TDK-Lambda HFE1600/S series, HFE1600-24/S, HFE1600-12/S, HFE1600-32/S, HFE1600-48/S Instruction Manual

...
IA688-04-01/S Rev. G
HFE1600/S (PMBUS) SERIES INSTRUCTION MANUAL
CHAPTER 1: HFE1600/S (PMBus) SERIES SPECIFICATIONS .......................................................1
1.1
HFE1600 rated output Current and Voltage versus Line Voltage. ............................. 3
1.2
HFE1600 Output Power vs. Temp derating. ............................................................... 4
1.3
HFE1600 Outline Drawing .......................................................................................... 5
1.4 Rear Panel IN/OUT Connector Pins Function Description
CHAPTER 2: SAFETY APPROVALS ...........................................................................................7
2.1
Safety Instructions ...................................................................................................... 7
CHAPTER 3: SINGLE UNIT OPERATION ................................................................................. 10
3.1
Front Panel Indicators .............................................................................................. 10
3.2
Single unit operation ................................................................................................ 11
3.2.1 Basic configuration (Local Sense) ............................................................... 11
3.2.2 Basic configuration (Remote Sense) ........................................................... 11
3.2.3 ON/OFF Control by Enable .......................................................................... 12
3.2.4 ON/OFF Control by INHIBIT ........................................................................ 12
3.2.5 Output Voltage Programming by External Voltage .................................... 12
3.2.6 Output Voltage Programming by PMBus ................................................... 13
3.2.7 SUPERVISORY Signals (Typical Connection) ................................................ 13
CHAPTER 4: POWER SUPPLIES CONNECTION ....................................................................... 14
4.1
Parallel Operation .................................................................................................... 14
4.2
Series Operation ....................................................................................................... 15
CHAPTER 5: PMBus INTERFACE............................................................................................ 16
5.1
HFE1600/S Series I²C Specification .......................................................................... 16
5.1.1 PMBus Interface ......................................................................................... 17
5.1.2 HFE1600 May Have Optional Power Management Bus Hardware ............ 17
5.1.3 Addressing (A3, A2, A1, A0 Inputs) ............................................................. 17
5.1.4 Serial Clock .................................................................................................. 17
5.1.5 Serial Data ................................................................................................... 17
5.1.6 SMB Alert .................................................................................................... 18
5.1.7 PMBus Typical Connection ......................................................................... 18
5.2
PMBus Command Set ............................................................................................... 19
5.2.1 Read Status ................................................................................................. 19
5.2.2 Clear Faults ................................................................................................. 19
5.2.3 Operation (ON/OFF) ................................................................................... 19
5.2.4 Commands to Read Inventory Details ........................................................ 19
5.3
Programming and Monitoring Functions ................................................................. 20
5.3.1 Monitoring Output Voltage (READ_VOUT) ................................................. 20
5.3.2 Monitoring Output Current (READ_IOUT) .................................................. 21
5.3.3 Monitoring Supply Temperature (READ_TEMPERATURE_1) ..................... 21
5.3.4 Programming Output Voltage (VOUT_COMMAND) ................................... 21
5.3.5 Programmable Maximum Output Voltage (VOUT_MAX) ........................... 22
5.3.6
Enabling / Disabling Monitoring Filter ........................................................ 22
1
CHAPTER 1: HFE1600/S (PMBUS) SERIES SPECIFICATIONS
HFE1600 SERIES SPECIFICATIONS:
HFE1600-12/S
HFE1600-24/S
HFE1600-32/S
HFE1600-48/S
1
Rated output voltage
V
12
24
32
48
2
Output voltage set point
V
12+/-1%
24+/-1%
32+/-1%
48+/-1%
3
Output voltage range
V
9.6~13.2
19.2~29.0
25.6~38.4
38.4~58
4
Rated Output Current at Vin ≥ 170Vac (*1)
A
133
67
47
33
5
Rated Output Current at 100 ≤ Vin ≤ 132Vac (*1)
A
100
50
37.5
25
6
Rated Output Current at 85V ≤Vin < 100Vac (*1)
A
Linear derating 1% per 1Vac from output curre nt at 100Vac.
