TDK-Lambda HFE2500-S1U Instruction Manual

HFE2500-S1U RACK INSTRUCTION MANUAL
HFE2500-S1U SERIES RACK SPECIFICATIONS
1
Number of power supply modules to be inserted
(*1) --- Maximum of 4 x HFE2500 of the same model (output voltage rating and options).
2 Maximum output power W 9500W for 4 units inserted, refer to HFE2500 specifications for derating. 3 Maximum output current A 320A per output (Total 640A)
(*2)
--- 85~265Vac continuous, 47~63Hz, Single phase, separate input for each PS module.
5
Maximum input current (at 115/230Vac)
A 15/12 for each HFE2500 power supply module.
6 Maximum Line Regulation (*4) Less than 0.25% of rated output voltage 7 Maximum Load Regulation (*5) Less than 0.8% of rated output Current
8 AC input connector (*6) ---
Separate for each power supply. HFE2500-S1U: IEC inlet, type C20.
* HFE2500-S1U /TB: Terminal Block.
9 Output terminals ---
Two bus-bars outputs for each output terminal (two sides). Refer to outline drawing.
10 Remote sensing
(*3)
V Possible. Refer to Fig 3.2.
11 Parallel operation --- Possible. Refer to Fig 3.9. 12 Series operation --- Possible. Refer to Fig 3.10.
13
Remote On/Off control (INHIBIT)
---
Separate control for each PS unit, by electrical signal or dry contact. "OFF": 0~0.6V or short. "ON": 2~15V or open. Refer to Fig 3.4.
14
Remote On/Off control (ENABLE)
---
Common for all PS units, by electrical signal or dry contact. "ON": 0~0.6V or short. "OFF": 2~15V or open. Refer to Fig 3.3.
15 DC OK signal ---
Separate signal for each PS unit, Open collector signal. Maximum sink current: 10mA. Tracking output setting, "LOW" when Vout>90+/-5% from output voltage setting. Refer to Fig 3.5
16 AC fail signal ---
Separate signal for each PS unit. Open collector signal. Maximum sink current: 10mA "LOW" when input voltage is 85Vac<Vin<270Vac. Refer to Fig 3.5
17 Over Temperature alarm signal ---
Separate signal for each PS unit. Open collector signal. Maximum sink current 10mA "LOW" when the internal temperature of the unit is within safe limit, "HIGH" approximately 10°C below Thermal shut down. Refer to Fig 3.5
18 Output voltage trimming --- Common for all PS units, by built-in potentiometer. Refer to Sec 1.4.
19
Output voltage programming by external voltage
--- Common for all PS units, by 0~5V signal. Refer to Fig 3.6.
20
OCP programming by external voltage
--- Common for all PS units, by 0~5V signal. Refer to Fig 3.6.1.
21
Output voltage programming via PMbus interface
--- Common for all PS units. Refer to Instruction Manual Fig 3.7.
22
OCP programming via PMbus interface
--- Common for all PS units. Refer to Instruction Manual. Refer to Fig 3.7.1.
23 Auxiliary power supply 11.2~12.5VDC. Maximum output current: 0.5A.
24 Operating temperature ---
-10~+50°C -- 100% load. +50°C to +60°C -- Derating 2%/°C.
+60°C to +70°C -- Derating 2.5%/°C. 25 Storage temperature --- -30~+85°C 26 Operating humidity --- 10~90% RH, no condensation. 27 Storage humidity --- 10~95% RH, no condensation. 28 Vibration --- Built to meet IEC60068-2-64 (Basic Transportation) 29 Shock --- Built to meet IEC60068-2-27 (Basic Transportation) 30 Applicable safety standards UL60950-1 Second Edition, EN60950-1 Second Edition
31 Withstand voltage ---
Input-Output: 3000Vrms, 1min. Input-Ground: 2000Vrms, 1min.
Output-Ground: 12V,24V models - 500Vrms, 1min.
Output-Ground: 48V model - 2250Vdc, 1min. 32 Insulation resistance --- More than 100Mohm at 25°C and 70% RH. Output-Ground: 500Vdc 33 Weight (Typ) (with accessories) kg 5.0 34 Size (W*H*D) mm 445x43.6x401 Refer to Outline Drawing.
