TDK-Lambda
PFE300SA・500SA Series
INSTRUCTION MANUAL
PFE300SA・500SA Series
Instruction Manual
BEFORE USING THE POWER SUPPLY UNIT
Be sure to read this instruction manual thoroughly before using this product. Pay attention to all cautions and warnings before
using this product. Incorrect usage could lead to an electrical shock, damage to the unit or a fire hazard.
DANGER
Never use this product in locations where flammable gas or ignitable substances are present. There are risks of igniting these
substances and exploding by an arcing.
WARNING
· Do not touch this product or its internal components while circuit is live, or shortly after shut down.
high voltage or high temperature present and you may receive an electric shock or burn.
· While this product is operating, keep your hands and face away from it as you may be injured by an unexpected situation.
· Do not make unauthorized changes to this product, otherwise you may receive an electric shock and void your warranty.
· Do not drop or insert anything into the product. It might lead to a failure, fire and electric shock.
· Do not use this product under unusual condition such as emission of smoke or abnormal smell and sound etc.
It might lead fire and electric shock, In such cases, please contact us. Do not attempt repair by yourself, as it is dangerous for
the user.
· Do not operate these products in the presence of condensation. It might lead to fire and electric shock.
CAUTION
· This power supply is designed and manufactured for use within an end product such that it is accessible to
SERVICE ENGINEERS only.
· Confirm connections to input/output terminals and signal terminals are correct as indicated in the instruction manual
before switching on.
· Input voltage, Output current, Output power, ambient temperature, base-plate temperature and ambient humidity should be
kept within specifications, otherwise the product will be damaged.
· Do not operate and store this product in an environment where condensation might occur. In such case, waterproof treatment
is necessary.
· The equipment has been evaluated for use in a Pollution Degree 2 environment.
· Do not use this product in environment with a strong electromagnetic field, corrosive gas or conductive substances.
· For application which requires very high reliability (Nuclear related equipment, medical equipment, traffic control
equipment, etc.), It is necessary to provide a fail-safe mechanism in the end equipment.
· Do not inject abnormal voltages into the output terminal or signal terminal of this product. The injection of reverse voltage or
over voltage exceeding nominal output voltage into the output terminal or signal terminal might cause damage to internal
components.
· Never operate the product under overcurrent or short circuit conditions. Insulation failure, or other damages may occur.
· The output voltage of this power supply unit is considered to be a hazardous energy level (The voltage is 2V or more and the
electric power is 240VA or more). It must not be made accessible to users. Protection must be provided for Service Engineers
against indirect contact with the output terminals and/or to prevent tools being dropped across them. While working on this
product, the AC input power must be switched off and the input, output, +BC, -BC and R terminal voltage should be safe
level.
· The application circuits and their parameters are for reference only. Be sure to verify effectiveness of these circuits and their
parameters before finalizing the circuit design.
· Use a Fast-Blow external fuse to each module to ensure safe operation and compliance with the safety standards to which it is
approved. The recommended input fuse rating within the instructions is as follows: 15A, 250V fast acting fuse. The breaking
capacity and voltage rating of this fuse may be subject to the end use application.
C265-04-11D
![](/html/66/6696/6696483f793a13f254b1365c21a4f7877c417a145bd4e40db2a19abb9c3f5c1f/bg2.png)
TDK-Lambda
・
PFE300SA
INSTRUCTION MANUAL
500SA Series
CAUTION
· The outputs less than 28V model has possibility that hazardous voltage may occur in output terminal depending on failure mode.
The output of these products must be protected in the end use equipment to maintain SELV.
· 48V output model are considered non-SELV. End equipment manufacturers must provide protection against inadvertent
contact by a service engineer.
· This information in this document is subject to change without prior notice. Please refer to the latest version of the data sheet,
etc., for the most up-to date specifications of the product.
· No part of this document may be copied or reproduced in any form without prior written consent TDK-Lambda.
Note : CE MARKING
CE Marking, when applied to a product covered by this handbook, indicates compliance with the low voltage directive.
C265-04-11D
![](/html/66/6696/6696483f793a13f254b1365c21a4f7877c417a145bd4e40db2a19abb9c3f5c1f/bg3.png)
1. Model name identification method
PFE 500 SA – 12 /□
Option(*1)
Rated Output Voltage
Simple function
Output Power type
Series Name
2. Terminal Explanation
①
②
- Base-plate can be connected to FG through M3 mounting tapped holes.
- Consider contact resistance when connecting AC(L), AC(N), R, +BC, –BC, +V, –V.
- Note that +BC and –BC terminal are primary voltage with high voltage (390VDC).
Do not connect load from these terminals.
