TDK-Lambda TPS3000 Series, TPS300048, TPS300024 Operation Manual

TPS3000 SERIES
POWER SUPPLY
OPERATION MANUAL
GENERAL SAFETY INSTRUCTIONS ........................................................................................................ 2
High Voltage Warning ................................................................................................................................ 2
Critical Components ................................................................................................................................... 2
Servicing ..................................................................................................................................................... 2
Safety Class of Protection........................................................................................................................... 2
Installation .................................................................................................................................................. 2
Ratings, Specifications and Features .............................................................................................................. 4
Emissions.................................................................................................................................................... 4
Immunity .................................................................................................................................................... 4
Maximum Ratings ...................................................................................................................................... 5
Input Specifications .................................................................................................................................... 5
Output Performance Specifications ............................................................................................................ 6
Protective Functions ................................................................................................................................... 6
Operating Modes ........................................................................................................................................ 6
DC Output Controls and Indicators ............................................................................................................ 7
Remote Control Features ............................................................................................................................ 7
PMBus Features.......................................................................................................................................... 8
Input, Output and Signal Connections ........................................................................................................ 8
Signal Connector ........................................................................................................................................ 9
Local Sense Setup...................................................................................................................................... 11
Remote Sense Setup .................................................................................................................................. 11
Parallel Operation Setup ............................................................................................................................12
Series Operation Setup ..............................................................................................................................14
Ripple and Noise Notes .................................................................................................................................16
Mechanical Drawing .....................................................................................................................................17
PMBus Interface ............................................................................................................................................18
1
30 July 2019
GENERAL SAFETY INSTRUCTIONS
TPS3000 SERIES
POWER SUPPLY
OPERATION MANUAL
High Voltage Warning
Dangerous voltages are present within the power supply.
Critical Components
This product is not authorized for use as a critical component in nuclear control systems, life support systems or equipment for use in hazardous environments without the express written approval of the Engineering Director of TDK-Lambda Americas.
Servicing
This product is not customer serviceable. Unit repairs shall only be carried out by TDK- Lambda Americas or their Authorized agents.
Contact: TDK-Lambda Americas 401 Mile of Cars Way, Suite 325 National City, CA 91950
Tel 619-575-4400 Fax 619-575-7185
Safety Class of Protection
The unit is designed for the following parameters: Material Group IIIb, Pollution Degree 2, Overvoltage Category II, Class 1 (earthed), Indoor use. The unit is considered as fixed and rated IPX0. The TPS300024 and TPS300048 are classed as having SELV outputs. All outputs are capable of providing hazardous energy (>240VA). The final equipment should provide protection to service personnel against inadvertent contact with the PSU output terminals.
Installation
This product is designed for use within other equipment which restricts access to Authorized competent personnel only. The unit covers/chassis must not be made user accessible.
The appliance may be mounted in any orientation.
The mains input connector is not acceptable for use as field wiring terminals. The appliance must be securely mounted and earthed before any connection to AC mains supply is made.
The ventilation openings must not be impeded – ensure a space at least 5cm between any obstruction and the ventilation openings.
BEFORE USING THE POWER SUPPLY UNIT
Be sure to read this instruction manual thoroughly before using this product. Pay attention to all cautions and warnings before using this product. Incorrect usage could lead to an electrical shock, damage to the unit or a fire hazard.
DANGER
Never use this product in locations where flammable gas or ignitable substances are present.
WARNING
Do not make unauthorized changes to power supply unit, otherwise you might have electric shock and void your warranty. Do not touch this unit and the internal components in operation or shortly after shut down. They might have high voltage or high temperature and as the unit dissipates its heat so the surface of the unit is hot. You might receive electric shock or burn.
When the unit is operating, keep your hands and face away from it; you might be injured by an accident. Do not use unit under unusual conditions such as emission of smoke or abnormal smell and sound etc.
It might cause fire and electric shock. In such case, please contact us; do not repair by yourself, as it is dangerous for the user.
