
WARRANTY ..........................................................................................................................................
SAFETY INSTRUCTIONS.....................................................................................................................
GERMAN SAFETY INSTRUCTIONS ...................................................................................................
....................................................................................
1.1 OPERATION MANUAL CONTENT .................................................................................................
1.2 INTRODUCTION .............................................................................................................................
1.2.1 General description ................................................................................................................
1.2.2 Models covered ......................................................................................................................
1.2.3 Features and options .............................................................................................................
1.2.4 Multiple output power system .................................................................................................
1.2.5 Control via the serial communication port ..............................................................................
1.2.6 Analog voltage programming and monitoring .................................................................. ......
1.2.7 Parallel operation ...................................................................................................................
1.2.8 Output connections ................................................................................................................
1.2.9 Cooling and mechanical construction ....................................................................................
1.3 ACCESSORIES ...............................................................................................................................
1.3.1 General ..................................................................................................................................
1.3.2 Serial link cable ......................................................................................................................
1.3.3 Misc. hardware .......................................................................................................................
1.3.4 AC cables ..............................................................................................................................
1.3.5 Rack Mount kit.......................................................................................................................
1.3.6 Serial Port Cables...................................................................................................................
...................................................................................................
2.1 OUTPUT RATING ...........................................................................................................................
2.2 INPUT CHARACTERISTICS ..........................................................................................................
2.3 CONSTANT VOLTAGE MODE .......................................................................................................
2.4 CONSTANT CURRENT MODE ......................................................................................................
2.5 ANALOG PROGRAMMING AND MONITORING ............................................................................
2.6 PROGRAMMING AND READBACK ...............................................................................................
2.7 PROTECTIVE FUNCTIONS ...........................................................................................................
2.8 FRONT PANEL ................................................................................................................................
2.9 ENVIRONMENTAL CONDITIONS ..................................................................................................
2.10 MECHANICAL ..............................................................................................................................
2.11 SAFETY/EMC ...............................................................................................................................
2.12 SUPPLEMENTAL CHARACTERISTICS .......................................................................................
2.13 OUTLINE DRAWINGS .................................................................................................................
.......................................................................................................
3.1 GENERAL .......................................................................................................................................
3.2 PREPARATION FOR USE ..............................................................................................................
3.3 INITIAL INSPECTION .....................................................................................................................
3.4 RACK MOUNTING ..........................................................................................................................
3.4.1 Single unit installation .............................................................................................................
3.4.2 Dual unit installation ..............................................................................................................
3.4.3 GENH/RM Rack Mounting outline drawings ..........................................................................
3.5 LOCATION MOUNTING AND COOLING .......................................................................................
3.6 AC SOURCE REQUIREMENTS .....................................................................................................
3.7 AC INPUT POWER CONNECTION ................................................................................................
3.7.1 AC input connector................. ................................................................................................
3.7.2 AC input cord ..........................................................................................................................
3.8 TURN-ON CHECKOUT PROCEDURE ...........................................................................................
3.8.1 General ...................................................................................................................................
3.8.2 Prior to operation ...................................................................................................................
3.8.3 Constant voltage check ..........................................................................................................
3.8.4 Constant current check ..........................................................................................................
3.8.5 OVP check .............................................................................................................................
3.8.6 UVL check ..............................................................................................................................
3.8.7 Foldback check ......................................................................................................................
3.8.8 Address setting ......................................................................................................................
3.8.9 Baud rate setting ....................................................................................................................
CHAPTER 1 GENERAL INFORMATION
CHAPTER 2 SPECIFICATIONS
CHAPTER 3 INSTALLATION
TABLEOF CONTENTS
Pg.6
Pg.6
Pg.6
Pg.6
Pg.6
Pg.6
Pg.7
Pg.7
Pg.7
Pg.7
Pg.7
Pg.8
Pg.8
Pg.8
Pg.8
Pg.8
Pg.8
Pg.8
Pg.8
Pg.9
Pg.9
Pg.9
Pg.9
Pg.9
Pg.9
Pg.10
Pg.10
Pg.10
Pg.10
Pg.10
Pg.10
Pg.11
Pg.12
Pg.13
Pg.13
Pg.13
Pg.13
Pg.14
Pg.14
Pg.14
Pg.15
Pg.15
Pg.15
Pg.15
Pg.16
Pg.16
Pg.16
Pg.16
Pg.16
Pg.17
Pg.17
Pg.17
Pg.17
Pg.18
Pg.18
Pg.18
Pg.1
Pg.2
Pg.4

WARRANTY ..........................................................................................................................................
SAFETY INSTRUCTIONS.....................................................................................................................
GERMAN SAFETY INSTRUCTIONS ...................................................................................................
....................................................................................
1.1 OPERATION MANUAL CONTENT .................................................................................................
1.2 INTRODUCTION .............................................................................................................................
1.2.1 General description ................................................................................................................
1.2.2 Models covered ......................................................................................................................
1.2.3 Features and options .............................................................................................................
1.2.4 Multiple output power system .................................................................................................
1.2.5 Control via the serial communication port ..............................................................................
1.2.6 Analog voltage programming and monitoring .................................................................. ......
1.2.7 Parallel operation ...................................................................................................................
1.2.8 Output connections ................................................................................................................
1.2.9 Cooling and mechanical construction ....................................................................................
1.3 ACCESSORIES ...............................................................................................................................
1.3.1 General ..................................................................................................................................
1.3.2 Serial link cable ......................................................................................................................
1.3.3 Misc. hardware .......................................................................................................................
1.3.4 AC cables ..............................................................................................................................
1.3.5 Rack Mount kit.......................................................................................................................
1.3.6 Serial Port Cables...................................................................................................................
...................................................................................................
2.1 OUTPUT RATING ...........................................................................................................................
2.2 INPUT CHARACTERISTICS ..........................................................................................................
2.3 CONSTANT VOLTAGE MODE .......................................................................................................
2.4 CONSTANT CURRENT MODE ......................................................................................................
2.5 ANALOG PROGRAMMING AND MONITORING ............................................................................
2.6 PROGRAMMING AND READBACK ...............................................................................................
2.7 PROTECTIVE FUNCTIONS ...........................................................................................................
2.8 FRONT PANEL ................................................................................................................................
2.9 ENVIRONMENTAL CONDITIONS ..................................................................................................
2.10 MECHANICAL ..............................................................................................................................
2.11 SAFETY/EMC ...............................................................................................................................
2.12 SUPPLEMENTAL CHARACTERISTICS .......................................................................................
2.13 OUTLINE DRAWINGS .................................................................................................................
.......................................................................................................
3.1 GENERAL .......................................................................................................................................
3.2 PREPARATION FOR USE ..............................................................................................................
3.3 INITIAL INSPECTION .....................................................................................................................
3.4 RACK MOUNTING ..........................................................................................................................
3.4.1 Single unit installation .............................................................................................................
3.4.2 Dual unit installation ..............................................................................................................
3.4.3 GENH/RM Rack Mounting outline drawings ..........................................................................
3.5 LOCATION MOUNTING AND COOLING .......................................................................................
3.6 AC SOURCE REQUIREMENTS .....................................................................................................
3.7 AC INPUT POWER CONNECTION ................................................................................................
3.7.1 AC input connector................. ................................................................................................
3.7.2 AC input cord ..........................................................................................................................
3.8 TURN-ON CHECKOUT PROCEDURE ...........................................................................................
3.8.1 General ...................................................................................................................................
3.8.2 Prior to operation ...................................................................................................................
3.8.3 Constant voltage check ..........................................................................................................
3.8.4 Constant current check ..........................................................................................................
3.8.5 OVP check .............................................................................................................................
3.8.6 UVL check ..............................................................................................................................
3.8.7 Foldback check ......................................................................................................................
3.8.8 Address setting ......................................................................................................................
3.8.9 Baud rate setting ....................................................................................................................
CHAPTER 1 GENERAL INFORMATION
CHAPTER 2 SPECIFICATIONS
CHAPTER 3 INSTALLATION
TABLEOF CONTENTS
Pg.6
Pg.6
Pg.6
Pg.6
Pg.6
Pg.6
Pg.7
Pg.7
Pg.7
Pg.7
Pg.7
Pg.8
Pg.8
Pg.8
Pg.8
Pg.8
Pg.8
Pg.8
Pg.8
Pg.9
Pg.9
Pg.9
Pg.9
Pg.9
Pg.9
Pg.10
Pg.10
Pg.10
Pg.10
Pg.10
Pg.10
Pg.11
Pg.12
Pg.13
Pg.13
Pg.13
Pg.13
Pg.14
Pg.14
Pg.14
Pg.15
Pg.15
Pg.15
Pg.15
Pg.16
Pg.16
Pg.16
Pg.16
Pg.16
Pg.17
Pg.17
Pg.17
Pg.17
Pg.18
Pg.18
Pg.18
Pg.1
Pg.2
Pg.4

