Techfluid SC250H, DP65, SM250, SC250V, SC250 Instruction Manual

...
Page 1
R-MI-SC250 Rev.: 8 English version
Series SC250
Variable area flowmeter
Instructions manual
Page 2
2
Thank you for choosing a product from Tecfluid S.A.
This instruction manual allows the installation, configuration, programming and maintenance. It is recommended to read it before using the equipment.
 This document shall not be copied or disclosed in whole or in any
part by any means, without the written permission of Tecfluid S.A.
 Tecfluid S.A. reserve the right to make changes as deemed
necessary at any time and without notice, in order to improve the quality and safety, with no obligation to update this manual.
 Make sure this manual goes to the end user.
 Keep this manual in a place where you can find it when you need
it.
 In case of loss, ask for a new manual or download it directly from
our website www.tecfluid.com Downloads section.
 Any deviation from the procedures described in this instruction
manual, may cause user safety risks, damage of the unit or cause errors in the equipment performance.
 Do not modify the equipment without permission. Tecfluid S.A. are
not responsible for any problems caused by a change not allowed. If you need to modify the equipment for any reason, please contact us in advance.
PREFACE
WARNINGS
Page 3
3
TABLE OF CONTENTS
SERIES SC250
1 INTRODUCTION ........................................................................... 6
2 WORKING PRINCIPLE ................................................................... 6
3 RECEPTION .................................................................................. 8
4 INSTALLATION ............................................................................. 8
4.1 Valves ................................................................................ 9
4.2 Filters ................................................................................. 9
4.3 Straight pipe sections ......................................................... 9
5 OPERATION ................................................................................. 10
5.1 Gas flow measurement ....................................................... 10
5.2 Gas damping mechanism .................................................... 11
5.3 Liquid flow measurement .................................................... 12
LIMIT SWITCH AMD
6 INTRODUCTION ........................................................................... 13
7 OPERATION ................................................................................. 13
8 MOUNTING THE LIMIT SWITCH IN AN EXISTING EQUIPMENT ....... 14
8.1 Kit contents ........................................................................ 14
8.2 Preparing the kit ................................................................. 14
8.3 Assembling the AMD kit ...................................................... 15
8.4 Switching point adjustment ................................................. 15
8.5 Electrical connection ........................................................... 16
8.6 Mounting ........................................................................... 16
9 ELECTRICAL CONNECTION .......................................................... 16
LIMIT SWITCH AMM
10 INTRODUCTION ........................................................................... 17
11 MOUNTING THE LIMIT SWITCH IN AN EXISTING EQUIPMENT ....... 17
11.1 Kit contents ........................................................................ 17
11.2 Preparing the kit ................................................................. 17
11.3 Assembling the AMM kit ..................................................... 18
11.4 Switching point adjustment ................................................. 19
11.5 Electrical connection ........................................................... 19
11.6 Mounting ........................................................................... 20
12 ELECTRICAL CONNECTION .......................................................... 20
Page 4
4
TH7 TRANSMITTERS
13 INTRODUCTION ........................................................................... 21
14 MODELS ...................................................................................... 21
14.1 TH7 ................................................................................... 21
14.2 TH7H ................................................................................. 21
14.3 TH7T and TH7TH ............................................................... 21
15 MOUNTING THE TRANSMITTER IN AN EXISTING EQUIPMENT ....... 21
15.1 Kit contents ........................................................................ 21
15.2 Preparing the kit ................................................................. 22
15.3 Assembling the TH7 or TH7H kit .......................................... 22
15.4 Assembling the TH7T or TH7TH kit ...................................... 23
15.5 Electrical connection ........................................................... 23
15.6 Mounting ............................................................................ 24
16 ELECTRICAL CONNECTION .......................................................... 24
16.1 Power supply and analog output ......................................... 25
16.2 Digital output ...................................................................... 25
16.3 Reset input ......................................................................... 26
17 4-WIRE CONNECTION .................................................................. 26
18 HART TRANSMITTERS ................................................................. 27
18.1 Additional functions with HART communication .................... 28
18.2 HART communication characteristics ................................... 28
19 ”WRITE PROTECT” ....................................................................... 29
20 ASSOCIATED SOFTWARE WINSMETER TH7 ................................. 29
20.1 USB cable connection and drivers installation ...................... 29
20.2 Port connection ................................................................... 30
20.3 Access to Calibration and Programming .............................. 31
20.4 Visualization ....................................................................... 34
20.5 Firmware updates ............................................................... 34
21 MAINTENANCE ............................................................................ 36
21.1 Series SC250 ..................................................................... 36
21.2 Float for SC250 with hygienic design ................................... 37
21.3 Potential problems with the metering tube ............................ 38
21.3.1 Jammed float .......................................................... 38
21.3.2 Bent top float stop ................................................... 38
21.3.3 Lack of magnetic field ............................................. 38
Page 5
5
21.3.4 Damaged calibrated orifice and/or float .................... 38
21.4 Potential problems with the indicator housing ....................... 39
21.4.1 The indicator pointer rubs on the reading scale ........ 39
21.4.2 Deviation of the zero on the scale ............................ 39
21.5 AMD limit switch maintenance ............................................ 40
21.5.1 Electrical verification ............................................... 40
21.6 AMM limit switch maintenance ............................................ 40
21.7 TH7 transmitter maintenance .............................................. 40
22 TECHNICAL CHARACTERISTICS .................................................. 41
22.1 Series SC250 ..................................................................... 41
22.2 AMD limit switch ................................................................ 42
22.3 AMM limit switch ................................................................ 42
22.4 TH7 transmitter .................................................................. 43
22.4.1 Power supply ........................................................ 43
22.4.2 Outputs .................................................................. 43
22.4.3 General characteristics ........................................... 43
23 SAFETY INSTRUCTIONS ............................................................... 44
23.1 Pressure equipment directive ............................................. 44
23.2 IECEx certification .............................................................. 44
23.3 Certificate of conformity TR CU (EAC marking) ..................... 45
24 ADDITIONAL INSTRUCTIONS FOR THE Ex VERSION ..................... 45
24.1 Surface temperature .......................................................... 45
24.1 Non-metallic parts ............................................................. 45
24.2 Connecting conductive parts to earth .................................. 46
24.3 AMD limit switch ................................................................ . 46
24.4 AMM limit switch ................................................................. . 46
24.5 TH7 transmitters ................................................................ 46
24.7 Maintenance ...................................................................... 47
24.6 Marking .............................................................................. . 47
25 FLOW RANGES ........................................................................ 48
25.1 SC250 .............................................................................. 48
25.2 SC250H, SC250V .............................................................. 50
25.3 SM250/INOX (EN 1.4404 – AISI 316L) ................................. . 51
26 DIMENSIONS ............................................................................... 52
27 DECLARATIONS OF CONFORMITY ACCORDING TO ATEX ............. 58
Page 6
6
SERIES SC250
1 INTRODUCTION
The series SC250 are flowmeters for liquids, gases and steam.
They are very robust instruments prepared to work in extreme conditions.
They have local flow rate indication by means of magnetic coupling, with scales calibrated in l/h, m
3
/h, kg/h, t/h, %, etc.
They can incorporate switches and/or electronic transmitters that allow to detect a specific flow rate and provide a flow rate signal to a remote device.
2 WORKING PRINCIPLE
Based on variable area principle.
The flowmeter consists of a measuring tube and a float inside it. The flow pushes the float to an equilibrium point. The area obtained between the float and the tube is proportional to the flow rate.
The point of equilibrium depends on:
E = Force of the fluid flow
Pf = Weight of the float
Al = Free area of flow
where:
(Al = Ao, calibrated orifice area, - Af, float area)
Page 7
7
For flowmeters SC250H and SC250V, the force of the fluid moves the float and compresses a spring. This allows that the float can return to its initial position regardless of its position inside the tube when there is no flow.
