TDK-Lambda HFE1600/S series, HFE1600-24/S, HFE1600-12/S, HFE1600-32/S, HFE1600-48/S Instruction Manual

...
IA688-04-01/S Rev. G
HFE1600/S (PMBUS) SERIES INSTRUCTION MANUAL
CHAPTER 1: HFE1600/S (PMBus) SERIES SPECIFICATIONS .......................................................1
1.1
HFE1600 rated output Current and Voltage versus Line Voltage. ............................. 3
1.2
HFE1600 Output Power vs. Temp derating. ............................................................... 4
1.3
HFE1600 Outline Drawing .......................................................................................... 5
1.4 Rear Panel IN/OUT Connector Pins Function Description
CHAPTER 2: SAFETY APPROVALS ...........................................................................................7
2.1
Safety Instructions ...................................................................................................... 7
CHAPTER 3: SINGLE UNIT OPERATION ................................................................................. 10
3.1
Front Panel Indicators .............................................................................................. 10
3.2
Single unit operation ................................................................................................ 11
3.2.1 Basic configuration (Local Sense) ............................................................... 11
3.2.2 Basic configuration (Remote Sense) ........................................................... 11
3.2.3 ON/OFF Control by Enable .......................................................................... 12
3.2.4 ON/OFF Control by INHIBIT ........................................................................ 12
3.2.5 Output Voltage Programming by External Voltage .................................... 12
3.2.6 Output Voltage Programming by PMBus ................................................... 13
3.2.7 SUPERVISORY Signals (Typical Connection) ................................................ 13
CHAPTER 4: POWER SUPPLIES CONNECTION ....................................................................... 14
4.1
Parallel Operation .................................................................................................... 14
4.2
Series Operation ....................................................................................................... 15
CHAPTER 5: PMBus INTERFACE............................................................................................ 16
5.1
HFE1600/S Series I²C Specification .......................................................................... 16
5.1.1 PMBus Interface ......................................................................................... 17
5.1.2 HFE1600 May Have Optional Power Management Bus Hardware ............ 17
5.1.3 Addressing (A3, A2, A1, A0 Inputs) ............................................................. 17
5.1.4 Serial Clock .................................................................................................. 17
5.1.5 Serial Data ................................................................................................... 17
5.1.6 SMB Alert .................................................................................................... 18
5.1.7 PMBus Typical Connection ......................................................................... 18
5.2
PMBus Command Set ............................................................................................... 19
5.2.1 Read Status ................................................................................................. 19
5.2.2 Clear Faults ................................................................................................. 19
5.2.3 Operation (ON/OFF) ................................................................................... 19
5.2.4 Commands to Read Inventory Details ........................................................ 19
5.3
Programming and Monitoring Functions ................................................................. 20
5.3.1 Monitoring Output Voltage (READ_VOUT) ................................................. 20
5.3.2 Monitoring Output Current (READ_IOUT) .................................................. 21
5.3.3 Monitoring Supply Temperature (READ_TEMPERATURE_1) ..................... 21
5.3.4 Programming Output Voltage (VOUT_COMMAND) ................................... 21
5.3.5 Programmable Maximum Output Voltage (VOUT_MAX) ........................... 22
5.3.6
Enabling / Disabling Monitoring Filter ........................................................ 22
1
CHAPTER 1: HFE1600/S (PMBUS) SERIES SPECIFICATIONS
HFE1600 SERIES SPECIFICATIONS:
HFE1600-12/S
HFE1600-24/S
HFE1600-32/S
HFE1600-48/S
1
Rated output voltage
V
12
24
32
48
2
Output voltage set point
V
12+/-1%
24+/-1%
32+/-1%
48+/-1%
3
Output voltage range
V
9.6~13.2
19.2~29.0
25.6~38.4
38.4~58
4
Rated Output Current at Vin ≥ 170Vac (*1)
A
133
67
47
33
5
Rated Output Current at 100 ≤ Vin ≤ 132Vac (*1)
A
100
50
37.5
25
6
Rated Output Current at 85V ≤Vin < 100Vac (*1)
A
Linear derating 1% per 1Vac from output curre nt at 100Vac.
7
Rated output power Vin ≥ 170Vac
W
1596
1608
1504
1584
8
Rated output power 100 ≤ Vin ≤ 132Vac
W
1200
1200
1200
1200
9
Rated output power 85Vac ≤ Vin < 100Vac
W
Linear derating 1% per 1Vac from output power at 100Vac.
10
Input voltage / frequency range (*2)
---
85~265Vac continuous, 47~63Hz, Single phase.
11
Maximum input current (at 115/230Vac)
A
12.4/8.1.
12
Power Factor ( Typ.) (at 115/230Vac)
---
>0.99/0.98 at maximum output power.
13
Efficiency at 75% rated load (Typ.) (*3)
%
87/90
88/90
88/90
89/92
14
Efficiency at 100% rated load (Typ.) (*3)
%
87/90
87/90
87/90
88/91
15
Inrush curre nt (*4)
A
Less than 35.
16
Hold-up time
mS
≥ 10mS typical at 115/230Vac input, rated output voltage and less than 80% of rated load.
17
Maximum line regulation (*5) % 0.25
18
Max load regulation (*6) % 0.50
19
Output Ripple and noise P-P (*7)
0~+70°C
mV
240
240
320
480
-10~0°C
mV
360
360
580
780
20
Temperature stability
---
0.05% of rated Vout for 8hrs after 30min warm-up. Constant line, load and temp.
21
Temperature coefficient of output voltage
PPM/°C
+/-200.
22
Remote sensing (*8)
---
Possible. Refer to Instruction Ma nual.
23
Parallel operatio n (*9)
---
Possible. Single wire c urrent sha re, 5% accuracy of ra ted Iout, up to 10 units of the sa me voltage rating.
24
Series operation
---
Possible (with externa l diodes), 2 units. Refer to Ins truction Manual.
25
Over current protection
85V ≤ Vin < 132Vac
---
Minimum 105% of rated o utput current.