3.9 CONNECTING THE LOAD ..........................................................................................................
3.9.1 Load Wiring ..........................................................................................................................
3.9.2 Current Carrying Capacity ...................................................................................................
3.9.3 Wire termination .................................................................................................................
3.9.4 Noise and Impedance Effects ..............................................................................................
3.9.5 Inductive loads .....................................................................................................................
3.9.6 Making the load connections ................................................................................................
3.9.7 Connecting single loads, local sensing (default) ..................................................................
3.9.8 Connecting single loads, remote sensing ............................................................................
3.9.9 Connecting multiple loads, radial distribution method ..........................................................
3.9.10 Multiple loads connection with distribution terminals .........................................................
3.9.11 Grounding outputs .............................................................................................................
3.10 LOCAL AND REMOTE SENSING .............................................................................................
3.10.1 Sensing wiring ...................................................................................................................
3.10.2 Local sensing .....................................................................................................................
3.10.3 Remote sensing .................................................................................................................
3.10.4 J2 sense connector technical information ..........................................................................
3.11 REPACKAGING FOR SHIPMENT .............................................................................................
...............
4.1 INTRODUCTION ..........................................................................................................................
4.2 FRONT PANEL CONTROLS AND INDICATORS ........................................................................
4.3 REAR PANEL ...............................................................................................................................
4.4 REAR PANEL SW1 SETUP SWITCH .........................................................................................
4.4.1 SW1 positions functions ......................................................................................................
4.4.2 Resetting the switch .............................................................................................................
4.5 REAR PANEL J1 PROGRAMMING AND MONITORING CONNECTOR ....................................
4.5.1 Making J1 connections ........................................................................................................
.............................................................................................
5.1 INTRODUCTION ..........................................................................................................................
5.2 STANDARD OPERATION ............................................................................................................
5.2.1 Constant Voltage Mode .......................................................................................................
5.2.2 Constant Current Operation .................................................................................................
5.2.3 Automatic Crossover ............................................................................................................
5.3 OVER VOLTAGE PROTECTION (OVP) ......................................................................................
5.3.1 Setting the OVP level ..........................................................................................................
5.3.2 Activated OVP protection indications ...................................................................................
5.3.3 Resetting the OVP circuit .....................................................................................................
5.4 UNDER VOLTAGE LIMIT (UVL) ..................................................................................................
5.4.1 Setting the UVL level ...........................................................................................................
5.5 FOLDBACK PROTECTION ..........................................................................................................
5.5.1 Setting the Foldback protection ...........................................................................................
5.5.2. Resetting activated Foldback protection ............................................................................
5.6 OUTPUT ON/OFF CONTROL ......................................................................................................
5.7 OUTPUT SHUT-OFF (SO) CONTROL VIA REAR PANEL J1 CONNECTOR ..............................
5.8 ENABLE/DISABLE CONTROL VIA REAR PANEL J1 CONNECTOR ..........................................
5.9 CV/CC SIGNAL .............................................................................................................................
5.10 PS_OK SIGNAL ..........................................................................................................................
5.11 SAFE START AND AUTO-RESTART MODES ............................................................................
5.11.1 Automatic start mode .........................................................................................................
5.11.2 Safe start mode ..................................................................................................................
5.12 OVER TEMPERATURE PROTECTION (OTP) ..........................................................................
5.13 LAST SETTING MEMORY .........................................................................................................
5.14 SERIES OPERATION .................................................................................................................
5.14.1 Series connection for increased output voltage .................................................................
5.14.2 Series connection for positive and negative output voltage ...............................................
5.15 PARALLEL OPERATION ............................................................................................................
CHAPTER 4FRONT AND REAR PANEL CONTROLS AND CONNECTORS
CHAPTER 5LOCAL OPERATION
TABLEOF CONTENTS
Pg.18
Pg.18
Pg.18
Pg.19
Pg.20
Pg.20
Pg.20
Pg.23
Pg.23
Pg.23
Pg.24
Pg.24
Pg.25
Pg.25
Pg.25
Pg.26
Pg.26
Pg.26
Pg.27
Pg.27
Pg.27
Pg.29
Pg.30
Pg.30
Pg.31
Pg.32
Pg.32
Pg.34
Pg.34
Pg.34
Pg.34
Pg.34
Pg.35
Pg.35
Pg.35
Pg.35
Pg.35
Pg.36
Pg.36
Pg.36
Pg.36
Pg.36
Pg.36
Pg.36
Pg.37
Pg.37
Pg.37
Pg.38
Pg.38
Pg.38
Pg.38
Pg.38
Pg.38
Pg.39
Pg.40
Pg.41
TABLEOF CONTENTS
Pg.43
Pg.43
Pg.43
Pg.43
5.16 DAISY-CHAIN CONNECTION......................................................................................................
5.17 FRONT PANEL LOCKING.............................................................................................................
5.17.1 Unlocked front panel ............................................................................................................
5.17.2 Locked front panel ...............................................................................................................
CHAPTER 6 REMOTE ANALOG PROGRAMMING
.................................................................
6.1 INTRODUCTION ...........................................................................................................................
6.2 LOCAL/REMOTE ANALOG CONTROLL.......................................................................................
6.3 LOCAL/REMOTE ANALOG INDICATION......................................................................................
6.4 REMOTE VOLTAGE PROGRAMMING OF OUTPUT VOLTAGE AND CURRENT LIMIT .............
6.5 RESISTIVE PROGRAMMING OF OUTPUT VOLTAGE AND CURRENT LIMIT ...........................
6.6 REMOTE MONITORING OF OUTPUT VOLTAGE AND CURRENT .............................................
TABLEOF CONTENTS
Pg.44
Pg.44
Pg.44
Pg.44
Pg.45
Pg.46
Pg.47
Pg.43
Pg.43
Pg.43
Pg.43
5.16 DAISY-CHAIN CONNECTION......................................................................................................
5.17 FRONT PANEL LOCKING.............................................................................................................
5.17.1 Unlocked front panel ............................................................................................................
5.17.2 Locked front panel ...............................................................................................................
CHAPTER 6 REMOTE ANALOG PROGRAMMING
CHAPTER7RS232&RS485 REMOTE CONTROL
.................................................................
6.1 INTRODUCTION ...........................................................................................................................
6.2 LOCAL/REMOTE ANALOG CONTROLL.......................................................................................
6.3 LOCAL/REMOTE ANALOG INDICATION......................................................................................
6.4 REMOTE VOLTAGE PROGRAMMING OF OUTPUT VOLTAGE AND CURRENT LIMIT .............
6.5 RESISTIVE PROGRAMMING OF OUTPUT VOLTAGE AND CURRENT LIMIT ...........................
6.6 REMOTE MONITORING OF OUTPUT VOLTAGE AND CURRENT .............................................
...............................................................
7.1 INTRODUCTION ...........................................................................................................................
7.2 CONFIGURATION .........................................................................................................................
7.2.1 Default setting .......................................................................................................................
7.2.2 Address setting .....................................................................................................................
7.2.3 RS232 or RS485 selection ...................................................................................................
7.2.4 Baud rate setting ...................................................................................................................
7.2.5 Setting the unit into Remote or Local mode ..........................................................................
7.2.6 RS232/458 port at Local mode .............................................................................................
7.2.7 Front panel in Remote mode ................................................................................................
7.3 REAR PANEL RS232/485 CONNECTOR ......................................................................................
7.4 CONNECTING POWER SUPPLIES TO RS232 OR RS485 BUS .................................................
7.4.1 Single power supply ..............................................................................................................
7.4.2 Multi power supplies connection to RS232 or RS485 bus ....................................................
7.5 COMMUNICATION INTERFACE PROTOCOL ..............................................................................
7.5.1 Data format ...........................................................................................................................
7.5.2 Addressing ............................................................................................................................
7.5.3 End of message ....................................................................................................................
7.5.4 Command repeat .................................................................................................................
7.5.5 Checksum .............................................................................................................................
7.5.6 Acknowledge .........................................................................................................................
7.5.7 Error message ......................................................................................................................
7.5.8 Backspace ............................................................................................................................
7.6 ERROR MESSAGES .....................................................................................................................
7.7 COMMAND SET DESCRIPTION ..................................................................................................
7.7.1 General guides .....................................................................................................................
7.7.2 Command set categories ......................................................................................................
7.7.3 Initialization control commands .............................................................................................
7.7.4 ID control commands ............................................................................................................
7.7.5 Output control commands .....................................................................................................
7.7.6 Global output commands ....................................................................................................
7.7.7 Status control commands .....................................................................................................
7.8 STATUS, ERROR AND SRQ REGISTERS ...................................................................................
7.8.1 General .................................................................................................................................
7.8.2 Conditional registers .............................................................................................................
7.8.3 Service Request: Enabled and Event Registers ...................................................................
7.9 SERIAL COMMUNICATION TEST SET-UP ..................................................................................
TABLEOF CONTENTS
Pg.44
Pg.44
Pg.44
Pg.44
Pg.45
Pg.46
Pg.47
Pg.43
Pg.43
Pg.43
Pg.43
Pg.48
Pg.48
Pg.48
Pg.48
Pg.48
Pg.48
Pg.48
Pg.48
Pg.49
Pg.49
Pg.49
Pg.50
Pg.50
Pg.51
Pg.51
Pg.51
Pg.51
Pg.51
Pg.51
Pg.51
Pg.51
Pg.52
Pg.52
Pg.52
Pg.52
Pg.52
Pg.52
Pg.53
Pg.53
Pg.53
Pg.55
Pg.56
Pg.57
Pg.57
Pg.57
Pg.58
5.16 DAISY-CHAIN CONNECTION......................................................................................................
5.17 FRONT PANEL LOCKING.............................................................................................................
5.17.1 Unlocked front panel ............................................................................................................
5.17.2 Locked front panel ...............................................................................................................
CHAPTER 6 REMOTE ANALOG PROGRAMMING
CHAPTER7RS232&RS485 REMOTE CONTROL
CHAPTER8ISOLATED ANALOG PROGRAMMING OPTION
.................................................................
6.1 INTRODUCTION ...........................................................................................................................
6.2 LOCAL/REMOTE ANALOG CONTROLL.......................................................................................
6.3 LOCAL/REMOTE ANALOG INDICATION......................................................................................
6.4 REMOTE VOLTAGE PROGRAMMING OF OUTPUT VOLTAGE AND CURRENT LIMIT .............
6.5 RESISTIVE PROGRAMMING OF OUTPUT VOLTAGE AND CURRENT LIMIT ...........................
6.6 REMOTE MONITORING OF OUTPUT VOLTAGE AND CURRENT .............................................
...............................................................
7.1 INTRODUCTION ...........................................................................................................................
7.2 CONFIGURATION .........................................................................................................................
7.2.1 Default setting .......................................................................................................................
7.2.2 Address setting .....................................................................................................................
7.2.3 RS232 or RS485 selection ...................................................................................................
7.2.4 Baud rate setting ...................................................................................................................
7.2.5 Setting the unit into Remote or Local mode ..........................................................................
7.2.6 RS232/458 port at Local mode .............................................................................................
7.2.7 Front panel in Remote mode ................................................................................................
7.3 REAR PANEL RS232/485 CONNECTOR ......................................................................................
7.4 CONNECTING POWER SUPPLIES TO RS232 OR RS485 BUS .................................................
7.4.1 Single power supply ..............................................................................................................
7.4.2 Multi power supplies connection to RS232 or RS485 bus ....................................................
7.5 COMMUNICATION INTERFACE PROTOCOL ..............................................................................
7.5.1 Data format ...........................................................................................................................
7.5.2 Addressing ............................................................................................................................
7.5.3 End of message ....................................................................................................................
7.5.4 Command repeat .................................................................................................................
7.5.5 Checksum .............................................................................................................................
7.5.6 Acknowledge .........................................................................................................................
7.5.7 Error message ......................................................................................................................
7.5.8 Backspace ............................................................................................................................
7.6 ERROR MESSAGES .....................................................................................................................
7.7 COMMAND SET DESCRIPTION ..................................................................................................
7.7.1 General guides .....................................................................................................................
7.7.2 Command set categories ......................................................................................................
7.7.3 Initialization control commands .............................................................................................
7.7.4 ID control commands ............................................................................................................
7.7.5 Output control commands .....................................................................................................
7.7.6 Global output commands ....................................................................................................
7.7.7 Status control commands .....................................................................................................
7.8 STATUS, ERROR AND SRQ REGISTERS ...................................................................................
7.8.1 General .................................................................................................................................
7.8.2 Conditional registers .............................................................................................................
7.8.3 Service Request: Enabled and Event Registers ...................................................................
7.9 SERIAL COMMUNICATION TEST SET-UP ..................................................................................
..............................................
8.1 INTRODUCTION ...........................................................................................................................
8.2 SPECIFICATIONS .........................................................................................................................
8.2.1 0-5V/0-10V option .................................................................................................................
8.2.2 4-20mA option .......................................................................................................................
8.3 ISOLATED PROGRAMMING & MONITORING CONNECTOR ....................................................
8.4 SETUP AND OPERATING INSTRUCTIONS .................................................................................
8.4.1 Setting up the power supply for 0-5/0-10V Isolated Programming and Monitoring ...............
8.4.2 Setting up the power supply for 4-20mA Isolated Programming and Monitoring ..................
TABLEOF CONTENTS
Pg.44
Pg.44
Pg.44
Pg.44
Pg.45
Pg.46
Pg.47
Pg.43
Pg.43
Pg.43
Pg.43
Pg.48
Pg.48
Pg.48
Pg.48
Pg.48
Pg.48
Pg.48
Pg.48
Pg.49
Pg.49
Pg.49
Pg.50
Pg.50
Pg.51
Pg.51
Pg.51
Pg.51
Pg.51
Pg.51
Pg.51
Pg.51
Pg.52
Pg.52
Pg.52
Pg.52
Pg.52
Pg.52
Pg.53
Pg.53
Pg.53
Pg.55
Pg.56
Pg.57
Pg.57
Pg.57
Pg.58
Pg.61
Pg.62
Pg.62
Pg.62
Pg.62
Pg.62
Pg.63
Pg.64
Pg.64
Pg.64
5.16 DAISY-CHAIN CONNECTION......................................................................................................
5.17 FRONT PANEL LOCKING.............................................................................................................
5.17.1 Unlocked front panel ............................................................................................................
5.17.2 Locked front panel ...............................................................................................................
CHAPTER 9 MAINTENANCE ......................................................................................................
9.1 INTRODUCTION ...........................................................................................................................
9.2 UNITS UNDER WARRANTY .........................................................................................................
9.3 PERIODIC MAINTENANCE ..........................................................................................................
9.4 ADJUSTMENT AND CALIBRATION .............................................................................................
9.5 PA RTS REPLACEMENT AND REPAIRS .......................................................................................
9.6 TROUBLESHOOTING ...................................................................................................................
9.7 FUSE RATING ...............................................................................................................................
TABLEOF CONTENTS
Pg.65
Pg.65
Pg.65
Pg.65
Pg.65
Pg.65
Pg.65
Pg.66
CHAPTER 9 MAINTENANCE ......................................................................................................
9.1 INTRODUCTION ...........................................................................................................................
9.2 UNITS UNDER WARRANTY .........................................................................................................
9.3 PERIODIC MAINTENANCE ..........................................................................................................
9.4 ADJUSTMENT AND CALIBRATION .............................................................................................
9.5 PA RTS REPLACEMENT AND REPAIRS .......................................................................................
9.6 TROUBLESHOOTING ...................................................................................................................
9.7 FUSE RATING ...............................................................................................................................
USER MANUAL INDEX .......................................................................................................................
TABLEOF CONTENTS
Pg.65
Pg.65
Pg.65
Pg.65
Pg.65
Pg.65
Pg.65
Pg.66
Pg.67

