TDK-Lambda LZS-A1500-3-001 Installation, Operation And Maintenance Manual

LZS-A1500-3-001 POWERSUPPLY
Installation, Operation, and Maintenance Manual
IM-LLZSA1500-33-0001
November 2013
Revision C
Revision C : November 2013
LZS-AA1500-33-0001 Power Supply
Page. 1
Table of Contents
1) Safety and Recommended Practices 2
1.1
General safety instructions 2
1.2
Safety Agency Approvals 2
2) RATINGS AND SPECIFICATIONS 4
3) FEATURES 6
4) GUIDE TO
APPLICATION 8
4.1
Safety Notice
8
4.2
Input Voltage
8
4.3
Output Voltage
8
4.4
Overvoltage Protection Circuit Adjustment
8
4.5
Overtemperature and Overvoltage Shutdown
8
4.6
Auxiliary Control and Alarm Signals
8
5) FIGURES 9
LZS-AA1500-33-0001 Power Supply
Revision C : November 2013
Page. 2
1 Safety and Recommended Practices
1.1 General Safety Instructions
This power supply is a switch mode power supply for use in applications meeting a Pollution Degree 2 environment. A suitable mechanical and fire enclosure must be provided by the end use equipment for shock hazard protection, fire protection and protection from hazardous energy levels.
READ SAFETY INSTRUCTIONS carefully before working on the unit.
HIGH VOLTAGE WARNING: Dangerous voltages are present within the power supply.
NO USER SERVICEABLE PARTS INSIDE.
1. Do not install, test or operate this product near water, and do not spill any liquid on it.
2. Do not operate this product unless it is in a secure position.
3. This product must be installed and put into service by authorized competent per­sonnel only who are fully conversant with the hazards of AC line operated equipment and with the particular dangers associated with switch mode power supplies.
4. This product is designed for use within other equipment or enclosures which restrict access to authorized competent per­sonnel only and must not be user accessible.
5. This product must be reliably earthed and professionally installed in accordance with the prevailing electrical wiring regula­tions and safety standards. The product's PE connection is via the tapped standoff and screw on the front panel marked with IEC 60417-1 Symbol 5019.
6. The case is connected to the product's PE connection with screws. Therefore, screws at the case must not be removed or loosened.
7. The output power taken from the power supply must not exceed the rating stated on the power supply label.
1 Sicherheitsvorschriften und Vorsichtsmassnahmen
1.1 Allgemeine Sicherheitsanweisungen
Dieses Netzteil ist ein Primaerschaltregler Geraet für Applikationen mit Verschmutzungsgrad 2. Eine passende mechanische Abdeckung und Brandschutzumhuellung ist in der Endanwendung sicherzustellen zum Schutz gegen Beruehren gefaehrlicher Spannungen, als Brandschutz und zum Schutz vor Personenschaeden durch gefaehrliche Energieinhalte.
DIE SICHERHEITSHINWEISE SIND gruendlich zu beachten bevor Arbeiten am Geraet vorgenommen werden.
ACHTUNG HOCHSPANNUNG: Gefaehrliche Spannungen sind im Geraet vorhanden.
ES SIND KEINE SERVICETEILE INNERHALB DES GERAETES VORHANDEN.
1. Dieses Produkt darf nicht in der Naehe von Wasser betrieben werden. Fluessigkeiten duerfen darauf nicht verschuettet werden.
2. Schalten Sie das Geraet nicht ein bevor es sicher eingebaut ist und im bestim­mungsgemaeßen Einsatz installiert ist.
3. Die Installation sowie Servicearbeiten sind nur durch geschultes und zugelassenes Personal zulaessig, welches sowohl die Gefahren von gefaehrlichen AC­Netzspannungen kennt und die beson­deren Gefahren die in einem Primaerschaltreglernetzteil auftreten erfahrungsgemaess einschaetzen kann.
4. Dieses Geraet ist eine Einbaukomponente für Endanwendungen mit Gehaeuse, welches nur limitierten Zugang für autorisiertes Personal zulaesst. Die Geraeteabdeckung darf nicht durch Endanwender geoeffnet werden.