170V ≤ Vin < 265Vac
---
105~120% of ra ted output current.
26
Over voltage protection (*10)
V
Tracking OVP, range: 1.1xVout, accuracy: +/-3%, refer to Instruction Manual.
27
Over temperature protection
---
Inverter shut down method, automatic recovery.
28
Remote On/Off control
---
Two complementary inputs. By electrical signal or dry contact. Refer to Instruction Manual.
29
"DC OK" signal (*13)
---
Tracking, On when Vout>90+/-5% of output voltage setting.
30
Over-Temperature warning (*13)
---
Refer to Instruction Ma nual.
31
"AC FAIL" signal (*13)
---
On when 85Vac<Vin<270Vac.
32
Auxiliary po wer supply output (*11)
---
11.2~12.5V, 0.5A. 240mV p-p ripple and no ise.
33
Vout programming by ex ternal voltage
---
By 0~5V, equal to Vout min ~ Vout max. Refer to Instruction Manual.
34
Vout programming by ex ternal resistor
---
By 1Kohm potentiometer. Refer to Instruction Manual.
35
Front panel indicators
---
AC OK, DC OK/FAIL.
36
I²C Interface
---
Optional, PMBus compatible. Refer to Instr uction Manual.
37
Operating temperature (*15)
---
-10~+50°C: 100% load.
+50°C to +60°C Derate 2%/°C of load.
+60°C to +70°C Derate 2.5%/°C of loa d.
38
Storage tempera ture
---
-30~85°C.
39
Operating humidity
---
10~90% RH, no condensation.
40
Storage humidity
---
10~95% RH, no condensation.
41
Cooling
---
By internal Fans. Varia ble speed control based on ambient temp and power level.
42
Vibration
---
Built to meet IEC60068-2-64 (Basic Transportation).
43
Shock
---
Built to meet IEC60068-2-27 (Basic Transportation).
44
Conducted emission (*14)
---
Built to meet EN55032 Class B, FCC part 15 Class-B, VCCI Class-B.
45
Radiated emission (*14)
---
Built to meet EN55032 Class A, FCC part 15 Class-A, VCCI Class-A.
46
Immunity
---
Built to meet IEC61000-4-2 (Level 2,3),
-3 (Level 2), -4 ( Level 2), -5 (Level 3,4), -6 (Level 2), -8 (Level 4), -11.
47
Applicable safety standards
---
UL60950-1, EN60950-1.
48
Withstand volta ge
Input-Output:
---
3000Vrms, 1min.
Input-Ground:
2000Vrms, 1min.
Output - Ground:
500Vrms, 1min.
500Vrms, 1min.
500Vrms, 1min.
2250Vdc, 1min.
49
Insulation resistance
---
More than 100Mohm at 25°C and 70% RH. Output-Ground: 500Vdc.
50
Leakage current (*12)
mA
Less Than 0.75/1.5 at 115/230Vac range.
51
Weight (Typ.)
Kg
Max. 1.55.
52
Size (W*H*D)
---
85x41x300mm. Refer to Outline Drawing.
2
Notes:
*1 Refer to Figure 1.
*2 For cases where conformance to various safety standards (UL, EN etc.) is required, to be described as
100-240Vac (50/60Hz). *3 At 115/230Vac, 25˚C ambient temperature. *4 Not applicable for the noise filter inrush current less than 0.2mS. *5 From 85~132Vac or 170~265Vac, constant load. *6 From No-load to Rated load, constant input voltage. Measured at the sensing point in Remote sense. *7 Measured with JEITA-RC9131A 1:1 probe with 2x270uF electrolytic capacitors and 1uF film capacitor on the
output, 20MHz B.W. When Power Supplies are installed in HFE1600-S1U shelf, measured with 1uF film
capacitor on the output terminals of the HFE1600-S1U. *8 Voltage drop on load wires: HFE1600-12: 0.25V/wire; HFE1600-24: 0.5V/wire; HFE1600-32: 0.75V/wire;
HFE1600-48: 1V/wire. *9 Accuracy applicable for load current > 50% of rated output current. Derate maximum output power by 5%. *10 Inverter shut down method. Reset by AC voltage recycle or by On/Off control. *11 Measured with JEITA-RC9131A 1:1 probe with 470uF electrolytic capacitor and 0.1uF film capacitor on the
output, 20MHz B.W. Capacitors are not required when the Power Supply is installed in HFE1600-S1U shelf. *12 Measured according to UL, EN method at 60Hz, 25˚C ambient temperature. *13 Open collector signal. Maximum sink current: 10mA, maximum voltage 15V. *14 HFE1600 series considered as professional equipment and not intended for sale to general public. *15 Refer to Output Power vs. temp derating figure A, B, C (Paragraph 1.2).
3
76A
1.1
HFE1600 rated output Current and Voltage versus Line Voltage.
Figure 1–1: HFE1600-48
Figure 1–2: HFE1600-32
Figure 1–3: HFE1600-24
Figure 1–4: HFE1600-12
17A
21A
25A
28A
33A
265Vac 170Vac 132Vac 100Vac
85Vac
26A
31.5A
37.5A
39A
47A
265Vac 170Vac 132Vac 100Vac 85Vac
34A
42.5A
50A
56A
67A
265Vac
170Vac 132Vac
100Vac
85Vac
85A
91A
100A
121A
133A
265Vac 170Vac 132Vac 100Vac 85Vac
1584W Max*
12
1000W Max*
Iout
Vin
1504W Max*
1200W Max*
1000W Max*
Iout
Vin
1608W Max*
1200W Max*
1000W Max*
Iout
Vin
1596W Max*
1200W Max*
1000W Max*
Iout
Vin
38.4~48V
58V
25.6~32V
38.4V
19.2~24V
29V
9.6~12V
13.2V
4
1.2
HFE1600 Output Power vs. Temp derating.
Figure 1–5: Output Power at temp -10~50°C.
Figure 1–6: Output Power derating at temp 60°C.
Figure 1–7: Output Power derating at temp 70°C.