Notes:
*1. Mixing of PMBus option units (HFE2500-xx/s) and standard units (HFE2500-xx) is not allowed.
The Output of all HFE2500 Modules are connected in parallel in the Rack.
*2. For cases where conformance to various safety standards (UL, EN etc.) is required, Input Voltage is to be described as 100-240Vac (50/60Hz). *3. Maximum voltage drop on load connection: HFE2500-12: 0.25V/wire, HFE2500-24: 0.5V/wire, HFE2500-48: 1V/wire. *4. From 85~132Vac or 170~265Vac constant load. *5. From No-load to rated load, constant input voltage. Measured at the sensing point in remote sense. *6 Use UL approved Insulated terminal lugs.
1
SAFETY APPROVALS
UL 60950-1 and CSA22.2 No.60950-1 - UL Recognized. C-UL for Canada. IEC 60950-1 - CB Report and Certificate. EN 60950-1 - CE mark. Marking by the CE Symbol indicates compliance to the Low Voltage Directive of the European Union. A “Declaration of Conformity” in accordance with the preceding directives and standards has been made and is on file at our EU representative TDK LAMBDA UK, located at Kingsley Avenue, Ilfracombe, Devon EX34 8ES, UK.
A “Declaration of Conformity” may be accessed via company website www.uk.tdk-lambda.com/technical-data
2
SAFETY INSTRUCTIONS
CAUTION: The following safety precaution must be observed during all phases of operation, service and repair of this equipment.
Failure to comply with the safety precautions or warnings in this document violates safety standards of design, manufacture and intended use of this equipment and may impair the built-in protections within. TDK Lambda shall not be liable for user’s failure to comply with these requirements.
CAUTION: HFE2500-S1U rack is not authorized for use as critical component in nuclear control systems, life support systems or equipment for use in hazardous environments without the express written approval of the managing director of TDK-Lambda.
INSTALLATION (OVERVOLTAGE) CATEGORY& ENVIRONMENTAL CONDITIONS
The HFE2500-S1U has been evaluated to Overvoltage category II. The HFE2500-S1U intended for use in the following operation conditions: * Indoor use * Pollution degree 2 * Max. operational altitude: 3000m above sea level *Ambient temperature: -10°C-50°C at 100% load, up to 70°C with output de-rating applied (refer to Specification above).
GROUNDING
HFE2500-S1U rack is Class I product. To minimize shock hazard, the HFE2500-S1U rack must be connected to an electrical ground. The instruments must be connected to the AC power supply mains through a three conductor power cable, with the ground wire firmly connected to an electrical ground (safety ground) at the power outlet. For instruments designed to be hard-wired to the supply mains, the protective earth terminal must be connected to the safety electrical ground before any other connection is made. Any interruption of the protective ground conductor or disconnection of the protective earth terminal will cause a potential shock hazard that might cause personal injury.
LIVE CIRCUITS
Operating personnel must not remove the HFE2500-S1U rack cover. No internal adjustment or component replacement is allowed by non-TDK Lambda qualified service personnel. Never replace components with power cable connected. To avoid injuries, always disconnect power, discharge circuits and remove external voltage sources before touching components. Restricted Access Area: HFE2500-S1U rack should only be installed in a Restricted Access Area. Access should be available to service personnel only.
PARTS SUBSTITUTIONS & MODIFICATIONS
Parts substitutions and modifications are allowed by authorized TDK Lambda service personnel only. For repairs or modifications, the instrument must be returned to TDK Lambda service facility.
AC INPUT, AC INPUT RATING, AC POWER CABLES
CAUTION
Risk of electrical shock and energy hazard. Disconnecting one power supply line disconnects only one power supply module. To isolate the unit completely, disconnect all power supply lines. Terminal blocks should only be used by professional workers to connect AC cables.
ACHTUNG
Spannungsführende Teile - Gefahr durch elektrischen Schlag order hohe Energieinhalte. Alle Netzstecker der einzelnen Komponenten bzw. der Einschübe müssen getrennt werden, damit das System “spannungsfrei” ist. Die Eingangsklemme der Stromversorgung ist nur innerhalb eines Gesamtsystemes zu verwenden.