7
Rated output power Vin ≥ 170Vac
W
1596
1608
1504
1584
8
Rated output power 100 ≤ Vin ≤ 132Vac
W
1200
1200
1200
1200
9
Rated output power 85Vac ≤ Vin < 100Vac
W
Linear derating 1% per 1Vac from output power at 100Vac.
10
Input voltage / frequency range (*2)
---
85~265Vac continuous, 47~63Hz, Single phase.
11
Maximum input current (at 115/230Vac)
A
12.4/8.1.
12
Power Factor ( Typ.) (at 115/230Vac)
---
>0.99/0.98 at maximum output power.
13
Efficiency at 75% rated load (Typ.) (*3)
%
87/90
88/90
88/90
89/92
14
Efficiency at 100% rated load (Typ.) (*3)
%
87/90
87/90
87/90
88/91
15
Inrush curre nt (*4)
A
Less than 35.
16
Hold-up time
mS
≥ 10mS typical at 115/230Vac input, rated output voltage and less than 80% of rated load.
17
Maximum line regulation (*5) % 0.25
18
Max load regulation (*6) % 0.50
19
Output Ripple and noise P-P (*7)
0~+70°C
mV
240
240
320
480
-10~0°C
mV
360
360
580
780
20
Temperature stability
---
0.05% of rated Vout for 8hrs after 30min warm-up. Constant line, load and temp.
21
Temperature coefficient of output voltage
PPM/°C
+/-200.
22
Remote sensing (*8)
---
Possible. Refer to Instruction Ma nual.
23
Parallel operatio n (*9)
---
Possible. Single wire c urrent sha re, 5% accuracy of ra ted Iout, up to 10 units of the sa me voltage rating.
24
Series operation
---
Possible (with externa l diodes), 2 units. Refer to Ins truction Manual.
25
Over current protection
85V ≤ Vin < 132Vac
---
Minimum 105% of rated o utput current.
170V ≤ Vin < 265Vac
---
105~120% of ra ted output current.
26
Over voltage protection (*10)
V
Tracking OVP, range: 1.1xVout, accuracy: +/-3%, refer to Instruction Manual.
27
Over temperature protection
---
Inverter shut down method, automatic recovery.
28
Remote On/Off control
---
Two complementary inputs. By electrical signal or dry contact. Refer to Instruction Manual.
29
"DC OK" signal (*13)
---
Tracking, On when Vout>90+/-5% of output voltage setting.
30
Over-Temperature warning (*13)
---
Refer to Instruction Ma nual.
31
"AC FAIL" signal (*13)
---
On when 85Vac<Vin<270Vac.
32
Auxiliary po wer supply output (*11)
---
11.2~12.5V, 0.5A. 240mV p-p ripple and no ise.
33
Vout programming by ex ternal voltage
---
By 0~5V, equal to Vout min ~ Vout max. Refer to Instruction Manual.
34
Vout programming by ex ternal resistor
---
By 1Kohm potentiometer. Refer to Instruction Manual.
35
Front panel indicators
---
AC OK, DC OK/FAIL.
36
I²C Interface
---
Optional, PMBus compatible. Refer to Instr uction Manual.
37
Operating temperature (*15)
---
-10~+50°C: 100% load.
+50°C to +60°C Derate 2%/°C of load.
+60°C to +70°C Derate 2.5%/°C of loa d.
38
Storage tempera ture
---
-30~85°C.
39
Operating humidity
---
10~90% RH, no condensation.
40
Storage humidity
---
10~95% RH, no condensation.
41
Cooling
---
By internal Fans. Varia ble speed control based on ambient temp and power level.
42
Vibration
---
Built to meet IEC60068-2-64 (Basic Transportation).
43
Shock
---
Built to meet IEC60068-2-27 (Basic Transportation).
44
Conducted emission (*14)
---
Built to meet EN55032 Class B, FCC part 15 Class-B, VCCI Class-B.
45
Radiated emission (*14)
---
Built to meet EN55032 Class A, FCC part 15 Class-A, VCCI Class-A.
46
Immunity
---
Built to meet IEC61000-4-2 (Level 2,3),
-3 (Level 2), -4 ( Level 2), -5 (Level 3,4), -6 (Level 2), -8 (Level 4), -11.
