TECH L-6 User Manual

L-6 User’s manual
1
User’s manual
L-6
TECH
2
I. Safety
Before using the device for the first time the user should read the following regulations carefully. Not obeying the rules included in this manual may lead to personal injuries or controller damage. The user’s manual should be stored in a safe place for further reference. In order to avoid accidents and errors it should be ensured that every person using the device has familiarized themselves with the principle of operation as well as security functions of the controller. If the device is to be sold or put in a different place,
make sure that the user’s manual is there with the device so that any potential user has
access to essential information about the device. The manufacturer does not accept responsibility for any injuries or damage resulting from negligence; therefore, users are obliged to take the necessary safety measures listed in this manual to protect their lives and property.
WARNING
High voltage! Make sure the regulator is disconnected from the mains before
performing any activities involving the power supply (plugging cables, installing the device etc.)
The device should be installed by a qualified electrician.
Before starting the controller, the user shoud measure earthing resistance of the
electric motors as well as the insulation resistance of the cables.
The regulator should not be operated by children.
WARNING
The device may be damaged if struck by a lightning. Make sure the plug is
disconnected from the power supply during storm.
Any use other than specified by the manufacturer is forbidden. Before and during the heating season, the controller should be checked for
condition of its cables. The user should also check if the controller is properly mounted and clean it if dusty or dirty.
!
!
L-6 User’s manual
3
II. Description of the device
L-6 external controller is intended for both wired and wireless control of the valves. It allows the user to limit considerably the power consumption due to precise control of the room temperature. Thanks to advanced software, the device offers a wide range of functions:
control of the mixing valve control of up to 18 thermostatic valves via 6 room regulators (wired connection)
o 3 room regulators may support 12 actuators (the maximum of 4 actuators per one
regulator)
o 3 room regulators may support up to 6 actuators (the maximum of 2 actuators per
one regulator)
possibility of controlling thermostatic valves via radio signal one 230V pump output supporting pump with speed control (via PWM signal) voltage-free contact possibility of connecting ST-65 GSM module allowing the user to control some of
the functions via a mobile phone.
possibility of connecting ST-500 Ethernet module allowing the user to control some
of the functions and view certain parameters via the Internet
possibility of connecting an external control panel with RS communication
Buttons used
to navigate
the menu
Display
Controller
cover
TECH
4
III. Controller installation
The controller should be installed by a qualified person.
WARNING Risk of fatal electric shock from touching live connections. Before working on the controller switch off the power supply and prevent it from being switched on again.
L-6 regulator may be installed as a free-standing device or as a panel mountable on a wall.
The controller may be installed on a DIN strip.
In order to wire up the controller, the cover should be removed.
!
L-6 User’s manual
5
TECH
6
IV. Wireless communication
L-6 controller enables wireless communication with the following devices:
Function
Configuration
ST-290v4 ST-292v4 two-state room regulators
Sending information about sufficient/insufficient temperature in a given zone
- the room regulator needs to be assigned to a selected area in the room regulator menu
- the current communication channel must be the same as in L-6
ST-286 two-state room regulators (colour)
Sending information about sufficient/insufficient temperature in a given zone.
- the room regulator needs to be assigned to a selected area in the room regulator menu
- the current communication channel must be the same as in L-6
ST-285 master room regulator
Enabling the user to view and change certain parameters of the room regulators assigned to the zones
- an appropriate option should be selected in ST-L­6 menu (Main menu/
Fitter’s menu/ Room
regulator/ TECH regulator)
- ST-260 module is necessary
ST-291 external temperature sensor
Enabling the user to view the external temperature and use weather-based control of the built-in valve module
- the current communication channel must be the same as in L-6
ST-500 Internet module
Enabling the user to view and change certain operation parameters of L-6 via the Internet
- additional ST-260 module is necessary
STT-868 wireless thermostatic actuator
Helping to maintain the pre-set temperature
- it needs to be registered in L-6 controller.