TABLEOF CONTENTS
Pg.43
Pg.43
Pg.43
Pg.43
5.16 DAISY-CHAIN CONNECTION......................................................................................................
5.17 FRONT PANEL LOCKING.............................................................................................................
5.17.1 Unlocked front panel ............................................................................................................
5.17.2 Locked front panel ...............................................................................................................
CHAPTER 6 REMOTE ANALOG PROGRAMMING
.................................................................
6.1 INTRODUCTION ...........................................................................................................................
6.2 LOCAL/REMOTE ANALOG CONTROLL.......................................................................................
6.3 LOCAL/REMOTE ANALOG INDICATION......................................................................................
6.4 REMOTE VOLTAGE PROGRAMMING OF OUTPUT VOLTAGE AND CURRENT LIMIT .............
6.5 RESISTIVE PROGRAMMING OF OUTPUT VOLTAGE AND CURRENT LIMIT ...........................
6.6 REMOTE MONITORING OF OUTPUT VOLTAGE AND CURRENT .............................................
TABLEOF CONTENTS
Pg.44
Pg.44
Pg.44
Pg.44
Pg.45
Pg.46
Pg.47
Pg.43
Pg.43
Pg.43
Pg.43
5.16 DAISY-CHAIN CONNECTION......................................................................................................
5.17 FRONT PANEL LOCKING.............................................................................................................
5.17.1 Unlocked front panel ............................................................................................................
5.17.2 Locked front panel ...............................................................................................................
CHAPTER 6 REMOTE ANALOG PROGRAMMING
CHAPTER7RS232&RS485 REMOTE CONTROL
.................................................................
6.1 INTRODUCTION ...........................................................................................................................
6.2 LOCAL/REMOTE ANALOG CONTROLL.......................................................................................
6.3 LOCAL/REMOTE ANALOG INDICATION......................................................................................
6.4 REMOTE VOLTAGE PROGRAMMING OF OUTPUT VOLTAGE AND CURRENT LIMIT .............
6.5 RESISTIVE PROGRAMMING OF OUTPUT VOLTAGE AND CURRENT LIMIT ...........................
6.6 REMOTE MONITORING OF OUTPUT VOLTAGE AND CURRENT .............................................
...............................................................
7.1 INTRODUCTION ...........................................................................................................................
7.2 CONFIGURATION .........................................................................................................................
7.2.1 Default setting .......................................................................................................................
7.2.2 Address setting .....................................................................................................................
7.2.3 RS232 or RS485 selection ...................................................................................................
7.2.4 Baud rate setting ...................................................................................................................
7.2.5 Setting the unit into Remote or Local mode ..........................................................................
7.2.6 RS232/458 port at Local mode .............................................................................................
7.2.7 Front panel in Remote mode ................................................................................................
7.3 REAR PANEL RS232/485 CONNECTOR ......................................................................................
7.4 CONNECTING POWER SUPPLIES TO RS232 OR RS485 BUS .................................................
7.4.1 Single power supply ..............................................................................................................
7.4.2 Multi power supplies connection to RS232 or RS485 bus ....................................................
7.5 COMMUNICATION INTERFACE PROTOCOL ..............................................................................
7.5.1 Data format ...........................................................................................................................
7.5.2 Addressing ............................................................................................................................
7.5.3 End of message ....................................................................................................................
7.5.4 Command repeat .................................................................................................................
7.5.5 Checksum .............................................................................................................................
7.5.6 Acknowledge .........................................................................................................................
7.5.7 Error message ......................................................................................................................
7.5.8 Backspace ............................................................................................................................
7.6 ERROR MESSAGES .....................................................................................................................
7.7 COMMAND SET DESCRIPTION ..................................................................................................
7.7.1 General guides .....................................................................................................................
7.7.2 Command set categories ......................................................................................................
7.7.3 Initialization control commands .............................................................................................
7.7.4 ID control commands ............................................................................................................
7.7.5 Output control commands .....................................................................................................
7.7.6 Global output commands ....................................................................................................
7.7.7 Status control commands .....................................................................................................
7.8 STATUS, ERROR AND SRQ REGISTERS ...................................................................................
7.8.1 General .................................................................................................................................
7.8.2 Conditional registers .............................................................................................................
7.8.3 Service Request: Enabled and Event Registers ...................................................................
7.9 SERIAL COMMUNICATION TEST SET-UP ..................................................................................
TABLEOF CONTENTS
Pg.44
Pg.44
Pg.44
Pg.44
Pg.45
Pg.46
Pg.47
Pg.43
Pg.43
Pg.43
Pg.43
Pg.48
Pg.48
Pg.48
Pg.48
Pg.48
Pg.48
Pg.48
Pg.48
Pg.49
Pg.49
Pg.49
Pg.50
Pg.50
Pg.51
Pg.51
Pg.51
Pg.51
Pg.51
Pg.51
Pg.51
Pg.51
Pg.52
Pg.52
Pg.52
Pg.52
Pg.52
Pg.52
Pg.53
Pg.53
Pg.53
Pg.55
Pg.56
Pg.57
Pg.57
Pg.57
Pg.58
5.16 DAISY-CHAIN CONNECTION......................................................................................................
5.17 FRONT PANEL LOCKING.............................................................................................................
5.17.1 Unlocked front panel ............................................................................................................
5.17.2 Locked front panel ...............................................................................................................
CHAPTER 6 REMOTE ANALOG PROGRAMMING
CHAPTER7RS232&RS485 REMOTE CONTROL
CHAPTER8ISOLATED ANALOG PROGRAMMING OPTION
.................................................................
6.1 INTRODUCTION ...........................................................................................................................
6.2 LOCAL/REMOTE ANALOG CONTROLL.......................................................................................
6.3 LOCAL/REMOTE ANALOG INDICATION......................................................................................
6.4 REMOTE VOLTAGE PROGRAMMING OF OUTPUT VOLTAGE AND CURRENT LIMIT .............
6.5 RESISTIVE PROGRAMMING OF OUTPUT VOLTAGE AND CURRENT LIMIT ...........................
6.6 REMOTE MONITORING OF OUTPUT VOLTAGE AND CURRENT .............................................
...............................................................
7.1 INTRODUCTION ...........................................................................................................................
7.2 CONFIGURATION .........................................................................................................................
7.2.1 Default setting .......................................................................................................................
7.2.2 Address setting .....................................................................................................................
7.2.3 RS232 or RS485 selection ...................................................................................................
7.2.4 Baud rate setting ...................................................................................................................
7.2.5 Setting the unit into Remote or Local mode ..........................................................................
7.2.6 RS232/458 port at Local mode .............................................................................................
7.2.7 Front panel in Remote mode ................................................................................................
7.3 REAR PANEL RS232/485 CONNECTOR ......................................................................................
7.4 CONNECTING POWER SUPPLIES TO RS232 OR RS485 BUS .................................................
7.4.1 Single power supply ..............................................................................................................
7.4.2 Multi power supplies connection to RS232 or RS485 bus ....................................................
7.5 COMMUNICATION INTERFACE PROTOCOL ..............................................................................
7.5.1 Data format ...........................................................................................................................
7.5.2 Addressing ............................................................................................................................
7.5.3 End of message ....................................................................................................................
7.5.4 Command repeat .................................................................................................................
7.5.5 Checksum .............................................................................................................................
7.5.6 Acknowledge .........................................................................................................................
7.5.7 Error message ......................................................................................................................
7.5.8 Backspace ............................................................................................................................
7.6 ERROR MESSAGES .....................................................................................................................
7.7 COMMAND SET DESCRIPTION ..................................................................................................
7.7.1 General guides .....................................................................................................................
7.7.2 Command set categories ......................................................................................................
7.7.3 Initialization control commands .............................................................................................
7.7.4 ID control commands ............................................................................................................
7.7.5 Output control commands .....................................................................................................
7.7.6 Global output commands ....................................................................................................
7.7.7 Status control commands .....................................................................................................
7.8 STATUS, ERROR AND SRQ REGISTERS ...................................................................................
7.8.1 General .................................................................................................................................
7.8.2 Conditional registers .............................................................................................................
7.8.3 Service Request: Enabled and Event Registers ...................................................................
7.9 SERIAL COMMUNICATION TEST SET-UP ..................................................................................
..............................................
8.1 INTRODUCTION ...........................................................................................................................
8.2 SPECIFICATIONS .........................................................................................................................
8.2.1 0-5V/0-10V option .................................................................................................................
8.2.2 4-20mA option .......................................................................................................................
8.3 ISOLATED PROGRAMMING & MONITORING CONNECTOR ....................................................
8.4 SETUP AND OPERATING INSTRUCTIONS .................................................................................
8.4.1 Setting up the power supply for 0-5/0-10V Isolated Programming and Monitoring ...............
8.4.2 Setting up the power supply for 4-20mA Isolated Programming and Monitoring ..................
TABLEOF CONTENTS
Pg.44
Pg.44
Pg.44
Pg.44
Pg.45
Pg.46
Pg.47
Pg.43
Pg.43
Pg.43
Pg.43
Pg.48
Pg.48
Pg.48
Pg.48
Pg.48
Pg.48
Pg.48
Pg.48
Pg.49
Pg.49
Pg.49
Pg.50
Pg.50
Pg.51
Pg.51
Pg.51
Pg.51
Pg.51
Pg.51
Pg.51
Pg.51
Pg.52
Pg.52
Pg.52
Pg.52
Pg.52
Pg.52
Pg.53
Pg.53
Pg.53
Pg.55
Pg.56
Pg.57
Pg.57
Pg.57
Pg.58
Pg.61
Pg.62
Pg.62
Pg.62
Pg.62
Pg.62
Pg.63
Pg.64
Pg.64
Pg.64
5.16 DAISY-CHAIN CONNECTION......................................................................................................
5.17 FRONT PANEL LOCKING.............................................................................................................
5.17.1 Unlocked front panel ............................................................................................................
5.17.2 Locked front panel ...............................................................................................................
CHAPTER 9 MAINTENANCE ......................................................................................................
9.1 INTRODUCTION ...........................................................................................................................
9.2 UNITS UNDER WARRANTY .........................................................................................................
9.3 PERIODIC MAINTENANCE ..........................................................................................................
9.4 ADJUSTMENT AND CALIBRATION .............................................................................................
9.5 PA RTS REPLACEMENT AND REPAIRS .......................................................................................
9.6 TROUBLESHOOTING ...................................................................................................................
9.7 FUSE RATING ...............................................................................................................................
TABLEOF CONTENTS
Pg.65
Pg.65
Pg.65
Pg.65
Pg.65
Pg.65
Pg.65
Pg.66
CHAPTER 9 MAINTENANCE ......................................................................................................
9.1 INTRODUCTION ...........................................................................................................................
9.2 UNITS UNDER WARRANTY .........................................................................................................
9.3 PERIODIC MAINTENANCE ..........................................................................................................
9.4 ADJUSTMENT AND CALIBRATION .............................................................................................
9.5 PA RTS REPLACEMENT AND REPAIRS .......................................................................................
9.6 TROUBLESHOOTING ...................................................................................................................
9.7 FUSE RATING ...............................................................................................................................
USER MANUAL INDEX .......................................................................................................................
TABLEOF CONTENTS
Pg.65
Pg.65
Pg.65
Pg.65
Pg.65
Pg.65
Pg.65
Pg.66
Pg.67