These flowmeters can be installed in a horizontal pipe with flow from left to right or vice versa or vertical pipe with upwards or downwards flow.
The SC250 model always works always in a vertical position with the flow direction from bottom to top.
The equilibrium point is determined by considering the fluid force and the float weight.
Page 8
8
3 RECEPTION
The series SC250 flowmeters are supplied conveniently packaged for their protection during transportation and storage, together with their instructions manual for installation and operation.
The instruments are supplied tested in our calibration rigs, ready for installation and service.
Before installing the flowmeter, remove all the blocking elements.
With the instrument in its working position, move the float and check that the indicating needle moves all over the scale and returns to zero.
4 INSTALLATION
Flowmeters models SC250 and SM250 must be installed in a completely vertical position and with the flow direction upwards.
The flowmeter SC250V must be installed vertically (flow direction upwards or downwards).
The flowmeter SC250H must be installed in horizontal position (flow direction from left to right or from right to left).
The instrument must be installed so that the flow direction indicated on the dataplate of the instrument matches the flow direction of the fluid.
The “0” of the scale indicates flowmeter inlet, and the full scale indicates the flowmeter outlet.
The model SM250 is a version of the flowmeter SC250 designed for liquids with high viscosity, whose flows can not be measured with the standard SC250. This is achieved thanks to its internal design and the use of special floats.
Page 9
9
It is important that the position is completely horizontal or vertical (depending on the model of the instrument), given that deviations of about 5º can produce errors of about 8-10% of the readings.
4.1 Valves
If the fluid to be measured is a liquid, it is recommended to install a regulating valve before the flowmeter (see point 5.3).
In gas flow measurement, the valve position will depend on the calibrating pressure (see point 5.1).
Valves should always be opened slowly to avoid water hammers.
4.2 Filters
The installation of a filter before the instrument is important, this will avoid possible obstructions and breakdowns in the measuring system.
The mesh of the filter should be maximum 2 mm.
In case of having abundant magnetic particles in suspension, it is necessary to mount a magnetic filter on the inlet of the instrument to avoid the accumulation of particles around the float, which would make it to jam.
4.3 Straight pipe sections
In order to have stable readings, it is essential to avoid turbulences. To do this, it is necessary to install the instrument in a straight pipe section. This section should have the same inner diameter as the flowmeter. The required minimum distances upstream and downstream of the sensor are the following:
Upstream 5 DN Downstream 3 DN
These distances must be free of elements that can disturb the flow profile, such as elbows, diameter changes, valves, etc.
Page 10
10
5 OPERATION
Once the meter is installed, the regulating valve should be opened slowly. The fluid flow will move the float which, by means of magnetic coupling, moves the indicating needle.
Any variations of working conditions with respect to those when calibrated can induce reading errors. The calibration working conditions are indicated on the instrument’s dataplate.
5.1 Gas flow measurement
The working pressure and temperature are of maximum importance for correct gas measurement as they directly affect the scale readings.
For example, if a meter is calibrated at 2 bar gauge and the working pressure is 1 bar gauge there will be an error of about 22%.
In the same way, if working temperature does not match calibrating temperature, errors will be induced in the flow rate readings.
In applications of gas flow measurement where the calibrating pressure of the instrument corresponds to the inlet pressure, being higher than the atmospheric pressure, the regulating valve must be installed downstream of the flowmeter. Thus, it is ensured that the instrument works at calibrating pressure and a back pressure that keeps the float in equilibrium is obtained.
NOTE: Scheme valid for gas flow measurement applications with a pressure higher than atmospheric. For gases at atmospheric pressure, turn valves upside down.
REGULATING VALVE
SHUT OFF VALVE
The flow should be adjusted by means of the regulating valve, while keeping the shut off valve fully open.
Page 11
11
If the regulation is done using the shut off valve, in open circuits or at low gas flow in the meter, the gas will expand which will sharply diminish its density, providing very serious reading errors.
If the flow is regulated by the shut off valve, the float usually experiences an oscillating movement which produces a shut off action until sufficient pressure is gained to overcome its weight. The sudden fall of pressure, when the gas escapes, will make it fall. This cycle is repeated generating an oscillating measurement (resonance).
In applications where the gas outlet is at atmospheric pressure, install the regulating valve upstream of the flowmeter if the flowmeter was calibrated at atmospheric pressure. The shut off valve is then installed downstream of the flowmeter and it should be fully open.
The valve opening procedure should be as following:
- With the regulating valve closed, fully open the shut off valve.
- Gradually open the regulating valve until the desired flow rate.
And for closing:
- Close the regulating valve gradually until zero flow rate.
- Fully close the shut off valve to isolate the flowmeter.
Operating in a different way may involve water hammers that can damage the meter reading or generate instabilities.
5.2 Gas damping mechanism
1. Upper float stop
2. Float
3. Piston
4. Piston locking circlip
5. Guide cylinder
6. Circlips for locking upper float stop & guide cylinder
Page 12
12
When measuring low pressure gas flow with AISI 316L floats, oscillation of the float often occurs, which makes it very difficult to read the flow rates. In these cases it is recommended to install a damper in the instrument.
The damper consists of a piston mounted inside a cylinder, closed at its lower end. The compression forces of the gas absorb the floats oscillations, maintaining it stable in the reading point.
Close the valves during work stops at the end of the working day in order to avoid sudden surges when started up. If the float hits the stops sharply this could cause damage to the meter.
5.3 Liquid flow measurement
When measuring liquids the regulating valve should be installed as shown in the following figure.
Being the shut off valve partially open, open the regulating valve slowly until the needle of the indicator housing shows a low flow rate. Then also open the shut off valve slowly in order to get rid of the air and then progressively fully opened.
The required flow rate is then regulated by using the regulating valve.
Close the valves during work stops at the end of the working day in order to avoid sudden surges when started up. If the float hits the stops sharply this could cause damage to the meter.
SHUT OFF VALVE
REGULATING VALVE
Page 13
13
LIMIT SWITCH AMD
6 INTRODUCTION
The AMD limit switch can be used to generate an alarm or an operation when the flow rate that the instrument is measuring reaches a preset value on the scale plate.
The AMD limit switch consists of a NAMUR slot type inductive sensor, that is actuated by a vane. Given that there is no physical contact in the operation, the limit switch has no influence on the indicator needle movement.
An instrument can be equipped with one or two sensors, depending on the number of points to be detected. A NAMUR amplifier with a relay output can be supplied as an option.
7 OPERATION
The indicator needle moves together with the vane mounted on its shaft. When the vane enters into the slot of the sensor, the limit switch changes its state.
The sensor is mounted on a support which includes a switching point indicator that indicates the switching position. The indicator, that is below the scale plate, can be seen through the scale slot.
Switching points
Page 14
14
8 MOUNTING THE LIMIT SWITCH IN AN EXISTING EQUIPMENT
When the AMD limit switch is to be fitted to an existing device, please follow these steps.
8.1 Kit contents
The kit contains the following elements:
In the kits, the O-rings (5) and the blanking plugs (7) are not provided as loose parts. They are incorporated in the cable glands (6).
8.2 Preparing the kit
Remove the cover, unscrewing the four screws "Allen" M5 and plastic washers, in the back side of the indicator housing, using a 4 mm Allen key.
Slide the scale plate in the direction indicated in the figure, until it is released from the slot.
Ensure that the O-rings (5) are placed in the thread of the gland (6). If not, they should be placed. Remove the plugs from the indicator box with a flat screwdriver and replace them by the two cable glands.
The cable glands that are not expected to be used should be left with the blanking plug (7) placed to preserve watertight.