47
Applicable safety standards
---
UL60950-1, EN60950-1.
48
Withstand volta ge
Input-Output:
---
3000Vrms, 1min.
Input-Ground:
2000Vrms, 1min.
Output - Ground:
500Vrms, 1min.
500Vrms, 1min.
500Vrms, 1min.
2250Vdc, 1min.
49
Insulation resistance
---
More than 100Mohm at 25°C and 70% RH. Output-Ground: 500Vdc.
50
Leakage current (*12)
mA
Less Than 0.75/1.5 at 115/230Vac range.
51
Weight (Typ.)
Kg
Max. 1.55.
52
Size (W*H*D)
---
85x41x300mm. Refer to Outline Drawing.
2
Notes:
*1 Refer to Figure 1.
*2 For cases where conformance to various safety standards (UL, EN etc.) is required, to be described as
100-240Vac (50/60Hz). *3 At 115/230Vac, 25˚C ambient temperature. *4 Not applicable for the noise filter inrush current less than 0.2mS. *5 From 85~132Vac or 170~265Vac, constant load. *6 From No-load to Rated load, constant input voltage. Measured at the sensing point in Remote sense. *7 Measured with JEITA-RC9131A 1:1 probe with 2x270uF electrolytic capacitors and 1uF film capacitor on the
output, 20MHz B.W. When Power Supplies are installed in HFE1600-S1U shelf, measured with 1uF film
capacitor on the output terminals of the HFE1600-S1U. *8 Voltage drop on load wires: HFE1600-12: 0.25V/wire; HFE1600-24: 0.5V/wire; HFE1600-32: 0.75V/wire;
HFE1600-48: 1V/wire. *9 Accuracy applicable for load current > 50% of rated output current. Derate maximum output power by 5%. *10 Inverter shut down method. Reset by AC voltage recycle or by On/Off control. *11 Measured with JEITA-RC9131A 1:1 probe with 470uF electrolytic capacitor and 0.1uF film capacitor on the
output, 20MHz B.W. Capacitors are not required when the Power Supply is installed in HFE1600-S1U shelf. *12 Measured according to UL, EN method at 60Hz, 25˚C ambient temperature. *13 Open collector signal. Maximum sink current: 10mA, maximum voltage 15V. *14 HFE1600 series considered as professional equipment and not intended for sale to general public. *15 Refer to Output Power vs. temp derating figure A, B, C (Paragraph 1.2).
3
76A
1.1
HFE1600 rated output Current and Voltage versus Line Voltage.
Figure 1–1: HFE1600-48
Figure 1–2: HFE1600-32
Figure 1–3: HFE1600-24
Figure 1–4: HFE1600-12
17A
21A
25A
28A
33A
265Vac 170Vac 132Vac 100Vac
85Vac
26A
31.5A
37.5A
39A
47A
265Vac 170Vac 132Vac 100Vac 85Vac
34A
42.5A
50A
56A
67A
265Vac
170Vac 132Vac
100Vac
85Vac
85A
91A
100A
121A
133A
265Vac 170Vac 132Vac 100Vac 85Vac
1584W Max*
12
1000W Max*
Iout
Vin
1504W Max*
1200W Max*
1000W Max*
Iout
Vin
1608W Max*
1200W Max*
1000W Max*
Iout
Vin
1596W Max*
1200W Max*
1000W Max*
Iout
Vin
38.4~48V
58V
25.6~32V
38.4V
19.2~24V
29V
9.6~12V
13.2V
4
1.2
HFE1600 Output Power vs. Temp derating.
Figure 1–5: Output Power at temp -10~50°C.
Figure 1–6: Output Power derating at temp 60°C.
Figure 1–7: Output Power derating at temp 70°C.