1600W
265Vac 170Vac 132Vac 100Vac 85Vac
1500W
265Vac 170Vac 132Vac 100Vac 85Vac
1280W
265Vac 170Vac 132Vac 100Vac
85Vac
1200W
265Vac 170Vac 132Vac 100Vac
85Vac
880W
265Vac 170Vac 132Vac 100Vac 85Vac
825W
265Vac 170Vac 132Vac 100Vac 85Vac
550W
550W
HFE1600-32V
HFE1600-12, 24, 48V
HFE1600-12, 24, 48V
HFE1600-32V
HFE1600-32V
HFE1600-12, 24, 48V
1200W
1100W
1000W
1200W
1100W
1000W
Pout
Pout
Pout
Pout
Pout
Pout
960W
880W
800W
960W
880W
800W
660W
605W
660W
605W
Vin
Vin
Vin
Vin
Vin
Vin
5
1.3
HFE1600 Outline Drawing
6
1.4
Rear Panel IN/OUT Connector Pins Function Description
Pin #
Function
Description
Referenced to
A1~A5
-V
Main Negative Output Voltage.
A6~A10
+V
Main Positive Output Voltage.
B1
SIGNAL RETURN
Return for the following control signals: ENABLE, INHIBIT;
Supervisory signals: TEMP ALARM, AC FAIL, AUX, DC OK and PS EXIST. PMBus signals: SCL, SDA and SMB ALERT. SIGNAL RETURN and mentioned signals are isolated from the output terminals
and -SENSE. B2
PS EXIST
Indicates that Power Supply module is inserted into the shelf. "Active Low".
SIGNAL RETURN
B3
+12V AUX OUT
11.2 ~ 12.5V Auxiliary Voltage Output. Maximum load current is 0.5A.
This output has a built in O-Ring diode.
Not affected by the INHIBIT/ENABLE signal or any other fault.
SIGNAL RETURN
B4
-SENSE
Negative sense. The -SENSE signal should be connected to -V on Power Supply or Load side.
-SENSE
B5,B10,B14,B16
A2,A3,A1,A0
(PMBus)
PMBus Address lines. Refer to Section 5.1.3 for Addressing.
-SENSE
B6
CURRENT
SHARE
Current sharing signal should be connected when Power Supplies are connected in parallel, to allow accurate current share between units.
-SENSE
B7 (short pin)
ENABLE
Turns ON the main output by electrical signal or dry contact. ON: 0~0.6v or short; OFF: open.
SIGNAL RETURN
B8
VOLTAGE
PROGRAMMING
Input 0~5V. Provides Vout programming by Voltage. Refer to Section 3.2.5 and Section 3.2.6.
-SENSE
B9
+SENSE
Positive sense. The +SENSE signal should be connected to +V on Power Supply or Load side.
+SENSE
B11
NOT
CONNECTED
B12
INHIBIT
Turns OFF the main output by electrical signal or dry contact.
OFF: 0~0.6v or short; ON: open.
Requires the "ENABLE" signal to be connected to "Signal Return"
SIGNAL RETURN
B13
SLC
(PMBus)
Serial Clock signal. Refer to Section 5.1.4.
SIGNAL RETURN
B15
DC OK
DC OK signal. LOW when the output voltage is higher than 85~95% of set Vout. Open collector type (15V, 10mA).
SIGNAL RETURN
B17
SDA
(PMBus)
Serial Data signal. Refer to Section 5.1.5.
SIGNAL RETURN
B18
TEMPERATURE
ALARM
TEMP ALARM signal. LOW when the internal temperature is within safe limit; HIGH approx. 10°C below Thermal shut down. Open collector type (15V, 10mA).
SIGNAL RETURN
B19
V_REF
Variable output for Voltage programming with PMBus option.
-SENSE
B20
SMB ALERT
(PMBus)
PMBus INTERRUPT signal. Refer to Section 5.1.6.
SIGNAL RETURN
B21
AC FAIL
AC FAIL Signal; LOW when the input voltage is 85Vac<Vin<270Vac; HIGH when the input voltage is 85Vac>Vin or Vin>270Vac. Open collector type (15V, 10mA).
SIGNAL RETURN
C1 (long pin)
PROTECTIVE
GROUND
AC GROUND. Refer to Section 2.1 for Safety Instructions.
C2 (long pin)
AC NEUTRAL
AC NEUTRAL. Refer to Section 2.1 for Safety Instructions.
C3 (long pin)
AC LINE
AC LINE. Refer to Section 2.1 for Safety Instructions.
Table 1-1:
Rear panel IN/OUT pins
Figure 1–8: IN/OUTPUT CONNECTOR POSITRONIC P/N: PCIM34W13M400A1/AA
7
CHAPTER 2:
SAFETY APPROVALS
UL 60950-1 and CSA22.2 No.60950-1 - UL Recognized. C-UL for Canada. IEC 60950-1 - CB Report and Certificate. EN 60950-1 - CE mark. Marking by the CE Symbol indicates compliance to the Low Voltage Directive of the European Union. A “Declaration of Conformity” in accordance with the preceding directives and standards has been made and available on file at our EU representative TDK LAMBDA GERMANY GmbH, located at Karl-Bold-Str. 40, D-77855 Achern. A "Declaration of Conformity” may be accessed via company website www.emea.tdk-lambda.com/manual.
2.1
Safety Instructions
CAUTION: The following safety precaution must be observed during all phases of operation, service and repair of this equipment. Failure to comply with the safety precautions or warnings in this document violates safety standards of design, manufacture and intended use of this equipment and may impair the built-in protections within. TDK Lambda shall not be liable for user’s failure to comply with these requirements.
Vorsicht
Die folgenden Sicherheitsvorschriften müssen vor Inbetriebnahme und in jedem Betriebszustand bei Service oder Reparatur beachtet werden. Missachtung der Sicherheitsvorschriften und Warnhinweise aus diesem Handbuch führen zur Verletzung der bestehenden Sicherheitsstandards. Bei Betrieb des Gerätes ausserhalb dem bestimmungsgemässen Einsatz können die im Gerät integrierten Schutzfunktionen beeinträchtigt werden.