SAFETY INSTRUCTIONS.
ENVIRONMENTAL CONDITIONS
The Genesys power supply series safety approval applies to the following operating conditions:
*Indoor use *Ambient temperature: 0Cto 50 C
*Maximum relative humidity: 90% (no condensation) *Altitude: up to 3000m
*Pollution degree 2
TM
oo
FCC COMPLIANCE NOTICE:
Note: This equipment has been tested and found to comply with the limits for aClassA
digital device, pursuant to part 15 of the FCCRules. These limits are designed to
provide reasonable protection against harmful interference when the equipment is
operated inacommercial environment. This equipment generates uses, and can
radiate radio frequency energy and, if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio communications.
Operation of this equipment inaresidential area is likely to cause harmful interference
in which case the user will be required to correct the interference at his own expense.
!
Instruction manual symbol. The instrument will be marked with this symbol when it is
necessary for the user to refer to the instruction manual.
CAUTIONRisk of Electrical Shock.
Indicates hazardous voltage.
Indicates ground terminal.
Protective Ground Conductor Terminal
Off (Supply)
On (Supply)
The WARNING sign denotes a hazard. An attention toaprocedure is called.
Not following procedure correctly could result in personal injury.
AWARNING sign should not be skipped and all indicated conditions must be
fully understood and met.
The CAUTION sign denotes a hazard. An attention toaprocedure is called. Not
following procedure correctly could result in damage to the equipment. Do not proceed
beyond aCAUTION sign until all indicated conditions are fully understood and met.
WARNING
CAUTION
FCC Notice
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two
conditions: (1) this device may not cause harmful interference, and (2) this device must accept any
interference received, including interference that may cause undesired operation.
CE Notice (European Union)
Marking by the CE Symbol indicates compliance to the EMC Directive and the Low Voltage
Directive of the European Union. Such marking is indicative that the Genesys series GENH meets
the following technical standards:
EN 55022:2010 Information technology equipment - Radio disturbance characteristics Limits and methods of measurement.
EN 55024:2010 Information thecnology equipment - Immunity characteristics - Limits and
methods of measurement.
EN 60950-1:2006+A11:2009 + A1:2010 + A12:2011 Information technology equipment Safety - Part 1: General requirements.
A “Declaration of Conformity” in accordance with the preceding directives and standards has been
made and is on file at our EU representative TDK-Lambda Limited, located at Kingsley Avenue,
Ilfracombe, Devon EX34 8ES, UK.
TM
NOTE: This equipment has been tested and found to comply with the limits for a Class A digital
device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio frequency energy and, if not
installed and used in accordance with the instruction manual, may cause harmful interference to
radio communications. Operation of this equipment in a residential area is likely to cause harmful
interference in which case the user will be required to correct the interference at his own expense.
WARNING: Modifications not expressly approved by the party responsible for compliance could
void the user’s authority to operate the equipment under FCC Rules.
WARNING: This is a Class A product. On a domestic environment this product may cause radio
interference in which case user may be required to take adequate measures.
SAFETY APPROVALS:
UL 60950-1 Second Edition, UL Listed, C-UL for Canada, IEC 60950-1 Second Edition, CE
marking, when applied to the GENH product, indicates compliance with the Low Voltage Directive
2006/95/EC in that it complies with EN 60950-1 Second Edition.

SICHERHEITS-INSTALLATIONS ANWEISUNGEN
Vorsicht
Betriebsbedingungen
Erdungskonzept
Vorsicht
Absicherung
Anschluss an Versorgungsstromkreis
Spannungsfuhrende Teile
Vor Anschluss an das Netz ist die Aufstellanleitung wie nachstehend beschrieben zu beachten.
Die nachstehenden Sicherheitsanweisungen mussen während aller Phasen des Betriebes, des
Services und der Reparatur dieser Ausrustung beachtet werden. Alle notwendigen Bedingungen
die sicherstellen, dassdie Einrichtung zu keiner GefahrimSinne dieser Norm fuhren kann, sind
in diesem Handbuch beschrieben.
TDK-Lambda Ltd.ist nichtverantwortlich furFehler, die bei der Inbetriebnahme desGerätesauf
Grundlage dieser Sicherheitsanweisungen durch den Betreiber entstehen können.
Die Genesys Stromversorgungs-Reihe ist zurInstallation gemäss Uberspannungs-Kategorie 2
entwickelt worden.
Installations Kategorie (Uberspannungs-Kategorie)2bedeutet: Kleinindustrie, Geräte,
bewegliche Ausrustung etc.. mit Uberspannungen kleiner als Installation Kategorie 3.
Dieses Produkt ist ein Gerät mitSchutzklasse1. Damitgefährliche Energieinhalte und
Spannungen vermieden werden, ist das Gerätechassis an eine Schutzerde anzuschliessen. Das
Gerät mussandie AC-Wechselspannungsversorgung mit3Leitern (L,N, PE) angeschlossen
werden. Der PE-Anschluss ist an einen festenErder anzuschliessen. BeiFestverdrahtungdes
Gerätes ist sicherzustellen, dass der PE Anschluss alserstes durchgefuhrtwird.
Jede mögliche Unterbrechung des PE-Leiters oder Trennungder PE Masse kann einen
möglichen elektrischen Schlag hervorrufen, der Personenschäden zur Folge hätte.
Es besteht Energiegefahr am RS232/485 und IEEE Anschluss, falls die Ausgangsspannung des
Gerätes grösser ist als 400V und der positive Ausgangsanschluss desNetzteiles geerdet wird.
Dies gilt insbesondere auchbei Reihenschaltungen vonunterschiedlichen Netzteilen. Wird die
RS232/485 oder IEEE Schnittstelle verwendet, ist darauf zu achten, dassder
Plus-Ausgangsanschluss nicht geerdet wird.
Sicherungen durfennur durch autorisierte Service Personen ausgetauscht
werden. Um Brandgefahr vorzubeugen, sindnur Sicherungen zu verwendenmit gleicher Bauart
und Auslösecharakteristik. Siehe hierzu Wartungsanweisungen in Kapitel9bezuglich
Sicherungen.
Der Betrieb des Gerätes ist nur fur den dafurspezifiziertenWechselspannungsbereich und der
angegebenen Frequenz erlaubt.
Der Nominaleingangsspannungsbereich der Genesys Serie liegt bei 100-240VACmit
50/60Hz. Fur einen sicheren Betrieb des Gerätes ist eine Abweichung von max.+/-10% der
Nominalsp
annung erlaubt.
Die Geräteabdeckung darf nur im stromlosen Zustand geöffnet werden. Interne Modifikationen,
sowie Bauteileaustausch ist nur durch qualifiziertes Personalerlaubt. Vor
Austausch von Bauteilen ist das Netzkabel bzw. dieVersorgungsspannung zu trennen.
Energieversorgungsanschlusse sindimmer zu trennenum Personenverletzungen durch
gefährliche Energieinhalte und Spannungen auszuschliessen. DieStromkreise sindzuentladen,
externeSpannunsquellen sindzu entfernen bevor Bauteile bzw. Komponenten getauschtwerden.
TM
TM
Erdung des DC-Ausgangs
TDK-Lambda Ltd.
TDK-Lambda Ltd.
!
Anderungen und Bauteileersatz
Umweltbedingungen
Sicherheits- und Warnsymbole
Ersatzteilaustausch-und Anderungen durfennur von
autorisierte
SERVICE-
PERSONEN durchgefuhrt werden. Fur Reparaturen oder Anderungen ist das Gerät zur
TDK-Lambda Ltd. Service-Niederlassung zu retournieren.
Die Genesys -Stromversorgungs-Serie ist gemäss den Sicherheitsabnahmenfur folgende
Betriebsbedingungen zugelassen.
*StationäreEinrichtungen in Gebäuden.
* Umgebungstemperaturbereich:0-50C.
* Maximale Relative Luftfeuchtigkeit: 90%(nicht kondensierend).
* Betriebshöhe: biszu 3000m.
*Verschmutzungsgrad 2.
VORSICHT Spannungsfuhrende Teile - Gefahr durch elektrischenSchlag bzw. Energieinhalte.
Handbuch-Symbol. Das Gerät bzw. Geräteteile werden mit diesemSymbolgekennzeichnet,
wenn es fur den Benutzernotwendig ist, sich aufdieAnweisungen im Handbuch zubeziehen.
Zeigt "spannungsfuhrende Te ile"mit gefährlicher Spannung an.
Zeigt Masse-Anschluss an, keineSchutzerde.( z.B. Masseanschluss an einen Verbraucher).
Schutzleiter-Anschlussklemme.
Symbol furSchalter oder Druckknöpfe-Zeigt die"Ein"-Stellung hier an.
Symbol furSchalter oder Druckknöpfe-Zeigt die"Aus"-Stellung hier an.
Dieses Warnaufschrift weist auf eine Gefahrhin,die eine Uberprufunganweisungnach
sich zieht.Nichteinhaltung kann zu Personenschäden fuhren.
Dieser Warnhinweisdarfnichtubersprungen werdenund diebeschriebene Vorgehensweise muss
strikt verstanden werden und dementsprechend umgesetzt werden.
Diese"Vorsichtswarnung" weist aufeine Gefahrhin,die einerVorkehrung bedarf.
Nichteinhaltung kann zur Zerstörung der Anlage oder des Gerätes fuhren.Bitte berucksichtigen
Sie Anweisungen, die dort beschrieben sind, bevor Siemit Benutzung der Anlage bzw. des
Gerätes fortfahren.
SICHERHEITS-HINWEISE
TM
o
alle
WARNING
CAUTION
!
MASCHINENLAERM
Maschinenlaerminformations Verordnung3. GPSGV, der hoechste Schalldruckpegelbetraegt
70 dB A) oder weniger gemassENISO7779.
––
(
TDK-Lambda Ltd.

