdoor unit capacity and the total capacity of the indoor units.) (It is not possible to connect individual remote controllers for independent operation.) A maximum of 8 indoor units can be connected to 1 remote controller. When 2 or 3 indoor units are connected to each outdoor unit in the refrigerant system, set the system address (refrigerant tubing system address) before turning on the remote power switch. (Refer to 10-8-3. Setting the out­door unit system addresses.) (Set using the system address rotary switch on the outdoor unit control PCB.)
Fig. 10-6
1
2
1
2
1 2
U2
U1
1 2
U2
U1
1 2
U2
U1
12
1
2
L
N
L
N
L N
TNLNL
1
2
U2
U1
L N
L N
1 2
U2
U1
Outdoor unit
Indoor
unit
Indoor
unit
Indoor
unit
Indoor
unit
Indoor
unit
Outdoor unit
Ground
Ground
Ground
Ground
Ground Ground Ground
(Optional)
Wired remote controller
Remote controller wiring
Remote controller crossover wiring for group control
System address rotary switch (Change the setting.)
System address rotary switch (Change the setting.)
Indoor power crossover wiring – up to 16 units (no-heater units only)
Inter-unit control wiring
WHT
BLK
Leakage breaker
Leakage breaker
Leakage breaker
Leakage breaker
(Wiring procedure)
(1) Connect the remote controller to the indoor unit remote controller wiring terminal plate (1, 2). (Remote controller
wiring)
(2) Connect the indoor units (U1, U2) and the outdoor units (1, 2). Connect the other outdoor units and indoor units
(with different refrigerant systems) in the same way. (Inter-unit control wiring) Connect the remote controller crossover wiring to the indoor units (U1, U2) for each refrigerant system. (Inter­unit control wiring)
(3) Connect the remote controller crossover wiring (2 wires) from the remote controller wiring terminal plate (1, 2)
on the indoor unit (unit where the remote controller is connected) to the remote controller terminal plates (1, 2) on the other indoor units. (Remote controller crossover wiring)
(4) Turn ON both the indoor and outdoor unit power and perform automatic address setting from the remote con-
troller. (For the automatic address setting procedure, refer to 10-8-4.)
* Models with auxiliary heaters cannot be used for crossover wiring of the indoor unit power wires. (Use a pull box
to divide the wiring.) Be sure to use the indoor unit temperature sensor (body sensor) when using this control. (Status at shipment.)
NOTE
04-393 DC INV Tech p 64-110 12/13/04 11:35 AM Page 69
Page 70
70
10-8-3. Setting the outdoor unit system addresses
For basic wiring diagram 2 (Set the system addresses: 1, 2, 3...)
ON
1
2
0
System address rotary switch (Set to 0 at time of shipment)
System address rotary switch
System address
DIP switch
OFF
ON
10s 20s
3 ~ 5H P
Outdoor unit control PCB
Fig. 10-7
System address No.
System address 10s digit
(2P DIP switch)
System address 1s place
(Rotary switch)
0 Automatic address
(Setting at shipment = 0)
1 (If outdoor unit is No. 1)
0 setting
Both OFF
Both OFF
Both OFF
10s digit ON
20s digit ON
10s digit and 20s digit ON
1 setting
2 setting
1 setting
1 setting
0 setting
2 (If outdoor unit is No. 2)
11 (If outdoor unit is No. 11)
21 (If outdoor unit is No. 21)
30
(If outdoor unit is No. 30)
ON
ON
OFF
1 2
ON
ON
OFF
1 2
ON
ON
OFF
1 2
ON
ON
OFF
1 2
ON
ON
OFF
1 2
ON
ON
OFF
1 2
10-8-4. Automatic address setting using the remote controller
When the outdoor unit shown in 10-8-2. Basic wiring diagram 2 is used for group control of multiple units , use
the remote controller to perform automatic address setting. (During automatic address setting, SETTING blinks on the remote controller display.)
Press the remote controller timer time button and button simultaneously. (Hold for 4 seconds or longer.)
Then press the button. (Item code AA appears: All systems automatic address setting.) (Automatic address setting is performed in sequence for all outdoor units from No. 1 to No. 30. When automatic address setting is completed, the units return to normal stopped status.)
To select each refrigerant system individually and perform automatic address setting, press the remote controller
timer time button and button simultaneously. (Hold for 4 seconds or longer.) Then press either the tem­perature setting or button. (Item code A1 appears: Individual system automatic address setting) Use either the or button to select the outdoor unit to perform automatic address setting for. (R.C.1 is displayed.) Then press the button. (Automatic address setting is performed for refrigerant system 1.) When automatic address setting for system 1 is completed, the system returns to normal stopped status. Again press the remote controller timer time button and the button simultaneously. Then in the same way as above (use the button to display R.C.2), select the next system and perform automatic address setting.
System address rotary switch
System address 10s digit and 20s digit
DIP switch
Automatic address button (black)
Terminal plug (black)
04-393 DC INV Tech p 64-110 12/13/04 11:35 AM Page 70
Page 71
71
10-8-5. Indicating (marking) the indoor and outdoor unit combination number
Indicate (mark) the number after automatic address setting is completed.
(1) So that the combination of each indoor unit can be easily checked when multiple units are installed, ensure that
the indoor and outdoor unit numbers correspond to the system address number on the outdoor unit control PCB, and use a magic marker or similar means which cannot be easily erased to indicate the numbers in an easily visible location on the indoor units (near the indoor unit nameplates).
Example: (Outdoor) 1 - (Indoor) 1, 2... (Outdoor) 2 - (Indoor) 1, 2...
(2) These numbers will be needed for maintenance. Be sure to indicate them.
* Use the remote controller to check the addresses of the indoor units. Press and hold the button and
button for 4 seconds or longer (simple settings mode). Then press the button and select the indoor
address. (Each time the button is pressed, the address changes as follows: 1-1, 1-2, ... 2-1, 2-2, ....) The
indoor unit fan operates only at the selected indoor unit. Confirm that correct fan is operating, and indicate address on the indoor unit.
Press the button again to return to the normal remote controller mode. For details, refer to the separate handbook.
10-8-6. Main-sub remote controller control
Control using 2 remote controller switches
Main-sub remote controller control refers to the use of 2 remote controllers to control 1 or multiple indoor units. (A maximum of 2 remote controllers can be connected.)
Connecting 2 remote controllers to
control 1 indoor unit
Connecting 2 remote controllers to control a
simultaneous-operation multi system
1 2
1 2
1 2
U1U2
1 2
1 2
U1U2
1 2
U1U2
1 2
1 2
1 2
U1U2
1 2
Remote controller wiring
Optional
Optional
Optional
Optional
Remote controller switch (sub)
Remote controller switch (main)
Remote controller switch (main)
Indoor unit
Indoor unit 1
Outdoor unit
Indoor unit 2 Indoor unit 3
Outdoor unit
Ground
Ground
Ground Ground
Ground
Ground
Remote controller switch (sub)
Remote controller crossover wiring
Inter-unit control wiring
for remote controller wiring
Terminal plate
Terminal plate
for remote
controller wiring
Terminal plate
for remote
controller wiring
(Setting procedure)
(1) Set 1 of the 2 connected remote controllers as the
main remote controller.
(2) On the other remote controller (sub remote con-
troller), change the remote controller address con­nector on the reverse side of the remote controller switch PCB from the Main position to the Sub position. The remote controller will now function as the sub remote controller. The sub remote controller will also operate if con­nected to indoor unit 2.
Fig. 10-8
TIMER TMNL.
RCU
TMNL.
RCU.ADR
RCU.Main
RCU.Sub
RCU.CK
To Service Technicians
To display the sensor temperature:
WARNING
To avoid an electric shock hazard, DO NOT touch any ter­minal on the Printed Cir­cuit Board with a metal rod, a screwdriver edge or bare hand when power is supplied.