AMD kit
Quantity Material Position
1 AMD limit switch circuit 1
2 Self tapping screw DIN7982 B-2,2 x 9,5 Nº2 A2 2
1 Screw DIN7985 M3 x 6 A2 3
1 External tooth lock M3 A4 4
2 O-ring Ø 16 x 18,5 x 1,25 mm NBR-70 5
2 Cable gland IP68 6
2 Cable gland blanking plug 7
Page 15
15
Limit switch pointers Fixing nuts
8.3 Assembling the AMD kit
Slide the circuit into the slot until it stops, and then screw it as shown in the figure.
Screw the earth cable terminal with the screw (3) and tooth lock (4).
8.4 Switching point adjustment
The circular fixing nuts of the switching point are in the rear part of the indicator needle.
Screw (3) + tooth lock (4)
Slot
Screw (2)
Screw (2)
Page 16
16
To move the limit switch needle, the circular fixing nuts have to be slightly loosen by turning them to the left, without removing the scale plate (see the figure on the next page). After that, place the switching point indicator in the required scale value, and fix it again with the screw.
As standard, when the instrument has one AMD, it comes configured as a minimum limit switch.
8.5 Electrical connection
Do it according to section 9.
8.6 Mounting
Slide the scale plate into the slot until it stops as shown in the figure. Mount the cover with the four screws "Allen" M5 and the plastic washers.
9 ELECTRICAL CONNECTION
To gain access to the electrical terminal block, the scale plate must be removed. To do this, slide it to the left by the guide and free it.
In order to make the electrical connection of the instrument, the limit switch has a screw terminal strip.
For the electrical installation it is recommended to use multiple conductor cables with individual cable sections in the order of 0.25 to 0.5 mm
2
in order to make it easier to
connect.
Before starting the installation, check that the cable glands are the right size for the cables to be used, this will guarantee the instrument will stay watertight. The supplied M16 cable glands are for cables with outside diameters between 6 mm and 10 mm.
Peel the outside insulation to free the inner cables. It is recommended to tin the ends of the wires to avoid loose ends. Next, feed the cables through the cable glands, and connect to the corresponding screw terminals. Last, tighten up the cable glands so that they maintain their ingress protection.
Page 17
17
In the kits, the O-rings (5) and the blanking plugs (7) are not provided as loose parts. They are incorporated in the cable glands (6).
11.2 Preparing the kit
Remove the cover, unscrewing the four screws "Allen" M5 and plastic washers, in the back side of the indicator housing, using a 4 mm Allen key.
LIMIT SWITCH AMM
10 INTRODUCTION
The AMM limit switch can be used to generate an alarm or an operation when the flow rate or the instrument is measuring reaches a preset value on the scale plate.
It consists of a micro-switch driven by a cam mounted on the indicating needle.
An instrument can be equipped with one or two micro-switches, depending on the number of points to be detected.
11 MOUNTING THE LIMIT SWITCH IN AN EXISTING EQUIPMENT
In order to add an AMM limit switch to an existing device, follow the steps shown below.
11.1 Kit contents
The kit contains the following elements:
AMM kit
Quantity Material Position
1 AMM limit switch circuit 1
2 Self tapping screw DIN7982 B-2,2 x 9,5 Nº2 A2 2
1 Screw DIN7985 M3 x 6 A2 3
1 External tooth lock M3 A4 4
2 O-ring Ø 16 x 18,5 x 1,25 mm NBR-70 5
2 Cable gland IP68 6
2 Cable gland blanking plug 7
The numbering of the terminals is given on the printed circuit board.
Page 18
18
Slide the scale plate in the direction indicated in the figure, until it is released from the slot.
Ensure that the O-rings (5) are placed in the thread of the gland (6). If not, they should be placed. Remove the plugs from the indicator box with a flat screwdriver and replace them by the two cable glands.
The cable glands that are not expected to be used should be left with the blanking plug (7) placed to preserve watertight.
11.3 Assembling the AMM kit
Slide the circuit into the slot until it stops, and then screw it as shown in the figure.
Screw the earth cable terminal with the screw (3) and tooth lock (4).
Slot
Screw (2)
Screw (2)
Page 19
19
Cam shown acting on the micro-switch lever
11.5 Electrical connection
Do it according to section 12.
11.4 Switching point adjustment
To adjust the switching point, loosen slightly the cam’s grub screw (C) and turn the cam on the shaft until the required switching point is achieved.
To turn the cam on the shaft, do not hold the shaft by the indicating needle, as this may move the needle on the shaft. The shaft should be held directly.
For the models SC250, SC250V/BD, SC250H/DES and SM250, if the cam is turned in the “A” direction, the acting point will move away from the zero point of the scale. If the cam is turned in the “B” direction, the acting point will move towards the zero point of the scale.
For the models SC250V/DAB, SC250H/ED, if the cam is turned in the “A” direction, the acting point will move towards to the zero point of the scale. If the cam is turned in the “B” direction, the acting point will move away from the zero point of the scale.
Once the cam is in its position, making sure that it rests on the follower of the micro-switch lever, and the grub screw (C) has been tightened, the correct working of the limit switch should be verified by turning the indicating needle shaft and checking the switching at the required point.
Screw (3) + tooth lock (4)
Page 20
20
12 ELECTRICAL CONNECTION
In order to make the electrical connection of the instrument, the limit switch has a screw terminal strip.
For the electrical installation it is recommended to use multiple conductor cables with individual cable sections in the order of 0.25 to 0.5 mm
2
in order to make it easier to connect. Loose cables should not be used given that they can affect the seal of the cable glands. It is better to maintain the mains cables separated from the cables with low level signals.
Before starting the installation, check that the cable glands are the right size for the cables to be used, this will guarantee the instrument will stay watertight. The M16 cable glands used are for cables with outside diameters between 6 mm and 10 mm.
Peel the outside insulation to free the inner cables. It is recommended to tin the ends of the wires to avoid loose ends. Next, feed the cables through the cable glands, and connect to the corresponding screw terminals. Last, tighten up the cable glands so that they maintain their ingress protection.
The numbering of the terminals is given on the printed circuit board.
11.6 Mounting
Slide the scale plate into the slot until it stops as shown in the figure. Mount the cover with the four screws "Allen" M5 and the plastic washers.
Page 21
21
TH7 TRANSMITTERS
13 INTRODUCTION
TH7 transmitters are microprocessed electronic position transducers. The instrument uses the Hall effect to capture the field of a magnet. The resulting signal, after the micro-controller processing, is converted into a current signal of 4-20 mA in a 2-wire loop. This signal is proportional to the flow rate.
14 MODELS
14.1 TH7
It is a 4 to 20 mA transmitter proportional to flow rate that incorporates a digital output configurable as synchronized pulse output or alarm output. 4 mA corresponds to beginning of the scale. 20 mA corresponds to full scale.
The cut off value can be programmed (see section 20.3 in page 32). By default, the cut off corresponds to the first point on the scale after the zero point.
14.2 TH7H
It is a TH7 transmitter that incorporates HART protocol compatibility. With this protocol the user can change the measuring range of the 4-20 mA loop, and data like flow rate and accumulated volume.
14.3 TH7T and TH7TH
They are the equivalent models to those of the sections 14.1 and 14.2, but in addition they include a 8-digit totalizer (7 entire numbers and 1 decimal).
15 MOUNTING THE TRANSMITTER IN AN EXISTING EQUIPMENT
When the transmitter is to be fitted to an existing device, please follow these steps.