TDK-Lambda ist nicht haftbar für Schäden, die durch Missachtung dieser Sicherheitsvorschriften entstehen können.
CAUTION: HFE1600-xy units are not authorized for use as critical component in nuclear control systems, life support systems or equipment for use in hazardous environments without the express written approval of the managing director of TDK­Lambda.
Vorsicht
Dieses Produkt ist nicht für die Verwendung als kritische Komponente in nuklearen Steuerungssystemen, lebenserhaltenden Systemen oder Geräte für den Einsatz in gefährlichen Umgebungen, ohne die ausdrückliche
schriftliche Genehmigung durch TDK-Lambda zugelassen.
POWER SYSTEM, OVERVOLTAGE CATEGORY & ENVIRONMENTAL CONDITIONS
The HFE1600-xy units have been evaluated for using in TT and IT (230VAC line - to - line) power systems. The HFE1600-xy units have been evaluated to Overvoltage category II. The HFE1600-xy units intended for use in the following operation conditions: * Indoor use * Pollution degree 2 * Max. Operational altitude: 3000m above sea level *Ambient temperature: -10°C-50°C at 100% load, up to 70°C with output de-rating applied (refer to Specification above).
GROUNDING
HFE1600-xy units are Class I product. To minimize electrical shock hazard, the HFE1600-xy units must be connected to an electrical ground. The instruments must be connected to the AC power supply mains through a three conductor power cable, with the ground wire firmly connected to an electrical ground (safety ground) at the power outlet. For instruments designed to be hard- wired to the supply mains, the protective earth terminal must be connected to the safety electrical ground before any other connection is made. Any interruption of the protective ground conductor or disconnection of the protective earth terminal will cause a potential shock hazard that might cause personal injury.
Erdungskonzept
Dieses Produkt ist ein Gerät der Schutzklasse 1. Zur Vermeidung von gefährlichen Energieinhalten und Spannungen, ist das Gehäuse an eine Schutzerde anzuschliessen. Der PE-Anschluss ist an einen festen Erder anzuschliessen. Bei Festverdrahtung des Gerätes ist sicherzustellen, dass der PE Anschluss als erstes angeklemmt wird. Jede mögliche Unterbrechung des PE-Leiters oder Trennung der PE Verbindung kann einen möglichen elektrischen Schlag
hervorrufen, der Personenschäden zur Folge hätte.
LIVE CIRCUITS
Operating personnel must not remove the HFE1600-xy unit cover. No internal adjustment or component replacement is allowed by non-TDK Lambda qualified service personnel. Never replace components with power cable connected. To avoid injuries, always disconnect power, discharge circuits and remove external voltage sources before touching components. Restricted Access Area: HFE1600-xy units should only be installed in a Restricted Access Area. Access should be available to service personnel only.
8
Spannungsführende Teile
Die Geräteabdeckung darf nicht durch Endanwender geöffnet werden. Interne Modifikationen, sowie Bauteileaustausch ist nur durch TDK-Lambda qualifiziertes Personal erlaubt. Vor Austausch von Bauteilen ist das Netzkabel bzw. die Versorgungsspannung zu trennen. Energieversorgungsanschlüsse sind immer zu trennen, um Personenschäden durch gefährliche Energieinhalte und Spannungen auszuschliessen. Die Stromkreise sind zu entladen, externe
Spannungsquellen sind zu entfernen, bevor auf Bauteile bzw. Komponenten Ebene gearbeitet wird.
PARTS SUBSTITUTIONS & MODIFICATIONS
Parts substitutions and modifications are allowed to authorized TDK Lambda service personnel only. For repairs or
modifications, the instrument must be returned to TDK Lambda service facility.
AC INPUT
Do not connect HFE1600-xv unit to mains supply exceeding the input voltage and frequency rating. The input voltage and frequency rating is: 100-240V~, 50/60Hz. For safety reasons, the mains supply voltage fluctuations should not exceed ±10% of nominal voltage.
HEAT HAZARD
WARNING: Top, bottom and side surfaces may become hot when operating the unit continuously. To reduce the risk of
injury from a hot surface, allow the surface to cool before touching.
Heisse Oberflächen
WARNUNG: Im Dauerbetrieb erwärmen sich die Gehäuseoberflächen. Um das Verletzungs-Risiko durch heisse Oberflächen zu minimieren, sollte das Gerät einige Zeit abkühlen können, bevor weitere Arbeiten durchgeführt
werden.
ENERGY HAZARD
The main output of HFE1600-xy units is capable of providing hazardous energy. Due to hazardous energy level the output
and connections therefore must not be user accessible. Manufacturer’s final equipment must provide protection to service
personnel against inadvertent contact with output bus bars.
FUSE
Internal fuse is sized for fault protection and if a fuse was opened it would indicate that service is required.
Fuse replacement should be made by qualified technical personnel.
HFE1600-xy unit fuse rating is described below. F101: F20A H 250Vac.
SICHERUNGEN
Vor Anschluss an die Netzversorgung ist die Aufstellanleitung zu beachten!
1.
Absicherung: F1 01: F20A H 250VAC
2.
Die Gehäuseabdeckung darf nur im stromlosen Zustand geöffnet werden.
ACHTUNG: Sicherungen dürfen nur durch geschulte Service Personen getauscht werden.
OVERCURRENT PROTECTION:
A readily accessible branch circuit over-current protective device rated 30A max. Must be incorporated in the building
wiring. The protective device must be disconnect both supply line simultaneously.
Überstromschutz
Eine leicht zugängliche Vorsicherung mit 30A max.. pro Eingang muss in der Hausinstallation vorgesehen
werden
9
SYMBOLS/ ZEICHEN:
Caution, risk of danger. Instruction manual symbol. The instrument will be marked with this symbol
when it is necessary for the user to refer to the Safety & Installation or Instruction manual. Achtung Gefahr. Symbol im Benutzerhandbuch. Das Gerät wird mit diesem Symbol gekennzeichnet,
wenn der Benutzer auf das Sicherheits- & Installationshandbuch oder d ie Bedie nungs a nleitung verwiesen wird.