Press both and buttons on the remote controller for more than 4 seconds together. Change the sensor address (CODE NO.) with / (SET TEMP) buttons. Select the UNIT NO. that you want to call with button. Press the button to finish service mode.
To display the trouble history: Press both and buttons on the remote controller for more than 4 seconds together. Change the alarm message: / (SET TEMP) buttons CODE NO.
Press the button to finish service mode.
On the remote controller, press + + at the same time for more than 4 seconds. Set CODE No. with / (SET TEMP) button.
Set DATA from to with / (TIMER) button. Press Finally, Press
(New) (Old)
Changing method for room temperature sensor (from Indoor unit to RCU)
1
2
3
4
Remote Controller (Sub)
Remote controller address connector
Remote Controller (Main)
Checking remote controller
04-393 DC INV Tech p 64-110 12/13/04 11:35 AM Page 71
Page 72
72
MAFP Type 10-9. Caution
This unit may be used in a single-type refrigerant system where 1 outdoor unit is connected to 1 indoor
unit, and also in a system where 1 outdoor unit is connected to multiple indoor units (maximum 4).
* If multiple indoor units are used, also refer to 10-16. System Control.
The indoor and outdoor unit control PCBs utilize a semiconductor memory element (EEPROM). The set-
tings required for operation were made at the time of shipment. Only the correct combinations of indoor and outdoor units can be used.
10-10. Test Run Procedure
Recheck the items to check before the test run.
Turn ON the indoor and outdoor power.
Set the indoor unit control switch to TEST.
Turn ON the indoor and outdoor power.
Slide the indoor unit control switch back to ON.
YES
NO
YES
NO
YES
NO
(See 10-13-3)
(See 10-13-3)
(See 10-15)
(See 10-11)
(See 10-16)
Check the combination (wiring) of indoor and outdoor units.
Is system single-type?
(1 indoor unit is connected
to 1 outdoor unit)
Are multiple outdoor units used?
Can
operation be
started?
Refer to Table of Self-Diagnostic Functions to check the system. In addition, refer to 10-16 and correct any items that need to be corrected.
Note: Check the indoor-side drainage.
Confirm wiring is done in accordance with Fig. 2,
Basic Wiring.
(Automatic Address Setting)
(See 10-16-2) In case of group control
Set the automatic address setting from outside unit.
(See 10-16-3 ~ 10-16-6)
How to Set Automatic Address
(Automatic Address setting)
Fig. 10-9
04-393 DC INV Tech p 64-110 12/13/04 11:35 AM Page 72
Page 73
73
10-11. Items to Check Before the Test Run
(1) Turn the remote power switch ON at least 12 hours in advance in order to energize the crank case heater.
(2) Fully open the closed valves on the narrow-tube and wide-tube sides.
(3) Set the slide switch inside the wireless remote controller cover to match the unit type. After changing the set-
ting, press the ACL button.
10-12. Preparation for Test Run
10-12-1. Switching the temperature sensor
Temperature sensors are contained in the indoor unit and wireless remote controller. One or the other of the
temperature sensors is used for operation.
If (BODY SENSOR) appears on the LCD display of the wireless remote controller, then the indoor unit body
sensor is used for operation.
To switch to the remote controller sensor, open the remote controller cover and press the SENSOR button once. The (BODY SENSOR) display disappears and the remote control sensor is used for operation.
Even if the remote controller sensor is selected, the sensor will be automatically switched to the indoor unit body
sensor if no temperature signal has been received from the remote controller for 10 minutes. Install the remote controller in a position where the signal can be reliably received by the unit.
When group control is engaged, be sure to use the body sensor.
10-12-2. Using the remote controller
Face the remote controller toward the receiver (on the
main unit).
The signal can be received up to a distance of approxi-
mately 8 m. Use this distance as a guide. This distance may vary somewhat depending on the battery capacity and other factors.
Be sure that there are no objects between the remote
controller and the receiver which may block the signal.
The unit beeps when a signal is received correctly.
(For operation start only, the unit beeps twice.)
Do not drop, throw, or wash the remote controller.
Do not place the remote controller in locations exposed to direct sunlight or nearby a stove.
NOTE
S: Flap type with limit switch (4-way, ceiling-mounted, wall-mounted) K: Swing-only type (floor-mounted) installed N: No-flap type (built-in)
Check that sliding switch 1 is set to S. Set sliding switch 2 to match
the unit type.
A: Heat-pump type (H: Heat pump with no auto heat/cool) C: Cool-only type
Sliding switch 1
SKN
AHC AHC
ACL (ALL CLEAR) button
Sensor button
Sliding switch 2
<Indicators>
OPERATION TIMER STANDBY
Receiver
Fig. 10-10
Fig. 10-11
04-393 DC INV Tech p 64-110 12/13/04 11:35 AM Page 73
Page 74
74
10-13. Test Run
Using the control unit
(1) Change the indoor control unit switch from ONTEST.
(The outdoor unit will not operate for 3 minutes after the power is turned ON and after operation is stopped.)
(2) All the indicator lamps blink while the test run is in progress.
(3) Temperature control is not possible during the test run.
(4) If correct operation is not possible, the trouble will be indicated by the
indicator lamps. Refer to Table of Self Diagnostic Functions and Correc­tions and correct the problem.
(5) After the test is completed, change the control unit switch from TESTON. Confirm that the indicator
lamps have stopped blinking. (A function is included which cancels the test run after a 60-minute timer has elapsed, in order to prevent continuous test run operation.)
This mode places a large load on the devices. Use it only for performing test runs.
A test run is not possible if the power is turned ON with the switch in the TEST position.
After the power has been turned ON, change the switch once to ON or OFF, then switch it back to the TEST position.
10-14. Precautions
Request that the customer be present when the test run is performed. At this time, explain the operation manual
and have the customer perform the actual steps.
Be sure to pass the manuals and warranty certificate to the customer.
Check that the AC 220 – 240 V wiring is not connected to the inter-unit control wiring connector terminal.
* If AC 220 – 240 V is accidentally applied, the indoor or outdoor unit control PCB fuse (0.5 A for both indoor and
outdoor units) will blow in order to protect the PCB. Correct the wiring connections, then disconnect the 2P con­nectors (indoor: blue) (outdoor: blue, serial 1) that are connected to the PCB, and replace them with 2P con­nectors (indoor: brown) (outdoor: brown, serial 2). (Refer to the figure below.) If operation is still not possible after changing the brown connectors, try cutting the varistor (black) (both indoor and outdoor). (Be sure to turn the power OFF before performing this work.)
NOTE
2 HP
2P connector (blue)
2P connector (blue)
Fuse (0.5A)
Fuse (0.5A)
CHK (2P plug)
CHK (2P plug)
SW103
ON OFF TEST
SW103
TEST ON OFF
2P connector (brown)
2P connector (brown)
Varistor (black)
VA002
Varistor (black) VA002
Indoor unit control PCB
3 HP
Indoor unit control PCB
Fig. 10-12
Outdoor unit control PCB
Varistor (black)
Fuse
VA002
Serial 1 (blue) connector
0.5A
Terminal plug (black)
3 ~ 5 HP
Serial 2 (brown) connector
ON OFF TEST
Indoor control unit switch
OPERATION
TIMER STANDBY
Indicator lamps
04-393 DC INV Tech p 64-110 12/13/04 11:35 AM Page 74
Page 75
75
10-15. Table of Self-Diagnostic Functions and Corrections
Wired remote
controller display
(Field supply)
Cause
Correction
Nothing is displayed
Nothing is displayed
Operating lamp is blinking.
Standby lamp is blinking.
Operation lamp and Standby lamp are blinking alternately.
Both the Operation lamp and Standby lamp are blinking together.
Indoor unit
receiver lamp
E14 displayed
E04
displayed
E06
displayed
E15
displayed
1:1 connection
(Single type)
Group connection
(Simultaneous multi system)
Set the indoor operation switch ON.