L-6 User’s manual
7
V. First start-up
In order for the controller to operate correctly, the following steps must be followed when starting the device for the first time:
1. Wire up the controller
2. Switch on the controller.
3. If the set includes the master room regulator (ST-285), it needs to be activated
in the controller menu: Main Menu/ Fitter’s menu/ Room regulator/ TECH regulator.
4. If the set includes ST-500 Internet module, it needs to be activated in the
controller menu: Main menu/ Fitter’s menu/ Internet module/ ON.
5. Define the type of external sensor by selecting one of the options in the controller
menu: OFF, Standard or Wireless (ST-291) in the controller menu: Main Menu / External sensor.
6. Configuration of room regulators sending information about sufficient/insufficient
temperature in a given zone.
a. The user should check if the selected communication channel in the room
regulators is the same as in L-6. ‘0’ is the default channel in all devices. If there is a conflict with other devices using radio communication, the user needs to select a different channel.
Channel change in ST-286 controller: In order to change the channel, press Controller settings in the main menu and go to Channel selection. After a channel is selected, confirm the change by pressing OK.
Channel change in ST-290v4 or ST-292v4:
ST-290v4
Screenshot
ST-292v4
- Press and hold MENU button to view the controller functions.
- Using arrows and go to channel change
(see: screenshot)
- Select a desired channel by
using PLUS and MINUS buttons.
- Confirm the change by
pressing MENU and holding it for a few seconds.
- Press MENU to view the
controller functions
- Press MENU button until the
channel change panel appears on the screen. (see: screenshot)
- Using and
buttons select a desired channel.
- Confirm the change by
pressing MENU and holding it for a few seconds or by pressing EXIT.
b. Each room regulator should be assigned to a zone.
NOTE
Each room regulator should be assigned to only one zone. If there are more room regulators assigned to the same zone, L-6 controller will not work properly.
!
TECH
8
How to assign ST-286room regulator to a selected zone: Press Controller settings in the main menu and go to Regulator number (zone number). Select a zone number and confirm by pressing OK icon.
How to assign ST-290v4 or ST-292v4 to a selected zone:
ST-290v4
Screenshot
ST-292v4
- Press and hold MENU
button to view the controller functions
- Using and
go to zone selection (see: screenshot)
- Zone change function is
secured with 215 code – use PLUS and MINUS buttons to enter the first digit of the
code (‘2’). Press MENU to
confirm. Follow the same procedure with ‘1’ and ‘5’.
- Press MENU to view the
controller functions
- Press MENU button until the
zone selection panel appears on the screen. (see: screenshot)
- Zone change function is
secured with 215 code - use
and buttons to
enter the first digit of the
code (‘2’). Confirm by
pressing and holding MENU button. Follow the same
procedure with ‘1’ and ‘5’.
- Choose a desired zone
number using PLUS and MINUS buttons.
- Press and hold MENU to
confirm the change.
- Choose a desired zone
number using buttons.
- Confirm the change by
pressing MENU and holding it for a few seconds or by pressing EXIT.
7. If wireless thermostatic actuators are used, they need to be registered in the
zones.
VI. How to use the controller
V.a) Principle of operation
L-6 controls the CH pump switching it on when the temperature in any of the six zones or the built-in valve is too low. The controller receives temperature information from the subordinate room regulators assigned to particular zones. If the temperature in any of the zones is too low, the controller opens the valves in this particular zone. L-6 receives temperature information from different zones via room regulators e.g. ST­292v4, ST-290v4 or ST-286. Room regulators use wireless communication to send information to the L-6 controller. It is possible to connect a master room regulator (ST-285) which controls the operation of the room regulators in all zones via wireless communication. To each zone the user may assign wired valve actuators and the maximum of 9 wireless actuators communicating with L-6 via radio signal (registration is required).
L-6 User’s manual
9
V.b) Main screen view and description
The user operates the controller using buttons located next to the display.