Indicates ground terminal.
Zeigt einen Erdungsanschlu ss an .
Protective Ground Conductor Terminal.
Schutzleiterklemme.
CAUTION Live component danger due to electric shock or energy content.
VORSICHT Spannungsfuhrende Teile-Gefahr durch elektrischen Schlag bzw. Energieinhalte.
Indicates the presence of a hot surface or component. Touch of a hot surface can cause injury.
Dieses Symbol weist auf das Vorhandensein einer heißen Oberflache oder Komponente. Das Beruhren dieser Oberflache kann zu Verletzungen fuhren.
Direct current (DC).
Gleichstrom (DC).
Alternate current (AC).
Wechselstrom (AC).
Denotes hazard. A procedure requires specific attention. Not following the procedure correctly could
result in a personal injury. A WARNING sign should not be skipped and all indicated conditions must be fully understood and met.
Weist auf Gefahren hin, die eine besondere Aufmerksamkeit erfordern. Eine Nichteinhaltung dieser Vorgehensweise, kann zu Körperverletzungen führen. Ein WARN-Hinweis sollte nicht übergangen und alle angeführten Bedingungen müssen eindeutig verstanden und umgesetzt werden.
Denotes hazard. A procedure requires specific attention. Not following the procedure correctly could
result in damage to the equipment. Do not proceed beyond a CAUTION sign until all indicated conditions are fully understood and met.
Weist auf Gefahren hin, die eine besondere Aufmerksamkeit erfordern. Wenn die beschriebene Vorgehensweise nicht korrekt durchgeführt wird, kann dadurch das Gerät beschädigt werden. Führen Sie einem VORSICHTS-Hinweis erst durch, wenn Sie alle angezeigten Handlungen eindeutig verstanden und umgesetzt haben.
10
CHAPTER 3: SINGLE UNIT OPERATION
3.1
Front Panel Indicators
1. DC OK – LED indicator:
GREEN Output Voltage is above 90% ± 5% of set Output Voltage.
RED Output Voltage is below 90% ± 5% of set Output Voltage.
2. AC OK – LED indicator:
GREEN Input Voltage (Vin) is in the range of 85Vac to 270Vac.
OFF Input Voltage (Vin) is below 85Vac or above 270Vac.
Figure 3–1: Front Panel Indicators
CAUTION:
When inserting a power supply into the rack, do not use unnecessary force; Slamming the power supply into the rack can damage the connectors on the rear of the supply and inside the rack.
ATTENTION:
Power supplies are factory programmed to the rated output voltage. For applications requiring lower / higher voltage,
power supplies should be adjusted to the required voltage before connection to the load.
11
3.2
Single unit operation
3.2.1 Basic configuration (Local Sense)
± SENSE have to be connected to the HFE1600 ±V terminals prior to operating the supply.
ENABLE input must be connected to SIGNAL RETURN in order for the supply to turn on.
Figure 3–2: Local Sense Connection
3.2.2 Basic configuration (Remote Sense)
± SENSE have to be connected to the ±V terminals on the Load side prior to operating the supply.
ENABLE input must be connected to SIGNAL RETURN in order for the supply to turn on.
Figure 3–3: Remote Sense Connection
ATTENTION:
1. Maximum voltage drop on load connection:
HFE1600-12: 0.25V/wire; HFE1600-24: 0.5V/wire; HFE1600-32: 0.75V/wire; HFE1600-48: 1V/wire.
2. Twisted wires should be used for Remote Sensing connection.
3. If Remote Sensing is used, do not break Main Output connection.
12
3.2.3 ON/OFF Control by Enable
SIGNAL RETURN and ENABLE control are isolated from the output terminals and“-SENSE”.
Figure 3–4:
Control by ENABLE
3.2.4 ON/OFF Control by INHIBIT
Power Supply operation requires the "ENABLE" signal to be connected to "Signal Return".
Logic of the "INHIBIT" signal is reversed to logic of the "ENABLE" signal.
SIGNAL RETURN, INHIBIT and ENABLE controls are isolated from the output terminals and -SENSE.
Figure 3–5:
Control by INHIBIT
3.2.5 Output Voltage Programmin g b y E xte rn al Voltage
Output Voltage of HFE1600 Series can be programmed by external voltage source between approximately
80%-120% for 24V, 32V, 48V and 80%-110% for 12V of nominal output voltage
(For Output voltage limits see Graph enclosed)
.
Figure 3–6:
Control by Ex. Voltage
Figure 3–7:
Output Voltage Limits
Switch closed: Output ON Switch open: Output OFF
HFE1600
SIGNAL RETURN B1
ENABLE B7
INHIBIT B12
Switch closed: Output OFF Switch open: Output ON
HFE1600
-SENSE B4
VOLTAGE PROG. B8
0~5V
+
60
50
40
30
20
10
0
0
2
5
58
38.4
29
13.2
3
HFE1600-48
HFE1600-32
HFE1600-24
HFE1600-12
Voltage Programming
V PROG [V]
Vout [V]
1 4
ENABLE B7
SIGNAL RETURN B1
HFE1600
13
3.2.6 Output Voltage Programmin g b y PMBu s
Output Voltage of HFE1600 Series can be programmed by PMBus between approximately 80%-120% for 24V, 32V, 48V and 80%-110% for 12V of nominal output voltage (limits see HFE1600 series specifications line 3).
ATTENTION:
If PMBus is used for voltage programming, the Reference voltage will not be fixed to 5V but variable.
Figure 3–8:
Programming by PMBus
3.2.7 SUPERVISORY Signals (Typical Connection)
The following supervisory signals are accessible:
DC OK
AC FAIL
PS EXIST
TEMP ALARM
Figure 3–9:
Signals
SIGNAL RETURN and mentioned signals are isolated from the output terminals and -SENSE.
These signals are Open Collector type (max 15V, max 10mA) shunted by internal 24V Zener, isolated from Output and referenced to “SIGNAL RETURN”.