Turn ON the indoor unit power.
Check the inter-unit control wiring.
Perform automatic address setting
(See 10-16).
Check the remote controller crossover wiring.
Perform automatic address setting again.
Connect the wiring correctly.
E01 displayed
Refer to 10-16 System Control, and make the correct settings.
Check that the total capacities of the indoor and outdoor units are appropriate.
Connect the units correctly.
Connect the units correctly.
Connect the units correctly.
Perform automatic address setting
(See 10-16).
Reverse 2 phases of the outdoor unit
3-phase power and connect them correctly.
Same as in the left.
Same as in the left.
Remote controller crossover wiring is cut or is not connected
Same as in the left.
Inter-unit control
wiring is cut or is not connected
Same as in the left.
Same as in the left.
Outdoor unit
address is duplicated
Remote controller crossover wiring is connected to the indoor unit, however, it is set for individual operation.
Same as in the left.
Same as in the left.
Indoor operation switch is OFF.
Indoor unit power is not ON.
Automatic address setting has not
been completed.
Inter-unit control wiring is cut or is not connected correctly.
Indoor-outdoor inter-unit wiring is not connected correctly.
Indoor unit capacity is too low.
Indoor unit capacity is too high.
Indoor-outdoor unit type mismatch.
Indoor-outdoor units are not setting
correctly.
Reversed phase or open phase in the outdoor unit 3-phase power
E16
displayed
P05
displayed
L02
displayed
L13
displayed
L04
displayed
L07
displayed
04-393 DC INV Tech p 64-110 12/13/04 11:35 AM Page 75
Page 76
76
L
N
L
N 1 2
1
2
1
2
2
1
1 2
0
L N
L N
2
1
N
L
LN 12
Ground
Ground
Ground
Ground
Ground
Ground
Wireless remote controller
*
Connection to lead wire (white/black)
For group control (wiring locally supplied)
Wired remote
controller
white black
(Field
supply)
Outdoor unit
Inter-unit control wiring
Wall-
mounted
type
Indoor
unit No. 1
2P
(white)
Wall-
mounted
type
Indoor
unit No. 2
Wall-
mounted
type
Out­door
unit
Indoor
unit
4P
terminal
plate
Indoor
unit No. 3
Remote controller crossover wiring (Dia. 0.5 to 2 mm2)
Total length of wiring 200 m or less
Leakage breaker Leakage breaker
Leakage breaker
Leakage breaker
(Using a wired remote controller with a single-type system)
1. Wall-mounted units do not include a terminal plate for connecting a remote controller.
2. To connect the remote controller, remote controller cord is required.
Example: Using a wireless remote controller
with a simultaneous-operation multi system
System address (S2) (Setting at shipment:
0)
When using wall-mounted units in a simultaneous-operation multi system, connect the remote controller crossover wiring to the remote controller connector (2P) on the main unit, as shown in the diagram.
10-16. System Control
System control refers to connecting link wiring for control, for simultaneous-operation multi systems, group control, and main-sub remote controller control.
10-16-1. Basic wiring diagram 1
Single type and simultaneous-operation multi system
Simultaneous-operation multi system
Up to 4 (Double-Twin) indoor units can be connected to 1 outdoor unit for operation. (However, coordinate the outdoor unit capacity and the total capacity of the indoor units.) (It is not possible to connect individual remote controllers for independent operation.)
Be careful to avoid miswiring when connecting the wiring. (Miswiring will damage the units.)
(Wiring procedure)
(1) Set the No. 1 wall-mounted indoor unit so that it can be operated by the wireless remote controller. (This is set
at the time of shipment.) On the indoor unit control PCBs, set the No. 2 and following wall-mounted units to the sub remote controller. (Refer to 10-16-5.)
(2) Connect the crossover wiring to the lead wires (white/black) which extend out from the remote controller connec-
tors of the No. 1 indoor unit and other wall-mounted indoor units (as shown in the basic wiring diagram 1 above). Connect the crossover wiring to 1 and 2 on the remote controller wiring terminal plate for units (4-way, ceiling­mounted, etc.) other than the No. 1 indoor unit.
(3) Connect the inter-unit control wiring to 1 and 2 on the No. 1 indoor unit terminal plate, and to 1 and 2 on the
outdoor unit terminal plate. Also connect the inter-unit control wiring between the indoor units.
(4) When the indoor and outdoor unit power is turned ON, automatic address setting is performed (when there is
only 1 outdoor unit or when the system address is 0).
Fig. 10-13
04-393 DC INV Tech p 64-110 12/13/04 11:35 AM Page 76
Page 77
77
* If the system address is 0, automatic address setting is performed when the power is turned ON (in the case
shown in basic wiring diagram 1). This requires approximately 4 – 5 minutes (when the outdoor / indoor unit ratio is 1:1 as shown in basic wiring diagram 1). During automatic address setting, LED 1 and 2 on the outdoor unit control PCB blink alternately. These LEDs turn OFF when automatic address setting is completed.
10-16-2. Basic wiring diagram 2
Group control (when a central control device is not used)
A maximum of 8 indoor units can be connected to a single remote controller.
Example: In a refrigerant system where 2 or 3 indoor units are connected to 1 outdoor unit, set the new system
address (refrigerant system address) before turning ON the remote power switch. (Refer to 10-15-3.) (Set using the system address black rotary switch on the outdoor unit control PCB.)
NOTE
1
2
2
1
1
2
L N
1
2
U2
U1
L N
1 2
U2
U1
L
N
N
L
1
2
N
L
1 2
U2
U1
L
N
1 2
U2
U1
L N
Leakage breaker
Leakage breaker
Leakage breaker
Leakage breaker
Outdoor unit
Indoor
unit
Indoor
unit
Indoor
unit
Indoor
unit
Indoor
unit
Outdoor unit
Ground Ground
GroundGround
GroundGround
Ground
System address rotary switch (Change the setting to 1.)
System address rotary switch (Change the setting to 2.)
Indoor power crossover wiring – up to 16 units (no-heater units only)
Inter-unit control wiring
No. 1
No. 2 No. 3 No. 4 No. 5
Remote controller crossover wiring for group control (field-supply wiring)
Up to 8 units can be set for group control
Connection to lead wires (Black / White)
Wall-mounted
type
(Thickness 0.5 – 2.0 mm2, total length 200 m or less)
1. Wall-mounted units do not include a terminal plate for connecting a remote controller.
2. For group control of wall-mounted units, connect the remote controller crossover wiring to the remote controller connector (2P) on the main unit, as shown in the diagram.
Fig. 10-14
(Wiring procedure)
(1) Set the No. 1 wall-mounted indoor unit so that it can be operated by the wireless remote controller. (This is set
at the time of shipment.) On the indoor unit control PCBs, set the No. 2 and following wall-mounted units to the sub remote controller. (Refer to Item 10-16-5.)
(2) Connect the crossover wiring to 1 and 2 on the remote controller wiring terminal plates of the No. 1 indoor unit
and the other indoor units (as shown in the basic wiring diagram 2 above).
04-393 DC INV Tech p 64-110 12/13/04 11:35 AM Page 77
Page 78
78
(3) Connect the inter-unit control wiring to 1 and 2 on the No. 1 indoor unit terminal plate, and to 1 and 2 on the
outdoor unit terminal plate. Connect the wiring in the same way from the other outdoor units to U1 and U2 on the indoor units terminal plates (different refrigerant system).
(4) Perform automatic address setting from the outdoor unit. (For the automatic address setting procedure, refer to
10-16-4.)
* Models with auxiliary heaters cannot be used for crossover wiring of the indoor unit power wires. (Use a pull
box to divide the wiring.)
* Be sure to use the indoor unit temperature sensor (body sensor) when using this control. (Status at shipment)
NOTE
10-16-3. Setting the outdoor unit system addresses
For basic wiring diagram 2 (Set the system addresses: 1, 2,...)