15.1 Kit contents
The kit contains the following elements:
Quantity Material Position
1 Transmitter 1
4 Screw DIN7985 M 3 x 4 A2 2
2 O-ring Ø 16 x 18,5 x 1,25 mm NBR-70 3
2 Cable gland IP68 4
2 Cable gland blanking plug 5
TH7 or TH7H kit
Quantity Material Position
1 Totalizer 1
2 Screw DIN7982 B-2,2 x 9 Nº2 A2 2
TH7T or TH7TH kit
Page 22
22
Ensure that the O-rings (3) are placed in the thread of the gland (4). If not, they should be placed. Remove the plugs from the indicator box with a flat screwdriver and replace them by the two cable glands.
The cable glands that are not expected to be used should be left with the blanking plug (5) placed to preserve watertight.
15.3 Assembling the TH7 or TH7H klit
Screw the transmitter as shown in the figure.
In the kits, the O-rings (3) and the blanking plugs (5) are not provided as loose parts. They are incorporated in the cable glands (4).
15.2 Preparing the kit
Remove the cover, unscrewing the four screws "Allen" M5 and plastic washers, in the back side of the indicator housing, using a 4 mm Allen key.
Slide the scale plate in the direction indicated in the figure, until it is released from the slot.
Screws (2)
Screws (2)
Page 23
23
15.4 Assembling the TH7T or TH7TH kit
Slide the circuit through the slot until it stops, and then screw it as shown in the figure.
The flat ribbon connecting the transmitter to the totalizer should be connected as in the figure below.
15.5 Electrical connection
Do it according to section 16.
Screw (2)
Screw (2)
Slot
Totalizer (1)
FLAT RIBBON
Page 24
24
16 ELECTRICAL CONNECTION
For the electrical connection, the transmitter has a screw terminal strip.
For the electrical installation it is recommended to use multiple conductor cables with individual cable sections in the order of 0.25 to 0.5 mm
2
in order to make it easier to
connect.
A twisted pair wiring should be used to avoid electrical interferences in the 4-20 mA loop. In some instances, shielded cable may be necessary.
Before starting the installation, check that the cable glands are the right size for the cables to be used, this will guarantee the instrument will stay watertight. The M16 cable glands used are for cables with outside diameters between 6 mm and 10 mm.
Peel the outside insulation to free the inner cables. It is recommended to tin the ends of the wires to avoid loose ends. Pass the cables through the cable glands and screw down in the corresponding positions of the terminal strip. Once the wiring is finished make sure that the cables are well gripped by the cable glands to maintain the ingress protection.
The cable glands must be always closed. Entry of dust or some types of vapours can damage the internal system of bearings and therefore the equipment.
To help in the wiring of the equipment, the description of the terminals is marked on the printed circuit next to the terminal strip.
15.6 Mounting
Slide the scale plate into the slot until it stops as shown in the figure. Mount the cover with the four screws "Allen" M5 and the plastic washers.
Page 25
25
The connection is made in the terminal block. The positive terminal of the power supply is connected to the position + and the positive terminal of the load in the position -. The negative terminals of the power supply and the load are connected together. The instrument works in a 2-wire system, that is, the supply and signal line is the same. It is recommended to use a twisted pair wiring or shielded cable to avoid interferences in the current loop.
16.2 Digital output
The digital output is connected in the positions D and S of the terminal block. The output is an N channel MOSFET transistor isolated from the rest of the circuit and potential free. The S terminal is the source and the D terminal is the drain.
By means of the Winsmeter TH7 software, the digital output can be programmed as pulse output or alarm output (see section 20.3 in page 31).
Before connecting the power supply, you must be sure that the supply voltage is the correct one for the installation. The power supply voltage is indicated on the label of the transmitter.
16.1 Power supply and analog output
Page 26
26
17 4-WIRE CONNECTION
If direct current power supply for the transmitter is not available in the installation, it will be necessary to incorporate an additional power supply as in the following figure.
Example of the connection of the pulse output to a PLC
16.3 Reset input
The terminals marked as RESET are a reset input for the totalizer. It can be connected to a normally open potential free contact. It is important that the contact works well with low level voltages, to avoid noise effects.
Note: The reset terminals are not isolated from the rest of the circuit. They must not be connected to other equipment.
Page 27
27
18 HART TRANSMITTERS
The TH7H and TH7TH transmitters have a modem for HART communication.
TH7H transmitters are fully compatible with the HART Server software from HART Communication Foundation.
Tecfluid S.A. do not guarantee that the TH7H transmitter is compatible with the different servers on the market.
When connecting the transmitter, an external resistor (R ext.) should be included. Its minimum value needs to be 200 Ω, and the maximum value depends on the power supply as follows:
In this case the power supply voltage needs to be 18 VDC minimum.
In order to establish HART communication, it is necessary to connect a terminal or PC with a HART modem, in one of the points indicated in the following figure.
Page 28
28
Summary of the main communication characteristics:
Manufacturer, Model and Revision Tecfluid S.A., TH7H, Rev. 0
Device type Transmitter
HART revision 6.0
Device Description available No
Number and type of sensors 1
Number and type of actuators 0
Number and type of host side signals 1, 4 – 20 mA analog
Number of Device Variables 2
Number of Dynamic Variables 1
Mappable Dynamic Variables No
Number of Common Practice Commands 5
Number of Device Specific Commands 0
Bits of Additional Device Status 12
Alternative working modes? No
Burst mode? No
Write Protection? Yes
Electrical characteristics referred to the analog loop and communications: Reception impedance:
Rx > 3,3 M Cx < 1000 pF
18.1 Additional functions with HART communication
By means of the implemented commands, the user can obtain the following information:
 Flow rate value in the scale units
 Totalizer value (even if the equipment does not have a display).
 Reset or writing of a totalizer value.
 Change of beginning and end of scale of the current loop.
 Possibility of writing tags and messages into the instrument.
18.2 HART communication characteristics
The detail of the characteristics with respect to the HART communication are available in the corresponding “Field Device Specification” document.
Page 29
29
19 “WRITE PROTECT”
The instrument has a jumper that can be used to avoid changes in the configuration. When the jumper is connected the instrument can be configured via HART. When the jumper is removed, “Write Protect” is activated for HART, thus avoiding any changes in the configuration.
20 ASSOCIATED SOFTWARE WINSMETER TH7
By means of this associated software the transmitter can perform the following functions, working in a comfortable and intuitive way.
 Complete re-calibration of the transmitter according to the scale of the instrument.
 Programming of 4 and 20 mA values
 Filter and cut off programming
 Totalizer reset or adjustment of a desired value
 Configuration of the digital output as pulse output or alarm
Such software can be downloaded from section “Downloads” of the Tecfluid S.A. website.
NOTE: Programming via USB can only be done in non-classified area.
20.1 USB cable connection and drivers installation
Extract the files from the winsmeterTH7.zip to a new system folder.
Execute the Setup.exe file and follow the steps for the installation.
In order to connect the converter to a computer an USB cable is required. This cable is type A at one end and mini USB type B at the other (cable not supplied).
The ends of the cables can be seen in the picture.
The first step to make the connection is to open the cover of the indicator housing by removing the four screws "Allen" M5 and plastic washers on the back of the housing.
After removing the graduated scale plate sliding it through the slots, the USB connector is visible at the bottom of the housing.
Page 30
30
Connect the USB cable at one end to the transmitter and at the other to the computer where the software is installed.
Power on the electronic converter.
Execute the program WinsmeterTH7 following the sequence Start – Programs – Tecfluid S.A. ­WinsmeterTH7.
20.2 Port connection
In the "Port" section, choose the appropriate port for the converter. This will appear with the name of the port followed by TH7 and its serial number. Then click "Open".
Page 31
31
Once the port is open, the button "Open" in the "Calibration" and “Programming” sections activates.
20.3 Access to Calibration and Programming
In order to change data in the tab "Calibration", you must enter a password.
The default password is calib, and it can be changed using the boxes on the right of the "Calibration" section.