Figure 3–10:
Open collector signals are shunted by internal 24V Zener
HFE1600
VOLTAGE PROG. B8
+5V/V_REF B19
14
CHAPTER 4: POWER SUPPLIES CONNECTION
4.1
Parallel Operation
Figure 4–1:
Parallel Connection
Up to 10 x HFE1600 units with the same rating (voltage and current) can be used in parallel to increase the output current.
By connecting the CS signal between the paralleled units, automatic current balance is achieved with accuracy of
Accuracy ±10%: 20% ≤ Iout < 50% of max Iout. Up to 10 units Accuracy ±5%: Iout ≥ 50% of max Iout. Up to 10 units.
Derate the total output current by 5% when using parallel operation to prevent unit overload condition.
The built-in O-Ring MOSFETs on the main output and the 12V Auxiliary output allow N+1 operation.
If Voltage programming is used, "Voltage Programming” Pin of all units must be connected in parallel.
Referenced to “SIGNAL RETURN” (floating from the output) controls/signals and +12V AUX can be connected in parallel.
ENABLE of all supplies can be connected to a single switch.
For PMBus option.
If voltage programming is done with PMBus, Voltage Programming and VREFERENCE OUT of all units must be connected in parallel.
Connect PMBus Signals in parallel (PMBUS is isolated from output), and choose different address for each unit.
HFE1600
+V A6~A10
+SENSE B9
-SENSE B4
-V A1~A5
ENABLE B7
SIGNAL RETURN B1
CURRENT SHARE B6
LOAD
+V
-V
HFE1600
+V A6~A10
+SENSE B9
-SENSE B4
-V A1~A5
ENABLE B7
SIGNAL RETURN B1
CURRENT SHARE B6
HFE1600
+V A6~A10
+SENSE B9
-SENSE B4
-V A1~A5
ENABLE B7
SIGNAL RETURN B1
CURRENT SHARE B6
15
4.2
Series Operation
Up to 2 units with the same rating (voltage and current) can be used in series to increase the output voltage.
Connect Main Output in series (as shown).
Diodes should be connected in parallel with each unit output to prevent reverse voltage. Each diode should be
rated to at least the power supply rated output voltage and output current.
Connect as shown: +Sense of positive unit and –Sense of negative unit (twisted pair) to Load point, or to +V
and –V accordingly for Local Sense.
In case PMBus is used, Connect PMBus signals in parallel (PMBus is isolated from Output), and choose different
address for each unit (see chapter 3).
Output Voltage can be adjusted independently for each unit.
Controls Monitoring signals and +12V AUX are referenced to “SIGNAL RETURN” and may be connected in
parallel.
Figure 4–2:
Series Connection (Remote Sense Configuration)
* Diodes rated to at least Vout max and lout max are supplied by user
HFE1600
+V A6~A10
+SENSE B9
-SENSE B4
-V A1~A5
ENABLE B7
SIGNAL RETURN B1
HFE1600
+V A6~A10
+SENSE B9
-SENSE B4
-V A1~A5
ENABLE B7
SIGNAL RETURN B1
LOAD
+V
-V
16
CHAPTER 5: PMBUS INTERFACE
5.1
HFE1600/S Series I²C Specification
1. FEATURES
1.1 Output voltage measurement
1.2 Output voltage programming.
1.3 Output current measurement
1.4 Internal ambient temperature measurement
1.5 Product information
1.6 Status information
1.7 SMBus alert
1.8 Clock frequency: 100KHz
1.9 Address lines: 4
2. OUTPUT VOLTAGE MEASUREMENT
HFE1600-12/S
HFE1600-24/S
HFE1600-32/S
HFE1600-48/S
2.1 Measurement accuracy
-
+/-2% of full scale. Refer to instruction manual
2.2 Measurement resolution - 10 bit
2.3 Measurement range (Full Scale, Only for Accuracy Calculation)
V
0~15
0~30
0~40
0~60
3. OUTPUT VOLTAGE PROGRAMMING
HFE1600-12/S
HFE1600-24/S
HFE1600-32/S
HFE1600-48/S
3.1 Programming accuracy - +/-2% of full scale
3.2 Programming resolution - 10 bit
3.3 Programming range
V
9.6~13.2
19.2~29.0
25.6~38.4
38.4~58
4. OUTPUT CURRENT MEASUREMENT
HFE1600-12/S
HFE1600-24/S
HFE1600-32/S
HFE1600-48/S
4.1 Measurement accuracy (*1)
-
+/-10% of full scale
4.2 Measurement resolution - 10 bit
4.3 Measurement range (Full Scale, Only for Accuracy Calculation)
A
0~160
0~80
0~60
0~40
(*1) Applicable for load above 15% of nominal output current
5. INTERNAL AMBIENT TEMPERATURE MEASUREMENT
5.1 Measurement device accuracy
-
±3°C
5.2 Measurement resolution - 10 bit
5.3 Measurement range  0~100
6. PRODUCT INFORMATION
.6 1 Product ID - Factory programmed
6.2 Model Name - Factory programmed
6.3 Revision
-
Factory programmed
6.4 Serial Number - Factory programmed
6.5 Manufacturing location
-
Factory programmed
6.6 Coefficients - Factory programmed
6.7 Date of Manufacture - Factory programmed
6.8 Nominal Output - Factory programmed
7. STATUS INFORMATION
7.1 "FAN FAIL" Signal - "1" -FAIL, "0"-OK
7.2 "DC FAIL" Signal - "1" -FAIL, "0"-OK
7.3 Output "OVP" Signal - "1"- OVP, "0"-OK
7.4 "TEMPERATURE ALARM" signal
-
"1"- ALARM, "0"-OK
7.5 "OTP" Signal - "1" -OTP, "0"-OK
7.6 "AC FAIL" Signal - "1" -FAIL, "0"-OK
7.7 I²C ON/OFF control - "1" -ON, "0"-OFF
17
5.1.1 PMBus Interface
The communications bus signals are powered by an external 3.3V power source pulled up with a 1.5kΩ resistor.