System address No.
System address 10s digit
(2P DIP switch)
System address 1s place
(Rotary switch)
0 Automatic address
(Setting at shipment = 0)
1 (If outdoor unit is No. 1)
0 setting
Both OFF
Both OFF
Both OFF
10s digit ON
20s digit ON
10s digit and 20s digit ON
1 setting
2 setting
1 setting
1 setting
0 setting
2 (If outdoor unit is No. 2)
11 (If outdoor unit is No. 11)
21 (If outdoor unit is No. 21)
30
(If outdoor unit is No. 30)
ON
ON
OFF
1 2
ON
ON
OFF
1 2
ON
ON
OFF
1 2
ON
ON
OFF
1 2
ON
ON
OFF
1 2
ON
ON
OFF
1 2
ON
1
2
0
System address rotary switch (Set to 0 at time of shipment)
System address rotary switch
System address
DIP switch
OFF
ON
10s 20s
3 ~ 5H P
Outdoor unit control PCB
Fig. 10-15
System address rotary switch
System address 10s digit and 20s digit
DIP switch
Automatic address button (black)
Terminal plug (black)
04-393 DC INV Tech p 64-110 12/13/04 11:35 AM Page 78
Page 79
79
10-16-4. Automatic address setting from the outdoor unit
When there are multiple outdoor units as shown in basic wiring diagram 2
If the power can be turned ON separately for the indoor and outdoor units in each system (indoor unit addresses
can be set without operating the compressor):
(1) Turn ON the indoor and outdoor unit power for refrigerant system 1.
Press and hold the automatic address setting button (black) for 1 second or longer at the outdoor unit where the power was turned ON.
Communication for automatic address setting begins. LED 1 and 2 on the outdoor unit control PCB blink alter­nately, and turn OFF when address setting is completed.
<Approximately 4 – 5 minutes are required.>
(2) Next, turn ON the power only at the indoor and outdoor units in a different system. Press the automatic address
setting button (black) on the outdoor unit.
LED 1 and 2 on the outdoor unit control PCB blink alternately, and turn OFF when address setting is completed. Repeat the same procedure for each system and complete automatic address setting.
(3) Operation using the remote controller is now possible.
10-16-5. Indoor unit remote controller main-sub setting
When multiple wall-mounted indoor units are installed for group control in a simultaneous-operation multi sys-
tem, set the control PCB at the No. 2 and following wall-mounted units to Sub remote control. If a wired remote controller is used, set the wired remote controller to Sub. If 2 wireless remote controllers are used, set the wireless PCB (DIP switch) on the second remote controller to Sub.
10-16-6. Indoor unit address setting
If multiple single-type units are installed in the same room, the addresses can be set to prevent signal interfer-
ence. By coordinating the numbers of the indoor unit (wireless PCB) and remote controller addresses, up to 6 indoor units can be controlled independently by their respective remote controllers. Independent control is not possible when a simultaneous-operation multi system is used.
Checking the addresses
Press the remote controller address button to display the current address on the remote controller display. If this address matches the indoor unit (wireless PCB) address, the buzzer will sound. (If ALL is set, the buzzer will always sound.) If ALL is set, operation is possible regardless of the indoor unit address. Point the remote controller toward the receiver (indoor unit) that you wish to operate, and send the operation sig­nal.
Remote controller address setting
Press and hold the address button for 4 seconds or longer to display the address on the remote controller dis­play. The current address appears blinking. The address changes each time the remote controller address button is pressed: ALL 1 2 3 ... 6. Set the address to match the remote controller you wish to operate. When the SET button is pressed, the address stops blinking and is displayed for 5 seconds. The buzzer sounds if the address matches the indoor unit.
04-393 DC INV Tech p 64-110 12/13/04 11:35 AM Page 79
Page 80
80
12312312 3123
6 5 4 ON 3 2 1 OFF
ON
123
ON
ONONON
6 5 4 ON 3 2 1 OFF
6 5 4 ON 3 2 1 OFF
6 5 4 ON 3 2 1 OFF
Address
Address
Address
Address
Address
ALL 1 2 6
Address Address Address
Indoor unit control PCB
2 HP
Indoor unit control PCB
3 HP
DIP switch
Address switch
(SW101)
(SW102)
DIP switch
Address switch
(SW101)
(SW102)
Remote controller address display
Indoor unit PCB address, DIP switch
Main
Sub
Off
On
Address switch
Test
Remote controller
For address switches 1, 2, and 3, turn DIP switch 1 to OFF. For address switches 4, 5, and 6, turn DIP switch 1 to ON.
Fig. 10-16
04-393 DC INV Tech p 64-110 12/13/04 11:35 AM Page 80
Page 81
81
CAFP, SPAFP, DSAFP Type (for Link Wiring)
10-17. Caution
This unit may be used in a single-type refrigerant system where 1 outdoor unit is connected to 1 indoor unit, and also in a system where 1 outdoor unit is connected to multiple indoor units (maximum 4 < Double­Twin >).
This test run manual describes primarily the procedure when using the wired remote controller.
If link wiring is used, set the outdoor unit system address to allow the combination of indoor and outdoor units to
be identified. At the same time, indicate the indoor-outdoor unit combination number in a location where it can be checked easily (near the indoor unit nameplates). (This number will be required for subsequent maintenance. Refer to 10-22-2, 3, 4.)
Request that the customer be present when the test run is performed. At this time, explain the operation manual
and have the customer perform the actual steps.
Be sure to pass the manuals and warranty certificate to the customer.
Check that the AC 220 – 240 V wiring is not connected to the inter-unit control wiring connector terminal.
If AC 220 – 240 V is accidentally applied, the indoor or outdoor unit control PCB fuse (0.5 A for both indoor and outdoor units) will blow in order to protect the PCB. Correct the wiring connections, then disconnect the 2P con­nectors (indoor: blue, OC) (outdoor: blue, serial 1) that are connected to the PCB, and replace them with 2P connectors (indoor: brown, EMG) (outdoor: brown, serial 2). (Refer to the figure below.) If operation is still not possible after changing the brown connectors, try cutting the varistor (black) (both indoor and outdoor). (Be sure to turn the power OFF before performing this work.)
Indoor unit control PCB
Outdoor unit control PCB
Varistor (black)
Varistor (black)
Fuse 0.5A
SG41
Fuse
VA002
2P connector (brown)
2P connector (blue)
CHK (2P plug)
Serial 1 (blue) connector
0.5A
3 ~ 5 HP
Serial 2 (brown) connector
Fig. 10-17
04-393 DC INV Tech p 64-110 12/13/04 11:35 AM Page 81
Page 82
82
Fig. 10-18
Recheck the items to check before the test run.
Set the outdoor unit system address.
Set the remote controller to test run.
Turn ON the indoor and outdoor power.
Return the remote controller to normal control.
YES
YES
YES
NO
NO
NO
(See 10-22-3, 4)
( * )
(See 10-20)
(See 10-21)
(See 10-19)
(See 10-22-1)
Check the combination (wiring) of indoor and outdoor units.
Is system single-type?
Is outdoor unit multiple?
(See 10-22-2) How to Set the Outdoor Unit System Address
Set the automatic address setting from
outside unit or remote controller.
(See 10-22-1) How to Set Automatic Address
Can
operation be
started?
Refer to Table of Self-Diagnostic Functions to check the system. In addition, refer to Item 10-22 and correct any items that need to be corrected.
Note: Check the indoor-side drainage. (*) Required for simultaneous-operation multi systems and for group control.
Automatic Address
Automatic Address
Indicate (mark) the combination number.
Turn ON the indoor and outdoor power.
10-18. Test Run Procedure
04-393 DC INV Tech p 64-110 12/13/04 11:35 AM Page 82
Page 83
83
10-19. Items to Check Before the Test Run
(1) Turn the remote power switch ON at least 12 hours in advance in order to energize the crank case heater.
