Technibel CA 250 X5TA*, CA 360 X5TA*, CA 480 X5TA*, SPA 250 X5TA*, SPA 360 X5TA* Installation Manual

...
EG
I
F
37.4140.218.0
INSTALLATION MANUAL ¥ MANUALE DÕINSTALLAZIONE
MANUEL DÕINSTALLATION ¥ AUFSTELLUNGS-HANDBUCH
MANUAL DE INSTALACION ¥
GENNAIO 2000
Split system air conditioner ¥ Condizionatore d'aria split system
Climatiseurs split system ¥ Split-klimagerŠt
Acondicionador de aire de consola partida sistema split ¥
DIAIROYMENES MONADES KLIMATISMO
Y
CA 250 X5TA* CA 360 X5TA* CA 480 X5TA*
SPA 250 X5TA* SPA 360 X5TA* SPA 480 X5TA*
1
Dear User
Thank you for selecting this product and we welcome you to the growing family of
satisfied products owners.
Like all products, it has been designed carefully and manufactured under strict quality
control.
We firmly believe that our products will give full satisfaction to users through proper
operation and maintenance.
Please read this manual, and be sure to keep it handy for your reference.
MODEL COMBINATIONS
CONTENTS
SEMI-CONCEALED MODEL ÒCAÓ
COOLING ONLY VERSION
INDOOR UNIT OUTDOOR UNIT
CA 250 X5 GR 250 X5
GR 250 X7
CA 360 X5 GR 360 X7
CA 480 X5 GR 480 X7
CEILING-MOUNTED MODEL ÒSPAÓ
COOLING ONLY VERSION
INDOOR UNIT OUTDOOR UNIT
SPA 250 X5 GR 250 X5
GR 250 X7
SPA 360 X5 GR 360 X7
SPA 480 X5 GR 480 X7
Conbine indoor and outdoor units as listed above.
IMPORTANT Please Read Before Starting
1. GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3
1-1. Tools required for Installation (not supplied) 1-2. Accessories Supplied with Unit 1-3. Type of copper Tube and Insulation Material 1-4. Additional materials required for Installation 1-5. Tubing Lenght
2. INSTALLATION SITE SELECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 6
Indoor Unit Outdoor Unit
3. HOW TO INSTALL THE INDOOR UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 8
4-WAY AIR DISCHARGE SEMI-CONCEALED TYPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 8
3-1. Suspending the Indoor Unit 3-2. Preparation for Suspending 3-3. Burying Inside the Ceiling 3-4. Installing the Drain Piping 3-5. Checking the Drainage
CEILING-MOUNTED TYPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 10
3-6. Suspending the Indoor Unit 3-7. Duct for fresh air 3-8. Installing the drain piping
4. HOW TO INSTALL THE OUTDOOR UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 13
4-1. Removing the Protective Spacer for Transportation 4-2. Installing the Outdoor Unit 4-3. Tubing Direction
5. ELECTRICAL WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 14
5-1. General Precautions on Wiring 5-2. Recommended Wire Lenght and Wire Diameter for Power Supply System 5-3. Wiring System Diagrams 5-4. Examples of incorrect wiring 5-5. How to connect wiring to the terminal
EG
2
EG
6. HOW TO INSTALL THE REMOTE CONTROLLER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 17
6-1. Wireless Remote Control Unit
7. HOW TO PROCESS TUBING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 18
7-1. Connecting Tubing Sides 7-2. Connecting Tubing between Indoor and Outdoor Unit 7-3. Insulation of Refrigerant Tubing 7-4. Taping the Tubes 7-5. Finishing the Installation
8. AIR PURGING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 20
9. HOW TO INSTALL THE CEILING PANEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 21
4-WAY AIR DISCHARGE SEMI-CONCEALED TYPE page 21
9-1. Before Installing the Ceiling Panel 9-2. Installing the Ceiling Panel 9-3. When Removing the Ceiling Panel for Servicing
10. TEST RUN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 23
10-1. Preparing for Test Run 10-2. Performing Test Run for models with wireless control
11. PUMP DOWN. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 24
IMPORTANT
PLEASE READ BEFORE STARTING
This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficienly.
For safe installation and trouble-free operation, you must:
¥ Carefully read this instruction booklet before beginning.
¥ Follow each installation or repair step exactly as shown.
¥ Observe all local, state, and national electrical codes.
¥ Pay close attention to all warning and caution notices given in this manual.
3
EG
WARNING
¥ This symbol refers to
a hazard or unsafe practice which can resuklt in severe personal injury or death.
IN CASE OF IMPROPER INSTALLATION
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instruction in this document.
When Transporting
Be careful when pocking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.
When Installing
ÉIn a Room
Properly insulate any tubing run inside a room to prevent ÒsweatingÓ that can cause driping and water damage to walls and floors.
ÉIn Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration.
ÉIn an area with High Winds
Securely anchor the aoutdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
When Connecting Refrigerant Tubing
¥ Executive enough ventilation in case refrigerant gases leak
during operations. Be careful that the contact of the refrigerant gases with the flare will cause the generation of poisonous gases.
¥ Keep all tubing runs as short as possible.
¥ Use the flare method for connecting tubing.
¥ Apply refrigerant lubricant to the matching surfaces of the
flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak-free connection.
¥ Check carefully for leaks before starting the test run.
When Servicing
¥ Turn the power OFF at the main power box (mains) before
opening the unit to check or repair electrical parts and wiring.
¥ Keep your fingers and clothing away from any moving parts.
¥ Clean up the site after you finish, remembering to check
that no metal scraps or bits of wiring have been left inside the unit being serviced.
CAUTION
¥ This symbol refers to
a hazard or unsafe practice which can resuklt in personal injury or product or property damage.
SPECIAL PRECAUTION
1. GENERAL
¥ ELECTRICAL SHOCK CAN CAUSE SEVERE
PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
When Wiring
¥ Do not supply power to the unit until all wiring and tubing are
completed or reconnected and checked.
¥ Highly dangerous electrical voltage are used in this system.
Carefully refer to the wiring diagram and these instruction when wiring. Improper connections and inadequate grounding can cause accidentaly injury or death.
¥ Ground the unit following local electrical codes.
¥ Connect all witing tightly. Loose wiring may cause
overheating at connection points and a possible fire hazard.
This booklet briefly outlines where and how to install the air conditioning system. Please read over the entire set of instructions for the indoor and outdoor units and make sure all accessory parts listed are with the system before beginning.