1600W
265Vac 170Vac 132Vac 100Vac 85Vac
1500W
265Vac 170Vac 132Vac 100Vac 85Vac
1280W
265Vac 170Vac 132Vac 100Vac
85Vac
1200W
265Vac 170Vac 132Vac 100Vac
85Vac
880W
265Vac 170Vac 132Vac 100Vac 85Vac
825W
265Vac 170Vac 132Vac 100Vac 85Vac
550W
550W
HFE1600-32V
HFE1600-12, 24, 48V
HFE1600-12, 24, 48V
HFE1600-32V
HFE1600-32V
HFE1600-12, 24, 48V
1200W
1100W
1000W
1200W
1100W
1000W
Pout
Pout
Pout
Pout
Pout
Pout
960W
880W
800W
960W
880W
800W
660W
605W
660W
605W
Vin
Vin
Vin
Vin
Vin
Vin
5
1.3
HFE1600 Outline Drawing
6
1.4
Rear Panel IN/OUT Connector Pins Function Description
Pin #
Function
Description
Referenced to
A1~A5
-V
Main Negative Output Voltage.
A6~A10
+V
Main Positive Output Voltage.
B1
SIGNAL RETURN
Return for the following control signals: ENABLE, INHIBIT;
Supervisory signals: TEMP ALARM, AC FAIL, AUX, DC OK and PS EXIST. PMBus signals: SCL, SDA and SMB ALERT. SIGNAL RETURN and mentioned signals are isolated from the output terminals
and -SENSE. B2
PS EXIST
Indicates that Power Supply module is inserted into the shelf. "Active Low".
SIGNAL RETURN
B3
+12V AUX OUT
11.2 ~ 12.5V Auxiliary Voltage Output. Maximum load current is 0.5A.
This output has a built in O-Ring diode.
Not affected by the INHIBIT/ENABLE signal or any other fault.
SIGNAL RETURN
B4
-SENSE
Negative sense. The -SENSE signal should be connected to -V on Power Supply or Load side.
-SENSE
B5,B10,B14,B16
A2,A3,A1,A0
(PMBus)
PMBus Address lines. Refer to Section 5.1.3 for Addressing.
-SENSE
B6
CURRENT
SHARE
Current sharing signal should be connected when Power Supplies are connected in parallel, to allow accurate current share between units.
-SENSE
B7 (short pin)
ENABLE
Turns ON the main output by electrical signal or dry contact. ON: 0~0.6v or short; OFF: open.
SIGNAL RETURN
B8
VOLTAGE
PROGRAMMING
Input 0~5V. Provides Vout programming by Voltage. Refer to Section 3.2.5 and Section 3.2.6.
-SENSE
B9
+SENSE
Positive sense. The +SENSE signal should be connected to +V on Power Supply or Load side.
+SENSE
B11
NOT
CONNECTED
B12
INHIBIT
Turns OFF the main output by electrical signal or dry contact.
OFF: 0~0.6v or short; ON: open.
Requires the "ENABLE" signal to be connected to "Signal Return"
SIGNAL RETURN
B13
SLC
(PMBus)
Serial Clock signal. Refer to Section 5.1.4.
SIGNAL RETURN
B15
DC OK
DC OK signal. LOW when the output voltage is higher than 85~95% of set Vout. Open collector type (15V, 10mA).
SIGNAL RETURN
B17
SDA
(PMBus)
Serial Data signal. Refer to Section 5.1.5.
SIGNAL RETURN
B18
TEMPERATURE
ALARM
TEMP ALARM signal. LOW when the internal temperature is within safe limit; HIGH approx. 10°C below Thermal shut down. Open collector type (15V, 10mA).
SIGNAL RETURN
B19
V_REF
Variable output for Voltage programming with PMBus option.
-SENSE
B20
SMB ALERT
(PMBus)
PMBus INTERRUPT signal. Refer to Section 5.1.6.
SIGNAL RETURN
B21
AC FAIL
AC FAIL Signal; LOW when the input voltage is 85Vac<Vin<270Vac; HIGH when the input voltage is 85Vac>Vin or Vin>270Vac. Open collector type (15V, 10mA).
SIGNAL RETURN
C1 (long pin)
PROTECTIVE
GROUND
AC GROUND. Refer to Section 2.1 for Safety Instructions.
C2 (long pin)
AC NEUTRAL
AC NEUTRAL. Refer to Section 2.1 for Safety Instructions.
C3 (long pin)
AC LINE
AC LINE. Refer to Section 2.1 for Safety Instructions.