(2) Fully open the closed valves on the narrow-tube and wide-tube sides.
10-20. Test Run Using the Remote Controller
(1) Press and hold the remote controller button for 4 seconds or longer. Then press the button.
TEST appears in the LCD display during the test run.
Temperature control is not possible when test run mode is engaged.
(This mode places a large load on the devices. Use it only when performing the test run.)
(2) Use either Heating or Cooling mode to perform the test run.
Note: The outdoor unit will not operate for approximately 3 minutes after the power is turned ON or after it stops
operating.
(3) If normal operation is not possible, a code appears on the remote controller LCD display.
Refer to the Table of Self-Diagnostic Functions and Corrections on the next page, and correct the problem.
(4) After the test run is completed, press the button again. Check that TEST disappears from the LCD display.
(This remote controller includes a function that cancels test run mode after a 60-minute timer has elapsed, in order to prevent continuous test run operation.)
(5) For the test run of an inverter outdoor unit, operate the compressors for a minimum of 10 minutes (in order to
check for open phase). * When performing a test run using a wired remote controller, operation is possible without attaching the cas-
sette-type ceiling panel. (P09 will not be displayed.)
04-393 DC INV Tech p 64-110 12/13/04 11:35 AM Page 83
Page 84
84
Wired remote
controller display
Cause
Correction
Nothing is displayed
Nothing is displayed
Operation lamp is blinking.
Standby lamp is blinking.
Timer lamp and Standby lamp are blinking alternately.
Timer lamp and Standby lamp are blinking alternately.
Both the Operation lamp and Standby lamp are blinking together.
Indoor unit
receiver lamp
E02 displayed
E14 displayed
E04
displayed
E06
displayed
E15
displayed
Group connection and simultaneous-operation multi system
Remote controller is not connected with indoor unit correctly.
Indoor unit power is not ON.
Connect the remote controller correctly. Turn ON the indoor unit power.
Check the remote controller and inter-unit control wiring. Perform automatic address setting (10-22).
Connect the remote controller correctly.
Check the remote controller crossover wiring. Perform automatic address setting again.
Connect the wiring correctly.
E01 displayed
Automatic address setting has not been completed.
Inter-unit control wiring is cut or is not connected correctly.
Remote controller is not connected with indoor unit correctly.
Reversed phase or open phase in the 3-phase power at one of the outdoor units in the group.
Insufficient gas
Ceiling panel connector at one of the indoor units
in the group is not connected correctly.
DC fan trouble at one of the indoor units in the group.
Indoor-outdoor unit type mismatch.
Remote controller is not connected with indoor
unit correctly.
Remote controller crossover wiring is cut or is not connected correctly.
Indoor-outdoor inter-unit wiring is not connected correctly.
Refer to 10-22-1. Basic wiring diagram, and make the correct setting.
Inter-unit control wiring is cut or is not connected correctly.
Check that the total capacities of the indoor and outdoor units are appropriate.
Connect the indoor unit ceiling panel connector correctly.
Check whether the fan holder is loose. Check the wiring between the DC fan and the PCB.
Check that the indoor and outdoor unit types are correct.
Remote controller crossover wiring is connected to the indoor unit, however it is set for individual operation.
Perform automatic address setting (10-22).
Check outdoor operation with separate maintanance-use remote controller.
Reverse 2 phases of the outdoor unit 3-phase power and connect them correctly.
Indoor unit capacity is too low.
E16
displayed
P05
displayed
P09
displayed
P12
displayed
L02 L13
displayed
L10
displayed
L07
displayed
Indoor unit capacity is too high.
10-21. Table of Self-Diagnostic Functions and Corrections CAFP, SPAFP, DSAFP, MAFP Type
04-393 DC INV Tech p 64-110 12/13/04 11:35 AM Page 84
Page 85
85
10-22. Automatic Address Setting
10-22-1. Basic wiring diagram
Link wiring
A terminal plug (black) is attached to each of the outdoor unit control PCBs. At only one outdoor unit, leave the
terminal plug short-circuit socket on the Yes side. At all the other outdoor units, change the socket (from Ye s to No).
A maximum of 8 indoor units can be connected to 1 remote controller for group control.
NOTE
3-1
3-2
1
1-1
1-2
2-1
2-2
2
3
2-3
3-3
3-4
Refrigerant system No. 1 Refrigerant system No. 2 Refrigerant system No. 3
(Change setting to 1)
(Change setting to 2) (Change setting to 3)
No. 1 No. 2 No. 3
Inter-unit control wiring
Inter-unit control wiring
Terminal plate 1, 2
Terminal plate 1, 2
Outdoor unit
Indoor unit
Remote controller
Remote controller crossover wirin
g
for group control
Remote controller Remote controller
Change the terminal plug (black) short­circuit socket
Change the terminal plug (black) short-circuit socket
System address rotary switch on the outdoor unit PCB
Automatic address setting from the outdoor unit CAFP, SPAFP, DSAFP type
Case 1
If the power can be turned ON separately for the indoor and outdoor units in each system, the indoor unit
addresses can be set without running the compressor.
(1) Turn on the indoor and outdoor unit power for refrigerant system 1.
Press and hold the automatic address setting button (black) for 1 second or longer at the outdoor unit where the power was turned ON.
Communication for automatic address setting begins.
LED 1 and 2 on the outdoor unit control PCB blink alternately, and turn OFF when address setting is completed.
<Approximately 4 – 5 minutes are required.>
(2) Next, turn ON the power only at the indoor and outdoor units in a different system. Press the automatic address
setting button (black) on the outdoor unit.
LED 1 and 2 on the outdoor unit control PCB blink alternately, and turn OFF when address setting is completed.
Repeat the same procedure for each system and complete automatic address setting.
(3) Operation using the remote controller is now possible.
Fig. 10-19
04-393 DC INV Tech p 64-110 12/13/04 11:35 AM Page 85
Page 86
86
Case 2
If the power cannot be turned ON separately for the indoor and outdoor units in each system:
The compressors must be run in order to automatically set the indoor unit addresses. Therefore perform this step after completing the refrigerant tubing work.
(1) Turn ON the power to the indoor and outdoor units in all refrigerant systems.
When setting addresses in cooling mode (2) Short-circuit the mode-change pin at the outdoor unit where automatic address setting will be performed. Then
press the automatic address setting button (black).
When setting addresses in heating mode (2) Press the automatic address setting button (black) at the outdoor unit where automatic address setting will be
performed.
(3) LED 1 and 2 blink alternately. The compressors begin running in Cooling (or Heating) mode. Communication for
automatic address setting begins, using the temperature changes at the indoor units.
<All indoor units are in operating status.>
Address setting is completed when the compressors stop and the LED indicators turn OFF. <Approximately 15 minutes is required for 1 system.> If address setting fails, LED 1 and 2 blink simultaneously and the alarm contents are displayed at the remote controller.
(4) After 1 system is completed, be sure to press the automatic address setting button (black) at the other outdoor
units to complete automatic address setting in the same way for each system.
(5) Operation using the remote controller is now possible.
Automatic address setting using the remote controller
Case 3
If the power can be turned ON separately for the indoor and outdoor units in each system (indoor unit addresses
can be set without running the compressor):
Individual system automatic address setting: Display item code A1.
(1) Press the remote controller timer time button and button simultaneously. (Hold for 4 seconds or longer.)
(2) Then press either the temperature setting or button.
(Confirm that the item code is A1.”)
(3) Use either the or button to select the outdoor unit to perform automatic address setting for. Then
press the button. (R.C.1 is displayed, and automatic address setting is performed for refrigerant system 1.) When automatic address setting for system 1 is completed, the units return to normal stopped status. <Approximately 4 – 5 minutes are required.>
During automatic address setting, SETTING blinks on the remote controller display. This display disappears when address setting is completed.
