TDK-Lambda LZS-A1500-3-001 Installation, Operation And Maintenance Manual

LZS-A1500-3-001 POWERSUPPLY
Installation, Operation, and Maintenance Manual
IM-LLZSA1500-33-0001
November 2013
Revision C
Revision C : November 2013
LZS-AA1500-33-0001 Power Supply
Page. 1
Table of Contents
1) Safety and Recommended Practices 2
1.1
General safety instructions 2
1.2
Safety Agency Approvals 2
2) RATINGS AND SPECIFICATIONS 4
3) FEATURES 6
4) GUIDE TO
APPLICATION 8
4.1
Safety Notice
8
4.2
Input Voltage
8
4.3
Output Voltage
8
4.4
Overvoltage Protection Circuit Adjustment
8
4.5
Overtemperature and Overvoltage Shutdown
8
4.6
Auxiliary Control and Alarm Signals
8
5) FIGURES 9
LZS-AA1500-33-0001 Power Supply
Revision C : November 2013
Page. 2
1 Safety and Recommended Practices
1.1 General Safety Instructions
This power supply is a switch mode power supply for use in applications meeting a Pollution Degree 2 environment. A suitable mechanical and fire enclosure must be provided by the end use equipment for shock hazard protection, fire protection and protection from hazardous energy levels.
READ SAFETY INSTRUCTIONS carefully before working on the unit.
HIGH VOLTAGE WARNING: Dangerous voltages are present within the power supply.
NO USER SERVICEABLE PARTS INSIDE.
1. Do not install, test or operate this product near water, and do not spill any liquid on it.
2. Do not operate this product unless it is in a secure position.
3. This product must be installed and put into service by authorized competent per­sonnel only who are fully conversant with the hazards of AC line operated equipment and with the particular dangers associated with switch mode power supplies.
4. This product is designed for use within other equipment or enclosures which restrict access to authorized competent per­sonnel only and must not be user accessible.
5. This product must be reliably earthed and professionally installed in accordance with the prevailing electrical wiring regula­tions and safety standards. The product's PE connection is via the tapped standoff and screw on the front panel marked with IEC 60417-1 Symbol 5019.
6. The case is connected to the product's PE connection with screws. Therefore, screws at the case must not be removed or loosened.
7. The output power taken from the power supply must not exceed the rating stated on the power supply label.
1 Sicherheitsvorschriften und Vorsichtsmassnahmen
1.1 Allgemeine Sicherheitsanweisungen
Dieses Netzteil ist ein Primaerschaltregler Geraet für Applikationen mit Verschmutzungsgrad 2. Eine passende mechanische Abdeckung und Brandschutzumhuellung ist in der Endanwendung sicherzustellen zum Schutz gegen Beruehren gefaehrlicher Spannungen, als Brandschutz und zum Schutz vor Personenschaeden durch gefaehrliche Energieinhalte.
DIE SICHERHEITSHINWEISE SIND gruendlich zu beachten bevor Arbeiten am Geraet vorgenommen werden.
ACHTUNG HOCHSPANNUNG: Gefaehrliche Spannungen sind im Geraet vorhanden.
ES SIND KEINE SERVICETEILE INNERHALB DES GERAETES VORHANDEN.
1. Dieses Produkt darf nicht in der Naehe von Wasser betrieben werden. Fluessigkeiten duerfen darauf nicht verschuettet werden.
2. Schalten Sie das Geraet nicht ein bevor es sicher eingebaut ist und im bestim­mungsgemaeßen Einsatz installiert ist.
3. Die Installation sowie Servicearbeiten sind nur durch geschultes und zugelassenes Personal zulaessig, welches sowohl die Gefahren von gefaehrlichen AC­Netzspannungen kennt und die beson­deren Gefahren die in einem Primaerschaltreglernetzteil auftreten erfahrungsgemaess einschaetzen kann.
4. Dieses Geraet ist eine Einbaukomponente für Endanwendungen mit Gehaeuse, welches nur limitierten Zugang für autorisiertes Personal zulaesst. Die Geraeteabdeckung darf nicht durch Endanwender geoeffnet werden.
5. Dieses Geraet ist zuverlaessig zu erden nach Schutzklasse1. Die Installation ist nach den allgemein gueltigen und zutreffenden elektrischen Sicherheitsrichtlinien profes­sionell durchzufuehren. Der PE Anschluss, Gewindebolzen bzw./und Schraube auf der Frontplatte gekennzeichnet mit IEC 60417-1 Symbol 5019 sind dafür vorgesehen.
6. Das Geraetegehaeuse ist durch Schrauben mit der Schutzerde verbunden. Gehaeuseschrauben duerfen daher weder gelockert noch entfernt werden.
7. Die entnommene Ausgangsleistung darf nicht hoeher sein als die auf dem Geraetelabel angegebene Ausgangsleistung.
LZS-AA1500-33-0001 Power Supply
8. Openings in the product case are designed for ventilation and must not be obstructed when the product is installed and/or operated.
9. Never push objects of any kind into the product through openings in its case as this could result in electric shock or fire hazard.
10. Use copper stranded wire only, 12 to 14 AWG rated at 105°C for the AC input. All strands must be secured in the terminal block to avoid potential danger of short circuit.
11. Properly torque AC input terminals to 9 in-lb.
12. An internal fuse protects the unit and must not be replaced by the user. In case of internal defect, the unit must be returned to the manufacturer.
13. The output of this power supply is haz­ardous and must not be user accessible in the end use equipment. The (+) or (-) output can be earthed. Use wire rated at 105°C and sized for 150% of the rated load.
