TECH ST-85 User Manual

ST-85 – USER'S MANUAL
TECH
Declaration of Conformity No. 35/2010
Hereby, we declare under sole responsibility that the ST-85
230V 50Hz thermoregulator manufactured by TECH, ul. St.
Batorego 14, 34-120 Andrychów, is compliant with the
Regulation by the Ministry of Economy. (Journal of Laws
Dz.U. 155 Item 1089) of July 21, 2007 implementing
of January 16, 2007.
The ST-85 controller has been tested for
electromagnetic compatibility (EMC) with optimal loads
applied.
For compliance assessment, harmonized standards were
used:
PN-EN 60730-2-9:2006.
Co-owners:
Paweł Jura, Janusz Master
- 2 -
ST- 85 – USER'S MANUAL
ATTENTION!
HIGH VOLTAGE!
Make sure the regulator is disconnected from
the mains before working on the power
supply (cable connections, device
installation, etc.)!
All connection works must only be carried out
by qualified electricians.
Before activating the controller, measure the
motor resetting efficiency, check the boiler
and inspect wire insulation.
- 3 -
Blow
ST- 85 – USER'S MANUAL
I. Description
The ST–85 temperature regulator is intended for use with central heating
boilers. The regulator is used for controlling the central heating water
circulation pump, hot consumption water pump and blow (fan).
The ST-85 is a PID-basedcontroller using a continuous signal. In this
type of controllers, the fan power is calculated based on boiler temperature
and flue gas temperature measured at the boiler outlet. The fan runs
continuously and its power depends directly on the measured boiler
temperature and flue gas temperature as well as the difference between the
two parameters and their setpoint values. Advantages of zPID regulators
include their ability to maintain a stable setpoint temperature without
unnecessary overregulations and oscillations.
By fitting the controller with a flue gas outlet sensor, you can save
from a few up to several percent of fuel, and ensure a steady water
temperature for a longer service life of your heat exchanger (boiler). Flue gas
outlet temperature monitoring ensures reduced harmful dust and gas
- 5 -
C.H. Pump
H.C.W. Pump
Manual Mode
Encoder knob
Blow
Exit
Standby
ST-85 – USER'S MANUAL
emissions. The thermal energy from the flue gases is used for heating instead
of being wasted and disposed of through the funnel.
Research results presented below were obtained using the Tech PID-based
controller:
and the controller without PID control:
You can change all parameters with an encoder knob. Turning the knob
allows you to select a function or modify its value, while pressing the knob
allows you to enter the function or confirm changed values. To leave any
function, push the EXIT button.
- 6 -
ST- 85 – USER'S MANUAL
I.a) Basic Terms
Fire up. The cycle begins when you activate the fire up function in the
controller's menu and is active until the central heating boiler temperature
reaches 40oC (the default fire-up threshold), on condition that the
temperature does not drop below this value for 2 minutes (the default fire-up
time). If these conditions are met, the regulator will switch to the duty mode
and the manual operation symbol on the housing will be deactivated. If the
controller fails to reach parameters required for entering into the duty
mode within 30 minutes from activation of the fire-up function, the "Unable
to fire up" message will appear on the display. In such a case, the fire-up
cycle needs to be restarted.
Duty – once the fire-up cycle is finished, the controller enters the duty cycle.
The duty cycle is the basic functionality of the regulator. The blow is
controlled automatically using the zPID algorithm and the temperature is
close to its setpoint value. In the user menu, fan item will appear in place of
the fire-up function. The fan can be deactivated when needed (e.g. while
feeding fuel). If the temperature rises unexpectedly by more than 5oC over
the setpoint value, the so-called Supervision Mode is activated.
Supervision Mode – the mode is activated during the Duty Cycle if the
temperature rises by more than 5oC over the setpoint value. In such case,
the controller is switched from the PID control to manual settings (according
to parameters entered in the Fitter’s Menu) to reduce the temperature of the
circulation water.
Damping – if boiler temperature drops by 2oC below the fire-up threshold
and fails to rise above this value for 30 minutes (default damping time), the
regulator will switch to thedamping mode. While in this mode, the fan is
deactivated and the display shows "Damping".
- 7 -
ST-85 – USER'S MANUAL
In case of voltage loss, the regulator ceases to operate. When power is
restored, the controller returns to operation with previously set parameters
using its built-in memory. Lack of voltage does not cause the stored
parameters to be lost.
II. Regulator Functionality
This chapter describes regulator functionality, how to change settings and
navigate in the menu with the encoder (knob). Depending on the mode the
boiler is currently in, the display will show boiler operational parameters. The
given mode is selected by the user.
II.a) Main Page
During normal operation, the LCD display shows the Main Page containing
the following:
Boiler temperature (to the left of the display).
Setpoint temperature (to the right of the display).
Fan stop. After manually stopping the fan while in the duty mode, the star
symbol ( ) will appear in the down right corner.
Operation Mode. In the up right corner, the corresponding letter of the
operation mode is displayed. Depending on the operation mode, the
corresponding symbol is displayed:
house heating, water heater priority,
parallel pumps, summer mode.
Pressing the encoder will move you to the main menu. The display
shows two options of the menu. To select a different option, turn the encoder
knob.
- 8 -
42 Oc | 55 Oc *
C.H. Setpoint
C.H. Setpoint