04-393 DC INV Tech p 64-110 12/13/04 11:35 AM Page 86
Page 87
87
Case 4
If the power cannot be turned ON separately for the indoor and outdoor units in each system:
(The compressors must be run in order to automatically set the indoor unit addresses. Therefore perform this step after completing the refrigerant tubing work.)
All-systems automatic address setting: Display item code AA.
(1) Press the remote controller timer time button and button simultaneously. (Hold for 4 seconds or longer.)
(2) Next press the button.
(Automatic address setting is performed in sequence for all outdoor units from No. 1 to No. 30. When automatic address setting is completed, the units return to normal stopped status.) <Approximately 15 minutes is required for each system.>
During automatic address setting, SETTING blinks on the remote controller display. This display disappears when address setting is completed.
Fig. 10-20
04-393 DC INV Tech p 64-110 12/13/04 11:35 AM Page 87
Page 88
88
Fig. 10-21
10-22-2. Setting outdoor unit system addresses
For the basic wiring diagram (Set the system addresses: 1, 2, 3...)
ON
1
2
0
System address rotary switch (Set to 0 at time of shipment)
System address rotary switch
System address
DIP switch
OFF
ON
10s 20s
Outdoor unit control PCB
3 ~ 5 HP
System address No.
System address 10s digit
(2P DIP switch)
System address 1s place
(Rotary switch)
0 Automatic address
(Setting at shipment = 0)
1 (If outdoor unit is No. 1)
0 setting
Both OFF
Both OFF
Both OFF
10s digit ON
20s digit ON
10s digit and 20s digit ON
1 setting
2 setting
1 setting
1 setting
0 setting
2 (If outdoor unit is No. 2)
11 (If outdoor unit is No. 11)
21 (If outdoor unit is No. 21)
30
(If outdoor unit is No. 30)
ON
ON
OFF
1 2
ON
ON
OFF
1 2
ON
ON
OFF
1 2
ON
ON
OFF
1 2
ON
ON
OFF
1 2
ON
ON
OFF
1 2
(black)
System address 10s digit and 20s digit DIP switch
Automatic address button (black)
Terminal plug
Mode change pin
System address rotary switch
04-393 DC INV Tech p 64-110 12/13/04 11:35 AM Page 88
Page 89
89
10-22-3. Checking indoor unit addresses
Use the remote controller to check the addresses of the indoor units. Press and hold the button and button for 4 seconds or longer (simple settings mode, ALL appears on the remote controller). Then press the but­ton and select the indoor address. (For the system addresses of the No. 1 outdoor unit, each time the button is pressed, the address changes as fol­lows: 1-1, 1-2, ... 1-1, ...) The indoor unit fan operates only at the selected indoor unit. Confirm the indoor unit address. (For the system addresses of the No. 2 outdoor unit, the displayed addresses are 2-1, 2-2, ...)
Press the button again to return to the normal remote controller mode.
10-22-4. Indicating (marking) the indoor and outdoor unit combination number
Indicate (mark) the number after automatic address setting is completed.
(1) So that the combination of each indoor unit can be easily checked when multiple units are installed, ensure that
the indoor and outdoor unit numbers correspond to the system address number on the outdoor unit control PCB, and use a magic marker or similar means which cannot be easily removed to indicate the numbers in an easily visible location on the indoor units (near the indoor unit nameplates).
Example: (Outdoor) 1 – (Indoor) 1, 2... (Outdoor) 2 – (Indoor) 1, 2...
(2) These numbers will be needed for maintenance. Be sure to indicate them.
Fig. 10-22
04-393 DC INV Tech p 64-110 12/13/04 11:35 AM Page 89
Page 90
90
MAFP Type (for Link Wiring)
10-23. Caution
This unit may be used in a single-type refrigerant system where 1 outdoor unit is connected to 1 indoor
unit, and also in a system where 1 outdoor unit is connected to multiple indoor units (maximum 4).
If link wiring is used, set the outdoor unit system address to allow the combination of indoor and outdoor units to
be identified. At the same time, indicate the indoor-outdoor unit combination number in a location where it can be checked easily (near the indoor unit nameplates). (This number will be required for subsequent maintenance. Refer to 10-26-3, 4.)
Request that the customer be present when the test run is performed. At this time, explain the operation manual
and have the customer perform the actual steps.
Be sure to pass the manuals and warranty certificate to the customer.
Check that the AC 220 – 240 V wiring is not connected to the inter-unit control wiring connector terminal.
If AC 220 – 240 V is accidentally applied, the indoor or outdoor unit control PCB fuse (0.5 A for both indoor and outdoor units) will blow in order to protect the PCB. Correct the wiring connections, then disconnect the 2P con­nectors (indoor: blue, OC) (outdoor: blue, serial 1) that are connected to the PCB, and replace them with 2P connectors (indoor: brown, EMG) (outdoor: brown, serial 2). (Refer to the figure below.) If operation is still not possible after changing the brown connectors, try cutting the varistor (black) (both indoor and outdoor). (Be sure to turn the power OFF before performing this work.)
2 HP
2P connector (blue)
2P connector (blue)
Fuse (0.5A)
Fuse (0.5A)
CHK (2P plug)
CHK (2P plug)
SW103
ON OFF TEST
SW103
TEST ON OFF
2P connector (brown)
2P connector (brown)
Varistor (black)
VA002
Varistor (black) VA002
Indoor unit control PCB
3 HP
Indoor unit control PCB
Fig. 10-23
Outdoor unit control PCB
Varistor (black)
Fuse
VA002
Serial 1 (blue) connector
0.5A
Terminal plug (black)
3 ~ 5 HP
Serial 2 (brown) connector
04-393 DC INV Tech p 64-110 12/13/04 11:35 AM Page 90
Page 91
91
10-24. Test Run Procedure
Recheck the items to check before the test run.
Indicate (mark) the combination number.
Set the outdoor unit system address.
(See 10-26-2) How to Set the Outdoor Unit System Address
Set the automatic address setting
from outside unit.
(See 10-26-1, 2) How to Set Automatic Address
Set the indoor unit control unit to TEST.
Turn ON the indoor and outdoor power.
Turn the power back ON to the indoor unit.
YES
NO
YES
NO
YES
NO
(See 10-26-3, 4)
(See 10-26-3)
(See 10-13)
(See 10-25)
(See 10-11)
(See 10-26-1)
Check the combination (wiring) of indoor and outdoor units.
Is system single-type?
(1 indoor unit is connected
to 1 outdoor unit)
Are multiple outdoor units used?
Can
operation be
started?
Refer to Table of Self-Diagnostic Functions to check the system. In addition, refer to Item 10-26 and correct any items that need to be corrected.
Note: Check the indoor-side drainage.
(Automatic Address)
Turn ON the indoor and outdoor power.
(Automatic Address)
Fig. 10-24
04-393 DC INV Tech p 64-110 12/13/04 11:35 AM Page 91
Page 92
92
Wired remote
controller display
Cause
Correction
Nothing is displayed
Nothing is displayed
Operation lamp is blinking.
Standby lamp is blinking.
Timer lamp and Standby lamp are blinking alternately.
Timer lamp and Standby lamp are blinking alternately.
Both the Operation lamp and Standby lamp are blinking together.
Indoor unit
receiver lamp
E02 displayed
E14 displayed
E04
displayed
E06
displayed
E15
displayed
Group connection and simultaneous-operation multi system
Remote controller is not connected with indoor unit correctly.
Indoor unit power is not ON.
Connect the remote controller correctly. Turn ON the indoor unit power.
Check the remote controller and inter-unit control wiring. Perform automatic address setting (10-22).
Connect the remote controller correctly.
Check the remote controller crossover wiring. Perform automatic address setting again.
Connect the wiring correctly.
E01 displayed
Automatic address setting has not been completed.
Inter-unit control wiring is cut or is not connected correctly.
Remote controller is not connected with indoor unit correctly.