Likewise, to change data in the tab "Programming" it is necessary to enter the password which by default is program. This can be changed using the boxes on the right of the "Programming" section.
Page 32
32
Once the password is written, press "Enter" or "Open", and the Calibration or Programming tab will open. At the bottom of each section the text "Calibration tab open" or "Programming tab open" will be displayed
To enter the Installation window, just click the corresponding tab.
In the calibration window a complete re-calibration of the transmitter according to the scale plate can be done.
The first step is to choose the scale units, then the specific units.
In the combo N. points the number of points with which the calibration will be performed is selected. The minimum is 10 and the maximum 16.
With these data, the boxes P0 ... P10 to P16 are filled with the values of the scale in which the adjustment will be made.
To perform the calibration, the instrument must be in its operating position.
Depending on the instrument in question, move the float or the disc until the needle points each calibration point, and press the "Calibrate" button of the corresponding point.
Once calibrated every point, to send all the data to the transmitter TH7, click the "Send" button. The data is then stored in the transmitter memory.
Page 33
33
Changing the parameters of this screen, (see previous page) you can program the different functions of the equipment.
In the box Totalizer units power can be selected. The power allows to multiply or divide by a factor multiple of 10 the totalizer speed as well as the pulse output.
By default, with the power = 0, the totalizer and the pulse output indicate the scale units, ie, if the scale of the instrument is in litres / hour, the totalizer indicates liters and the digital output gives one pulse for each litre.
If, for example, the power is programmed to 1, the totalizer and pulse output will run 10 times faster. If a power = -2 is programmed, they will run 100 times slower.
In the box Digital output this output can be configured as pulse output or as alarm. In the latter case, the activation and deactivation values for the alarm can be programmed.
In the box Current loop the values of flow rate equivalent to 4 and 20 mA can be programmed. These values do not have to be the beginning of scale and end of scale values.
In the box Flow rate the values of cut off and filter can be changed.
The cut off is the value below which the TH7 transmitter will consider zero flow rate, and therefore the analog output will give 4 mA and the digital output will be deactivated if it is programmed in pulse mode.
The filter offers stable current loop readings despite fluctuations in the flow reading. It is programmed in seconds, between 1 and 8.
Likewise, to enter into the programming window, just click the corresponding tab.
Page 34
34
To program this data to the transmitter, press the “Send” button. The programming data will be stored in the memory of the transmitter.
Regardless of the programming process, in the box Totalizer value the value of the totalizer can be changed.
20.4 Visualization
When the communication with the computer port is established (see section 20.2), the tab "Visualization" opens. This tab lets you view real-time flow rate, totalizer and velocity values, as well as the current value of the analog output and the status of the digital output if configured as alarm.
It is an intuitive tool to verify that the instrument has been installed and programmed correctly.
20.5 Firmware updates
New firmware updates can be published in the website. These updates contain improvements or bug fixes that make the equipment operates at best conditions.
The updates can be downloaded from the section “Downloads” of Tecfluid S.A. website.
Page 35
35
To update the equipment, go to menu “Firmware” - “Update”, and a screen with the button “File” will appear. Pressing this button system can be accessed. The downloaded file has to be searched there.
Once the file is selected, press the “Program” button. A message “Programming device” will appear.
The process takes about 90 seconds, after which the message “Device programmed” will appear.
From this moment, the transmitter already has the new version of Firmware.
Page 36
36
21 MAINTENANCE
21.1 Series SC250
To perform the maintenance of the meter, it is necessary to remove some parts of the flowmeter. Check below drawings for reference.
In flowmeters up to DN80 remove the circlip (6) which locks the top float stop (7). Then remove the float stop (7). The float (2) can now be extracted. Check it is in perfect condition.
For flowmeters DN100 or larger sizes, remove the screw (9) which holds the float end (8). Then remove the float end (8). The float (2) can be extracted from the top of the flowmeter. Clean the magnetic cylinder (10).
In both cases also check the status of the calibrated orifice (3).
They should have no impact or scratches. Also check that there has been no chemical attack.
If the float (2) is in poor condition it must be replaced. If the calibrated orifice (3) is also in poor condition, the meter body (5) and float (2) should be replaced. In both cases we recommend to re-calibrate the instrument in Tecfluid S.A. facilities.
To remove adhered chemical dirt to the float (2), metering tube (5) or calibrated orifice (3), clean the parts with suitable products or solvents and soft brushes, never use metallic tools.
Follow the above steps in reverse to reassemble the equipment.
Page 37
37
21.2 Float for SC250 with hygienic design
Two special tools are necessary to disassemble the float (2) from the flowmeter. They can be supplied on demand by Tecfluid S.A.
These tools fit into the side guides of the float (2) and of the float end (8).
Once the tools have been fitted into their respective guides, turn the float end (8) as if it was a nut. That way the float (2) will be separated from the float end (8), and the float can be taken out from the top of the meter and the float end from the bottom.
Clean the inside of the metering tube and the float (2).
To remove adhered chemical dirt, clean the parts with suitable products or solvents and soft brushes, never use metallic tools.
Follow the above steps in reverse to reassemble the equipment, making sure that the O-ring (10) is correctly placed between the float (2) and the float end (8). Tighten the float end (8) moderately onto the float (2).
If you are interested in acquiring the special tools in Tecfluid S.A., please indicate for which nominal diameter they are required.
Page 38
38
21.3 Potential problems with the metering tube
21.3.1 Jammed float
In flowmeters up to DN80 a possible cause is that the float upper guide (4) or the lower one (1) are bent due to a water hammer. To solve this, remove the circlip (6) which locks the top float stop (7). Then remove the float stop (7). The float (2) can now be extracted. Align the guide rods and manually check that the movement is good without rubbing.
For flowmeters DN100 or larger, the cause can be that the magnetic cylinder (10) is bent or dirty. To solve this, extract the float (2) from the flowmeter by removing the screw (9) which holds the float end (7). Then remove the float end. Extract the float (2) from the top of the flowmeter and straighten or clean the magnetic cylinder (10).
Follow the above steps in reverse to reassemble the equipment.
The float may also become clogged by accumulation of metallic particles around it due to the float magnetic field. In this case disassemble the float (2) following the above instructions, clean it, and install a magnetic filter on the inlet of the meter, or just a normal filter depending on the size and nature of the particles.
21.3.2 Bent top float stop
If the top float stop (7) is bent due to a water hammer, disassemble it following the instructions of the section 21.1. If it is possible, straighten it and check its alignment. Otherwise change it for a new one.
21.3.3 Lack of magnetic field
Disassemble the float (2) as indicated in section point 21.1. Check if the float has suffered chemical aggression and if so the permanent magnet has been affected. If this is the case, the float must be replaced and the flowmeter will have to be re-calibrated in Tecfluid S.A. facilities.
21.3.4 Damaged calibrated orifice and / or float
Check that they do not show any impacts or scratches. Also check for any chemical attack. If the float (2) is in bad condition it must be replaced. If the calibrated orifice (3) is damaged, the metering tube and the float must be replaced. In both cases the flowmeter has to be re­calibrated in Tecfluid S.A. facilities.
Page 39
39
21.4 Potential problems with the indicator housing
21.4.1 The indicator pointer rubs on the reading scale
To remove the cover, remove the four screws "Allen" M5 and plastic washers, in the back side of the indicator housing, using a 4 mm Allen key.
Rubbing normally happens if the meter has been hit or dropped. Simply straighten the pointer (2) by bending it slightly until it is separated between 2-3 mm from the reading scale surface (1)
21.4.2 Deviation of the zero on the scale
When the indicator pointer (2) does not point zero in its rest position, place the flowmeter in its real working position on top of a non-magnetic table. If when the float is moved the pointer moves but does not return to 0, check that the pointer hub (3) is firmly attached to the pointer shaft (7). If it isn’t, secure the pointer hub (3) onto the conical tip (7) of the shaft by tapping it lightly and carefully.