ATTENTION
Risque de choc et de danger e’lectriques. Le de’branchement d’une seule alimenttation stabilise’e ne de’branche uniquement qu’un module “Alimentation Stabilise’e”. Pour isoler completement le module en cause, il faut de’brancher toutes les alimentations stabilise’es.
Do not connect HFE2500-S1U to mains supply exceeding the input voltage and frequency rating of HFE2500-S1U. The input voltage and frequency rating is: 100-240V~, 50/60Hz. For safety reasons, the mains supply voltage fluctuations should not exceed +/-10% of nominal voltage.
AC Cables are not provided with unit. Refer to table below for recommended AC cables.
HEAT HAZARD WARNING: Top, bottom and side surfaces may become hot when operating the unit continuously. To reduce the risk of injury from a
hot surface, allow the surface to cool before touching.
ENERGY HAZARD
The main output of HFE2500-S1U is capable of providing hazardous energy. Due to hazardous energy level the output bus bars and connections therefore must not be user accessible. Manufacturer’s final equipment must provide protection to service personnel against inadvertent contact with output bus bars.
HFE2500- S1U HFE2500- S1U/TB
Standard high temprature power cable with type C19 appliance plug rated: EU - 16A/250V; US/C - 20A/250V
Min. - 14AWG (1.5 mm2), rated Min. 300Vac, 80ºC for supply and ground connection.
Terminal Lug - Use UL approved Insulated terminal lugs.
3
SYMBOLS
CAUTION Risk of Electrical Shock.
Instruction manual symbol. The instrument will be marked with this symbol when it is necessary for the user to refer to the instruction manual.
Indicates hazardous voltage.
This symbol indicates the presence of a hot surface or component. Touching this surface could result in bodily injury.
Indicates ground terminal.
Protective Ground Conductor Terminal
L1 Indicates first Line supply terminal
L2/N Indicates second Line or Neutral supply terminal
Denotes hazard. An attention to a procedure is called. Not following the procedure correctly could result in personal injury. A WARNING sign should not be skipped and all indicated conditions must be fully understood and met.
Denotes hazard. An attention to a procedure is called. Not following the procedure correctly could result in damage to the equipment.
FUSES
There are no fuses in the HFE2500-S1U rack.
OVERCURRENT PROTECTION:
A readily accessible branch circuit over current protective device rated 30A max. per each input must be incorporated in the building wiring. The protective device must disconnect both supply line simultaneously.
4
SICHERHEITS - HINWEISE
Vorsicht
Die folgenden Sicherheitsvorschriften müssen vor Inbetriebnahme und in jedem Betriebszustand bei Service oder Reparatur beachtet werden. Missachtung der Sicherheitsvorschriften und Warnhinweise aus diesem Handbuch führen zur Verletzung der bestehenden Sicherheitsstandards. Bei Betrieb des Gerätes ausserhalb dem bestimmungsgemässen Einsatz können die im Gerät integrierten Schutzfunktionen beeinträchtigt werden. TDK-Lambda ist nicht haftbar für Schäden, die durch Missachtung dieser Sicherheitsvorschriften entstehen können.
Vorsicht
Das HFE2500-S1U-Rack ist nicht für die Verwendung als kritische Komponente in nuklearen Steuerungssystemen, lebenserhaltenden Systemen oder Geräte für den Einsatz in gefährlichen Umgebungen, ohne die ausdrückliche schriftliche Genehmigung durch TDK­Lambda zugelassen
Betriebsbedingungen und Umweltbedingungen
Das HFE2500-S1U-Rack ist zur Installation gemäss Überspannungs-Kategorie 2 evaluiert worden. Das HFE2500-S1U-Rack ist gemäss den Sicherheitsabnahmen für folgende Betriebsbedingungen bestimmt. * Stationäre Einrichtungen in Gebäuden. * Verschmutzungsgrad 2. * Erlaubte Betriebshöhe: bis zu 3000m. * Umgebungstemperaturbereich: -10 bis +50° C, bis zu 70°C mit Derating (Details entnehmen Sie bitte dem Datenblatt)
Erdungskonzept
Dieses Produkt ist ein Gerät der Schutzklasse 1. Zur Vermeidung von gefährlichen Energieinhalten und Spannungen, ist das Gehäuse an eine Schutzerde anzuschliessen. Der PE-Anschluss ist an einen festen Erder anzuschliessen. Bei Festverdrahtung des Gerätes ist sicherzustellen, dass der PE Anschluss als erstes angeklemmt wird. Jede mögliche Unterbrechung des PE-Leiters oder Trennung der PE Verbindung kann einen möglichen elektrischen Schlag hervorrufen, der Personenschäden zur Folge hätte.