5. Dieses Geraet ist zuverlaessig zu erden nach Schutzklasse1. Die Installation ist nach den allgemein gueltigen und zutreffenden elektrischen Sicherheitsrichtlinien profes­sionell durchzufuehren. Der PE Anschluss, Gewindebolzen bzw./und Schraube auf der Frontplatte gekennzeichnet mit IEC 60417-1 Symbol 5019 sind dafür vorgesehen.
6. Das Geraetegehaeuse ist durch Schrauben mit der Schutzerde verbunden. Gehaeuseschrauben duerfen daher weder gelockert noch entfernt werden.
7. Die entnommene Ausgangsleistung darf nicht hoeher sein als die auf dem Geraetelabel angegebene Ausgangsleistung.
LZS-AA1500-33-0001 Power Supply
8. Openings in the product case are designed for ventilation and must not be obstructed when the product is installed and/or operated.
9. Never push objects of any kind into the product through openings in its case as this could result in electric shock or fire hazard.
10. Use copper stranded wire only, 12 to 14 AWG rated at 105°C for the AC input. All strands must be secured in the terminal block to avoid potential danger of short circuit.
11. Properly torque AC input terminals to 9 in-lb.
12. An internal fuse protects the unit and must not be replaced by the user. In case of internal defect, the unit must be returned to the manufacturer.
13. The output of this power supply is haz­ardous and must not be user accessible in the end use equipment. The (+) or (-) output can be earthed. Use wire rated at 105°C and sized for 150% of the rated load.
14. The unit contains components that require special disposal. Make sure that the unit is properly disposed of at the end of its service life.
1.2 Safety Agency Approvals
Regulatory agency compliance applies only for operating frequencies between 47-63Hz.
No safety agency approvals for 100-380VDC operation.
This product is approved to UL 60950­1/CAN CSA C 22.2 No. 60950-1-07 Second Edition, UL 508, Seventeenth Edition, EN 60950-1:2006+A11, IEC 60950-1:2005, FM.
The CE Marking, when applied to the prod­uct, indicates conformance to the provi­sions of the following European Directives:
2006/95/EC Low Voltage Directive 2008/108/EC EMC Directive
8. Oeffnungen und Lochungen am Gehaeuse sind fuer Lueftungszwecke vorgesehen und duerfen nicht abgedeckt werden.
9. Fremdgegenstände oder Teile niemals in Gehaeuseoeffnungen bringen, es besteht Gefahr durch moeglichen elektrischen Schlag der ggf. Personenschaeden zur Folge haette.
10. Als Netzanschluss ist eine flexible Kupferleitung (Litze) mit 2,5 mm² Mindest­Querschnitt zu verwenden die bis 105°C zugelassen ist. Alle Adern sind im Anschlussklemmblock zu sichern damit Gefahren von Kurzschluessen vermieden werden.
11. Empfohlenes Drehmoment für die AC Anschlussklemmen ist 1,2Nm.
12. Eine interne Geraete - Absicherung ist eingebaut. Diese sollte nicht durch den Anwender getauscht werden. Bei Defekt des Geraetes ist dieses zu Servicezwecken an den Hersteller oder dessen zugelassene Servicestelle zurueckzugeben.
13. Das Geraet liefert gefaehrliche Energieinhalte und Spannungen, die Anschluesse sind in der Endanwendung beruehrungsfrei einzubauen. Es kann entweder der (+) oder der (-) Anschluss geerdet werden. Dafuer sind geeignete Kabel mit 105°C Temperaturfestigkeit und 150% Ueberlastfestigkeit zu beruecksichtigen.
14. Das Geraet enthaelt Bauteile die nach geltendem nationalem Recht getrennt zu entsorgen sind. Bitte beachten Sie die sichere und bestimmungsgemaesse Entsorgung am Ende der Produktlebenszeit.
1.2 Sicherheitszulassungen
Die amtlichen Zulassungen treffen zu für Anwendungen im Frequenzbereich von 47 bis 63 Hz.
Es bestehen keine Zulassungen für den DC- Betrieb im Bereich 100 bis 380VDC.
Das Geraet is zugelassen nach UL 60950­1/CAN CSA C 22.2 No. 60950-1-07 Second Edition, UL 508, Seventeenth Edition, EN 60950-1:2006+A11, IEC 60950-1:2005, FM.