1. Information about active master room regulator (ST-285)
2. Current time
3. Buttons used to navigate
4. Current communication channel
5. Information about the zones:
A digit displayed on the screen refers to the room regulator which reports insufficient/sufficient room temperature. If the digit is flashing, the room temperature is too low – the valves are open. If a digit is not displayed, there is no signal from the room regulator assigned to this number.
6. Information about active built-in valve
V.c) Controller functions – main menu.
Due to a great number of functions offered by the controller, the menu is divided into Main menu and Fitter’s menu.
3
1
2
3
4 5 6
7
TECH
10
V.c.1) Block diagram – Main menu
V.c.2) Manual operation
This function enables the user to control operation of particular devices. Each of the following devices may be switched on manually: main valve, pump, voltage-free contact and particular valve actuators.
Main menu
Manual mode
Main valve
Pump
Voltage-free contact
Valve 1-6
Channel 0 Channel; range: 0÷20
Main valve
Valve status
Pre-set valve temperature
Opening time
Valve type
Weather-based control
Factory settings
External sensor
OFF
Standard
Wireless
Pump Delay
Language selection
Display contrast
Fitter's menu
Registration
Room regulator
Internet module
Clock
L-6 User’s manual
11
V.c.3) Channel
This function is used to select the channel for wireless communication with the room regulators and the external sensor. The user needs to select the same channel in all devices communicating with the L-6 controller. The range of channels is 0-20.
‘0’ is the default channel in the devices cooperating
with L-6. The channel must be changed only if there is a conflict with other devices using radio communication. In such a case the user must remember to change the channel in all the devices communicating with L-6.
V.c.4) Main valve
L-6 controller is equipped with a built-in module
controlling the mixing valve. There is a range of parameters regulating the valve operation and allowing the user to customize it to individual needs.
Valve status
In order to activate the valve select ON.
Pre-set valve temperature
This function is used to define the pre-set temperature of the valve. It is measured by the valve sensor.
Opening time
This parameter defines the time needed for the valve to open from 0% to 100%. The value should be adjusted to the valve actuator used (information on the rating plate).
Valve type
This function is used to select the type of valve to be controlled:
CH VALVE this option is selected when the user
wants to control the CH circuit temperature
FLOOR VALVE - this option is selected when the
user wants to control the temperature in the underfloor heating circuit. This function protects the underfloor heating system against hazardous temperature. If CH valve type is
TECH
12
selected when the valve is connected to the underfloor heating system, the fragile installation may be damaged.
Weather-based control
For the function of weather control to be active, the external sensor mustn't be exposed to sunlight or influenced by the weather conditions. After it is installed in an appropriate place and wired up, weather control function needs to be activated in the controller menu. For the valve to operate correctly, the user defines the pre-set temperature (behind the valve) for 4 intermediate external temperatures:
-20ºC, -10ºC, 0ºC and 10ºC. The user selects external temperature value using LEFT and RIGHT arrows and defines a corresponding pre-set temperature value using DOWN and UP arrows. Subsequently, the display shows the heating curve. Heating curve it is a curve according to which the pre- set controller temperature is determined, on the basis of external temperature. In our controller, this curve is constructed on the basis of four pre-set temperatures for respective values of external temperatures. The more points constructing the curve, the greater its accuracy, which allows its flexible shaping. In our opinion, four points seem a very good compromise ensuring decent accuracy and easiness of setting the course of this curve.
NOTE After weather-based control is switched on, pre-set valve temperature parameter is not available. (Main menu-valve settings)
Factory settings
This function enables the user to restore the factory settings for a particular valve. Restoring factory settings does not change the selected valve type (CH or floor).
V.c.5) External sensor
The controller may be connected to a standard or wireless external temperature sensor which enables weather­based control of the built-in valve. Current external temperature is displayed on the main screen. After the external sensor is installed, the user needs to define its type: standard or wireless.
!
L-6 User’s manual
13
WARNING If a wireless external sensor is used, the user needs to check if the same communication channel is selected in L-6 controller. ‘0’ is the default channel in the external sensor.