5.1.2 HFE1600 May Have Option al Pow e r M an age m en t Bu s Har dw are
The PMBUS interface in the HFE1600 (/S option) includes:
Monitoring the Output Voltage, Current and Temperature.
Programming the Output Voltage.
Programming the Maximum allowed output Voltage.
Programming the Supply On/OFF.
Reading and Clearing Faults.
Reading the Manufacturing Related Data (Model Name, Serial No, Manufacturing Date, etc.).
Storing the following conditions at AC Off.
- Set Output voltage.
- Max allowed programmable output voltage.
ATTENTION:
If PMBus is used for voltage programming, the reference voltage will not be fixed to 5V but can be variable
(Reference voltage will be used for voltage programming).
The PMBUS supports:
100 KHz Operation.
Block Read Protocol.
Group Command Protocol.
Direct Data Format for Monitoring and Programming Functions.
5.1.3 Addressing (A3, A2, A1, A0 Inputs)
Four variable address lines allow up to 16 Supplies to be connected on a single bus. PMBus uses 7 bit addressing. There is constant part of address and variable part of address: Constant part of address consists of 3 Most Significant Bits A6, A5, A4 always equals 001. Variable part of address consists of 4 Least Significant bits: A3, A2, A1, and A0. Value of these four bits have to be assigned by hardware connections of 4 pins of the PS connectors. The Address lines (A3, A2, A1, and A0) are internally pulled up by resistors to +5V. The address lines can be left open for ‹1› address or connected to -S for ‹0› address. So, available Address Space contains 16 possible addresses: from 0010000 to 0011111.
In case more than one unit is connected to PMBus, each unit must be set to its own unique address. Duplicate addressing is not allowed.
For example: First unit - A3(J1.B10), A2(J1.B5), A1(J1.B14), A0(J1.B16) are not connected – ADDRESS 0011111;
Second unit - A0(J1.B16) is connected to -SENSE – ADDRESS 0011110;
Third unit – A1(J1.B14) is connected to -SENSE – ADDRESS 0011101;
ATTENTION:
A3, A2, A1, A0 signals and -SENSE are NOT isolated from the Output Terminals. Hot Plug: When hot plugging a power supply into a live system, the supply takes about 1-2 seconds to configure
It is address on the bus (based on the analog voltage levels present on the back plane).
5.1.4 Serial Clock
This line is clocked by the Controller which controls the PMBUS. It should be connected to +3.3V (Referenced to "Signal RTN") via a 1.5kΩ pull-up resistor.
5.1.5 Serial Data
This is a Bi-Directional line which must be connected to +3.3V (referenced to Signal RTN) via a 1.5kΩ pull up resistor.
18
5.1.6 SMB Alert
SMBALERT is used to indicate to the HOST about any Faults/Error Conditions. This line must be connected to +3.3V (referenced to Signal RTN) via a 1.5kΩ pull up resistor. This Signal is HIGH to indicate that no fault/error is present. If some fault/error occurs, the signal will go LOW. The Host system must poll multiple supplies after receiving SMBALERT to retrieve fault/warning information.
5.1.7 PMBus Typical Connection
"SIGNAL RETURN" and PMBus signals are isolated from the Output terminals and Senses.
Figure 5–1: PMBus Typical Connection
19
5.2
PMBus Command Set
The interval between two consecutive commands to the power supply should be at least 25ms to ensure proper monitoring functionality.
5.2.1 Read Status
This Command is used to read the status of the Power Supply. The Status information is stored in a special register called the “STATUS REGISTER”. The PMBUS reads 8 different types of Faults and Warnings.
Command Used
Type
#Data bytes
D0h
Read Byte
1
Fault is indicated by “1”. No fault is indicated by ”0”. For Example: If DC Fail occurs, READ_STATUS will return 01h. SMBALERT will go “LOW”.
If AC Fail occurs, READ_STATUS will return 11h. SMBALERT will go “LOW”.
Faults Type
Bit No in
Status
Register
Meaning Main Output Behavior
DC Fail
FAULT
0
Output Voltage < 85~95% of Set Vout
Output OFF/Output Low
Over Temperature Protection
FAULT
1
Internal temperature higher than safe limit
Output OFF
Over Temperature Alarm
WARNING
2
Internal temperature ~ 10℃ below safe limit
Output ON
Fan Fail
FAULT
3
One or both Fans are not working
Output OFF
AC Fail
FAULT
4
Input Voltage <85Vac / >270Vac
Output OFF/Output ON
Over Voltage Protection
FAULT
5
Output Voltage > 1.15xVset
Output OFF
Programmed Voltage more than allowed
WARNING
6
Programmed Voltage more than Max Allowed Voltage (*1)
Output ON Command Error
WARNING
7
Command not understood by Power Supply (*2)
Output ON
(*1) If Max Allowed Voltage is set to 48V and Programmed Voltage is set to 50V, Output will be programmed to 48V, Bit No 6 will be “1”, and SMBALERT will become “LOW”. (*2) If any Command sent is not understood by the Supply, bit no 7 will be “1” and SMBALERT will become “LOW”.
5.2.2 Clear Faults
This command is used to clear the “STATUS REGISTER” after any fault occurs. If the CLEAR_FAULTS command is not sent after any fault, the “STATUS REGISTER” will not be cleared. SMBALERT signal will remain “LOW” until “CLEAR_FAULTS” command is sent. If a Fault or Warning is still present after “CLEAR_FAULTS” is sent, “STATUS REGISTER” will be updated and the SMBALERT signal will be “LOW” again.
Command Code
Type
#Data bytes
03h
Send Byte
0
5.2.3 Operation (ON/OFF)
Command Code
Type
#Data bytes
01h
R/W Byte
00h=OFF
01h
R/W Byte
80h=ON
If the Power Supply is turned OFF with the “OPERATION OFF” command, the Supply can be turned ON with the “OPERATION ON” command only. Inhibit and Enable signals are disabled.