Die CE Kennzeichnung, wenn auf dem Geraet angebracht, zeigt Uebereinstimmung mit den folgenden EU Richtlinien:
2006/95/EC Niederspannungsrichtlinie 2008/108/EC EMV Richtlinie
Page. 3
Revision C : November 2013
Page. 3
Revision C : November 2013
LZS-AA1500-33-0001 Power Supply
Revision C : November 2013
Page. 4
Emissions
Table 1
AC Line Conducted Emissions EN55022/EN55011 (0.15-30 MHz) Class B Radiated RF Emissions EN55022/EN55011 30-1000 MHz Class B Powerline Harmonics EN61000-3-2 Class A Limits Powerline Fluctuation/Flicker EN61000-3-3 Complies
Immunity
Electrostatic Discharge IEC61000-4-2 +/-8 kV Air
+/-6 kV Contact
RF Radiated Fields IEC61000-4-3 10 V/m, 80 MHz-2.5GHz
80% AM @ 1kHZ
Electrical Fast Transients IEC61000-4-4 +/-2 kV AC Line, Criteria A
+/-1 kV I/O Line > 3m, Criteria A
Lightning Surge IEC61000-4-5 +/-2 kV line to GND (CM), Criteria A
+/-1 kV line to line (DM), Criteria A
Conducted RF Common Mode IEC61000-4-6 10 V/m RMS, 150 kHz-80 MHz
80% AM at 1kHz Power Frequency Magnetic Field IEC61000-4-8 3 A/m Voltage Dips/Short Variations IEC61000-4-11 5% of nom. line for .5 cycles - Criteria A
40% for 5 cycles - Criteria A
70% for 25 cycles - Criteria A
95% Dip for 5 seconds -
Unit should not latch
SEMI-F47 50% of nom. line for 200 msec (110 VAC@1000W, 70% for 500 msec 220 VAC@1500W) 80% for 10 seconds
90% for 15 seconds
0% for 1 cycle or 20mS
Additional Immunity
Ring Wave Lightning Surge Test IEEE C62.41 6 kV/30 Ohm Criteria A
This manual is a description of specifications, features and applications of LZS-A1500 power supplies.
RATINGS AND SPECIFICATIONS *
Maximum Ratings
Units LZS-A1500-3
Table 2
Output Voltage Range V 18-29.4 Output Current (Power) @ 60°C** A(W) 63 (1512) DC Output @ 24V Output Current (Power) @ 70°C** A(W) 37.8 (907) Operating Temperature °C 100% rated load from -30°C to 60°C derate linearly to
60% @ 70°C (4%/°C)
Start-up Temperature °C -40° to +70°
* Refer to figures 1-7 for supply-load connection information. ** Output current and power, as measured at output terminals, must be less than
or equal to quoted maximum values for a given ambient temperature and input voltage. See Table 4.
LZS-AA1500-33-0001 Power Supply
Revision C : November 2013
Page. 5
Input Specifications
Units LZS-A1500-3
Table 3
Input Voltage Range*** VAC Input Voltage Range*** VAC 85-265 (47-440Hz) Single phase;
VDC 100-380 Input Current (RMS, maximum) A 18 RMS Inrush Current (Peak, at cold start) A 30A /110VAC; 40A /220VAC Power Factor Harmonics - EN61000-3-2 Compliant Power Factor (at max output power) - 0.98 typical @ 170VAC Input Power (maximum) W 1800W @ 63A (1512W) and 170VAC line Input Surge Protection - 1kV Differential Mode; 2kV common mode Input EMI Conducted Emissions - FCC Class B, CISPR 22 Class B
Efficiency (at max.output power) % 84 typical @ 110VAC line
Output Performance Specifications
Units LZS-A1500-3
Voltage Line Regulation % 0.1 Voltage Load Regulation % 0.1 Ripple and Noise @ 20 MHz measurement Bandwidth. EIAJ RC-9002A procedure. (PARD-mVP-P) 75 Temperature Coefficient %/°C .01 Startup Time (at 110 VAC input) Sec. Less than 1 second Overshoot mV No overshoot at turn on or turn off Holdup Time (Full Power/220VAC) mS 10 Ride through (Full Power/220VAC) mS 20 Voltage Sag Immunity (Full Power/110VAC) - Semi-F47 compliant Load Transient Response +/-1% of Vo; 1A /μS; Recovers to within (25% step load change) - +/-0.2% in < 1.25 mS
*** Regulatory agency compliance applies only for operating frequencies between 47-63 Hz.
No Safety agency approvals for 100-380 VDC opercation Minimum Turn-ON voltage for DC Input is 110VDC, unit will operate as low as 65 VDC after power-up. Lambda does not recommend operation below 100VDC for more than one minute, or damage may occur.