2
30 July 2019
TPS3000 SERIES
POWER SUPPLY
OPERATION MANUAL
Do not drop or insert anything into unit. It might cause failure and fire. Do not operate these units under condensation condition. It might cause fire and electric shock.
CAUTION
As a component part, compliance with the standard will be based upon installation in the final application. This product must be installed in a restricted access location, accessible to authorized competent personnel only. These AC to DC converters have reinforced insulation between the input and the output. The outputs of these products are energy hazards. The equipment has been evaluated for use in a Pollution Degree 2 environment. This product is designed for use within other equipment or enclosures which restrict access to authorized competent personnel only and must not be user accessible. Confirm connections to input/output terminals and signal terminals are correct as indicated in the instruction manual. Input voltage, Output current, Output power, ambient temperature and ambient humidity should be used within specifications, otherwise the unit will be damaged. For application equipment, which requires very high reliability (Nuclear related equipment, traffic control equipment, medical equipment, etc.), please provide fail safety function in the equipment. Do not use the product in environment with strong electromagnetic field, corrosive gas and conductive substance. Do not operate and store this unit at an environment where condensation occurs. In such case, waterproof treatment is necessary Never operate the unit under over current or shorted conditions for 30 seconds or more and out of Input Voltage Range as specification. Insulation failure, smoking, burning or other damage might occur to the unit. The output voltage of this power supply unit is considered to be a hazardous energy level (The voltage is 2V or more and the electric power is 240VA or more). Prevention from direct contact with output terminal is highly necessary. While installing or servicing this power supply unit, avoid dropping tools by mistake or direct contact with output terminal. This might cause an electrical shock. While repairing this power supply unit, the AC input power must be switched off and the input and output voltage should be level. To maintain the SELV output, under fault conditions, the output must be connected to earth in the final application. The application circuits and their parameter are for reference only. Be sure to verify effectiveness of application circuits and their parameters before finalizing circuit design. Do not inject abnormal voltage to output terminal and signal terminal from the outside. The injection of reverse voltage or over voltage exceeding nominal output voltage to output terminals might cause damage to internal components. This information in this document is subject to change without prior notice. For actual design-in, please refer to the latest publications of data sheet, etc., for the most up-to date specifications of the unit.
3
30 July 2019
OPERATION MANUAL
AC Line Conducted Emissions
Conducted RF Common Mode
Power Frequency Magnetic
Ratings, Specifications and Features
Emissions
EN 55022: 2010+AC: 2011 (0.15-30 MHz) Class A
Radiated RF Emissions EN55032/EN55022/ EN55011 0-1000 MHz Class A
Immunity
Electrostatic Discharge IEC61000-4-2: 2008 +/-8 kV Air
+/-4 kV Contact
TPS3000 SERIES
POWER SUPPLY
RF Radiated Fields EN 61000-4-3: 2006
+A1:2008 +A2:2010
Electrical Fast Transients EN61000-4-4: 2004+A1:2010 Power line pulses of ± 1 kV;
Lightning Surge IEC61000-4-5: 2005 ±4kV common mode,
EN61000-4-6: 2009 150 kHz - 80 MHz at 3 Vrms
IEC61000-4-8:2009 30A/m (Continuous), 300A/m (Short)
Field
Voltage Dips/Short Variations IEC61000-4-11:2004 5% of nom. line for .5 cycles - Criteria B
Voltage Dips/Short Variations SEMI F47-0706 50% of nom. line for 10 cycles - Criteria B
3 V/m from 80-1000 MHz (80% AM at 1kHz)
I/O line pulses of ± 0.5 kV
±2kV differential mode
1 kHz 80% amplitude modulated
70% for 25 cycles - Criteria B 40% for 5 cycles - Criteria B 95% Dip for 5 seconds - Criteria B
70% for 25 cycles - Criteria B 80% for 50 cycles - Criteria B 0% for 1 cycle - Criteria B 80% for 10 seconds - Criteria B 95% Dip for 5 seconds - Criteria B
Table 1
4
30 July 2019
TPS3000 SERIES
Units
A(W)
A(W)
A(W)
A(W)
A(W)
POWER SUPPLY
OPERATION MANUAL
Maximum Ratings
Output Voltage Range1 V 19.5-28.5 38.4-56.5
Maximum Output Current (Power) @ 50°C2
Maximum Output Current (Power) @ 50°C3
Maximum Output Current (Power) @ 60°C3
Maximum Output Current (Power) @ 70°C3
Maximum Output Power with Dropped Phase4
53.75(1290W @ 350VAC)
81.25(1950W @ 480VAC)
Minimum Current5 A 0.5
Operating Temperature °C -10°C to 50°C.