Reversed phase or open phase in the 3-phase power at one of the outdoor units in the group.
Insufficient gas
Ceiling panel connector at one of the indoor units
in the group is not connected correctly.
DC fan trouble at one of the indoor units in the group.
Indoor-outdoor unit type mismatch.
Remote controller is not connected with indoor
unit correctly.
Remote controller crossover wiring is cut or is not connected correctly.
Indoor-outdoor inter-unit wiring is not connected correctly.
Refer to 10-22-1. Basic wiring diagram, and make the correct setting.
Inter-unit control wiring is cut or is not connected correctly.
Check that the total capacities of the indoor and outdoor units are appropriate.
Connect the indoor unit ceiling panel connector correctly.
Check whether the fan holder is loose. Check the wiring between the DC fan and the PCB.
Check that the indoor and outdoor unit types are correct.
Remote controller crossover wiring is connected to the indoor unit, however it is set for individual operation.
Perform automatic address setting (10-22).
Check outdoor operation with separate maintanance-use remote controller.
Reverse 2 phases of the outdoor unit 3-phase power and connect them correctly.
Indoor unit capacity is too low.
E16
displayed
P05
displayed
P09
displayed
P12
displayed
L02 L13
displayed
L10
displayed
L07
displayed
Indoor unit capacity is too high.
10-25. Table of Self-Diagnostic Functions and Corrections CAFP SPAFP, DSAFP MAFP Type
04-393 DC INV Tech p 64-110 12/13/04 11:35 AM Page 92
Page 93
93
3-1
3-2 3-3
1
1-1
1-2 1-3
2-1
2-2
2
3
System address 1
(Change setting to 1)
System address 2
(Change setting to 2) (Change setting to 3)
System address 3
No. 3No. 2No. 1
Outdoor unit
Inter-unit control wiring
Terminal plate 1, 2
Terminal plate 1, 2
Indoor unit
Change the terminal plug (black) short-circuit socket
Change the terminal plug (black) short-circuit socket
Inter-unit control wiring
Wired remote controller
Wireless remote controller
Wired remote controller
Remote controller crossover wiring for group control
Remote controller crossover wiring for group control
10-26. Automatic Address Setting
10-26-1. Basic wiring diagram
Link wiring
A terminal plug (black) is attached to each of the outdoor unit control PCBs. At only 1 outdoor unit, leave the ter-
minal plug short-circuit socket on the Yes side. At all the other outdoor units, change the socket (from Ye s toNo”).
A maximum of 8 indoor units can be connected to 1 remote controller for group control.
NOTE
* If wall-mounted type units are used for a simultaneous-operation multi system (group control), refer to 10-16. System Con-
trol (basic wiring diagrams and wiring procedures) on the reverse cover of this manual when wiring.
Fig. 10-25
04-393 DC INV Tech p 64-110 12/13/04 11:35 AM Page 93
Page 94
94
10-26-2. Setting the outdoor unit system addresses
For basic wiring diagram (Set the system addresses: 1, 2, 3...)
System address rotary switch
System address 10s digit and 20s digit
DIP switch
Automatic addresses button (black)
Terminal plug (black)
System address No.
System address 10s digit
(2P DIP switch)
System address 1s place
(Rotary switch)
0 Automatic address
(Setting at shipment = 0)
1 (If outdoor unit is No. 1)
0 setting
Both OFF
Both OFF
Both OFF
10s digit ON
20s digit ON
10s digit and 20s digit ON
1 setting
2 setting
1 setting
1 setting
0 setting
2 (If outdoor unit is No. 2)
11 (If outdoor unit is No. 11)
21 (If outdoor unit is No. 21)
30
(If outdoor unit is No. 30)
ON
ON
OFF
1 2
ON
ON
OFF
1 2
ON
ON
OFF
1 2
ON
ON
OFF
1 2
ON
ON
OFF
1 2
ON
ON
OFF
1 2
Fig. 10-26
ON
1
2
0
System address rotary switch (Set to 0 at time of shipment)
System address rotary switch
System address
DIP switch
OFF
ON
10s 20s
Outdoor unit control PCB
3 – 5 HP
04-393 DC INV Tech p 64-110 12/13/04 11:35 AM Page 94
Page 95
95
Case 1
If the power can be turned ON separately for the indoor and outdoor units in each system:
(The indoor unit addresses can be set without running the compressor.)
Automatic address setting from the outdoor unit (MAFP type)
(1) Turn on the indoor and outdoor unit power for refrigerant system 1.
Press and hold the automatic address setting button (black) for 1 second or longer at the outdoor unit where the power was turned ON. The compressor operates when the power is turned ON at a different outdoor unit.
Communication for automatic address setting begins.
LED 1 and 2 on the outdoor unit control PCB blink alternately, and turn OFF when address setting is completed.
<Approximately 4 – 5 minutes are required.>
(2) Next, turn ON the power only at the indoor and outdoor units in a different system. Press the automatic address
setting button (black) on the outdoor unit.
LED 1 and 2 on the outdoor unit control PCB blink alternately, and turn OFF when address setting is completed.
Repeat the same procedure for each system and complete automatic address setting.
(3) Operation using the remote controller is now possible.
Case 2
If the power cannot be turned ON separately for the indoor and outdoor units in each system:
The compressors must be run in order to automatically set the indoor unit addresses. Therefore perform this step after completing the refrigerant tubing work.
(1) Turn ON the power to the indoor and outdoor units in all refrigerant systems.
When setting addresses in cooling mode (2) Short-circuit the mode-change pin at the outdoor unit where automatic address setting will be performed. Then
press the automatic address setting button (black).
When setting addresses in heating mode (2) Press the automatic address setting button (black) at the outdoor unit where automatic address setting will be
performed.
(3) LED 1 and 2 blink alternately. The compressors begin running in cool (or heat) mode. Communication for auto-
matic address setting begins, using the temperature changes at the indoor units.
Address setting is completed when the compressors stop and the LED indicators turn OFF. <Approximately 15 minutes is required for 1 system.> If address setting fails, LED 1 and 2 blink simultaneously and the alarm contents are displayed at the remote controller.
(4) After 1 system is completed, be sure to press the automatic address setting button (black) at the other outdoor
units to complete automatic address setting in the same way for each system.
(5) Operation using the remote controller is now possible.
04-393 DC INV Tech p 64-110 12/13/04 11:35 AM Page 95
Page 96
96
10-26-3. Checking indoor unit addresses
Use the remote controller to check the addresses of the indoor units. Press and hold the button and button for 4 seconds or longer (simple settings mode, ALL appears on the remote controller). Then press the but­ton and select the indoor address. (For the system addresses of the No. 1 outdoor unit, each time the button is pressed, the address changes as fol­lows: 1-1, 1-2, ... 1-1, ...) The indoor unit fan operates only at the selected indoor unit. Confirm the indoor unit address. (For the system addresses of the No. 2 outdoor unit, the displayed addresses are 2-1, 2-2, ...)
Press the button again to return to the normal remote controller mode.
10-26-4. Indicating (marking) the indoor and outdoor unit combination number
Indicate (mark) the number after automatic address setting is completed.
(1) So that the combination of each indoor unit can be easily checked when multiple units are installed, ensure that
the indoor and outdoor unit numbers correspond to the system address number on the outdoor unit control PCB, and use a magic marker or similar means which cannot be easily removed to indicate the numbers in an easily visible location on the indoor units (near the indoor unit nameplates).
Example: (Outdoor) 1 – (Indoor) 1, 2... (Outdoor) 2 - (Indoor) 1, 2...
(2) These numbers will be needed for maintenance. Be sure to indicate them.
10-26-5. Setting a wired remote controller as a sub remote controller
Change the remote controller address connected on the reverse side of the remote controller switch PCB from the Main position to the Sub position.
Fig. 10-27
Fig. 10-28
TIMER TMNL.
RCU
TMNL.