Table 5
LZS-A1500-3 Output De-rating
Table 4
85 VAC 18 63 1134 62.50 1125 37.50 675 (120 VDC) 24 50 1200 46.90 1125 28.20 675
29.4 40.8 1200 38.30 1125 23.00 675 90 VAC 18 63 1134 63.00 1134 40.00 720 (127 VDC) 24 54.2 1300 50.00 1200 30.00 720
29.4 44.2 1300 40.80 1200 24.50 720 95 VAC 18 63 1134 63.00 1134 42.50 765 (134 VDC) 24 58.4 1400 53.10 1275 31.90 765
29.4 47.6 1400 43.40 1275 26.10 765 100 VAC 18 63 1134 63.00 1134 45.00 810 (142 VDC) 24 63 1512 56.30 1350 33.80 810
29.4 51.4 1512 46.00 1350 27.60 810 105 VAC 18 63 1134 63.00 1134 47.50 855 (148 VDC) 24 63 1512 59.40 1425 35.70 855
29.4 51.4 1512 48.50 1425 29.10 855 110-265 VAC 18 63.00 1134 50.30 907 (155-380 VDC) 24 63.00 1512 37.80 907
29.4 51.40 1512 37.80 907
Max. Ambient 50°C Max. Ambient 60°C Max. Ambient 70°C
Input Output Max. Max. Max. Max. Max. Max. Voltage Voltage Output Output Output Output Output Output
(VDC) Current (A) Power (W) Current (A) Power (W) Current (A) Power (W)
LZS-AA1500-33-0001 Power Supply
Revision C : November 2013
Page. 6
Operating Modes
Table 6
Series Operation Yes (see Fig. 7) Parallel Operation Two or more identical units (see Fig. 6). (Use of D. con. terminal 5 will (with current sharing) provide current sharing to within 10% nominal of rated 60°C current.)
DC Output Controls and Indicators
Table 7
Output Voltage Adjust Screwdriver adjustment over entire range. Output voltage range is from
18-29.4V. (Multi-turn potentiometer accessible from terminal end of chassis.)
Overvoltage Protection Adjust Screwdriver adjustment over entire range. Overvoltage trip range is from
20-34V. Factory setpoint is 31.0V. (Multi-turn potentiometer accessible
from terminal end of chassis.) Output Good Indicator Green colored LED illuminates when output is within specified operating range Fault Indicator Red colored LED illuminates if overvoltage, overtemperature, or overcurrent
shutdown occurs. The LED is also illuminated if the output is less than approximately
95% of its adjusted output or if the output is inhibited (stand-by mode).
Remote Control Features
Table 8
Remote Voltage Sensing Provides precise regulation directly at load (see Fig. 3). Maximum total
DC voltage drop between output terminals and load must be limited to
<1.0 V. In addition, the voltage at the output terminals must be limited to
29.4V. Remote Voltage Programming 1000 ohms per volt for resistor connected between pins 1 and 2 external resistor. on TB201 (see Figs. 4 and 5). Remote Voltage Programming Volt per volt for voltage source connected between pins 1 and 2 external voltage source. on TB201 (see Figs. 4 and 5). Remote On/Off Control Enable/Disable output via TTL compatible signal connected between
pins 6 and 7 of “D” connector (see Fig. 9). Signals Isolation Pins 6 and 7 are fully isolated from all other power supply terminals. Signal Logic Logic zero (below 0.7 V), short circuit or open circuit disables power
supply output. Logic one (above 2.5 V) enables power supply output. Signal Current Draw Current draw from Logic 1 input is less than 4mA. Output Response Time Output will be within specified limits within 100 ms. of application of
logic “1” signal. Signal Enable Remote on/off function must be enabled by moving “OUTPUT ENABLE”
switch at terminal end of chassis from “LOCAL” to “REMOTE” position (see Fig. 9).