1-1. Tools Required for Installation (not
supplied)
1. Standard screwdriver
2. Phillips head screwdriver
3. Knife or wire stripper
4. Tape measure
5. Level
6. Sabre saw or key hole saw
7. Hacksaw
8. Core bits
9. Hammer
10. Drill
11. Tube cutter
12. Tube flaring tool
13. Tourque wrench
14. Adjustable wrench
15. Reamer (for deburring)
1-2. Accessories Supplied with Unit
See Table 1-1 to 1-3.
Table Type
1-1 4-Way AirDischarge Semi-Concealed
1-2 Ceiling-Mounted
1-3. Type of Copper Tube and Insulation
Material
To purchase these material from a local source, you will need:
1. Deoxidized annealed copper tube for refrigerant tubing.
2. Foamed polyethylene insulation for 15.88 mm (5/8Ó) or
19.05 mm (3/4Ó) O.D. copper tubes as required to precise length of tubing. Wall thickness of the insulation should be not less than 8 mm.
3. Use insulated copper wire for field wiring. Wire size varies with the total length of witing. Refer to Section 5. Electrical Wiring for details.
4
EG
1-4. Additional Materials Required for
Installation
1. Refrigeration (armored) tape
2. Insulated staples or clamps for connecting wire (See your local codes.)
3. Putty
4. Refrigeration tubing lubricant
5. Clamps or saddles to secure refrigerant tubing
CAUTION
¥ Check local electrical
codes and regulations before obtainig wire. Also, check any specified instructions or limitations.
Part Name Figure QÕty Remarks
Full-scale installation diagram 1 For determinig suspension bolt pitch
Flare insulator 2 For wide and narrow tubes
Installation gauge 1 For adjusting the unit position
Insulating tape 1 For wide tube flare nuts
Hose band 2 For Securing drain hose
Packing 1 For drain joint
Dran insulator 1 For drain joint
Drain hose 1 For drain hose joint
Sealing putty 1 For sealing recessed portion of power supply
Table 1-1. 4-Way Air Discharge Semi-Concealed
Table 1-2. Ceiling-Mounted
(White-for insulating)
Part Name Figure QÕty Remarks
Special washer 4 For suspending indoor unit from ceiling
Drain insulator 1 For drain hose joint
Flare insulator 1 Set For drain narrow tube joints
Drain hose clamp
4 For drain hose joint
2 For rubbe cao (in case of using left side drain pipe)
Insulating tape 2 For wide flare joint
Vinyl clamp 8 For ends of flare insulator
Sealing insulator
1 For sealing top face
1 For sealing rear face
Full-scale installation diagram 1 For determining suspension bolt pitch
Sealing putty 1 For sealing recessed portion of power supply
OwnerÕs manual 1 Ð
Drain hose 1 For drain hose joint
White (heat-resisting)
T10
T3T5
5
EG
1-5. Tubing Length
¥ Refrigerant tubing between the indoor and outdoor
units shall be kept as short as possible
¥ The length of the refrigerant tubes between the
indoor and outdoor units are limited by the elevation difference between the two units. During tubing work, try to make both the tubing length (L) and the difference in elevation (H) as short as possible. Refer to Table 1-4 for the details.
Installation Example 1
INDOOR
UNIT
Tubing length (L)
OUTDOOR
UNIT
Elevation difference (H)
Table 1-4.
250 type
6.35 (1/4)
15.88 (5/8)
40
40
25
15
a) 25
2.4
Tubing size
Narrow tube mm(in.)
outer diameter
Wide tube mm (in.)
Limit of tubing length (m)
Outdoor unit is placed upper (m)
Limit of elevation difference between the two units
Outdoor unit is placed lower (m)
Max. allowable tubing length at shipment (m)
Required additional refrigerant*
1
(g/m)
Refrigerant charged at shipment (kg)
360 type
9.52 (3/8)
19.05 (3/4)
50
50
30
15
b) 80
4.0
480 type
9.52 (3/8)
19.05 (3/4)
50
50
30
15
b) 80
4.3
Models
Tubing Data
No additional charge of compressor oil is necessary. *1 If total tubing length becomes a) 15 to 40 b) 15 to 50 (max), charge additional refrigerant (R22) by a) 25 or b) 80 g/m.
Table 1-3 Accessories for the Wireless
Remote Control Unit
6
EG
2. INSTALLATION SITE SELECTION
AVOID:
¥ ares where leakage of flammable gas may be expected.
¥ places where large amounts of oil mist exist.
¥ direct sunlight.
¥ location where nearby heat sources may affect performance
of the unit.
¥ locations where nearby external air may enter the room
directly. This may cause ÒsweatingÓ in the air discharge ports, causing them to spray or drip.
¥ location where the remote controller will be splashed with
water or affected by dampness or humidity.
¥ installing the remote controller behind curtains or furniture.
DO:
¥ select an appropiate position from which every corner of the
room can be uniformly cooled.
¥ select a location where the ceiling is strong enough to support
the weight of the unit.
¥ select a location where tubing and drain pipe have the
shortest run to the outside.
¥ allow room for operation and maintenance as well as
unrestricted ai flow around the unit.
¥ install the unit within the maximum elevation difference (H)
above or below the outdoor unit and within a total tubing length (L) from the outdoor unit as detailed in table 1-4.
¥ allow room for mounting the remote controller about 1 moff
the floor, in an area that is not in direct sunlight nor in the flow of cool air from the indoor unit.
INDOOR UNIT
NOTE
Air delivery will be degraded if the distance from the floor to the ceiling is greater than 3 m.
Ceiling-Mounted Type 4-Way Semi-Concealed Type
Ceiling
Wall
25 cm min.
Air discharge
Side view
Air intake
30 cm min.
25 cm min.
NOTE
The rear of the indoor unit can be installed flush against the wall.
Front view
1 m
1 m
1 m
1 m
1 m
7
EG
Min. 1 m Min. 1 m Min. 1 m Min. 1 m
Min. 20 cm
Min. 35 cm
Min. 35 cm
Min. 30 cm
Min. 30 cm
Air discharge chamber
Min. 1.5 m
Min. 30 cm
Min. 35 m
Min. 20 cm
In case of multiple installations
Unit spacing if air discharge chamber is not used. Unit spacing when air dscharge chamber is used.