Table 1-1:
Rear panel IN/OUT pins
Figure 1–8: IN/OUTPUT CONNECTOR POSITRONIC P/N: PCIM34W13M400A1/AA
7
CHAPTER 2:
SAFETY APPROVALS
UL 60950-1 and CSA22.2 No.60950-1 - UL Recognized. C-UL for Canada. IEC 60950-1 - CB Report and Certificate. EN 60950-1 - CE mark. Marking by the CE Symbol indicates compliance to the Low Voltage Directive of the European Union. A “Declaration of Conformity” in accordance with the preceding directives and standards has been made and available on file at our EU representative TDK LAMBDA GERMANY GmbH, located at Karl-Bold-Str. 40, D-77855 Achern. A "Declaration of Conformity” may be accessed via company website www.emea.tdk-lambda.com/manual.
2.1
Safety Instructions
CAUTION: The following safety precaution must be observed during all phases of operation, service and repair of this equipment. Failure to comply with the safety precautions or warnings in this document violates safety standards of design, manufacture and intended use of this equipment and may impair the built-in protections within. TDK Lambda shall not be liable for user’s failure to comply with these requirements.
Vorsicht
Die folgenden Sicherheitsvorschriften müssen vor Inbetriebnahme und in jedem Betriebszustand bei Service oder Reparatur beachtet werden. Missachtung der Sicherheitsvorschriften und Warnhinweise aus diesem Handbuch führen zur Verletzung der bestehenden Sicherheitsstandards. Bei Betrieb des Gerätes ausserhalb dem bestimmungsgemässen Einsatz können die im Gerät integrierten Schutzfunktionen beeinträchtigt werden.
TDK-Lambda ist nicht haftbar für Schäden, die durch Missachtung dieser Sicherheitsvorschriften entstehen können.
CAUTION: HFE1600-xy units are not authorized for use as critical component in nuclear control systems, life support systems or equipment for use in hazardous environments without the express written approval of the managing director of TDK­Lambda.
Vorsicht
Dieses Produkt ist nicht für die Verwendung als kritische Komponente in nuklearen Steuerungssystemen, lebenserhaltenden Systemen oder Geräte für den Einsatz in gefährlichen Umgebungen, ohne die ausdrückliche
schriftliche Genehmigung durch TDK-Lambda zugelassen.
POWER SYSTEM, OVERVOLTAGE CATEGORY & ENVIRONMENTAL CONDITIONS
The HFE1600-xy units have been evaluated for using in TT and IT (230VAC line - to - line) power systems. The HFE1600-xy units have been evaluated to Overvoltage category II. The HFE1600-xy units intended for use in the following operation conditions: * Indoor use * Pollution degree 2 * Max. Operational altitude: 3000m above sea level *Ambient temperature: -10°C-50°C at 100% load, up to 70°C with output de-rating applied (refer to Specification above).
GROUNDING
HFE1600-xy units are Class I product. To minimize electrical shock hazard, the HFE1600-xy units must be connected to an electrical ground. The instruments must be connected to the AC power supply mains through a three conductor power cable, with the ground wire firmly connected to an electrical ground (safety ground) at the power outlet. For instruments designed to be hard- wired to the supply mains, the protective earth terminal must be connected to the safety electrical ground before any other connection is made. Any interruption of the protective ground conductor or disconnection of the protective earth terminal will cause a potential shock hazard that might cause personal injury.
Erdungskonzept
Dieses Produkt ist ein Gerät der Schutzklasse 1. Zur Vermeidung von gefährlichen Energieinhalten und Spannungen, ist das Gehäuse an eine Schutzerde anzuschliessen. Der PE-Anschluss ist an einen festen Erder anzuschliessen. Bei Festverdrahtung des Gerätes ist sicherzustellen, dass der PE Anschluss als erstes angeklemmt wird. Jede mögliche Unterbrechung des PE-Leiters oder Trennung der PE Verbindung kann einen möglichen elektrischen Schlag
hervorrufen, der Personenschäden zur Folge hätte.
LIVE CIRCUITS
Operating personnel must not remove the HFE1600-xy unit cover. No internal adjustment or component replacement is allowed by non-TDK Lambda qualified service personnel. Never replace components with power cable connected. To avoid injuries, always disconnect power, discharge circuits and remove external voltage sources before touching components. Restricted Access Area: HFE1600-xy units should only be installed in a Restricted Access Area. Access should be available to service personnel only.