Auxiliary Monitoring and Alarm Signals
Table 9
Optically coupled, conductance outputs. (Conduct up to 1mA at a voltage of <0.4 V, when active.) Input Power Good Signal Conductance signal which indicates adequate input capacitor voltage to
provide 10 ms holdup time when operating at full output power.
Signal will be asserted when the unit is remotely disabled (AC still present)
or when unit shuts down due to overtemperature (see Fig. 10). Output Good Alarm Signal Conductance signal which indicates that delivered output voltage, as measured at
the +V and -V terminals, is above its minimum specified value (see Fig. 10). Inverter Good Signal Conductance signal which indicates that the power supply ’s inverter is
functional. At very light loads, this signal may be indeterminate (see Fig. 10). Signal Isolation Input power good, output UV/OV alarms, inverter good and remote on/off
signals are isolated from power supply output and each other for voltages up
to 500 volts, minimum. 3000 VAC isolation from AC input to all auxiliary signals. Synchronization (Sync) Auxiliary signal at approximately 200khz (switching frequency of unit) used for
synchronizing with other equipment.
FEATURES
* Not backward compatible with the LZS-1500-3 power supply.
LZS-AA1500-33-0001 Power Supply
Revision C : November 2013
Page. 7
Protection Features
Table 10
Output Voltage Range V 18-29.4V Nominal Factory Set Point V 24V Overvoltage Protection (adjustable) V 20-34V (Factory set to 31.0V) Overcurrent Protection - Factory set to 110% min. and 130% max. Thermal Protection - Self-resetting thermostat.* Fusing - Internal Isolation Voltages - 4242 VDC, Input to Output
2121 VDC, Input to Chassis Ground 500 VDC, Output to Chassis Ground
Regulatory Agency Compliance - UL 60950-1/CAN CSA C22.2 No. 60950-1-03, First Edition
UL 508, Seventeenth Edition EN 60950-1:2001+A11, IEC 60950-1:2001, IEC61000 2nd Edition
FM 3600, FM 3611, FM 3810, Semi F47 Leakage current (AC line to μA Less than 1.5 mA @ 265 VAC, 60 Hz chassis ground)
Mechanical Features
Units
Table 11
Storage Temperature (non-operating) °C -40°C - +85°C Weight lbs 9.2 lb net Size inches 5.62” x 4.75” x 10.5” Finish - Textured gray - painted Mounting - One mounting surface (mounting position not restricted)
Maximum allowable penetration into power supply is
1/4”. Requires No. M4 (metric) hardware - supplied
with unit.)
Input and Output Connections
Table 12
Input Heavy duty terminal block Chassis Ground Tapped hole and screw provided in chassis. DC Output Heavy-duty bus bars with 1/4” clearance holes for load connections.
(Connection hardware supplied with unit.) Local/Remote voltage sensing, Four-position lugless connector (TB201), see Fig. 1. Remote on/off, Parallel operation. (Accepts up to #14 AWG size stripped wire). Auxiliary Control and Alarm Signals Connections for remote and local sensing, remote on/off, parallel operation
current sharing, input power good signal, OV alarm, UV alarm, inverter
good signal and chassis are available via chassis mounted, 15-pin,
female, sub-miniature “D” connector (see Fig. 1).
Other Features
Table 13
Warranty 5 years Cooling Variable speed, Ball Bearing Fan Fungus Inert All LZSa power supplies are inherently fungus inert. Humidity 10%-90% Non-condensing Altitude 0-10,000 Ft (Operating); 40,000 Ft (Non-Operating)
* See “Overtemperature and Overvoltage Shutdown” on page 7
LZS-AA1500-33-0001 Power Supply
Revision C : November 2013
Page. 8
4. GUIDE TO APPLICATION
4.1 SAFETY NOTICE
Dangerous voltages exist in this equipment. Observe the usual safety precautions when operating, wiring, or servicing to reduce the risk of shock or injury.
4.2 INPUT VOLTAGE
See Table 3 on page 4.
4.3 OUTPUT VOLTAGE
This power supply operates as a constant-voltage source with maximum load ratings as listed on page 3. If the load current tries to exceed 110% of the 60°C rating, the output voltage will begin to decrease, thereby limiting the power delivered to the load. Upon removal of overload, normal operation will resume.