* If you would like to make the separation smaller on the air discharge side, use an air discharge chamber. * Your can install any number of units side-by-side.
* Only up to 3 units can be install side-by-side under the above conditions. the next group must be spaced at least 30 cm away from the first group.
AVOID:
¥ heat source, exhaust fans, etc. (Fig. 2-1).
¥ damp, humid or uneven locations.
DO:
¥ choose a place as cool as possible.
¥ choose a place that well ventilated and autside air
temperature does not exceed maximum 45 ¡c constantly.
¥ allow enough room around the unit for air intake/exhaust
and possible maintenance. (Fig. 2-2).
¥ provide a solid base; about 15 cm above ground level to
reduce humidity and possible water damage in unit and drecrease service life. (Fig. 2-3).
¥ use lug bolts or equal to bolt down unit, reducing vibration
and noise.
OUTDOOR UNIT
Air in
Air in
Min. 15 cm
Air discharge
Anchor bolts (4 pieces)
Model Min. (cm)
250 type 10
360, 480 type 20
Fig. 2-3
Hot air
Out­door unit
Exhaust fan
Heat sorce
Fig. 2-1
Fig. 2-2
Min. 1 cm
Min. 1 cm
Min. 2 m
Ground
Min. 2 m
Obstacle
Air dis­charge
Min. 50 cm
Obstacle above
Table 2-1 Dimension
A
8
4-WAY AIR DISCHARGE SEMI-CONCEALED TYPE
EG
3-1. Suspending the Indoor Unit
This unit uses a drain pump. Use a carpenterÕs level to chack that the unit is level.
3-2. Preparation for Suspending
(1) Fix the suspension bolts securely in the ceiling using
the method shown in the drawings (Figs. 3-1 / 3-2 / 3-3), by attaching them to the ceiling support structure, or by any other method that insures that the unit will be securely and safely suspended.
(2) Follow Fig. 3-2 and Table 3-1 to make the holes in the
ceiling.
3-3. Burying inside the Ceiling
(1) When placing the unit inside the ceiling, determine the
pitch of the suspension bolts using the provided full­scale installation diagram. (Fig. 3-4).
Tubing and wiring must be laid inside the ceiling when suspending the unit. If the ceiling is already constructed, lay the tubing and wiring into positiion for connection to the unit before placing the unit inside the ceiling.
(2) The length of suspension bolt must be so that the
distance between the botton of the bolt and the botton of the ceiling is more than 60 mm as shown in Fig. 3-4.
(3) Thread the 2 hexagonal nuts and washers (field supply)
onto the 4 suspension bolts as shown in Fig. 3-5. Use 2 sets of nuts and washers (upper and lower), so
that the unit with not fall off the suspension lugs.
(4) Remove the protective cardboard used to protect the
fan parts during transport.
(5) Adjust the distance between the unit and surface of
the ceiling (48 mm) using the supplied installation gauge. (Fig. 3-4).
Model A B
250 type 820 730
360, 480 type 1110 1020
3) Determine the pitch of the suspension bolts using the provided full-scale installation diagram. The diagram and table (Fig. 3-3 and Table 3-3) show the relationship between the position of the suspension fitting, the unit, and the panel.
Model ABCDE
250 type 150 200 255 298 125
360, 480 type 165 235 285 328 125
Hole-in-anchor Hole-in-plug
Concrete
Insert
Suspension bolt (M10 or 3/8ÕÕ) (field supply)
A (ceiling opening dimension)
B (suspension bolt itch)
Electrical component box
Refrigerant tubing side
Drain hose side
Refrigerant tubing joint (narrow tube side)
Refrigerant tubing joint (wide tube side)
Drain inspection port
Suspension lug
Power supply inlet
Unit: mm
820 (ceiling opening dimension)
590 (suspension bolt pitch)
Fig. 3-1
Fig. 3-3
Fig. 3-2
Full-scale installation drawiong
(provided)
Nuts and washers
(2 sets)
Suspension bolt
Suspension lug
Uppper
Lower
More than 60 mm
48 mm
Fig. 3-4
Fig. 3-5
3. HOW TO INSTALL THE INDOOR UNIT
Table 3-1
Table 3-2
Unit: mm
Unit: mm
9
EG
Fig. 3-15
CAUTION
¥ Do not install an air bleeder, as this may cause water
to spray from the drain tube outlet. (Fig. 3-9)
¥ If it is neccesary to increase the height of the drain
pipe somewhat, the portion directly after the connection port can be raised a maximum of 25 cm. Do not raise it any higher than 25 cm, as this could reasult in water leaks. (Fig. 3-10)
¥ Do not install pipe with an upward gradient from the
connection port. It will cause the drain water to flow backwards and leak when the unit is stopped. (Fig. 3-11)
¥ Do not apply force to the piping on the unit side when
connecting the drain pipe. The pipe should not be allowed to hang unsupported from its connection to the unit. Fasten the pipe to a wall, frame, or other support as close to the unit as possible. (Fig. 3-12)
¥ Be sure to provide insulation for any drain piping
installed indoors.
30 cm or less (as short as possible)
25 cm or less
Upward gradient
Support
pieces
Fig. 3-10
Fig. 3-11
Fig. 3-12
3-4. Installing the Drain Piping
(1) Prepare a standard hard (PVC) pipe (O.D. 32 mm) for
the drain and use the accessory drain hose and hose band to prevent water leaks.
The PVC pipe must be purchase separately. The transparent part allows you to check drainage.
(Fig. 3-6).
Transparent part for checking drainage
Hose band (supplied)
Hard PVC pipe pipe (not supplied)
Drain hose (supplied)
Packing (supplied)
CAUTION
¥ Tighten the hose band firmly after the supplied drain
hose has been inserted to touch the ends of both of the connection pipes, as shown in Fig. 3-7.
¥ Do not use an adhesive when connecting the supplied
hose. Reasons:
1. It may cause water to leak from the connection. Sin­ce the connection is slippery just after the adhesive has been applied, the pipes easily slip off.
2. The pipes cannot be removed when maintenaces is needed.
¥ Do not bend the supplied drain hose 90¡ or more. The
hose may slip off.
¥ Align the hose bands with the ends of the hoses. Ti-
ghten the hose bands firmly. PLease make sure that the stopper is not covered by the hose band, as shown in Fig. 3-7.
CAUTION
¥ Tighten the hose clamps so their locking nuts face
upward (Fig. 3-6).