Channel change in the external sensor: Press and hold the channel change button in order to change the communication channel. When the control light flashes twice, the process of channel change has been initiated. Hold the button and wait until the light starts flashing again. The number of flashes corresponds to the channel number (1 flash – channel 1; 5 flashes – channel 5). After the desired channel has been selected, release the button. In order to return to channel 0, repeat the procedure releasing the button after the first two flashes.
V.c.6) Pump
L-6 controls the pump operation switching it on when necessary.
The pump is activated when the temperature in any of the zones is too low or if the pre-set temperature of the built­in valve has not been reached (the built-in valve needs to be active). If all room regulators report sufficient temperature and the pre-set temperature of the built-in valve has been reached (if the valve is active), the controller switches off the pump. Delay function allows the user to define the time of pump activation delay after the temperature in any of the zones is too low or after the valve temperature drops below the pre-set value.
V.c.9) Language selection
This function is used to choose the language version.
!
Control light
Channel
change button
TECH
14
V.c.10) Display contrast
This function enables adjustment of display contrast.
V.c.11) Fitter’s menu
Fitter’s menu should be accessed by a qualified person.
It is intended mostly for adjusting additional functions of the controller.
1) Registration
Wireless thermostatic actuators must be registered in particular zones. The user may choose from 6 zones (Valve 1-6). The maximum of 9 actuators may be registered in one zone. Registration procedure:
1. Install the thermostatic actuator on the radiator.
2. Go to Registration in the Fitter’s menu of L-6
controller.
3. Choose the zone number in which the actuator
will be registered and select Registration.
4. Press registration button on the controller. It
must be done within 30 seconds from selecting Registration option in the menu – after this time the registration process is considered unsuccessful.
5. If the registration process has been successfully completed,
the display shows the message confirming the registration as well as the number of registered valves. If an error occurs during the registration process, the display shows an appropriate message. There are three possible causes of errors:
o an attempt to register more than 9 actuators o an attempt to register an actuator which has
already been registered
o no signal from the valve actuator within 30
seconds
2) Room regulator
L-6 controller may cooperate with a master room regulator (ST-285) which enables the user to:
view the status of particular valves change the pre-set temperature of a given zone – in
the case of using subordinate room regulators with RS communication (ST-286)
view the external temperature
Registration button on the wireless thermostatic actuator
L-6 User’s manual
15
view the status of an additional contact (ON/OFF)
Regulator TECH option needs to be selected in order for the communication between L-6 and the room regulator to be active.
3) Internet module
L-6 controller may cooperate with the Internet module allowing the user to view and change some of the parameters via the Internet. This type of control is available only after purchasing and connecting an additional controlling module ST-500 which is not included in the standard controller set.
The Internet module may be connected to L-6 controller with RS cable. Wireless communication is possible if an additional module - ST-260 is used.
Internet module is a device enabling the user remote control of the CH boiler via the Internet or local network. The user controls the status of all valves on the home computer screen.
If two-state room regulators are used, the user may check if the temperature is sufficient/insufficient. Room regulators with RS communication enable the user to view the current room temperature as well as change its pre­set value.
After switching the module on and selecting DHCP option, the controller automatically downloads such parameters as IP address, IP mask, gateway address and DNS address from the local network. If any problems arise when downloading the network parameters, they may be set manually. The procedure of obtaining these parameters is described in detail in the instruction manual of the Internet module.
Module password reset function may be used when the user has changed the default password on the login page. If the user's new password is lost, the default password may be restored by resetting the module password.
4) Clock
This function is used to set current time and day of the week.
TECH
16
VII. Protections and alarms
In order to ensure safe and failure-free operation, the regulator has been equipped with a range of safeguards. In case of alarm, a sound signal is activated and the display shows an appropriate message.
Automatic sensor control If the valve temperature sensor or the external sensor is damaged, an alarm sound is activated and the display message informs about the failure e.g. 'Sensor damaged'. The pump is active regardless of the current temperature.
The alarm is active until a new sensor is installed.