When shipped from the factory, the power supply is ready for use with output voltage (Vout) set to its nominal rating of 24.0V. Jumpers are in place on TB201 for local voltage sensing. Where precise regulation is required directly at the load, remote voltage sensing can be utilized. This can be achieved by utilizing the remote sense terminals on TB201 or "D" connector (see Figs.2 and 3). The output voltage can be increased by turning the Vout adjust potentiometer clockwise. The output voltage is decreased by turning the Vout adjust potentiometer counter clockwise.
As shown on page 4, LZS-A1500 power supplies have both a maximum current rating and a maximum output power rating (as a function of ambient temperature and input voltage). Care should be taken to limit both output current and output power to be within specified limits. If these limitations are not adhered to, the internal thermal protection circuit may shut down the power supply's operation. For remote voltage sensing, the maximum limits for output power, as given on page 4, apply at the power supply output terminals, not at the remote sensing point.
When adjusting the output voltage above 24.0V, ensure that there is sufficient OVP margin with respect to the output voltage, to avoid nuisance tripping.
4.4 OVERVOL
TAGE PROTECTION CIRCUIT ADJUSTMENT
The overvoltage protection circuit provides an adjustable means of disabling the DC output if it should exceed a pre-determined safe value. When shipped from the factory, the overvoltage level on each LZS unit is set as given in table 7 on page 5. If a different OVP threshold is required, it can be adjusted using the following method:
1. Turn the OVP Adjust potentiometer fully clockwise (at least 10 turns).
2. With the power supply unloaded, set Vout to the OVP threshold desired. In cases where the desired OVP threshold exceeds the unit’s adjustment range maximum of 29.4V, a programming resistor (see figures 4 & 5) will temporarily be needed to provide the higher output voltage to perform the adjustment. Once adjusted, remove the programming resistor. Alternatively, you may use an external voltage source to set the OVP threshold as shown in figures 4 & 5.
3. Slowly turn the OVP adjust control counter clockwise while monitoring the output voltage. Stop turning the control immediately when the red FAULT indicator lights, indicating an OVP shutdown. At that point, the OVP threshold is set to the desired value.
4.5 OVERTEMPERATURE AND OVERVOLTAGE SHUTDOWN
LZS-A1500 power supplies will automatically shut down if operating conditions cause excessive internal heating or excessive output voltage. After the occurrence of an overvoltage shut down, input power must be interrupted or the remote on/off feature must be toggled to re-establish the output. Overtemp shutdown resets itself once the unit has cooled off by approximately 10°C.
4.6 AUXILIARY CONTROL AND ALARM SIGNALS
LZSa power supplies provide auxiliary control and alarm signals per page 5. These signals are accessible via the15-pin, sub miniature "D" connector, located below the output terminals of the unit.
LZS-AA1500-33-0001 Power Supply
Revision C : November 2013
Page. 9
Figure 1 - PIN Assignments for TB201 and chassis mounted “D” connector
5. Figures
LZS-AA1500-33-0001 Power Supply
Revision C : November 2013
Page. 10
Figure 3 - Typical Remote Sense Connection
Figure 2 - Typical Local Sense Connection
LS = Local Sense S = Remote Sense
LS = Local Sense S = Remote Sense
LZS-AA1500-33-0001 Power Supply
Revision C : November 2013
Page. 11
Figure 5 - Remote Voltage Control with an External Programming Resistor or
Voltage Source (Remote Sensing)
Figure 4 - Remote Voltage Control with an External Programming Resistor or
Voltage Source (Local Sensing)
LS = Local Sense S = Remote Sense
LS = Local Sense S = Remote Sense
LZS-AA1500-33-0001 Power Supply
Revision C : November 2013
Page. 12
Figure 6 - Parallel Operation
LZS-AA1500-33-0001 Power Supply
Revision C : November 2013
Page. 13
Figure 7 - Series Operation
LZS-AA1500-33-0001 Power Supply
Revision C : November 2013
Page. 14
Figure 8 - Outline Drawing
LZS-AA1500-33-0001 Power Supply
Revision C : November 2013
Page. 15
Figure 9 - Remote Output On/Off Control
Figure 10 - Input Good, Inverter Good & Output Good Signals
Loading...