(2) After checking the drainage, wrap the supplied packing
and drain pipe insulator around the pipe. (Fig. 3-8.)
NOTE
Make sure the drain pipe has a downward gradient (1/100 or more) and that there are no water traps.
Fig. 3-6
Fig. 3-7
Drain insulator (supplied)
Air bleeder
Fig. 3-8
Fig. 3-9
Stopper
Hose band
Supplied drain hose
Drain pipe (not supplied)
Connection pipe
Hose band
Align the hose band with the end of the pipe
Align the hose band with the end of the pipe
10
EG
3-5. Checking the Drainage
After wiring and piping are completed, use the following procedure to check that the water will drain smoothly. For this, prepare a bucket and wiping cloth to catch and wipe up spilled water.
(1) Connect power to the power terminal board (L, N terminal) inside the electrical component box. (2) Remove the tube cover and through the opening, slowly pour about 1,200 cc of water into the drain pan to check drainage. (3) Do Test Run to check the drainage after completing installation. When performing Test Run, be sure to observe the Test Run
procedure. Refer to page 26.
CAUTION
¥ Be careful since the
fan will start when you short the pin on the in­door control board.
(4) After drain checking is finished, return the Operation
Selector switch to the Run position (ON position*) and remount the tube cover.
CAUTION
¥ To mount the tube co-
ver, use 4 x 8 tapping screws. Do not use long screws as they may puncture the drain pan and cause water leakage.
4 x 8 mm tapping screw
Tube cover
Front face
Rear
Full-scale diagram
Hole-in-anchor Hole-in-plug
Concrete
Insert
Suspension bolt (M10 or 3/8ÕÕ) (field supply)
Ceiling tiles
Ceiling support
A
A
Fig. 3-13
CEILING-MOUNTED TYPE
3-6. Suspending the Indoor Unit
(1) Place the full-scale diagram (supplied) on the ceiling
at the spot where you want to install the indoor unit. Use a pencil to mark the drill holes. (Fig. 3-14).
NOTE
Since the diagram is made of paper, it may shrink or stretch slightly because of high temperature or humidity. For this reason, before drilling the holes maintain the correct dimensions between the markings.
(2) Drill holes at the 4 points indicated on the fullscale
diagram.
(3) Depending on the ceiling type:
a) Insert suspension bolts as shown in Fig. 3-15.
or
b) Use existing ceiling supports or construct a suitable
support as shown in Fig. 3-16.
WARNING
¥ It is important that you use extreme care in supporting
the indoor unit from the ceiling. Ensure that the ceiling is strong enough to support the weight of the unit. Before hanging the ceiling unit, test the strength of each attached suspension bolt.
Fig. 3-14
Fig. 3-15
Fig. 3-16
unit
Fixture
Ceiling surface
Within
50 mm
Fig. 3-17
11
EG
Pul out the Air­Intake grille pushing claws of the hinges
Hinge
Screw
Latch
Air-intake grille
Suspension bolt (field supply)
Ceiling surface
Washer (supplied)
Double nut (field supply)
Fixture
unit
Slide toward front side
Sode panel
Ceiling
surface
Nut (field supply)
Suspension bolt
Washer
(supplied)
Approx.
25 mm
Slide
Fig. 3-18
Suspension bolt (field supply)
Washer (supplied)
Washer (field supply)
Double nut (field supply)
unit
Fig. 3-19
Fig. 3-20
Fig. 3-21
Fig. 3-22
Fig. 3-23
Fig. 3-24
(b) Lift the indoor unit, and place it on the washer throught the notches, so as to fix it in place.(Fig. 3-23)
(c) Tighten the two hexagonal nuts on each suspension bolt to suspend the indoor unit as shown in Fig. 3-24.
NOTE
A ceiling surface is not always level. Please confirm that the indoor unit is evenly suspended. For the installation to be correct, leave aclearance of about 10 mm between the ceiling panel and the ceiling surface and fill the gap with an appropriate insulation or filler material.
(8) If the tubing and wiring have to pass towards the rear
of the unit, make holes in the wall. (Fig. 3-25)
(9) Measure the thickness of the wall from the inside to
the outside and cut PVC pipe at a slight angle to fit. Insert the PVC pipe in the wall. (Fig. 3-26)
NOTE
The hole should be made at a slight downxard slant to the outside.
(4) Screw in the suspensions bolts, allowing them to
protrude from the ceiling as shown in Fig. 3-16. The distance od each exposed bolt must be of equal length within 50 mm. (Fig. 3-17)
(5) Before suspending the indoor unit; remove the 2 or 3
screws on the latch of the air-intake grilles, open the grilles, and remove them by pushing the claws of the hinges as shown in Fig. 3-18. Then remove both side panels sliding them along the unit toward the front after removing the two screws which fix them. (Fig. 3-19).
(6) Preparation for suspending the indoor unit. The
suspension method varies depending on whether the unit is next to the ceiling or not. (Fig. 3-20 and 3-21).
(7) Suspend the indoor unit as follows.
(a) mount a washer and two hexagonal nuts on each suspension bolt as shown in Fig. 3-22.
12
3-7. Duct for Fresh Air
There is a duct connection port (knock-out hole) at the right­rear on the Panle Top of the indoor unit for drawing in fresh air. If it is necessary to draw in fresh air, remove the cover by knocking out and connect the duct to the idoor unit throught the connection port. (Fig. 3-27)
If connection at the right-rear on the Panel Top is not appropriate, another duct connection port can be made by cutting an opening on the left side of the Rear Panel of the indoor unit as shown in Fig. 3-28.
3-8. Installing the Drain Piping
¥ Prepare a standar PVC pipe for the drain and connect it to
the indoor unit drain pipe with the supplied hose clamps to prevent water leaks.
CAUTION
¥ Tighten the drain pipe clamps so that the locking nuts
are facing upwards. (If tightened with the locking nuts facing downwards, it may cause water leakage).
¥ Do not use an adhesive when connecting the drain
hose (supplied) to the drain connection (main unit, PVC pipe).
¥ Connect the drain piping so that it slopes downward from
the unit to the outside. (Fig. 3-29) ¥ Never allow traps to occur in the course of the piping. ¥ Insulate any piping inside the room to prevent dripping. ¥ Use the supplied drain pipe to connect the drain pipe with the
drain outlet of the indoor unit. ¥ After connecting the drain pipe securely, wrap the supplied
drain pipe insulator around the pipe, seal the gap at the drain
socket with the supplied black insulation tape, then secure
it wit clamps. (Fig. 3-30) ¥ After the drain piping, pour water into the drain pan to check
that the water drains smoothly.