CHAPTER 1 GENERAL INFORMATION
1.1 USER MANUAL CONTENT
1.2 INTRODUCTION
This user’s manual contains the operating instructions, installation instructions and specifications of
the Genesys GENH 750W power supply series. The instructions refer to the standard power
supplies, including the built-in RS232/485 serial communication. For information related to
operation with the optional IEEE programming, refer to User Manual for Power Supply IEEE
Programming Interface.
Genesys power supplies are wide output range, high performance switching power supplies. The
Genesys series is power factor corrected and operates from worldwide AC voltage range
continuously .Output voltage and current are continuously displayed and LED indicators show the
complete operating status of the power supply. The Front panel controls allow the user to set the
output parameters, the protection levels (Over-Voltage protection, Under-Voltage limit and
Foldback) and preview the settings. The rear panel includes the necessary connectors to control
and monitor the power supply operation by remote analog signals or by the built-in serial
communication (RS232/485). GPIB programming and Isolated-Analog programming/monitoring
are optional.
Model Voltage Current
range(V) range(A)
GENH6-100
GENH8-90
GENH12.5-60
GENH20-38
GENH30-25
GENH40-19
GENH60-12.5
GENH80-9.5
GENH100-7.5
GENH150-5
GENH300-2.5
GENH600-1.3
Table1-1: Models covered by the manual
Constant Voltage /Constant Current with automatic crossover.
* Active Power Factor correction.
*Universal Input Voltage 85~265Vac, continuous operation.
*Embedded Microprocessor Controller.
* Built in RS232/485 Interface.
*Voltage&Current high resolution adjustment by digital encoders.
*High accuracy programming/readback-16 bit.
* Software Calibration (no internal trimmers / potentiometers).
* Last Setting Memory.
* Independent Remote ON/OFF (opto-isolated) and Remote Enable/Disable.
TM
TM
TM
1.2.1 General description
1.2.2 Models covered by this manual
1.2.3 Features and options
*
0-6
0-8
0-12.5
0-20
0-30
0-40
0-60
0-80
0-100
0-150
0-300
0-600
0-100
0-90
0-60
0-38
0-25
0-19
0-12.5
0-9.5
0-7.5
0-5
0-2.5
0-1.3
* Parallel operation (Master/Slave) with Active current sharing.
* Remote sensing to compensate for voltage drop of power leads.
* Cooling fan speed control for low noise and extended fan life.
* Zero stacking- no ventillation holes at the top and bottom surface of the power supply.
*Optional GPIB interface (SCPI compatible).
*Optional Isolated Analog programming/monitoring (0-5V or 0-10V, user selectable
and 4-20mA).
The Genesys power supplies series can be configured intoaprogrammable power
system of up to 31 units using the built-in RS232/RS485 communication port in the power
supply and the RS485 linking cable provided with each power supply.
InaGPIB system, each power supply can be controlled using the optional GPIB controller
(factory installed).
The following parameters can be programmed via the serial communication port:
1. Output voltage setting.
2. Output current setting.
3. Output voltage measurement.
4. Output on/off control.
5. Output current measurement.
6. Foldback protection setting.
7. Over-voltage protection setting and readback.
8. Under-Voltage limit setting and readback.
9. Power-supply start up mode (last setting or safe mode)
Analog inputs and outputs are provided at the rear panel for analog control of the power
supply. The output voltage and the current limit can be programmedby analog voltage or by
resistor, and can be monitored by analog voltage. The power supply output can be remotely
set to On or Off and analog signals monitor the proper operation of the power supply and the
mode of operation (CV/CC).
Genesys power supplies of the same output voltage and current rating can be paralleled in
master-slave configuration with automatic current sharing to increase power available.
Output connections are made to rear panel bus-bars for models up to 60V and toa4-
terminal wire clamp connector for models above 60V rated output voltage. Either the
positive or negative terminal maybe grounded or the output maybe floated. Models up to
60VDC Rated Output shall not float outputsmore than +/- 60VDC above/below chassis
ground. Models >60VDC Rated Output shall not float outputsmore than +/-600VDC
above/below chassis ground. Contact factory for assistance with higher float voltage
applications.
Local or remote sense maybe used.
In remote sense, the voltage drop on the load wires
should be minimized. Refer to the specifications for the maximum voltage drop value.
* External Analog Programming and Monitoring standard (0-5V or 0-10V, user selectable).
1.2.4 Multiple output power system
1.2.5 Control via the serial communication port
1.2.6 Analog voltage programming and monitoring
1.2.7 Parallel operation
TM
TM
1.2.8 Output connections

*1: Minimum voltage is guaranteed to maximum 0.2% of the rated output voltage.
*2: Minimum current is guaranteed to maximum 0.4% of the rated output current.
*3: For cases where conformance to various safety standards (UL, IEC etc.) is required, to be
described as 100-240Vac (50/60Hz).
*4: At 100/200V input voltage and maximum output power.
*5: From 85~132Vac or 170~265Vac, constant load.
*6: From No-load to Full-load, constant input voltage. Measured at the sensing point in Remote
Sense.
*7: For load voltage change, equal to the unit voltage rating, constant input voltage.
*8: For 6V models the ripple is measured at 2~6V output voltage and full output current. For
other models, the ripple is measured at 10~100% output voltage and full output current.
*9: With rated, resistive load.
*10:For 6V~300V models: Measured with JEITA RC-9131A (1:1) probe.
For 600V model: Measured with (10:1) probe.
The supplemental characteristics give typical but non-warranted performance characteristics.
The supplemental characteristics are useful in assessing applications for the power supply.
Several kinds of supplemental characteristics are listed below.
1.Evaluation Data:Typical performance of the power supply.
2.Reliability Data:Reliability performance of the power supply.
3.IEC1000 Data: Performance of the power supply under IEC1000 test conditions.
4.EMIData: Typical EMI (conducted and radiated) performance of the power supply.
The supplemental characteristics datais held in each Lambda sales and service facility. For further
details please contact the Lambda office nearest you.
NOTES:
2.12 SUPPLEMENTAL CHARACTERISTICS
10
2.6 PROGRAMMING AND READBACK (RS232/485, Optional IEEE Interface)
1.Vout programming accuracy
2.Iout programming accuracy
3.Vout programming resolution
4.Iout programming resolution
5.Vout readback accuracy
6.Iout readback accuracy
7.Vout readback resolution
8.Iout readback resolution
---
---
---
---
---
---
---
---
0.05%+0.05% of rated output voltage
0.1%+0.1% of rated output current
0.012% of full scale
0.012% of full scale
0.1%+0.1% of rated output voltage
0.1%+0.3% of rated output current
0.012% of full scale
0.012% of full scale
2.7 PROTECTIVE FUNCTIONS
1.Foldback protection
2.Over-voltage protection
3.Over-voltage trip point
4.Output under voltage limit
5.Over temperature protection
V
6 8 12.5 20 30 40 60 80 100 150 300 600
---
---
---
---
V
Output shut-down when power supply change from CV to CC User presetable.
Inverter shut-down, manual reset by AC input recycle or by OUT button or by communication port command.
Preset by front panel or communication port. Prevents from adjusting Vout bellow limit. Does not affect
analog programming.
User selectable, latched or non latched.
0.5~7.5 0.5~10 1~15 1~24 2~36 2~44 5~66 5~88 5~110 5~165 5~330 5~660
2.8 FRONT PANEL
---
---
---
---
---
---
---
---
---
---
---
---
---
Vout/Iout manual adjust by separate encoders (coarse and fine adjustment).
OVP/UVL manual adjust by Vout. Adjust encoder.
Address selection by Voltage Adjust encoder. No of addresses:31.
Go to local control.
Output on/off
AC on/off
Front panel Lock
Foldback control
Baud rate selection: 1200, 2400, 4800, 9600 and 19200.
Re-start modes (automatic restart, safe mode).
Vout: 4 digits, accuracy: 0.5%+/-1count.
Iout: 4 digits, accuracy: 0.5%+/-1count.
VOLTAGE, CURRENT, ALARM, FINE, PREVIEW, FOLDBACK, LOCAL, OUTPUT ON.
1.Control functions
2.Display
3.Indications
2.9 ENVIRONMENTAL CONDITIONS
1.Operating temperature
2.Storage temperature
3.Operating humidity
4.Storage humidity
5.Altitude
---
--%
%
---
0~50 C, 100% load.
-20~70 C
30~90% RH (no condensation).
10~95% RH (no condensation).
Maximum 3000m. Derate output current by 2%/100m above 2000m. Alternatively, derate maximum
ambient temperature by 1 C/100m above 2000m.
o
o
O
2.10 MECHANICAL
1.Cooling
2.Weight
3.Dimensions (WxHxD)
4.Vibration
5.Shock
--Kg
mm
---
---
Forced air cooling by internal fans.
Less than 4.5Kg.
W: 214.0, H: 43.6 (57.0 Benchtop Version), D: 437.5 (Refer to Outline drawing).
MIL-810E, method 514.4, test condition I-3.3.1
Less than 20G, half sine, 11mS. Unit is unpacked.
Models with Vout 50V: Output is SELV, all communication/control interfaces (RS232/485, IEEE,
Isolated Analog, LAN, Sense, Remote Programming and Monitoring) are SELV.
Models with 60V Vout 400V: Output is Hazardous, communication/control interfaces: RS232/485,
IEEE, Isolated Analog, LAN, Remote Programing and Monitoring (pins 1-3, pins14-16) are SELV,
Sense, Remote Programming and Monitoring (pins 8-13, pins 21-25) are Hazardous.
Models with 400V Vout 600V: Output is Hazardous, all communication/control interfaces (RS232/485,
IEEE, Isolated Analog, LAN, Sense, Remote Programming and Monitoring) are Hazardous.
Vout 50V models : Input-Output (SELV): 4242VDC 1min, Input-communication/control (SELV):
4242VDC 1min, Input-Ground: 2828VDC 1min,
60V Vout 100V models: Input-Output (Hazardous): 2600VDC 1min, Input-communication/control
(SELV): 4242VDC 1min, Output(Hazardous)-SELV: 1900VDC 1min, Output(Hazardous)-Ground:
1200VDC 1min, Input-Ground: 2828VDC 1min.
100V Vout 600V models: Input-Output(Hazardous): 3550VDC 1min, Input-communication/control
(SELV): 4242VDC 1min, Hazardous. Output-communication/control(SELV): 4242VDC 1min,
Output(Hazardous)-Ground: 2670VDC 1min, Input-Ground: 2828VDC 1min.
More than 100Mohm at 25 C, 70%RH.
O
2.11 SAFETY/EMC
2.Interface classification
4.Insulation resistance
3.Withstand voltage
1.Applicable standards: Safety
---
---
---
---
---
EMC
UL 60950-1, CSA22.2 No.60950-1, IEC 60950-1, EN 60950-1
EN55022, EN55024, EN61000-3-3, FCC part 15, VCCI.
Conducted emmision - EN55022 class B, FCC part 15 class B, VCCI class B.
Radiated emmision - EN55022 class A, FCC part 15 class A, VCCI class A.
Immunity - EN55024