Start-up Temperature °C -40°C to +70°C
1
Output voltage can be adjusted to be outside of the specified range. It is advised to limit the voltage to within the range.
2
Output adjustment at 24V only. Horizontal Mounting configuration only
3
Output current and power, as measured at output terminals, must be less than or equal to quoted maximum values for a
given ambient temperature.
4
Unit is able to handle the specified output power during dropped phase. Other specifications may not be met. Dropped phase should only be a temporary condition. Prolonged operation under dropped phase may result in decreased lifespan of the product.
5
Minimum current must be applied to meet all specifications. Without minimum power, some specifications may not be met.
Input Specifications
Units
Input Voltage VAC 400/480 (50/60Hz) Three Phase Delta
Input Current (RMS) Per Phase 400-480VAC input Inrush Current (Peak, at cold start) Per Phase, 400-480VAC input
*
Power Factor (at max output power) - 0.92 typical @ 400/480VAC line
Input EMI Conducted Emissions - FCC Class A, CISPR 22 Class A
Efficiency (at max output power) % 92 typical @ 400/480VAC line
*
excluding initial spike charging EMI capacitors lasting <2mS
A 5.5 5.5
A <15 <15
TPS300024 TPS300048
133.3(3200) 66.7(3200)
125(3000) 66.7(3200)
100(2400) 50(2400)
68.75(1650) 34.375(1650)
26.875(1290W @ 350VAC)
65(1560W @ 400VAC)
32.5(1560W @ 400VAC)
40.625(1950W @ 480VAC)
87.5(2100W @ 528VAC)
43.75(2100W @ 528VAC)
Derating 50°C-60°C - 2%/C, 60°C-70°C 2.5%/C
TPS300024 TPS300048
Table 2
Table 3
5
30 July 2019
TPS3000 SERIES
POWER SUPPLY
OPERATION MANUAL
Output Performance Specifications
Units TPS300024 TPS300048
Max Voltage Line Regulation % Less than 0.25%
Max Voltage Load Regulation % Less than 0.5%
Total Regulation % Less than 1.75%
Warm up Drift % Less than 0.15%
Temperature Stability - 0.05% of rated Vout for 8hrs after 30min
warm-up. Constant line, load & temp.
Temperature Coefficient ppm/°C 200ppm/C
Ripple/Noise P-P(20MHz), JEITA RC-9131C6 mVp-p 240 480
Output Ripple, JEITA RC-9131C6 mVrms <0.5% of Vout
Remote Sense Compensation (Total) V 1.0V 1.0V
6
See Ripple and Noise Notes for Details on Jeita RC-9131C method; All Three Phases present
Table 4
Protective Functions
Units TPS300024 TPS300048
OCP TYPE - CONSTANT CURRENT
OCP KNEE POINT7 - Adjustable (70% - 105% of max rated current)
KNEE POINT PROTECTION - NONE. NO DAMAGE AT KNEE POINT
S/C PROTECTION - CONSTANT CURRENT w/ time-delayed shutdown.
SHORTED OUTPUT ON - NO DAMAGE
OVP TYPE - Tracking, Inverter shut-down, manual reset by AC input
recycle or by On/Off control.
OVP RANGE - Vout*1.15
OVP RESET TIME s Less than 5s AC recycle or remote ON/OFF toggle
OTP - Yes. Standard: Non-Latch type (automatic reset),
7
OCP Knee point can physically be adjusted to a value greater than 105% of max rated current. It is advised to limit the current to 105% max.