CAUTION
¥ Check local electrical
codes and regulations before obtaining wire. Also, check any spe­cified instruction or li­mitations.
Duct connection port (Knock-out hole)
Panel Top
Right side
Right side
Cut this portion
Fig. 3-27
Fig. 3-28
Fig. 3-29
Fig. 3-30
ABC
250 110 100 100
110 100 150
360
480
Min. 1/100
Good
Not good
Drain hose (supplied)
Drain pipe camp (supplied)
Hard PVC pipe (not supplied)
Vinyl clamp (supplied)
Packing (supplied)
EG
Fig. 3-25
Fig. 3-26
Indoor side
Outdoor side
PVC pipe (localy purchased)
INSIDE OUTSIDE
PVC pipe
Slight angle
Cut at slight angle
Wall
13
4-1. Removing the Protective Spacer for
Transportation
Remove the packing skid from the botton of unit and then remove the plastic spacer used to secure the compressor during transportation (Fig. 4-1).
Place the unit on a level concrete pad, block or equal and anchor.
Refer to Section 2. ÒInstallation Site SelectionÓ.
4-2. Installing the Outdoor Unit
(1) Install blocks or a solid platform under the outdoor unit
which provides a minimum height of 15 cm from ground level. (Fig. 4-2)
(2) The outdoor unit must be bolted down tightly to the
blocks or platform with 4 anchor bolts.
4-3. Tubing Direction
¥ Tubing can be extended in 4 different directions as shown
in Fig. 4-3. ¥ Service valves are housed inside the unit. To access them,
remove the access panel by removing the 2 attaching screws
then slide the panel downward and pull it toward you.
If either rear, right, or front tubing is needed, punch out the
knockout hole with a hammer or similar tool. ¥ After punching out the Knockout holes, mount accessory
rubber bushings or plastic protector on the tubing outlets.
These accessories are packed inside the unit and can be
accessed through the access panel. ¥ Use tube benders to extend internal tubing to the outside.
4. HOW TO INSTALL THE OUTDOOR UNIT
Compressor
Plastic spacer
Anchor bolts (not supplied)
Inter-unit wiring outlets
Rear
power supply wiring outlets
Right
Down
Tubing outlets
Front
Access panel
Height: min: 15 cm
Packing skid
Fig. 4-1
Fig. 4-2
Fig. 4-3
GB
14
EG
5-1. General Precautions on Wiring
(1) Before wiring, confirm the rated voltage of the unit as
shown on its nameplate, then carry out the wiring closely following the wiring diagram.
(2) Provide a power outlet to be used exclusively for
each unit, and a power supply disconnect and circuit breaker for overcurrent protection should be provided in the exclusive line.
(3) To prevent possible hazard due to insulation failure,
the unit must be grounded.
(4) Each wiring connection must be done in accordance
with the wiring system diagram. Wrong wiring may cause the unit to misoperate or become damaged.
(5) Do not allow wiring to touch the refrigerant tubing
compressor, or any moving ports of the fan.
(6) Unauthorized changes in the internal wiring can be
very dangerous. The manufacturer will accept no responsibility for any damage or misoperation that occurs as a result of such unauthorized changes.
5. ELECTRICAL WIRING
(7) If the respective phases of the 3-phase power
wiring are not connected correctly, a reverse phase will occur and the compressor will not start running. If this happens, swap over 2 of the 3 phases (L1, L2 and L3).
You must insure that installation complies with all relevant rules and regulations.
(8) To prevent malfunction of the air conditioner caused by
electrical noise, care must be taken when wiring as follows:
¥ The inter-unit control wiring should be wired apart
from the inter-unit power wiring.
¥ It is recommended that shielded wires or twisted
pair wires be used for the inter-unit control wiring if the air conditioner is installed where it is exposed to the influence of electrical and/or electro-magnetic noise.
5-2. Recommended Wire Lenght and Wire Diameter for Power Supply System
Type
(A) Power Supply (B) Inter-unit wiring Power Supply Terminal Base
250 type (3 phase) 101 m 40 m 15 A 25 A 5.5 mm
2
360 type (3 phase) 91 m 50 m 15 A 25 A 5.5 mm
2
480 type (3 phase) 57 m 50 m 25 A 25 A 5.5 mm
2
250 type (1 phase) 14 m 40 m 40 A 50 A 14 mm
2
4 mm
2
2.5 mm
2
Capacity Max. Wire
Diameter
Time Delay Fuse or Circuit Capacity
NOTE
(1) Refer to the Wiring System Diagrams (See next page)
for the meaning of A and B in the above tables.
(2) For accordance with conformity of EC Directive No.
89/336/EEC, supply connection at the time of installtion work it should be consider guidance showing below.
¥ Do not share a common installation group with other
equipment.
¥ Be sure that supply network impedance is sufficiently
low (
ZSYS
R).
It may be necessary to consult the power supply authority before connection of the air conditioner to a low-voltage public network.
³
Models R Remarks
250 type (3 phase) Ð Care is not needed
360 type (3 phase) 0.270 confortms to the local code
480 type (3 phase) 0.122 Ditto
250 type (1 phase) 0.126 Ditto
15
5-3. Wiring System Diagrams
EG
CAUTION
5-4. Examples of Incorrect Wiring
The following are examples of improper wiring that result in system misoperation. You should confirm that you have wired the units correctly before beginning the test run described on page 26.
Outdoor unit: one-phase 50 Hz, 220-240V
Outdoor unit: three-phase 50 Hz, 380-415V
16
EG
When connecting each power wire to corresponding terminal, follow instructions ÒHow to connect wiring to the terminalÓ and fasten the wire securely tight with the fixing screw of the terminal plate.
5-5. How to connect wiring to the terminal
For solid core wiring (or F-cable)
(1) Cut the wire end with a wire cutter or wire-cutting pliers,
then strip the insulation to expose the solid wire about 25 mm. (Fig. 5-1)
(2) Using a screwdriver, remove the terminal screw(s) on the
terminal plate.
(3) Using the pliers, bend the solid wire to form a loop suitable
for the terminal screw.
(4) Shape the wire loop properly, position it on the terminal
plate and fix it securely with the terminal screw using a screwdriver.