Spannungsführende Teile
Die Geräteabdeckung darf nicht durch Endanwender geöffnet werden. Interne Modifikationen, sowie Bauteileaustausch ist nur durch TDK-Lambda qualifiziertes Personal erlaubt. Vor Austausch von Bauteilen ist das Netzkabel bzw. die Versorgungsspannung zu trennen. Energieversorgungsanschlüsse sind immer zu trennen, um Personenschäden durch gefährliche Energieinhalte und Spannungen auszuschliessen. Die Stromkreise sind zu entladen, externe Spannungsquellen sind zu entfernen, bevor auf Bauteile bzw. Komponenten Ebene gearbeitet wird.
Änderungen und Bauteileersatz
Ersatzteilaustausch - und Änderungen dürfen nur von autorisiertem TDK-Lambda SERVICE-PERSONAL durchgeführt werden. Für Reparaturen oder Änderungen ist das Gerät zur TDK-Lambda Service-Niederlassung zu retournieren.
Anschluss an Versorgungsstromkreis
Der Betrieb des HFE2500-S1U ist nur für den dafür spezifizierten Wechselspannungsbereich und der angegebenen Frequenz erlaubt. Die Eingangsspannung und Frequenz ist: 100-240V ~ bei 50/60Hz. Aus Gründen der Sicherheit sollten die Netzspannungsschwankungen im Bereich von + / -10% der Nennspannung liegen.
Heisse Oberflächen
WARNUNG: Im Dauerbetrieb erwärmen sich die Gehäuseoberflächen. Um das Verletzungs-Risiko durch heisse Oberflächen zu minimieren, sollte das Gerät einige Zeit abkühlen können, bevor weitere Arbeiten durchgeführt werden.
Gefährlicher Energieinhalt
Der Hauptausgang des HFE2500-S1U liefert gefährlich hohe Energieinhalte. Aufgrund der gefährlichen Energieinhalte müssen die Stromschienen und die Ausgangsanschlüsse abgedeckt sein und dürfen für den Benutzer nicht zugänglich sein. Der Endgeräte Lieferant hat für die Berührungssicherheit der Ausgänge und Stromschienen Sorge zu tragen.
Überstromschutz
Eine leicht zugängliche Vorsicherung mit 30A max.. pro Eingang muss in der Hausinstallation vorgesehen werden
SICHERUNGEN
Das HFE2500 S1U-Rack selbst verfügt über keine Absicherung
5
VORSICHT Spannungsführende Teile-Gefahr durch elektrischen Schlag bzw. Energieinhalte.
Handbuch-Symbol. Das Gerät bzw. Geräteteile warden mit diesem Symbol gekennzeichnet, wenn es für den Benutzer notwendig ist, sich auf die Anweisungen im Handbuch zu beziehen.
Zeigt “spannungsführende Teile” mit gefährlicher Spannung an.
Dieses Symbol weist auf das Vorhandensein einer heißen Oberfläche oder Komponente. Das Berühren dieser Oberfläche kann zu Verletzungen führen.
Zeigt Masse-Anschluss an, keine Schutzerde. ( z.B .Masseanschluss an einen Verbraucher).
Schutzleiter-Anschlussklemme.
WARNUNG
Dieser Warnhinweis beschreibt Gefahren, deren Nichteinhaltung zu Personenschäden führen können. Die Warnhinweise müssen daher zwingend wie im Handbuch beschrieben in der Applikation eingehalten werden.
ACHTUNG
Diese Sicherheitsinformation weist auf Gefahren im täglichen Umgang mit dem Gerät hin, deren Missachtung zu Fehlfunktionen oder Defekten in deer Applikation führen können. Bitte lesen Sie diese Sicherheitsinformationen , bevor Sie das Gerät einbauen oder in Betrieb nehmen.
Sicherheits- und Warnsymbole
6
Loading...
+ 14 hidden pages