Table 5
Operating Modes
Series Operation Yes
Parallel Operation Current share single wire (Terminal 1 on Signal Connector), 10%
accuracy of max Iout up to 8 units. Power derated 10% of rated. No Oring diodes are required for redundant operation as the power supplies contain internal Oring MOSFETS.
Table 6
6
30 July 2019
TPS3000 SERIES
POWER SUPPLY
OPERATION MANUAL
DC Output Controls and Indicators
Output Voltage Adjust Screwdriver adjustment over entire range. Output voltage range is
specified in Table 2. (Multi-turn potentiometer accessible from terminal end of chassis.)
Overcurrent Protection Adjust Screwdriver adjustable (70% - 105% of max rated current)
DC OK LED: Green when output >90% of set voltage, Red when fault.
LED will turn off when unit enters OTW range.
AC ON LED: Green when AC is present
Blinking RED/GRN when phase dropped (Applicable for 400/480 with 20% Load or greater).
Table 7
Remote Control Features
Remote Voltage Sensing Provides precise regulation directly at load. Maximum total DC voltage
drop between output terminals and load must be limited to <1.0 V. In addition, the voltage at the output terminals must be limited to the maximum voltage range specified in Table 2.
Remote On/Off Control On/Off control: Selectable Enable or Inhibit via front panel switch.
Switch in the ON position: Unit powers up if PSON left open; Unit in standby mode if PSON shorted to -SNS Switch in the OFF position: Unit in standby mode if PSON left open; Unit powers up if PSON shorted to -SNS PSON High / Low thresholds: 3.0V / 0.6V 12V Maximum allowable.
-5V Minimum allowable Signal applied between terminals 14 (PSON) and 18 (-SNS) on Signal
Connector. Remote Voltage Programming
Remote Overcurrent Limit Programming
Provides remote adjustment of the output voltage via a DC voltage
applied between terminals 3 (VADJ) and 18 (-SNS) on Signal
Connector.
0V = Vout max, 5V = Vout min
Adjustments of greater than 1V/Sec can cause Fault conditions
Adjustment range changes with adjustment of V
Provides remote adjustment of the Overcurrent limit via a DC voltage
applied between terminals 10 (IADJ) and 18 (-SNS) on Signal
Connector.
0V = Iout max, 5V = Iout min
Adjustment range changes with adjustment of I
Adj trim pot.
out
ADj trim pot.
LIMIT
Table 8
7
30 July 2019
TPS3000 SERIES
POWER SUPPLY
OPERATION MANUAL
PMBus Features
Output Voltage Monitoring Output voltage monitoring via the PMBus.
Accuracy of the voltage reading is +/-2% of full scale
Output Current Monitoring Output current monitoring via the PMBus.
Accuracy of the current reading is +/-10% of full scale Remote On/Off Control Supply ON/OFF control via the PMBus
Remote Voltage Programming
Remote Overcurrent Limit Programming
Input, Output and Signal Connections
Input Heavy Duty terminal block with M4 screws. Grounding terminal
DC Output Heavy-duty bus bars with 9mm clearance hole for load connections.
Signal Connector 20 pin signal connector. See Table 11 for pin configuration
Address Pin / PMBus Voltage Selector Pin
Provides remote adjustment of the output voltage via the PMBus
interface.
Adjustments of greater than 1V/Sec can cause Fault conditions
Provides remote adjustment of the Overcurrent limit via the PMBus
interface.
Table 9
included on terminal block.
Recommended mating connector: JST P/N: PHDR-20VS
Recommended receptacle contacts: JST P/N: SPHD-001T-P0.5
10 pin connector.
Rows 1-4 used for PMBus address selection.
Row 5 used to select PMBus Voltage Selection. Open = 5V; Short = 3.3V
Recommended shunt jumper: Samtec P/N: 2SN-BK-G
Table 10
8
30 July 2019
Loading...
+ 17 hidden pages