If the pointer hub is fixed, make the indicator pointer coincide with the 0 on the scale using the frontal adjusting screw (4) on the indicator pointer. Make sure that the shaft (7) is held fast so as not to be bent or damaged
Check that there is no rubbing between the pointer movement system and the cables connected to a limit switch or transmitter.
Page 40
40
21.5 AMD limit switch maintenance
21.5.1 Electrical verification
Check that the voltage at the terminals + and - is over 7.5 V when the vane is in the slot. Connect a multimeter with the scale in DC mA, in series with the terminal +.
Verify that the current is less than 1 mA when the vane is in the slot, and more than 3 mA when the vane is out of the slot.
If you do not have the NAMUR amplifier, the current can be checked using the following circuit diagram:
If you do not have the AMD sensor, the operation of the amplifier can be checked using the following circuit diagram:
With the potentiometer the current of the NAMUR amplifier can be modified. The switching point must be between 1.2 mA and 2.1 mA. That is, with the current below 1,2 mA the output relay must have a state and above 2,1 mA the output relay must have the other state.
21.6 AMM limit switch maintenance
No special maintenance is required.
21.7 TH7 transmitter maintenance
No special maintenance is required.
Page 41
41
22 TECHNICAL CHARACTERISTICS
22.1 Series SC250
Accuracy SC250, SC250H, SC250V According to VDI/VDE 3513 sheet 2 (qG=50%):
2.5% / 1.6% on request
SM250 According to VDI/VDE 3513 sheet 2 (qG=50%):
1.6%
Scales Direct in engineering units or in %
Mounting length 250 mm, except DN150/6" 300 mm
Scale range 10:1
Fluid density No restrictions
Fluid viscosity Up to 10 mPa·s approx., depending on flow rate
(SC250 models)
Working temperature Standard AISI316L: -50ºC ... +300ºC
PVC: 0ºC ... +50ºC PTFE: -20ºC ... +150ºC PP: -20ºC ... +90ºC
With thermal separator EN 1.4404: -200ºC ... +400ºC
Ambient temperature
EN 1.4404: -20ºC ... +80ºC PVC: 0ºC ... +45ºC PTFE: -20ºC ... +80ºC PP: -5ºC ... +80ºC
Working pressure EN 1.4404 PN40 DN15 ... DN50
PN16 DN65 ... DN150
PVC / PP / PTFE PN40 DN15 ... DN40
PN16 DN50 ... DN150
Fully PVC / Fully PP PN16
Connections DN15 … DN150 EN 1092-1 flange or ASME B16.5
equivalent Other flange standards on request (JIS,...) Threaded connections BSP or NPT
Sanitary connections according to ISO 2852, SMS
1145, DIN 11851, TRI-CLAMP®
Housing IP65 - coated aluminium IP65 - PP, on request IP67 - EN 1.4404 with glass window, on request
Page 42
42
22.2 AMD limit switch
Nominal voltage 8 V
Working voltage 5 ... 25 V
Power supply internal resistance 1 kΩ
Current with the vane into the slot < 1 mA
Current with the vane out of the slot ≥ 3 mA
Standard: DIN EN 60947-5-6 (NAMUR)
Ambient temperature -25ºC ... +100ºC
22.3 AMM limit switch
Maximum switching voltage 250 VAC
Maximum switching current 3 A
Potential free SPDT contacts
Ambient temperature -25ºC ... +100ºC
Page 43
43
22.4 TH7 transmitter
22.4.1 Power supply
2 wire
Minimum voltage (TH7 and TH7T): 0.02 Z + 12 (Volt) (Z is the load in the current loop
in Ohm)
The minimum value is 12 VDC for Z=0 Ohm
Minimum voltage (TH7H and TH7TH): 0.02 (Z+Rext) + 14 (Volt) (Z is the load in the
current loop in Ohm)
The minimum value is 18 VDC for Z=0 Ohm and
Rext=200 Ohm
Maximum voltage: 36 VDC
Consumption: maximum 20 mA
22.4.2 Outputs
Analog output: 4 - 20 mA, factory calibrated
Maximum load in the 4-20 loop: 1.1 kW (at 36 VDC supply voltage)
Pulse output: MOSFET transistor N channel potential free
I
max
: 200 mA
Maximum frequency: 6 Hz.
Pulse duration: Approx. 62.5 ms
Pulse / units of volume or mass depending on the scale; factory adjustable or by means of Winsmeter software
Totalizer: 8 digits. (7 + one decimal. Reset by means of
potential free contact)
22.4.3 General characteristics
Accuracy (analog output respect
the magnetic field): < 0.6 %
Ambient temperature: -20ºC … +70ºC
Cable gland: M16 x 1.5
Page 44
44
23 SAFETY INSTRUCTIONS
The series SC250 flowmeters are in conformity with all essential requirements of all EC directives applicable to them:
2014/68/EU Pressure equipment directive (PED)
Limit switches and transmitters:
2014/30/EU Electromagnetic compatibility directive (EMC)
2012/19/EU Waste electric and electronic equipment (WEEE).
Limit switch AMM:
2014/35/EU Low voltage directive (LV)
Equipment for hazardous areas:
2014/34/EU Equipment and protective systems intended for use
in potentially explosive atmospheres (ATEX).
In the last sections of this manual the EC type certificate and the declarations of conformity according to the ATEX directive are attached.
Other declarations of conformity EC can be downloaded from the section “Download” of the Tecfluid S.A. website.
23.1 Pressure equipment directive
Tecfluid S.A. have subjected the series SC250 of flowmeters to a conformity assessment method for the pressure equipment directive, specifically according to module H (full quality assurance).
Conformity with the directive is reflected by the CE marking in each pressure equipment and by the written declaration of conformity. The CE marking is accompanied by the identification number of the notified body involved at the production control phase.
The marking of the equipment takes into account the fluid type, the group of fluid and the category, for example: G1 CATII
G Gases and vapours
1 Group of liquids 1
CATII Category II
Devices that, due to their size, are not subject to conformity assessment, are considered outside the scope of the directive and therefore they have not the CE mark according to pressure directive. These devices are subject to applicable sound engineering practice (SEP).
This equipment is considered as being a pressure accessory and NOT a safety accessory as defined in the 2014/68/EU directive, Article 2, paragraph 4.
23.2 IECEx certification
This equipment has been certified IECEx. The respective documentation can be downloaded from the IECEx website www.iecex.com.
Page 45
45
23.3 Certificate of conformity TR CU (EAC marking)
Tecfluid S.A. have subjected the series SC250 of flowmeters to a certification procedure according to the technical regulations of the Customs Union of the Eurasian Economic Union (EEU).
This Certificate is an official document confirming the quality of production with the standards on the territory of the Customs Union, particularly regarding safety requirements and electromagnetic compatibility.
24 ADDITIONAL INSTRUCTIONS FOR THE Ex VERSION
This chapter only applies to equipment intended for use in explosive atmospheres.
These equipment conform with the directive 2014/34/EU (Equipment and protective systems intended for use in potentially explosive atmospheres) as indicated in the EC-type examination certificate and in its marking. They are also compliant with the IECEx scheme.
Given that this instrument is group II, it is intended for use in places likely to become endangered by explosive atmospheres, but not in mines.
For the category 1G, the equipment is intended for use in areas in which explosive atmospheres caused by mixtures of air and gases, vapours or mists are present continuously, for long periods or frequently.
For the category 1D, the equipment is intended for use in areas in which explosive atmospheres caused by inflammable dusts are present continuously, for long periods or frequently.