Fuse
The regulator has a WT 6,3A tube fuse-link (5x20mm) protecting the network.
CAUTION: Higher amperage fuse should not be used as it may damage the controller.
VIII. Technical data
No.
Specification
Unit
1
Supply voltage
V
230V/50Hz +/-10%
2
Maximum power consumption
W
7
3
Ambient temperature
O
C
50
4
CH pump output load
A
0,5
5
Range of CH temperature measurement
O
C
0÷90
6
Accuracy of measurement
O
C
1
7
Thermal resistance of the sensor
O
C
-25÷90
8
Fuse link
A
6,3
L-6 User’s manual
17
Table of contents
I. Safety .......................................................................................................... 2
II. Description of the device .............................................................................. 3
III. Controller installation ................................................................................... 4
IV. Wireless communication ............................................................................... 6
V. First start-up .............................................................................................. 7
VI. How to use the controller ............................................................................. 8
V.a) Principle of operation .................................................................................. 8
V.b) Main screen view and description ................................................................. 9
V.c) Controller functions – main menu. ................................................................ 9
V.c.1) Block diagram – Main menu ................................................................. 10
V.c.2) Manual operation ................................................................................ 10
V.c.3) Channel ............................................................................................. 11
V.c.4) Main valve ......................................................................................... 11
V.c.5) External sensor .................................................................................. 12
V.c.6) Pump ................................................................................................ 13
V.c.9) Language selection ............................................................................. 13
V.c.10) Display contrast ................................................................................ 14
V.c.11) Fitter’s menu .................................................................................... 14
1) Registration .......................................................................................... 14
2) Room regulator ..................................................................................... 14
3) Internet module .................................................................................... 15
4) Clock .................................................................................................... 15
VII. Protections and alarms ............................................................................... 16
Fuse .............................................................................................................. 16
VIII. Technical data ........................................................................................ 16
TECH
18
We are committed to protecting the environment. Manufacturing electronic devices imposes an obligation of providing for environmentally safe disposal of used electronic components and devices. Hence, we have been entered into a register kept by the Inspection For Environmental Protection. The crossed-out bin symbol on a product means that the product may not be disposed of to household waste containers. Recycling of wastes helps to protect the environment. The user is obliged to transfer their used equipment to a collection point where all electric and electronic components will be recycled.
L-6 User’s manual
19
EU Declaration of conformity
Hereby, we declare under our sole responsibility that L-6 manufactured by TECH,
headquartered in Wieprz Biała Droga 31, 34-122 Wieprz, is compliant with:
Directive 1999/5/EC of the European Parliament and of the Council of 9 March 1999 on radio equipment and telecommunications terminal equipment and the mutual recognition of their conformity,
Directive 2014/35/EU of the European Parliament and of the Council of February 26, 2014 on the harmonisation of the laws of Member States relating to the making available on the market of electrical equipment designed for use within certain voltage limits (EU Journal of Laws L 96, of 29.03.2014, p. 357),
Directive 2014/30/EU of the European Parliament and of the Council of February 26, 2014 on the harmonisation of the laws of Member States relating to electromagnetic compatibility (EU Journal of Laws L 96 of 29.03.2014, p.79),
Directive 2009/125/EC establishing a framework for the setting of ecodesign requirements for energy-related products, the regulation by the Ministry of Economy of May 8, 2013 concerning the essential requirements as regards the restriction of the use of certain hazard-ous substances in electrical and electronic equip-ment, implementing provisions of RoHS directive 2011/65/EU.
For compliance assessment, harmonized standards were used:
PN-ETSI EN 301 489-1 V1.9.2:2012 PN-ETSI EN 301 489-3 V1.6.1:2014-03 PN-ETSI EN 300 220-1 V2.4.1:2013-02 PN-ETSI EN 300 220-2 V2.4.1:2013-02 PN-EN 60730-2-9:2011, PN-EN 60730-1:2012
Wieprz, 12. 10. 2015
TECH
20
Loading...