2. Connect the unit to an AC source as described in section 3.7.
3. Connect aDVM with appropriate cables for the rated voltage to the output terminals.
4. Turn the front panel AC power switch to On.
1. Turn on the output by pressing OUT pushbutton so the OUT LED illuminates.
2. Observe the power supply VOLT display and rotate the Voltage encoder.Ensure that the
output voltage varies while the VOLT encoder is rotated. The minimum control range is from
zero to the maximum rated output for the power supply model.
Compare the DVM reading with the front panel VOLT display to verify the accuracy of the
VOLT display. Ensure that the front panel VOLT LED is on.
3. Turn off the front panel AC power switch.
1. Ensure that the front panel AC power switch is at Off position and the DVM connected to the
output terminals shows zero voltage.
2. Connect aDC shunt across the output terminals. Ensure that the shunt and the wires' current
ratings are higher than the power supply rating. Connect a DVM to the shunt.
3. Turn the front panel AC power switch to On position.
4. Turn on the output by pressing OUT pushbutton so the OUT LED illuminates.
5. Observe the power supply CURRENT display and rotate the CURRENT encoder. Ensure that
the output current varies while the CURRENT encoder is rotated. The minimum control range
is from zero to the maximum rated output for the power supply model.
Compare the DVM reading with the front panel CURRENT display to verify the accuracy of
the CURRENT display. Ensure that the front panel CURRENT LED is on.
6. Turn off the front panel AC power switch.
7. Remove the shunt from the power supply output terminals.
Refer to Section 5.3 for explanation of the OVP function prior to performing the procedure below.
1. Turn the front panel AC power switch to On position and turn on the output by pressing OUT
pushbutton.
2. Using the VOLT encoder, adjust the output voltage to approx. 10% of the unit voltage rating.
3. Momentarily press
the OVP/UVL button so that the CURRENT display shows“OUP”. The
VOLTAGE display will show the last setting of the OVP level.
4. Rotate the VOLT encoder CCW to adjust the OVP setting to 50% of the unit voltage rating.
5. Wait a few seconds until the VOLT display returns to show the output voltage.
6. Adjust the output voltage toward it’smaximum and check that the output voltage cannot be
increased more than the OVP setting.
7. Adjust OVP limit to the maximum by repeating step 3 and rotating the VOLT encoder CW.
Refer to Section 5.4 for explanation of the UVL function prior to performing the procedure below.
1. Press the OVP/UVL button TWICEso that the CURRENT display shows"UUL". The VOLTAGE
display will show the last setting of the UVL level.
2. Rotate the VOLT encoder to adjust the UVL level to approx. 10% of the unit voltage rating.
3. Wait a few seconds until the VOLT display returns to show the output voltage.
4. Adjust the output voltage toward it’sminimum and check that the output voltage cannot be
decreased below the UVL setting.
5. Adjust the UVL limit to the minimum by repeating step1 and rotating the VOLT encoder CCW.
3.8.3 Constant VoltageCheck
3.8.4 Constant Current Check
3.8.5 OVPCheck
3.8.6 UVLCheck
3.8 TURN-ON CHECKOUT PROCEDURE
3.8.1 General
3.8.2Priorto Operation
The following procedure ensures that the power supplyis operational and may be used as a basic
incoming inspection check. Refer to Fig.4-1 and Fig.4-2for thelocationofthe controls indicated in
theprocedure.
1. Ensurethat the power supplyis configured to the default setting:
-AC On/Off switchatOff position.
-Dip switch:All positions at Down (”Off”) position.
-Sense connector : Configured to Local Sense as shown in Fig.3-4:
1 Remote(+) sense
2 Local (+) sense
3 Not connected
4 Local (-) sense
5 Remote (-) sense
-For units equipped with IEEE option, ensurethat theIEEE_En switch is in Up (default) position
(Refer to Fig.4-2, item8for location),ifcheckout is to be done in IEEE mode.
Fig.3-4: Sense connector default connection
Plug P/N: MC 1.5/5-ST-3.81
(Phoenix)
3.7.1ACInput Connector
3.7.2ACInput Cord
An IEC connector is provided on therear panel for connectingthe unittothe AC power source with
an AC cord. The IEC connector also provides the safetyground connection while theAC cordis
plugged into an appropriate AC receptacle.
Refer to section1.3.4for details of theACinput cords recommended forthe GENH750W models.
WARNING
The AC input cordisthe disconnect device of the power
supply. The plug must be readily identifiable and accessibleto
the user. The AC input cord must be no longer than 3m.
WARNING
Some componentsinsidethe power supply areatACvoltage
even when the On/Offswitch is in the“Off” position. To avoi d
electric shock hazard,disconnectthe linecord and load and
waittwo minutes before removingcover.
16

2. Connect the unit to an AC source as described in section 3.7.
3. Connect aDVM with appropriate cables for the rated voltage to the output terminals.
4. Turn the front panel AC power switch to On.
1. Turn on the output by pressing OUT pushbutton so the OUT LED illuminates.
2. Observe the power supply VOLT display and rotate the Voltage encoder.Ensure that the
output voltage varies while the VOLT encoder is rotated. The minimum control range is from
zero to the maximum rated output for the power supply model.
Compare the DVM reading with the front panel VOLT display to verify the accuracy of the
VOLT display. Ensure that the front panel VOLT LED is on.
3. Turn off the front panel AC power switch.
1. Ensure that the front panel AC power switch is at Off position and the DVM connected to the
output terminals shows zero voltage.
2. Connect aDC shunt across the output terminals. Ensure that the shunt and the wires' current
ratings are higher than the power supply rating. Connect a DVM to the shunt.
3. Turn the front panel AC power switch to On position.
4. Turn on the output by pressing OUT pushbutton so the OUT LED illuminates.
5. Observe the power supply CURRENT display and rotate the CURRENT encoder. Ensure that
the output current varies while the CURRENT encoder is rotated. The minimum control range
is from zero to the maximum rated output for the power supply model.
Compare the DVM reading with the front panel CURRENT display to verify the accuracy of
the CURRENT display. Ensure that the front panel CURRENT LED is on.
6. Turn off the front panel AC power switch.
7. Remove the shunt from the power supply output terminals.
Refer to Section 5.3 for explanation of the OVP function prior to performing the procedure below.
1. Turn the front panel AC power switch to On position and turn on the output by pressing OUT
pushbutton.
2. Using the VOLT encoder, adjust the output voltage to approx. 10% of the unit voltage rating.
3. Momentarily press
the OVP/UVL button so that the CURRENT display shows“OUP”. The
VOLTAGE display will show the last setting of the OVP level.
4. Rotate the VOLT encoder CCW to adjust the OVP setting to 50% of the unit voltage rating.
5. Wait a few seconds until the VOLT display returns to show the output voltage.
6. Adjust the output voltage toward it’smaximum and check that the output voltage cannot be
increased more than the OVP setting.
7. Adjust OVP limit to the maximum by repeating step 3 and rotating the VOLT encoder CW.
Refer to Section 5.4 for explanation of the UVL function prior to performing the procedure below.
1. Press the OVP/UVL button TWICEso that the CURRENT display shows"UUL". The VOLTAGE
display will show the last setting of the UVL level.
2. Rotate the VOLT encoder to adjust the UVL level to approx. 10% of the unit voltage rating.
3. Wait a few seconds until the VOLT display returns to show the output voltage.
4. Adjust the output voltage toward it’sminimum and check that the output voltage cannot be
decreased below the UVL setting.
5. Adjust the UVL limit to the minimum by repeating step1 and rotating the VOLT encoder CCW.
3.8.3 Constant VoltageCheck
3.8.4 Constant Current Check
3.8.5 OVPCheck
3.8.6 UVLCheck