24.1 Surface temperature
Equipment is certificated as Exia IIC T4 or Exia IIC T6.
The maximum possible Surface temperature are the following:
24.2 Non metallic parts
WARNING: POTENTIAL RISK OF ELECTROSTATIC CHARGE
The front of the housing consists of a transparent plastic window in order to let the user see the position of the pointer on the scale.
Since the danger of ignition by electrostatic discharge when rubbing this window can not be avoided, the instrument must always be cleaned with a damp cloth.
WARNING: RISK OF IMPACT
Because the housing base is made of aluminium, the equipment must be installed and operated always in locations at low risk of impact.
Temperature
class
Maximum surface
temperature
Ignition temperature
of the specific gas
involved
T4 135ºC 135ºC
T6 85ºC 85ºC
Page 46
46
24.3 Connecting conductive parts to earth
When the instrument is not grounded securely through the connection process, it should be grounded through the housing screw, as shown in the figure.
24.5 AMM limit switch
When the equipment includes an AMM limit switch, can be certified as intrinsic safety. No specific electric parameters are required for gas. In case of dust, the parameters are the following:
Earth
Marking Ex ia IIC T4 Ex ia IIC T6
Ui : 16 V Ui : 16 V
Ii : 25 mA Ii : 76 mA
Pi : 64 mW Pi : 242 mW
Ci : 50 nF Ci : 50 nF
Li : 250 uH Li : 250 uH
Specific parameters
24.4 AMD limit switch
When the equipment includes an AMD limit switch, it is certified as intrinsic safety with the following parameters:
24.6 TH7 transmitters
Transmitters TH7 can be supplied with certification to be installed in potentially explosive atmospheres. They are intrinsic safety devices.
Differing from TH7 transmitters for safe zone, they do not have pulse output.
The electrical connection and the information respect the HART protocol is the same as in the TH7 transmitter (see sections 13 to 19).
Ii : 250 mA
Pi : According to certificate
Page 47
47
The technical characteristics that differ from TH7 transmitters are the following:
Maximum voltage: 30 VDC
Maximum load in the 4-20 loop: 900 Ω (at 30 VDC supply voltage)
Pulse output: Not available in this version.
The rest of characteristics are the same as TH7 transmitter (see section 22.4).
The specific intrinsic safety parameters are the following:
The marking of the equipment shows the following characteristics:
- Manufacturer - Model
- Serial number - CE marking
- ATEX and IECEx marking - Certification number
- Address of the manufacturer
The marking label is located at one side of the housing, always visible
Marking Ex ia IIC T4 Ex ia IIC T6
Specific parameters
Ui : 30 V Ui : 30 V
Pi : According to certificate
Pi : According to certificate
Ci : 57.3 nF Ci : 57.3 nF
NOTE: Programming via USB can only be done in non-classified area.
24.7 Maintenance
It is the same as in non-Ex equipment.
Ex-intrinsically safe equipment can not be repaired. In case of any incident that requires intervention in the equipment, a new equipment will be supplied.
24.8 Marking
Some examples of marking are sown as follows.
Page 48
48
25 FLOW RANGES
25.1 SC250
Size
DN
(NPS)
Float N.
Flow scales
EN 1.4404 (AISI 316L) float (7.95 g/cm³)
l/h water
Nm3/h air
1.013 bar abs 20ºC
∆P (mbar)
15
(½”)
15025 2.5-25 0.06-0.7 40 15040 4-40 0.11-1.2 40 15060 6-60 0.2-1.8 40 15100 10-100 0.3-3 40 15160 16-160 0.5-5 50 15250 25-250 0.6-7.6 50
15
(¾”)
15400 40-400 1.2-12 50 15600 60-600 2-18 50
15800 * 80-800 * 2.5-24 * 60 *
25
(1”)
25100 100-1000 3-30 60 25160 160-1600 5-50 70 25250 250-2500 6-76 90 25400 400-4000 12-120 110
40
(1 ½”)
40400 400-4000 15-120 45 40600 500-6300 20-180 55 40800 800-8000 25-240 90
40100 * 1000-10000 * 30-300 * 120 *
50
(2”)
50800 800-8000 25-240 70 50100 1000-10000 30-300 90 50150 1500-16000 50-480 100
50200 * 2000-20000 * 60-600 * 130 *
65
(2 ½”)
65150 1500-15000 45-450 70 65200 2000-20000 60-600 100
65300 * 3000-30000 * 90-900 * 140 *
80
(3”)
80020 2000-20000 60-600 80 80025 2500-25000 80-760 100
80030 3000-30000 100-900 120 80040 * 4000-40000 * 120-1200 * 160 * 80050 * 5000-50000 * 150-1500 * 190 * 80060 * 6000-60000 * 180-1800 * 220 *
100
(4”)
81040 4000-40000 150-1200 100
81050 5000-50000 150-1500 120
81060 6000-60000 200-1800 150 81085 * 8500-85000 * 260-2600 * 190 * 81095 * 10000-95000 * 300-2900 * 220 *
125
(5”)
82080 8000-80000 250-2400 120
82100 10000-100000 300-3000 150
82120 12000-120000 350-3600 180
150
(6”)
83150 15000-150000 500-4600 220
83180 18000-180000 500-5500 220
* Special flow ranges.
Page 49
49
Size
DN
(NPS)
Float N.
Flow scales
PVC float
l/h water
∆P
mbar
Nm³/h air
1.013 bar abs 20ºC
∆P
mbar
15
(½”)
15025 2.5-25 20 0.1-1 30 15040 6-60 15 0.2-2 25 15060 10-100 15 0.4-4 25 15100 16-160 15 0.6-6 25 15160 25-250 15 1-10 25 15250 40-400 15 1.6-16 25
15
(¾”)
15400 60-600 15 2-20 25
25
(1”)
25100 16-160 10 0.6-6 20 25160 25-250 10 1-10 20 25250 40-400 10 1.6-16 20 25400 60-600 10 2.5-25 20 25101 100-1000 10 4-40 20 25161 160-1600 10 6-60 20 25251 240-2400 10 9-96 20
40
(1 ½”)
40400 150-1500 20 5-50 25 40600 250-2500 20 8-80 25 40800 400-4000 20 14-140 25
50
(2”)
50800 250-2500 15 9-90 25 50100 400-4000 15 15-150 25 50150 600-6000 15 20-200 25 50101 1000-10000 15 35-350 25
65
(2 ½”)
65150 800-8000 15 25-250 25 65200 1000-10000 15 40-400 25
80
(3”)
80020 1000-10000 15 40-400 25 80025 1600-16000 15 60-600 25
100
(4”)
81040 1600-16000 20 60-600 25
81050 2000-20000 20 100-1000 25
125
(5”)
82080 3000-30000 20 150-1500 30 82100 4000-40000 20 200-2000 30 82120 6000-60000 20 220-2200 30
150
(6”)
83150 8000-80000 25 250-2500 35 83180 10000-100000 25 300-3200 35
Page 50
50
Size
DN
(NPS)
Flow scales
l/h water
p
mbar
Spring N.1 Spring N.2 Spring N.3
15
(
10-100 390 16-160 25-250 290 25-250 290 40-400 60-600 200 / 350
15
(¾”)
100-1000 350 150-1500 250-2500 350 / 600
25
(1”)
60-600
(1)
90
100-1000
(1)
90 160-1600 250-2500 290 400-4000 290 600-6000 290
800-8000
(1)
120
1000-10000 300
40
(1 ½")
400-4000
(1)