Name plate
④③
⑤
⑥
⑦
⑧
⑨
⑩
⑪
(*1) /Blank:Standard
/T :Mounting standφ3.3
① AC(N)
② AC(L)
③
④ +BC
⑤ -BC
⑥ -V
⑦ +V
⑧ -S
⑨ +S
⑩ TRIM
⑪ ENA
① : Input terminal neutral line
② : Input terminal live line
③ : External inrush current limiting
④ resister terminal
⑤ : +Boosted voltage terminal
⑥ : -Boosted voltage terminal
⑦ : -Output voltage
⑧ : +Output voltage
⑨ : -Remote sensing terminal
⑩ : +Remote sensing terminal
⑪ : Output voltage trimming terminal
⑫ : Power on signal terminal
TDK-Lambda
・
PFE300SA
INSTRUCTION MANUAL
(Non-threaded through hole)
500SA Series
1
![](/html/66/6696/6696483f793a13f254b1365c21a4f7877c417a145bd4e40db2a19abb9c3f5c1f/bg4.png)
3. Block Diagram
TDK-Lambda
・
PFE300SA
INSTRUCTION MANUAL
500SA Series
Rectifier
detector
Input voltage
Input current
Switching Frequency
PFHC Circuit (fixed) : 100kHz
DC/DC Converter Circuit (fixed) 12, 28V : 230kHz (primary), 460kHz (secondary)
DC/DC Converter Circuit (fixed) 12, 48V : 180kHz (primary), 360kHz (secondary)
4. Sequence Time Chart
Filter
Inrush current
limiting circuit
OVP
detector
Control circuit
voltage
detector
Boosted
Switching circuit
OCP
OTP
Control circuit
Rectifier
Output filter
ON
Input Line
OVP
Cut-off
Acitivate
Input Line
ON
Input Line
OCP
Note : This product has no remote ON/OFF function.
V* voltage level: Refer to Application Notes “6-8.Power ON Signal (ENA Terminal)” section.
OCP
Release
Activate
Cut-off
Input Line
ON
Input Line
OTP
Circuit
Cut-off
Activate
Input Line
ON
Input Line
2
![](/html/66/6696/6696483f793a13f254b1365c21a4f7877c417a145bd4e40db2a19abb9c3f5c1f/bg5.png)
TDK-Lambda
PFE300SA
INSTRUCTION MANUAL
5. Terminal connecting method
In order to use the PFE300SA,500SA Series, this module must be connected with external components
according to Fig.5-1.
Pay attention to the each wiring. If it is connected to wrong terminal, the power supply will be damaged.
PFE300SA,500SA Series employs conduction cooling method. Use heat sink and fan to dissipate heat.
For selection of heat sink and heat sink dissipation method, refer to the Power Module Application Note.
C13
C12
L= 50mm
C11
C15 C16
C14
F1
L1 L2
C2
C1
C3
AC(L)
C6
C4
R1
C7
C5
PFE300SA
PFE500SA
AC(N)
BASE-PLATE
TFR1
+S
+V
-V
-S
TRIM
ENA
+BCR
-BC
C8
Input Filter
(For VCCI-classA)
Fig.5-1 Basic connection
C9
C10
・
500SA Series
+
Load
-
3
![](/html/66/6696/6696483f793a13f254b1365c21a4f7877c417a145bd4e40db2a19abb9c3f5c1f/bg6.png)
F1 : External Input Fuse
PFE300SA,500SA Series has no internal fuse. Use external fuse to acquire each Safety Standard and to
further improve safety. PFE300SA,500SA Series acquired safety standard certification using 15A,
250V,Fast-Blow external fuse. Further, Fast-Blow type fuse must be used per one module. Also, in-rush
surge current flows during line throw-in. Be sure to check I2t rating of external switch and external fuse.
Recommended External Fuse:15A , 250V
Note) Select fuse based on rated voltage, rated current and surge current capability.
(1) Voltage Ratings
100VAC line : AC125V
200VAC line : AC250V
(2) Current Ratings
Rated current is determined by the maximum input current based on operating conditions and can be
calculated by the following formula.
For Efficiency and Power Factor values, refer to separate document “PFE300SA Series Evaluation Data”
or “PFE500SA Series Evaluation Data”.
C1, C4, C5 : 1uF (Film Capacitor)
Ripple current flows through this capacitor. When selecting capacitor, be sure to check the allowable
maximum ripple current rating of this capacitor. Verify the actual ripple current flowing through this
capacitor by doing actual measurement.
Connect C5 as close as possible towards the input terminals AC(N) and AC(L) of this power module.
Recommended Voltage Rating : 250VAC
L1, L2 : 6mH
Add common mode choke coil as EMI/EMS countermeasure. When using multiple modules, connect coil to
each module.
Note) Depending on the input filter used, noise might increase or power module might malfunction due to
C2, C3 : 4700pF(Ceramic Capacitor)
Add ceramic capacitor as EMI/EMS countermeasure. Be sure to consider leakage current of your equipment
when adding this capacitor.
High withstand voltage are applied across this capacitor depending on the application. Select capacitor with
high withstand voltage rating.
(max)Iin
Iin (max) : Maximum Input Current
Pout : Maximum Output Power
Vin : Minimum Input Voltage
η : Efficiency
PF : Power Factor
filter resonance.
Pout
=
(Arms)
PFηVin
´´
(Formula 5-1)
TDK-Lambda
PFE300SA
INSTRUCTION MANUAL
・
500SA Series
4