5.2.4 Commands to Read Inventory Details
Command Name
Command Code
Type
#Data Bytes
PMBUS_REVISION
98h
Read Byte
1
MFR_ID
99h
Read Block
16
MFR_MODEL
9Ah
Read Block
16
MFR_OUTPUT
D1h
Read Block
16
MFR_REVISION
9Bh
Read Block
16
MFR_LOCATION
9Ch
Read Block
16
MFR_DATE
9Dh
Read Block
16
MFR_SERIAL
9Eh
Read Block
20
All details except for ‹PMBUS_REVISION› are stored in ASCII format.
20
5.3
Programming and Monitoring Functions
For Monitoring and Programming functions use the following equation. This is the direct data format.
=( + ) 10, =

Where Y - digital value sent or received from the supply.
X is the normal value (V, A, °C) m, b, R - coefficients that are explained in
Table 5-1.
Voltage (V)
Physical value
Physical Unit
Min. Value
Max. Value
m b R
48
Voltage Programming
V
38.4
58
426
-15335
-1
Voltage monitoring
V 0 60
1705 0 -2
Current monitoring
A 0 40
25575 0 -3
Temperature monitoring
0
100
1023 0 -2
32
Voltage Programming
V
28.8
38.4
639
-15333
-1
Voltage monitoring
V 0 40
25575 0 -3
Current monitoring
A 0 60
1705 0 -2
Temperature monitoring
0
100
1023 0 -2
24
Voltage Programming
V
19.2
29
853
-15360
-1
Voltage monitoring
V 0 30
341 0 -1
Current monitoring
A 0 80
12787 0 -3
Temperature monitoring
0
100
1023 0 -2
12
Voltage Programming
V
9.6
13.2
1705
-15345
-1
Voltage monitoring
V 0 15
682 0 -1
Current monitoring
A 0 160
6394 0 -3
Temperature monitoring
0
100
1023 0 -2
Table 5-1:
Coefficients Table
m, b, R coefficients can also be recovered from the EEPROM.
Coefficients are stored in ASCII Format.
Command Name
Command Code
Type
#Data Bytes
MFR_VOLTAGE_MON_COEFF
D2h
Read Block
16
MFR_CURRENT_MON _COEFF
D3h
Read Block
16
MFR_TEMP_MON_COEFF
D4h
Read Block
16
MFR_VOLTAGE PROG_COEFF
D5h
Read Block
17
5.3.1 Monitoring Output Voltage (READ_VOUT)
The accuracy of the voltage reading is +/-2% The output voltage is read before the ORING Circuit (~50mV Voltage drop @ load, no drop @no load). The read back Output Voltage can be calculated using the “Direct data Format”. Refer to
Table 5-1 for the Coefficients for calculating the Output Voltage.
Command Code
Type
#Data Bytes
8Bh
Read Word
2
Example: Power Supply HFE1600-48;
Hex read back = 032Ch; Converted to Decimal = 812; Using the required coefficients the Output Voltage 812x100/1705 = 47.62V. Read the Actual Output Voltage on the Output Bus Bar (Ex: 47.90V). Add 0.05V to compensate O-Ring Circuit drop. So, the actual voltage is (Ex: 47.90 + 0.05 = 47.95V). Accuracy is (47.95-47.62)/60(*1) x100 = 0.55%
21
Supply (*1)
Full Scale (*1)
HFE1600-12
15V
HFE1600-24
30V
HFE1600-32
40V
HFE1600-48
60V
5.3.2 Monitoring Output Current (READ_IOUT)
The accuracy of the current reading is +/-10% The read back output current can be calculated using the “Direct data Format”. Refer to
Table 5-1 for the Coefficients for calculating the Output Current.
Command Used
Type
#Data Bytes
8Ch
Read Word
2
Example: Hex read back = 0361h;
Converted to Decimal = 865; Using the required coefficients the output current = 865x1000/25575 = 33.82A; Read the actual Output current (Ex: 33.05A) / Accuracy is (33.05-33.82)/40(*1)x100 = -1.92%.
Supply (*1)
Full Scale (*1)
HFE1600-12
160A
HFE1600-24
80A
HFE1600-32
60A
HFE1600-48
40A
5.3.3 Monitoring Supply Temperature (READ_TEMPERATURE_1)
The accuracy of the Temperature reading is +/-3 The read back supply temperature can be calculated using the “Direct data Format”. Please refer to
Table 5-1 for the Coefficients for calculating the Supply Temperature.
Command Used
Type
#Data Bytes
8Dh
Read Word
2
Example: Hex read back = 01DCh;
Converted to Decimal = 476; Using the required coefficients the Supply Internal Temperature = 476*100/1023 = 46.53.
5.3.4 Programming Output Voltage (VOUT_COMMAND)
The accuracy of the Output Voltage Programming is +/-2% The output Voltage can be programmed using the “Direct data Format”. Please refer to
Table 5-1 for the Coefficients to be used for calculating the Voltage Programming.
Command Used
Type
#Data Bytes
21h
R/W Word
2
Example: Power Supply HFE1600-24;
To program the Output Voltage to 24V, send (853x24+(-15360))/10 = 511 (DEC); Read the actual set output Voltage (Ex: 24.05V) / Accuracy is (24.05-24)/30(*1)x100 = 0.16%.
Supply (*1)
Full Scale (*1)
HFE1600-12
15V
HFE1600-24
30V
HFE1600-32
40V
HFE1600-48
60V
22
5.3.5 Programmable Maximum Output Voltage (VOUT_MAX)
The output Voltage can be programmed using the “Direct data Format”. Please refer to
Table 5-1 for the Coefficients to be used for calculating the Voltage Programming.
Command Used
Type
#Data Bytes
24h
R/W Word
2
Example: Power Supply HFE1600-24;
To program the maximum programmable output voltage to 29V. Send (853x29+(-15360))/10 = 938 (DEC).
5.3.6 Enabling / Dis ab ling Monitoring Filter
Monitoring filter can be enabled in order to reduce the effect of noise on the readback data.
Command Used
Type
#Data Bytes
D6h
R/W Byte
00h=OFF
D6h
R/W Word
01h=ON
23
This page intentionally left blank
Loading...