14. The unit contains components that require special disposal. Make sure that the unit is properly disposed of at the end of its service life.
1.2 Safety Agency Approvals
Regulatory agency compliance applies only for operating frequencies between 47-63Hz.
No safety agency approvals for 100-380VDC operation.
This product is approved to UL 60950­1/CAN CSA C 22.2 No. 60950-1-07 Second Edition, UL 508, Seventeenth Edition, EN 60950-1:2006+A11, IEC 60950-1:2005, FM.
The CE Marking, when applied to the prod­uct, indicates conformance to the provi­sions of the following European Directives:
2006/95/EC Low Voltage Directive 2008/108/EC EMC Directive
8. Oeffnungen und Lochungen am Gehaeuse sind fuer Lueftungszwecke vorgesehen und duerfen nicht abgedeckt werden.
9. Fremdgegenstände oder Teile niemals in Gehaeuseoeffnungen bringen, es besteht Gefahr durch moeglichen elektrischen Schlag der ggf. Personenschaeden zur Folge haette.
10. Als Netzanschluss ist eine flexible Kupferleitung (Litze) mit 2,5 mm² Mindest­Querschnitt zu verwenden die bis 105°C zugelassen ist. Alle Adern sind im Anschlussklemmblock zu sichern damit Gefahren von Kurzschluessen vermieden werden.
11. Empfohlenes Drehmoment für die AC Anschlussklemmen ist 1,2Nm.
12. Eine interne Geraete - Absicherung ist eingebaut. Diese sollte nicht durch den Anwender getauscht werden. Bei Defekt des Geraetes ist dieses zu Servicezwecken an den Hersteller oder dessen zugelassene Servicestelle zurueckzugeben.
13. Das Geraet liefert gefaehrliche Energieinhalte und Spannungen, die Anschluesse sind in der Endanwendung beruehrungsfrei einzubauen. Es kann entweder der (+) oder der (-) Anschluss geerdet werden. Dafuer sind geeignete Kabel mit 105°C Temperaturfestigkeit und 150% Ueberlastfestigkeit zu beruecksichtigen.
14. Das Geraet enthaelt Bauteile die nach geltendem nationalem Recht getrennt zu entsorgen sind. Bitte beachten Sie die sichere und bestimmungsgemaesse Entsorgung am Ende der Produktlebenszeit.
1.2 Sicherheitszulassungen
Die amtlichen Zulassungen treffen zu für Anwendungen im Frequenzbereich von 47 bis 63 Hz.
Es bestehen keine Zulassungen für den DC- Betrieb im Bereich 100 bis 380VDC.
Das Geraet is zugelassen nach UL 60950­1/CAN CSA C 22.2 No. 60950-1-07 Second Edition, UL 508, Seventeenth Edition, EN 60950-1:2006+A11, IEC 60950-1:2005, FM.
Die CE Kennzeichnung, wenn auf dem Geraet angebracht, zeigt Uebereinstimmung mit den folgenden EU Richtlinien:
2006/95/EC Niederspannungsrichtlinie 2008/108/EC EMV Richtlinie
Page. 3
Revision C : November 2013
Page. 3
Revision C : November 2013
LZS-AA1500-33-0001 Power Supply
Revision C : November 2013
Page. 4
Emissions
Table 1
AC Line Conducted Emissions EN55022/EN55011 (0.15-30 MHz) Class B Radiated RF Emissions EN55022/EN55011 30-1000 MHz Class B Powerline Harmonics EN61000-3-2 Class A Limits Powerline Fluctuation/Flicker EN61000-3-3 Complies
Immunity
Electrostatic Discharge IEC61000-4-2 +/-8 kV Air
+/-6 kV Contact
RF Radiated Fields IEC61000-4-3 10 V/m, 80 MHz-2.5GHz
80% AM @ 1kHZ
Electrical Fast Transients IEC61000-4-4 +/-2 kV AC Line, Criteria A
+/-1 kV I/O Line > 3m, Criteria A
Lightning Surge IEC61000-4-5 +/-2 kV line to GND (CM), Criteria A
+/-1 kV line to line (DM), Criteria A
Conducted RF Common Mode IEC61000-4-6 10 V/m RMS, 150 kHz-80 MHz
80% AM at 1kHz Power Frequency Magnetic Field IEC61000-4-8 3 A/m Voltage Dips/Short Variations IEC61000-4-11 5% of nom. line for .5 cycles - Criteria A
40% for 5 cycles - Criteria A
70% for 25 cycles - Criteria A
95% Dip for 5 seconds -
Unit should not latch
SEMI-F47 50% of nom. line for 200 msec (110 VAC@1000W, 70% for 500 msec 220 VAC@1500W) 80% for 10 seconds
90% for 15 seconds
0% for 1 cycle or 20mS
Additional Immunity
Ring Wave Lightning Surge Test IEEE C62.41 6 kV/30 Ohm Criteria A
This manual is a description of specifications, features and applications of LZS-A1500 power supplies.
RATINGS AND SPECIFICATIONS *
Maximum Ratings
Units LZS-A1500-3
Table 2
Output Voltage Range V 18-29.4 Output Current (Power) @ 60°C** A(W) 63 (1512) DC Output @ 24V Output Current (Power) @ 70°C** A(W) 37.8 (907) Operating Temperature °C 100% rated load from -30°C to 60°C derate linearly to
60% @ 70°C (4%/°C)
Start-up Temperature °C -40° to +70°
* Refer to figures 1-7 for supply-load connection information. ** Output current and power, as measured at output terminals, must be less than
or equal to quoted maximum values for a given ambient temperature and input voltage. See Table 4.