RCU.ADR
RCU.Main
RCU.Sub
RCU.CK
To Service Technicians
To display the sensor temperature:
WARNING
To avoid an electric shock hazard, DO NOT touch any ter­minal on the Printed Cir­cuit Board with a metal rod, a screwdriver edge or bare hand when power is supplied.
Press both and buttons on the remote controller for more than 4 seconds together. Change the sensor address (CODE NO.) with / (SET TEMP) buttons. Select the UNIT NO. that you want to call with button. Press the button to finish service mode.
To display the trouble history: Press both and buttons on the remote controller for more than 4 seconds together. Change the alarm message: / (SET TEMP) buttons CODE NO.
Press the button to finish service mode.
On the remote controller, press + + at the same time for more than 4 seconds. Set CODE No. with / (SET TEMP) button.
Set DATA from to with / (TIMER) button. Press Finally, Press
(New) (Old)
Changing method for room temperature sensor (from Indoor unit to RCU)
1
2
3
4
Remote Controller (Sub)
Remote controller address connector
Remote Controller (Main)
Checking remote controller
04-393 DC INV Tech p 64-110 12/13/04 11:35 AM Page 96
Page 97
97
Installing the Remote Controller
If the remote controller is to be installed onto a wall or other surface for use, first place the remote controller in
the location where it will be installed and press (ON / OFF). Confirm that the signal-received sound occurs at the indoor unit and that the A/C begins operating.
Place in holder
Installation screws Truss tapping 4 x 16
Press
1
2
Installing the batteries
(1) Press on both sides of the remote controller cover
and slide it downwards to remove it.
(2) Insert 2 AAA alkaline batteries. (Pay attention to
the + and – directions.)
(3) Use an object with a sharp point to press the ACL
(ALL CLEAR) button, then reattach the cover. (Be sure to press the ACL (ALL CLEAR) button after replacing the batteries.)
Fig. 10-29
Fig. 10-30
To remove the remote controller, pull it towards you.
Precautions for remote controller installation
Before mounting the remote controller on the wall, place the unit at the mounting position, then turn on any fluo-
rescent lamps, press the ON/OFF button, and check that the air conditioner operates correctly.
When using the remote controller to detect the room temperature, observe the following precautions during instal­lation:
Avoid locations where the remote controller will be exposed to the direct path of air blown from the air conditioner.
Avoid locations where the remote controller will be exposed to direct sunlight.
Avoid locations where the remote controller will be exposed to direct heat sources.
04-393 DC INV Tech p 64-110 12/13/04 11:35 AM Page 97
Page 98
98
10-27. Caution for Pump Down
Pump down means refrigerant gas in the system is returned to the outdoor unit. Pump down is used when the unit is to be moved, or before servicing the refrigerant circuit.
CAUTION
This outdoor unit cannot col-
lect more than the rated refrig­erant amount as shown by the nameplate on the back.
If the amount of refrigerant is
more than that recommended, do not conduct pump down. In this case use another refriger­ant collecting system.
Important Information Concerning Pump Down
Observe the following items when using pump down operation to recover refrigerant.
(1) If the length of inter-unit tubing exceeds 30 m, pump down cannot be used to recover the refrigerant. (The overload
protection device may be activated.) In that case, use refrigerant recovery equipment to recover the refrigerant.
(2) Press and hold the Recover refrigerant button on the outdoor unit PCB for 1 second or longer.
During refrigerant recovery, LED 1 blinks and LED 2 is lit.
Close the liquid-side valve during refrigerant recovery. If the unit is operated for 10 minutes or longer with the
liquid-side valve open, operation will be stopped, although no alarm will be displayed on the remote con­troller. If this occurs, close the valve and restart operation.
(3) When the valve service port pressure is approximately 0.1 MPa, press the S005 (Refrigerant recovery) button again
to end refrigerant recovery.
In order to protect the compressor, do not continue operating to generate a negative pressure in the inter­unit tubing.
Auto address
The S005 (Refrigerant recovery) button is
located at the bottom right of the outdoor unit PCB, as shown in the figure at left.
Refrigerant
recovery
ON
ON
(S001)
IC001
(S005)
System address
(S002)
04-393 DC INV Tech p 64-110 12/13/04 11:35 AM Page 98
Page 99
99
CAFP
11. HOW TO INSTALL THE WIRELESS REMOTE CONTROLLER RECEIVER
K70D037Z for 4-Way Cassette (CAFP Type)
11-1. Installing the Receiver Unit
The only corner where the receiver unit can be installed is the one shown in Fig. 11-1. Therefore, consider the direction of the panel when it is installed on the indoor unit.
(1) Remove the intake grille.
(2) Remove the screws that fasten the adjustable cor-
ner cap, then slide the adjustable corner cap to the side to remove it. (Fig. 11-2)
(3) The square hole used for the panel wiring is filled
with packing (sponge material) used for insula­tion.* Remove the packing, then pass the wiring from the wireless receiver unit through the grill. Twist the wires together and use a cable fastener to fasten them and attach with a screw, then replace the packing in the hole as it was before. (Fig. 11-3)
* If this packing is not used, there is danger of con-
densation on the wiring. Be sure to replace the packing.
(4) After completing wiring as described in Wiring the
Receiver Unit on the next page, twist the wires together and use a cable fastener to fasten them, leaving a length of wiring that is long enough to permit removal of the adjustable corner cap. (Fig. 11-3)
(5) Install the receiver unit in the panel. At this time,
slide the receiver unit so that each of the 3 tabs fits into its respective hole. Take care that the wires are not pinched. (Fig. 11-4)
* Refer to the instruction manual provided with the
panel.
Do not twist the control wiring together with the
power wiring because this may cause a malfunc­tion.
Install a noise filter or take other appropriate action
if electrical noise affects the power supply circuit of the unit.
* For wiring and test run procedures, refer to Wiring
the Receiver Unit and Test Run.
NOTE
Indoor unit refrigerant tube side
Indoor unit drain tube side
Receiver unit installation position (Right side of electrical components box)
Indoor unit electrical components box
Fig. 11-1
Ceiling panel
screw
Adjustable corner cap
Adjustable corner cap
Fig. 11-2
Remove the packing, twist the wires together and fasten them with the cable fastener. Then replace the packing.
Fig. 11-3
Fig. 11-4
04-393 DC INV Tech p 64-110 12/13/04 11:35 AM Page 99
Page 100
100
CAFP
11-2. Accessories
11-3. Wiring the Receiver Unit
Connect the wire from the receiver unit to the
indoor unit remote controller terminal board. (The wire has no polarity.)
11-4. Precautions on Simultaneous Installation of
Wired Remote Controller and Wireless Remote Controller
By installing a wired remote controller, the wireless remote controller kit can permit dual remote control operation at the same time.
(Up to 2 units of remote controllers – a wireless kit and a wired unit – can be installed.)
Dual remote control operation can control 1 or multi­ple air conditioners using several remote controllers.
1 1
2
1
3 1
4
6
7
5
Fastening screw 4 × 12
Remote control unit
Remote control holder
Parts
Q'ty
Parts
Q'ty
AAA alkaline battery
Receiver unit
Tapping screw 4 × 16
Clamp
No.No.
2
2
1
1
2PWHT
CN001
WHT
BLK
Indoor unit
Receiver PCB
Remote controller
Terminal board
CAUTION
Be sure to determine the correct ter-
minal numbers on the indoor unit when wiring the remote controller. The remote controller will be dam­aged if high voltage (such as 220 – 240 VAC) is applied.
The wireless remote controller kit
components cannot be used for more than 1 indoor unit at a time. (However, separate receiver units may be used simultaneously.)
When a wireless remote controller
kit and a wired remote controller are used simultaneously, assign either the wireless remote controller or the wired remote controller as the sub remote controller unit.
Connection diagram
04-393 DC INV Tech p 64-110 12/13/04 11:35 AM Page 100
Loading...