Refer to Section 5.5 for explanation of the FOLD function prior to performing the procedure
below.
1. Ensure that the output voltage is set to approx. 10% of the unit rating.
2. Adjust the CURRENT encoder to set the current limit to approx. 10% of the unit rating.
3. Momentarily press the FOLD button. Ensure that the FOLD LED illuminates. The output
voltage remains unchanged.
4. Short the output terminals momentarily (approx. 0.5 sec.). Ensure that the output voltage falls
to zero, the VOLT display shows “Fb” and the ALARM LED blinks.
5. Press the FOLD button again to cancel the protection. The output voltage remains zero.
6. Press OUT button. Ensure that the output voltage returns to it’s last setting.
7. Turn the output offby pressing OUT button. Ensure that the VOLT display shows“OFF”.
1. Press and hold the REM/LOC button for approx. 3sec. The VOLT display will show the
communication port address.
2. Using the VOLT adjust encoder, check that the address can be set within the range of0to 30.
1. Press and hold the REM/LOC button for approx. 3sec. The CURRENT display will show the
communication port Baud Rate.
2. Using The CURRENT adjust encoder, check that the Baud Rate can be set to 1200, 2400,
4800, 9600 and 19200.
3.8.8 Address Setting
3.8.9 Baud Rate Setting
3.9 CONNECTINGTHE LOAD
Shorting the output may expose the user to hazardous
voltages. Observe proper safety procedures.
Turn off the AC input power before making or changing any
rear panel connection. Ensure that all connections are
securely tightened before applying power. There isapotential
shock hazard when using a power supply with a rated output
greater than 40V.
WARNING
WARNING
3.9.1 Load Wiring
3.9.2 Current Carrying Capacity
at least
The following considerations should be made to select wiring for connecting the load to the power
supply:
* Current carrying capacity of the wire (refer to 3.9.2)
* Insulation rating of the wire should be at least equivalent to the maximum output voltage of
the power supply.
* Maximum wire length and voltage drop (refer to 3.9.2)
* Noise and impedance effectsof the load wiring (refer to 3.9.4).
Two factors must be considered when selecting the wire size:
1. Wires should be heavy enough not to overheat while carrying the power supply load
current at the rated load, or the current that would flow in the event the load wires were
shorted, whichever is greater.
3.8.7 Foldback Check
CAUTION
When local sensing, a short from +LS or +S to -V or -S or -LS,
will cause damage to the power supply.Reversing the sense
wires might cause damage to the power supply in local and
remote sensing. (Do not connect -S to +V or +S to -V.)
Table 3-2: Maximum wire length for 1V drop on lead (in feet)
Table 3-3: Maximum wire length for 1V drop on lead (in meters)
2. Wire size should be selected to enable voltage drop per lead to be less than 1.0V at the rated
current. Although units will compensate for up to 5V in each load wire, it is recommended to
minimize the voltage drop (1V typical maximum) to prevent excessive output power consum-
ption from the power supply and poor dynamic response to load changes. Please refer to
Tables 3-2 and 3-3 for maximum wire length to limit voltage drop in American and European
dimensions respectively.
Wire size
AWG
14
12
10
8
6
4
2
0
2.526
1.589
0.9994
0.6285
0.3953
0.2486
0.1564
0.0983
5A
80
120
200
320
500
800
1200
2000
10A
40
60
100
160
250
400
600
1000
20A
20
30
50
80
125
200
300
500
50A
8
12
20
32
50
80
125
200
150A
2
3.4
6
10
16
26
40
68
Resistivity
Ohm/1000ft
Maximum length in Feet to limit
voltage drop to 1V or less
Cross sect.
area
(mm )
2
2.5
4
6
10
16
25
35
8.21
5.09
3.39
1.95
1.24
0.795
0.565
5A
24.0
39.2
59.0
102.6
160.0
250.0
354.0
10A
12.0
18.6
29.4
51.2
80.0
125.0
177.0
20A
6.0
9.8
14.8
25.6
40.0
62.0
88.0
50A
2.4
4.0
5.8
10.2
16.0
25.2
35.4
150A
0.8
1.4
2.0
3.4
5.4
8.4
11.8
Resistivity
Ohm/Km
Maximum length in meters to limit
voltage drop to 1V or less
For currents not shown in Table 3-2 and 3-3, use the formula:
Maximum length=1000/(currentxresistivity)
where current is expressed in Amperes and resistivity in ohms/km or ohms/1000ft.
3.9.3 Wire termination
The wires should be properly terminated with terminals securely attached. DO NOT use unter-
minated wires for load connection at the power supply.

WARNING
There isapotential shock hazard at the sense point when using power supply
with a rated output voltage greater than 40V. Ensure that the connections at the
load end are shielded to prevent accidental contact with hazardous voltages.
CAUTION
When using shielded sense wires, ground the shield
in one place only. The location can be the power
supply chassis or one of the output terminals.
3.10.3 Remote sensing
Use remote sense where the load regulation at the load end is critical. In remote sense, the power
supply will compensate for voltage drop on the load wires. Refer to the power supply specifications
for the maximum voltage drop on load wires. The voltage drop is subtracted from the total voltage
available at the output. Follow the instructions below to configure the power supply for remote
sensing:
1. Ensure that the AC On/Off is in the Off position.
2. Remove the local sense jumpers from J2.
3. Connect the negative sense lead to terminal J2-5 (-S) and the positive sense lead to terminal
J2-1(+S) of the J2 mating connector. Ensure that the J2 mating connector is plugged securely
into the rear panel sense connector, J2.
4. Turn On the power supply.
1. If the power supply is operating in remote sense and either the positive or negative load
wire is not connected, an internal protection circuit will activate and shut down the power
supply.To resume operation, turn the AC On/Off to the Off position, connect the open load
wire, and turn On the power supply.
2. If the power supply is operated without the remote sense lines or local sense jumpers, it will
continue to work, but the output voltage regulation will be degraded. Also, the OVP circuit may
activate and shut down the power supply.
-J2 connector type: MC 1.5/5-G-3.81, Phoenix.
- Plug type: MC 1.5/5-ST-3.81, Phoenix.
-Wire AWG; 28 up to 16.
-Strippinglength: 7mm.
-Tightening torque:1.95-2.21Lb-Inch. (
To ensure safe transportation of the instrument, contact the Lambda sales or service facility near
you for Return Authorization and shipping information. Please attach atag to the power supply
describing the problem and specifying the owner,model number and serial number of the power
supply.Refer to Warranty Information for further instructions.
Notes:
3.10.4 J2 sense connector technical information
3.11 REPACKAGING FORSHIPMENT
0.22- 0.25Nm)
CHAPTER 4FRONT AND REAR PANEL CONTROLS
AND CONNECTORS
4.1INTRODUCTION
4.2FRONT PANEL CONTROLS AND INDICATORS
The Genesys Power Supplyseries has afullset of controls, indicators and connectors that allow
theuserto easily setu pand operate the unit. Beforestartingto operate the unit, please readthe
following sections forexplanationofthe functions of the controls andconnectors terminals.
- Section4.2:Front panel controls andindicators.
- Section4.3: Rear panel controls and connectors.
See Fig.4-1toreviewthe controls, indicators and meters located on the powersupply front panel.
TM
Fig.4-1: Front panel controls and indicators
1
Number
Control/Indicator
Description
Section
High resolutionrotary encoder foradjusting the Output
Voltage. Also adjuststhe OVP/UVL levels and selects
theAddress.
VOLTAGE control
VOLTAGE indicator
Green LED,lightsfor Constant-Voltage mode
operation.
2
3
VOLTAGE display
4digit, 7-segment LED display.Normally displays the
output voltage. When the PREV buttonispressed, the
displayindicatesthe programmed settingofthe output
voltage. When the OVP/UVL buttonispressed,the
Voltage displayindicatesthe OVP/UVL setting.
Table4-1:Front Panel controls and indicators
VOLTAGE
ALARM
FINE
PREV/
OVP
UVL
FOLD
REM/LOC
OUT
DC AMPS
CURRENT
'
'
'
'
'
'
'
'
DC VOLTS
POWER
1
14
17
18
19
2
15
16
3
13
10
4
11
5
12
9
6
7
8
5.2.1
5.3.1
5.4.1
7.2.2

16
Number Control/Indicator Description
Section
FINE button
18
ALARM indicator
Table4-1:Front Panel controls and indicators
17
FINE indicator
AC Power switch
19
Voltage and Current Fine/Coarse adjustment control.
Operates asatoggleswitch.InFine mode,the
VOLTAGE and CURRENT encoders operatewith high
resolution and in Coarse mode with lower resolution
(approx.6turns).
:Advanced Parallel Operation
Mode setting.
Auxiliary function
Green LED, lights when the unitisinFine mode.
Red LED, blinks in case of fault detection. OVP, OTP
Foldback, Enable and AC fail detectionwill cause the
ALARM LED to blink.
AC On/Off control.
4.3 REAR PANEL
See Fig.4-2toreview the connections and controls located on the power supplyrear panel.
Refer to Table4-2 for explanations about therear panel connections and controls.
Fig.4-2: Rear panel connections and controls
1
Number
Item
Description
Section
AC input
connector
2
DC output
Table4-2: Rear panel connections and controls
3
IEC connector
3.7.1
Bus-barsfor 6V to 60V models.
Wire clamp connector for 80V to 600V models.
3.9.6
RJ-45 typeconnector, usefor connectingpower supplies to
RS232 or RS485 port of computer for remotecontrol purposes.
When usingseveral powersupplies inapower system, the first
unit Remote-In is connectedtothe computerand theremaining
units arechained, Remote-In to Remote-Out.
Remote-In
connector
7.3
7.4
Green LED, lights when PREV buttonispressed.
PREV indicator
15
5
6
2
8
9
7
4
3
1
80~600V
Models
6~60V
Models
10
+
VDC
+
+
5.15.2
4
Number Control/Indicator Description
Section
4 digit, 7-segment LED display.Normally displays the
output current. When the PREV button is pressed, the
display indicates the programmed setting of output
current.
CURRENT display
6
CURRENT control
High resolution rotary encoder for adjusting the Output
Current. Also selects the Baud-Rate of the
communication port.
Table 4-1: Front Panel controls and indicators
5
CURRENT indicator
Green LED, lights for Constant-Current mode operation.
Main function
Auxiliary function
:Output ON/OFF control. Press OUT to
set the output On or Off. Press to reset and turn On the
output after OVPorFOLD alarm events have occurred.
: Selects between "Safe-Start" and
"Auto-Restart" modes. Press and hold OUT button to
toggle between "Safe-Start" and "Auto-Restart".The
VOLT display will cycle between "SAF" and "AU7”.
Releasing the OUT button while one of the modes is
displayed, selects that mode.
OUT button
OUT indicator
Green LED, lights when Foldback protection is On.
Over Voltage Protection and Under Voltage limit setting.
- Press once to set OVP using VOLTAGE encoder ( the
current display shows“OUP” )
- Press again to set the UVL using VOLTAGE encoder
( the current display shows “UUL” ).
Main function
Auxiliary function
:Goto local. Press REM/LOCto put the
unit into Local (REM/LOC button is disabled at Local
Lockout mode).
: Address and Baud Rate setting.
Press and hold REM/LOC for 3sec. to set the Address
with the VOLTAGE encoder and the Baud Rate with the
CURRENT encoder.
Green LED, lights when the unit is in Remote mode.
Foldback protection control.
- Press FOLD to set Foldback protection to On.
-To release Foldback alarm event, press OUT to
enable the output and re-arm the protection.
- Press FOLD again to cancel the Foldback protection.
Main function
Auxiliary function
: Press PREV to display the output
voltage and current limit setting. For5sec. the display
will show the setting and then it will return to show the
actual output voltage and current.
: Front Panel Lock. Press and hold
PREV button to toggle between “Locked front panel”
and “Unlocked front panel”. The display will cycle
between “LFP” and “UFP”. Releasing the PREV button
while one of the modes is displayed, selects that mode.
REM/LOC button
REM/LOC indicator
FOLD button
FOLD indicator
OVP/UVL button
PREV/ button
Green LED, lights when the DC output is enabled.
7
8
9
10
11
12
13
14
5.2.2
7.2.4
5.6
7.2.5
5.11
7.2.2
7.2.4
5.5
5.3
5.4
5.17
28