For stranded wiring
(1) Cut the wire end with a wire cutter or wire-cutting pliers,
then strip the insulation to expose the stranded wiring about 10 mm. (Fig. 5-2)
(2) Using a screwdriver, remove the terminal screw(s) on the
terminal plate.
(3) Using a ring connector fastener or pliers, securely clamp
each stripped wire end with a ring connector. (Fig. 5-2)
(4) Position the ring connector, then replace and tighten the
terminal screw with a screwdriver.
CAUTION
¥ Loose wiring may cau-
se the terminal to overheat or result in unit malfunction. A fi­re hazard may also exist. Therefore, be sure all wiring is to­ghtly connected.
Fig. 5-1
Fig. 5-2
Fig. 5-3
EG
17
6-1. Wireless Remote Control Unit
The remote control unit can be operated from either a non­fixed position or a wall-mounted position. To ensure that the air conditioner operates correctly, do not install the remote control unit in the following places: ¥ In direct sunlight ¥ Behind a curtain or other place where it is covered ¥ More than 8 m away from the air conditioner ¥ In the path of the air conditionerÕs airstream ¥ Where it may become extremely hot or cold ¥ Where it may be subject to electrical or magnetic interference
Mounting on a Wall
(a) Removable mounting
(1) Momentarily hold the remote control unit at the desired
mounting position.
(2) Confirm that the air conditioner responds correctly
when you press keys on the remote control from that position.
(3) After confirming correct operation, use a screwdriver
to screw the supplied special mounting screw into the wall. (Fig. 6-1)
(4) Hang the remote control unit from the mounting screw.
(b) Non-removable mounting
(1) Momentarily hold the remote control unit at the desired
mounting position.
(2) Confirm that the air conditioner responds correctly
when you press keys on the remote control from that position.
(3) After confirming correct operation, use a screwdriver
to screw the mounting screw into the wall. (Fig. 6-1)
(4) Remove the remote control cover by sliding it
downward. (5) Remove the batteries of the remote control unit. (6) Use a screwdriver to screw the remote control unit
securing screw into the wall through the hole in the
battery compartment. (Fig. 6-2) (7) Replace the batteries. (8) Again confirm that the remote control unit operates
correctly.
Fig. 6-1
Fig. 6-2
6. HOW TO INSTALL THE REMOTE CONTROLLER
18
EG
When reaming, hold the tube end downward and be sure that no copper scraps fall into the tube.
(3) Remove the flare nut from the unit and be sure to
mount it on the copper tube.
(4) Make a flare at the end of copper tube with a flare
tool.* *Use ÒRIGIDÓ or equivalent.
A good flare should have the following characteristics: ¥ inside surface is glossy and smooth. ¥ edge is smooth. ¥ tapered sides are of uniform length.
NOTE
NOTE
7-1. Connecting Tubing Sides
Use of the Flaring Method
Many of the conventional split system air conditioners employ the flaring method to connect refrigerant tubes which run between indoor and outdoor units. In this method, the copper tubes are flared at each end and connected with flare nuts.
Flaring Procedure with a Flare Tool
(1) Cut the copper tube to the required length with a tube
cutter. It is recommended to cut approx. 30 Ð 50 cm
longer than the tubing length you estimate.
(2) Remove burrs at the end of the copper tube with a
tube reamer or file. This process is important and
should be done carefully to make a good flare.
7. HOW TO PROCESS TUBING
Before
After
Copper tubing
Reamer
Flare nut
Flare tool
Copper tubing
Caution before Connecting Tubes Tightly
(1) Be sure to apply a sealing cap or water-proof tape to
prevent dust or water from getting into the tubes before
they are used.
(2) Be sure to apply refrigerant lubricant to the matching
surface of the flare and union before connecting them
together. This is effective for reducing gas leaks.
(3) For proper connection, align the union tube and flare
tube straight with each other, then screw in the flare nut
lightly at first to obtain a smooth match.
7-2. Connecting Tubing Between Indoor
and Outdoor Units
(1) Tightly connect the indoor side refrigerant tubing
extended from the wall with the outdoor side tubing.
(2) To fasten the flare nuts, apply specified torque as:
Aplly refrigerant
lubricant here and here
Union
Flare nut
Torque wrench
Spanner
Outdoor unit
Indoor unit
Tube Dia. Tightening Torque
6,35 mm (14Ó) Approx. 140 Ð 180 kg-cm
9.52 mm (3/8Ó) Approx. 340 Ð 420 kg-cm
15.88 mm (5/8Ó) Approx. 680 Ð 820kg-cm
19.05 mm (3/4Ó) Approx. 1000 Ð 1200 kg-cm
19
EG
Taping the flare nuts
Wind white insulation tape around the flare nuts at the wide tube connections. Then cover up the tubing connections with the flare nut insulator, and fill the gap at the union with the supplied black insulation tape. Finaly, fix the insulator at both ends with plastic clamps.
Insulation material
The material used for insulation must have good insulation characteristics, be easy to use, be age resistant, and must not easily absorb moisture.
7-3. Insulation of Refrigerant Tubing
CAUTION
¥ Always insulate tubes
after draining water and completing leak tests on all connection points.
CAUTION
¥ After a tube has been
insulated, never try to bend it into a narrow curve because it can cause the tube to break or crack.
IMPORTANT
To avoid condensation and water leaks, both the wide tube and narrow tube must be insulated with the insulation materials (field supply).
Insulation
Thickness:
Min. 8 mm
Thickness: Min. 8 mm
Wide tube
Narrow tube
Refrigerant tubing
Sealer (supplied)
Insulation tape (white)
(supplied)
Flare insulator (supplied)
Tube insulator (not supplied) Heat resistant 140 ¡C or higher
Vinyl clamps (supplied)
Refrigerant tiubing and insulator (not supplied)
Drain pipe and insualtor (not supplied)
Insulation
tape Vinyl clamp
Flare insulator
Packing clamp. Small hose band (supplied)
Drain insulator and clamp. Large (supplied)
Seal
The procedures used for installing the insulator for both wide and narrow tube are the same.
Unit side insulator
Fare nut
Never grasp the drain or refrigerant connecting outlets when moving the unit.
7-4. Taping the Tubes
(1) At this time, the refrigerant tubes (and electrical wiring
if local codes permit) should be taped with armoring tape as 1 bundle. To prevent the condensate from overflowing the drain pan, keep the drain hose separate from the refrigerant tubing.