90 650-6500 800-8000 130 / 160
1000-10000 150 1600-16000 2000-20000 180 / 270
50
(2”)
600-6000 120
1100-11000 120 1800-18000 150
2300-23000* 3000-30000* 4000-40000 170* / 280
65
(
1800-18000 110
2400-24000* 3000-30000* 4000-40000 150* / 220
80
(3”)
2500-25000
(1)
3000-30000
(1)
50 / 60 4000-40000 5000-50000 140 6000-60000 220
(1)
Flow ranges available only with plastic float (PP / PVC / PTFE)
25.2 SC250H, SC250V
Page 51
51
Size
DN
(NPS)
Flow scales
p
mbar
Flotador EN 1.4404 (7,95 g/cm³)
l/h water
Type T Type V Type T Type V
15
(½”)
6-60 55 12-120 55 16-160 55 25-250 30-300 55 55
15
(¾”)
25-250 30-300 55 55 40-400 50-500 55 55 60-630 80-800 55 55 80-800 100-1000 60 60
25
(1”)
25-250 30-300 60 70 40-400 50-500 60 70 60-630 80-800 60 70 80-800 100-1000 60 70
100-1000 130-1300 60 70
120-1200 160-1600 70 80 160-1600 200-2000 70 100 200-2000 250-2500 90 120 250-2500 300-3000 110 160
40
(1 ½" )
160-1600 200-2000 45 60 200-2000 250-2500 45 60 250-2500 300-3000 45 60 300-3000 400-4000 45 60 400-4000 500-5300 55 80
50
(2”)
300-3000 400-4000 50 60 400-4000 500-5300 50 60 500-5000 650-6500 50 60 600-6000 800-8000 55 80 750-7500 1000-10000 70 100
65
(
600-6000 800-8000 60 80
750-7500 1000-10000 60 80 1000-10000 1300-13000 60 80 1200-12000 1500-15000 70 90
80
(3”)
1000-10000 1300-13000 60 80 1200-12000 1500-15000 60 80 1600-16000 2000-20000 60 80 2000-20000 2500-25000 80 100
25.3 SM250/INOX (EN 1.4404 – AISI 316L)
Page 52
52
DN PN Ø D Ø k Ø g Ø l x n B
A C max
L
SC250 SM250 SC250 SM250
15 40 95 65 45 14 x 4 16 133 136 45 45 250
25 40 115 85 68 14 x 4 18 146 154 45 45 250
40 40 150 110 88 18 x 4 18 154 167 45 45 250
50 40 165 125 102 18 x 4 20 167 176 45 45 250
65 16 185 145 122 18 x 8 18 176 192 45 45 250
80 16 200 160 138 18 x 8 20 192 211 45 45 250
100 16 220 180 162 18 x 8 20 211 - 45 - 250
125 16 250 210 188 18 x 8 22 236 - 45 - 250
150 16 285 240 218 22 x 8 22 262 - 45 - 300
26 DIMENSIONS
EN 1092-1 flanges
(dimensions in mm)
Page 53
53
NPS Class Ø D Ø k Ø g Ø l x n B
A C max
L
SC250 SM250 SC250 SM250
½" 88.9 60.3 34.9 15.90 x 4 11.1 122 122 45 45 250
¾" 98.4 69.8 42.9 15.90 x 4 12.7 133 146 45 45 250
1" 107.9 79.4 50.8 15.90 x 4 14.3 146 154 45 45 250
1 ¼" 117.5 88.9 63.5 15.90 x4 15.9 146 154 45 45 250
1 ½" 127.0 98.4 73.0 15.90 x 4 17.5 154 167 45 45 250
2" 152.4 120.6 92.1 19.05 x 4 19.1 167 176 45 45 250
2 ½" 177.8 139.7 104.8 19.05 x 4 22.2 176 192 45 45 250
3" 190.5 152.4 127.0 19.05 x 4 23.8 192 211 45 45 250
4" 228.6 190.5 157.2 19.05 x 8 23.8 211 - 45 - 250
5" 254.0 215.9 185.7 22.20 x 8 23.8 236 - 45 - 250
6" 279.4 241.3 215.9 22.20 x 8 25.4 262 - 45 - 300
150#
ASME B16.5 flanges
(dimensions in mm)
Page 54
54
Sanitary conection DIN 11851 (EN 1.4404)
NW - DN 15 25 40 50 65 80 100
Ø C
7
Rd 34 Rd 52 Rd 65 Rd 78 Rd 95 Rd 110 Rd 130
x 1/8"
x 1/6" x 1/6" x 1/6" x 1/6" x 1/4" x 1/4"
Ø C
6
17 24.8 35.6 45.8 67 82.8 100
Ø d
2
21.3 30 42 51 73 88.9 108
A
114 118 124 129 140 148 157
DIN EQ. 15(PC)* 15 25 40 50-65 80 100
(dimensions in mm)
Page 55
55
Sanitary connection SMS 1145 (EN 1.4404)
NW - DN 15 25 40 50 65 100
Ø C
7
40 60 70 85 98 125
Ø C
6
22.5 35.5 48.5 60.5 72 100
Ø d
2
25 42 51 63.5 73 108
A
115 124 129 135 140 157
DIN EQ.
15 25 40 50 65 100
(dimensions in mm)
Page 56
56
Sanitary connecton CLAMP ISO 2852 (EN 1.4404)
Ø C
7
34 50.5 50.5 64 77.5 91 106
Ø C
6
17 24.8 35.6 45.8 58.3 67 82.8
Ø d
2
21.3 30 42 51 63.5 73 88.9
A
114 118 124 129 135 140 148
DIN EQ. 15(PC)* 15 25 40 50 65 80
130
100
108
157
100
(dimensions in mm)
Page 57
57
Threaded connection BSP / NPT (EN 1.4404)
R ½” ¾” 1” 1 ½” 2” 2 ½” 3”
L
275 275 285 300 300 310 310
D
35 40 50 65 80 90 110
A
114 118 124 129 135 140 146
E/C
30 35 45 60 70 84 104
DIN EQ. 15(PC)* 15 25 40 50 65 80
4”
310
130
156
124
100
(dimensions in mm)
Page 58
58
27 DECLARATIONS OF CONFORMITY ACCORDING TO ATEX
Page 59
59
Page 60
60
Page 61
61
WARRANTY
Tecfluid S.A. guarantee all the products for a period of 24 months from their sale, against all faulty materials, manufacturing or performance. This warranty does not cover failures which might be imputed to misuse, use in an application different to that specified in the order, the result of service or modification carried out by personnel not authorized by Tecfluid S.A., wrong handling or accident.
This warranty is limited to cover the replacement or repair of the defective parts which have not damaged due to misuse, being excluded all responsibility due to any other damage or the effects of wear caused by the normal use of the devices.
Any consignment of devices for repair must observe a procedure which can be consulted in the website www.tecfluid.com, “After-Sales” section.
All materials sent to our factory must be correctly packaged, clean and completely exempt of any liquid, grease or toxic substances.
The devices sent for repair must enclose the corresponding form, which can be filled in via website from the same “After-Sales” section.
Warranty for repaired or replaced components applies 6 months from repair or replacement date. Anyway, the warranty period will last at least until the initial supply warranty period is over.
TRANSPORTATION
All consignments from the Buyer to the Seller´s installations for their credit, repair or replacement must always be done at freight cost paid unless previous agreement.
The Seller will not accept any responsibility for possible damages caused on the devices during transportation.
Tecfluid S.A.
Narcís Monturiol 33
08960 Sant Just Desvern
Barcelona
Tel: +34 93 372 45 11
Fax: +34 93 473 44 49
tecfluid@tecfluid.com
www.tecfluid.com
The technical data described in this manual is subject to modification without notification if the technical innovations in the
manufacturing processes so require.
Quality Management System ISO 9001 certified by
Pressure Equipment Directive 2014/68/UE certified by
ATEX European Directive 2014/34/EU certified by
HART® is a registered trademark of Fielcomm Group
Loading...