(2) Wrap the armoring tape from the bottom of the outdoor
unit to the top of the tubing where it enters the wall. As you wrap the tubing, overlap half of each previous tape turn.
(3) Clamps the tubing bundle to the wall, using 1 clamp
approx. every 1 m.
7-5. Finishing the Installation
After finishing insulating and taping over the tubing, use sealing putty to seal off the hole in the wall to prevent rain and draft from entering.
Do not wind the armoring tape too tightly since this will decrease the heat insulation effect. Also be sure the condensation drain hose splits away from the bundle and drips clear of the unit and the tubing.
NOTE
Clamp
Drain hose
Isulated tubes
Apply putty here
Tubing
20
EG
8. AIR PURGING
Air and moisture remaining in the refrigerant system have undesirable effects as indicated below. Therefore, they must be purged completely. ¥ pressure in the system rises ¥ operating current rises ¥ cooling (or heating) efficiency drops ¥ moisture in the air may freeze and block capillary tubing ¥ water may lead to corrosion of parts in the refrigerant system
Air Purging with a Vacuum Pump (for Test Run)
(1) Check that each tube (both narrow and wide tubes)
between the indoor and outdoor units have been properly connected and all wiring for the test run has been completed. Note that both narrow and wide tube service valves on the outdoor unit are kept closed at this stage.
(2) Using an adjustable wrench or box wrench, remove the
valve caps from the service valve on both the narrow and wide tubes.
(3) Connect a vacuum pump and a manifold valve (with
pressure gauges) to the service port on the wide tube service valve. (Figs. 8-1 and 8-2)
CAUTION
¥ Be sure to use a ma-
nifold valve for air pur­ging. If it is not availa­ble, use a stop valve for this purpose. The ÒHiÓ knob of the ma­nifold valve must always be kept closed.
(4) With the ÒLoÓ knob of the manifold valve open, run the
vacuum pump. The operation time for the vacuum pump varies with tubing length and the capacity of the pump. The following table shows the amount of time for evacuation:
Required time for evacuation when capacity
of 100 liter/h vacuum pump is used
If tubing length is If tubing length is
shorter than 15 m longer than 15 m
30 min. or more 60 min. or more
The required time in the above table is calculated based on the assumption that the ideal (or target) vacuum condition is around 10 mmHg abs.
NOTE
Wide Tube
Narrow
tube
21
(5) With the vacuum pump still running, close the ÒLoÓ knob
of the manifold valve. Then stop the vacuum pump.
(6) With the accessory hex wrench, turn the valve stem on
the narrow tube service valve counter-clockwise by 90 degrees (1 / 4 turn) for 10 seconds, and then turn the stem clockwise to close it again.
CAUTION
¥ Be sure to completely
insert the hex wrench before attempting to turn the valve.
(7) Leak test all joints at the tubing (both indoor and outdoors)
with liquid soap. Bubbles indicate a leak. Be sure to wipe off the soap with a clean cloth.
(8) With the hex wrench, turn the narrow tube service valve
stem counterclockwise to fully open the valve. (Fig. 8-3)
(9) With a standard screwdriver, turn the wide tube service
valve 90 degrees (1 / 4 turn) counter-clockwise. (Fig. 8-3)
(10) Loosen the vacuum hose connected to the wide tube
service port. Then remove the hose.
(11) Replace the bonnet and flare nut on the wide tube service
port and fasten the flare nut securely with an adjustable wrench or box wrench. This process is very important to prevent gas from leaking
from the system. (12) Test run the air conditioner. (13) While the air conditioner is running, apply liquid soap to
check for any gas leaks around the service valves or
caps. (14) If there is no leakage, stop the air conditioner. (15) Wipe off the soap on the tubing.
This completes air purging with a vacuum pump and the air conditioner is ready for actual operation.
9. HOW TO INSTALL THE CEILING PANEL
4-WAY AIR DISCHARGE SEMI-CONCEALED TYPE
CAUTION
¥ Never touch or attemp
to move the air direc­tion louver by hand or you may damage the unit. Instead, use the remote controller if you want to change the direction or air flow.
Latch
Screw
Air intake grille
Ceiling panel
Fig. 9-1
EG
22
EG
9-1. Before Installing the Ceiling Panel
(1) Remove the air intake grille and air filter from the ceiling
panel. (Figs. 9-1 and 9-2)
(a) Remove the 2 screws by the latch from the air
intake grille. (Fig. 9-1)
(b) Press on the 2 latches of the air intake grille with
your thumb in the direction of the arrow to open the grille. (Fig. 9-1)
(c) With the air intake grille open about 45¡, remove
the safety string (hook on the grille side). (Fig. 9-2)
(d) Pull the air intake grille towards you to remove it
from the ceiling panel.
(2) Pull down the two panel catches of indoor unit body.
(Fig. 9-3)
Air filter
Safety string
Fig. 9-2
9-2. Installing the Ceiling Panel
(1) Lift the ceiling panel and position it to align the panel
hook with the panel catch of the indoor unit.
The ceiling panel must be mounted in the correct direction. Note that the 2 catches of the panel differ in size. Be sure to confirm that the catches are correctly matched between the ceiling panel and the indoor unit body.
(2) Next, check to see that the ceiling panel is properly
aligned with the seamline of the ceiling. If it is not, remove the ceiling panel and slightly readjust the indoor unit body to the proper suspension point.
(3) When the ceiling panel has been properly aligned, use
the provided 4 mounting srews (M5) with washers to permanently fasten the ceiling panel.
(4) Connect the wiring connector from the ceiling panel
to the connector inside the indoor unit inside the
NOTE
Panel catch (pull down)
Ceiling panel
Electrical component box
Clamp
Ceiling panel wiring connector
Connector on unit body (inside electrical component box)
Electrical component box
Connector of ceiling panel
Unit body
Panel catch (pull down)
Ceiling panel
Screws M5 with washer
Mark
Air filter
Air intake grille
Fig. 9-3
electrical component box. After doing the connection, use the clamp on the indoor unit body to secure the wiring.
(5) Install the air filter and air intake grille by performing the
steps in section 9-1 in reverse.
Be sure to rehook its safety string before closing the air intake grille.
9-3. When removing the Ceiling Panel for
Servicing
When removing the ceiling panel for servicing, remove the air intake grille and air filter, disconnect the wiring connector inside the electrical component box, and then remove the 4 mounting screws.
NOTE
23
10. TEST RUN
10-1. Preparing for Test Run
¥ Before attempting to start the air conditioner, check the
following:
(1) All loose matter is removed from the cabinet especially
metal filings, bits of wire, and clips.
(2) The control wiring is correctly connected and all
electrical connections are tight.
(3) The protective spacer for the compressor used for
transportation has been removed. If not, remove it now.
(4) Both the wide and narrow tube service valves are open.
If not, open them now.
(5) Check to see if the transportation cardboard protection
for the indoor fan has been removed. If not, remove it at this time.
Fig. 10-1
Fig. 10-2
EG
10-2. Performing Test Run for models with
wireless control
CAUTION
¥ Be careful since the
fan will start turning when is performed Test Run.
(1) Locate the Operation Selector on the electrical
component box inside the indoor unit. To access the Operation Selector, press on the 2 latches of the air intake grille in the direction of the arrow to open the grille. Open the air intake grille downward. Remove the air filter attached to the ceiling panel. (Fig. 10-3)
(2) Set the Operation Selector to the ÒTestÓ position. The
air conditioner will start running.
(3) Let the unit run for about 30 minutes and check that the
unit operates normally.
(4) After the test run, be sure to reset the Operation
Selector to the ÒONÓ position for normal operation. The air conditioner will still continue running.
(5) Referring to the Operation Instructions, select the
Cooling mode and press the ON / OFF operation button on the remote control unit, confirming remote control unit operation.
NOTE
If the Operation Selector is not in the ÒONÓ position for normal operation, the unit will not run correctly.
Fig. 10-3
24
EG
Pump down means collecting refrigerant gas in the system back into the outdoor unit without losing any of the gas. Pump down is used when the unit is to be moved or before servicing the refrigerant circuit.
11. PUMP DOWN
(1) Connect the LO side charging hose of the manifold
valve to the service port (B) on the wide tube service valve.
(2) Using a hex wrench, turn the narrow tube service valve
clockwise all the way to close the service valve. (3) Press the operation button and start cooling operation. (4) When the low pressure gauge reading falls to 1 to 0.5
kg/cm
2
, fully close the wide tube valve stem with a
standard screwdriver. Then quickly stop the unit. (5) Disconnect all gauges and hoses, and replace the
bonnets and the valve caps as they were previously. (6) Purge all air remaining inside the tubing before
operating the air conditioner.
CAUTION
¥ Be sure to carry out
pump down with the unit in cooling mode.
DICHIARAZIONE DI CONFORMITË
Questo prodotto • marcato in quanto conforme alle Direttive: Ð Bassa Tensione n. 73/23 CEE e 93/68 CEE. Ð Compatibilitˆ Elettromagnetica n. 89/336 CEE, 92/31 CEE e 93/68 CEE. Questa dichiarazione sarˆ nulla nel caso di impiego diverso da quello dichiarato dal Fabbricante e/o di mancata osservanza, anche solo parziale, delle istruzioni d'installazione e/o d'uso.
DECLARATION OF CONFORMITY
This product is marked as it satisfies Directives: Ð Low voltage no. 73/23 EEC and 93/68 EEC. Ð Electromagnetic compatibility no. 89/336 ECC, 92/31 EEC and 93/68 EEC. This declaration will become void in case of misuse and/or non observance though partial of manufacturer's installation and/or operating instructions.
DECLARATION DE CONFORMITE
Ce produit est marquŽ puisque il est conforme aux Directives: Ð Basse Tension n. 73/23 CEE et 93/68 CEE. Ð CompatibilitŽ ElectromagnŽtique n. 89/336 CEE, 92/31 CEE et 93/68 CEE. Cette dŽclaration sera nulle en cas d'une utilisation diffŽrente de celle dŽclarŽe par le Constructeur et/ou de la non-observation, m•me si partielle des instructions d'installation et/ou dÕutilisation.
DECLARACION DE CONFORMIDAD
Este Producto est‡ marcado porque responde a las Directivas: Ð Baja Tensi—n n¡ 73/23 CEE y 93/68 CEE. Ð Compatibilidad Electromagnetica n¡ 89/336 CEE, 92/31 CEE y 93/68 CEE. Esta declaraci—n no tendr‡ efecto en s—lo caso de que se haga un uso diferente al declarado por el Fabricante, y/o por el no respeto, incluso parcial, de las intrucciones de instalaci—n y/o de uso.
KONFORMIT€TSERKL€RUNG
Dieses Produkt ist mit -Zeichen gekennzeichnet, weil es den folgenden Richtlinien entspricht: Ð Niederspannungsrichtilinie 73/23 EWG und 93/68 EWG. Ð Elektromagnetische VertrŠglichkeit 89/336 EWG, 92/31 EWG und 93/68 EWG. Bei falschem Einsatz des GerŠtes und/oder Nichtbeachtung auch nur von Teilen der Bedienungsanleitung und der Installatinsanweisungen wird diese ErklŠrung ungŸltig.
D
DHLWSH SUMMORFWSHS
To proiüovn autov fevrei to shvma giativ antapokrivnetai sti" Odhgive"Ú
Ð
Camhlhv tavsh ariq
. 73/23
EOK kai
93/68
EOK
Ð
Hlektromagnhtikhv sumbatikovthta ariq.
89/336
EOK
92/31
EOK kai
93/68
EOK . H dhvlwsh authv qa eivnai akuvrh se perivptwsh crhvsh" diaforetikhv" apov authvn pou endeivknutai apov ton kataskeuasthv kaiÉhv mh thvrhsh, akovmh kai en mevrei, twn odhgiwvn topoqevthsh" kaiÉhv crhvsh".
centro effe fotocomposizioni - olgiate olona
R.D. 28 Reyrieux BP 131 - 01601 Trévoux CEDEX France Tél. 04.74.00.92.92 - Fax 04.74.00.42.00 R.C.S. Bourg-en-Bresse B 759 200 728
In order to carry on a constant improvement, our products can be modified without prior notice.
Per garantire un costante miglioramento dei nostri prodotti, ci riserviamo di modificarli senza preavviso.
Par souci dÕamŽlioration constante, nos produits peuvent •tre modifiŽs sans prŽavis.
Unsere Produkte werden laufend verbessert und kšnnen VorankŸndigung abgeŠndert Werden.
En el interŽs de mejoras constantes, nuestros productos pueden modificarse sin aviso prŽvio.
Loading...