CHAPTER 5LOCAL OPERATION
5.1 INTRODUCTION
5.2 STANDARD OPERATION
This Chapter describes the operating modes that are not involved in programming and monitoring
the power supply via its serial communication port (RS232/RS485) or by remote analog signals.
Ensure that the REM/LOC LED on the front panel is Off, indicating Local mode. If the REM/LOC
LED is On, press the front panel REM/LOC button to change the operating mode to local.
- For information regarding remote analog programming refer to Chapter 6.
- For information regarding usage of the serial communication port refer to Chapter 7.
The power supply has two basic operating modes: Constant Voltage Mode and Constant Current
Mode. The mode in which the power supply operates at any given time depends on the output
voltage setting, output current limit setting and the load resistance.
1. In constant voltage mode, the power supply regulates the output voltage at the selected value,
while the load current varies as required by the load.
2. While the power supply operates in constant voltage mode, the VOLTAGELED on the front panel
illuminates.
3.Adjustment of the output voltage can be made when the power supply output is enabled
(Output On)or disabled (Output Off). When the output is enabled, simply rotate the VOLTAGE
encoder knob to program the output voltage. When the output is disabled, press the PREV
button and then rotate the VOLTAGE encoder knob. The VOLTAGEmeter will show the
programmed output voltage for5seconds after the adjustment has been completed. Then the
VOLTAGEmeter will display "OFF".
4.Adjustment resolution can be set to coarse or fine resolution.
Press FINE button to select between the lower and higher resolution. The FINE LED turns On
when the resolution is set to FINE.
5.2.1 Constant VoltageMode
If after completing the adjustment, the display shows a different value
than the setting, the power supply maybeat current limit. Check the
load condition and the power supply current limit setting.
The maximum and minimum setting values of the output voltage are
limited by the Over Volt
age protection and Under Voltage limit setting.
Refer to Sec.5.3 and 5.4 for more details.
NOTE
NOTE
5.2.2 Constant Current Operation
1. In constant current mode, the power supply regulates the output current at the selected value,
while the voltage varies with the load requirement.
2. While the power supply is operating in constant current mode, the CURRENT LED on the front
panel illuminates.
3.Adjustment of the output current limit can be made when the power supply output is enabled
(Output On)or disabled (Output Off).
-Disabled output (Off): Press PREV button and then rotate the Current encoder knob. The
CURRENT meter will show the programmed current limit for 5 seconds after the adjustment
has been completed. Then the VOLTAGEmeter will display "OFF".
- Enabled output, power supply in Constant Voltage mode: Press the PREV button and then
rotate the CURRENT encoder knob. The CURRENT meter will show the programmed
current limit for5seconds after the adjustment has been completed, and then will return to
show the actual load current.
- Enabled output, power supply in Constant Current mode: Rotate the CURRENT encoder
knob to adjust the current limit.
4. Adjustment resolution can be set to Coarse or Fine adjustment. Press the FINE button to
select between the Coarse and Fine resolution. The FINE LED turns On when the resolution
is set to FINE.
If the power supply operates in Constant Voltagemode, while the load current is increased to greater
than the current limit setting, the power supply will automatically switch to Constant Current mode. If
the load is decreased to less than the current limit setting, the power supply will automatically switch
back to Constant Voltage mode.
The OVP circuit protects the load in the event ofaremote or local programming error orapower
supply failure. The protection circuit monitors the voltage at the power supply sense points and thus
providing the protection level at the load. Upon detection of an Over Voltage condition, the power
supply output will shut down.
The OVP can be set when the power supply output is Enabled (On) or Disabled (Off). To set the OVP
level, press the OVP/UVL button, so that the CURRENT meter shows"OUP".
The VOLTAGEmeter shows the OVP setting level. Rotate the VOLTAGE encoder knob to adjust the
OVP level. The display will show "OUP" and the setting value for5seconds after the adjustment has
been completed and then will return to it's previous state.
The minimum setting level is approx. 105% of the set output voltage, or the value in Table 7-6,
whichever is higher.The maximum setting level is shown in Table 5-1.
5.2.3 Automatic Crossover
5.3.1 Setting the OVP level
5.3 OVER VOLTAGEPROTECTION(OVP)
Table 5-1: Maximum OVP setting levels
5.3.2 Activated OVP protection indications
5.3.3 Resetting the OVP circuit
When the OVP is activated the power supply
output shuts down. The VOLTAGE display shows
"OUP" and the ALARM LED blinks.
To reset the OVP circuit after it activates:
1. Reduce the power supply Output Voltage setting below the OVP set level.
2. Ensure that the load and the sense wiring is connected properly.
3. There are four methods to reset the OVP circuit.
3.1 Press OUT button.
3.2 Turn the power supply Off using the AC On/Off switch, wait until the front panel display turns
Off, then turn the power supply On using the AC On/Off switch.
3.3 Turn the power supply output Off and then On using the SO control (refer to sect.5.7). In this
method the power supply should be set to Auto-Restart mode.
3.4 Send OUT1 command via the RS232/485 communication port.
60V
80V
100V
150V
300V
600V
66.0V
88.0V
110.0V
165.0V
330.0V
660.0V
Model
Max.
OVP
6V
8V
12.5V
20V
30V
40V
7.5V
10.0V
15.0V
24.0V
36.0V
44.0V
Model
Max.
OVP
To preview the OVP setting, press OVP/UVL
pushbutton so that the CURRENT display will show
"OUP". At this time, the VOLTAGE display will show the
OVP setting. After5seconds, the display will return to
it's previous state.

- Enabled output, power supply in Constant Voltage mode: Press the PREV button and then
rotate the CURRENT encoder knob. The CURRENT meter will show the programmed
current limit for5seconds after the adjustment has been completed, and then will return to
show the actual load current.
- Enabled output, power supply in Constant Current mode: Rotate the CURRENT encoder
knob to adjust the current limit.
4. Adjustment resolution can be set to Coarse or Fine adjustment. Press the FINE button to
select between the Coarse and Fine resolution. The FINE LED turns On when the resolution
is set to FINE.
If the power supply operates in Constant Voltagemode, while the load current is increased to greater
than the current limit setting, the power supply will automatically switch to Constant Current mode. If
the load is decreased to less than the current limit setting, the power supply will automatically switch
back to Constant Voltage mode.
The OVP circuit protects the load in the event ofaremote or local programming error orapower
supply failure. The protection circuit monitors the voltage at the power supply sense points and thus
providing the protection level at the load. Upon detection of an Over Voltage condition, the power
supply output will shut down.
The OVP can be set when the power supply output is Enabled (On) or Disabled (Off). To set the OVP
level, press the OVP/UVL button, so that the CURRENT meter shows"OUP".
The VOLTAGEmeter shows the OVP setting level. Rotate the VOLTAGE encoder knob to adjust the
OVP level. The display will show "OUP" and the setting value for5seconds after the adjustment has
been completed and then will return to it's previous state.
The minimum setting level is approx. 105% of the set output voltage, or the value in Table 7-6,
whichever is higher.The maximum setting level is shown in Table 5-1.
5.2.3 Automatic Crossover
5.3.1 Setting the OVP level
5.3 OVER VOLTAGEPROTECTION(OVP)
Table 5-1: Maximum OVP setting levels
5.3.2 Activated OVP protection indications
5.3.3 Resetting the OVP circuit
When the OVP is activated the power supply output
shuts down. The VOLTAGE display shows
"OUP" and the ALARM LED blinks.
To reset the OVP circuit after it activates:
1. Reduce the power supply Output Voltage setting below the OVP set level.
2. Ensure that the load and the sense wiring is connected properly.
3. There are four methods to reset the OVP circuit.
3.1 Press OUT button.
3.2 Turn the power supply Off using the AC On/Off switch, wait until the front panel display turns
Off, then turn the power supply On using the AC On/Off switch.
3.3 Turn the power supply output Off and then On using the SO control (refer to sect.5.7). In this
method the power supply should be set to Auto-Restart mode.
3.4 Send OUT1 command via the RS232/485 communication port.
60V
80V
100V
150V
300V
600V
66.0V
88.0V
110.0V
165.0V
330.0V
660.0V
Model
Max.
OVP
6V
8V
12.5V
20V
30V
40V
7.5V
10.0V
15.0V
24.0V
36.0V
44.0V
Model
Max.
OVP
To preview the OVP setting, press OVP/UVL
pushbutton so that the CURRENT display will show
"OUP". At this time, the VOLTAGE display will show the
OVP setting. After5seconds, the display will return to
it's previous state.
35

5.4 UNDER VOLTAGE LIMIT (UVL)
5.5 FOLDBACKPROTECTION
5.6 OUTPUT ON/OFF CONTROL
5.7 OUTPUT SHUT-OFF (SO) CONTROL VIA REAR PANEL J1 CONNECTOR
The UVL prevents adjustment of the output voltage below a certain limit.The combination of UVL
and OVP functions, allow the user to create a protection window for sensitive load circuitry.
Setting the UVL can be made when the power supply output is Enabled (On) or Disabled (Off). To set
the UVL level, press the OVP/UVL button TWICE, so that the CURRENT meter shows “UUL”. The
VOLTAGE meter shows the UVL setting level. Rotate the VOLTAGE encoder knob to adjust the UVL
level. The display will show “UUL” and the setting value for 5 seconds after the adjustment has been
completed and then will return to it’s previous state.
UVL setting values are limited at the maximum level to approximately 95% of the Output Voltage
setting. Attempting to adjust the UVL above this limit will result in no response to the adjustment
attempt. The minimum UVL setting is zero.
5.4.1 Setting the UVL level
Foldback protection will shut down the power supply output if the load current exceeds the current limit
setting level. This protection is useful when the load circuitry is sensitive to an over current condition.
To arm the Foldback protection, the FOLD button should be pressed so that the FOLDLED illuminates.
In this condition, transition from Constant Voltage to Constant Current mode will activate the Foldback
protection. Activation of the Foldback protection disables the power supply output, causes the ALARM
LEDtoblink and display "Fb" on the VOLTAGE meter.
There are four methods to reset an activated Foldback protection.
1. Press the OUT button. The power supply output is enabled and the Output Voltage and current
will return to their last setting. In this method, the Foldback protection remains armed, therefore if
the load current is higher than the current limit setting, the Foldback protection will be activated
again.
2. Press the FOLD button to cancel the Foldback protection. The power supply output will be disabled
and the VOLTAGE display will show “OFF”.Press the OUT button to enable the power supply output.
3. Turn the power supply output Off and then On using the SO control (refer to sect. 5.7). In this method
the foldback protection remains armed, therefore if the load current is higher than the current limit
setting the Foldback protection will be activated.
4. Turn the power supply Off using the AC On/Off switch, wait until the front panel display turns Off,
then turn the unit back ON again. The power supply output is enabled and the Output Voltage and
Current will return to their last setting. In this method, the Foldback protection remains armed,
therefore if the load current is higher than the current limit setting, the Foldback protection will be
activated again.
TheOutput On/Off enables or disables the power supply output. Use this function to make adjustments
to either the power supply or the load without shutting off the AC power.The Output On/Off can be
activated from the front panel using the OUT button or from the rear panel J1 connector.The OUT
button can be pressed at any timeto enable or disable the power supply output. When the output is
disabled, the output voltage and current fall to zero and the VOLTAGE display shows“OFF”.
Contacts 2,3 and 15 of J1 (Fig.4-2, Item 5) serve as Output Shut-Off (SO) terminals. The SO terminals
accept a 2.5V to 15V signal or Open-Short contact to disable or enable the power supply output. The
SO function will be activated only when a transition from On to Offis detected after applying AC power
to unit. (Thus ,inAuto-Restart mode, the output will be enabled after applying AC power, even if SO is in
Off level.). After On to Off transition is detected, the SO will enable or disable the power supply output
according to the signal level or the short/open applied to J1. This function is useful for connecting power
supplies ina“Daisy-chain” (refer to section 5.16). TheSO control can be used also to reset the OVP
and Fold Protection. Refer to sect. 5.3 and 5.5 for details.
5.5.1 Settingthe Foldback protection
5.5.2 Resetting activated Foldback protection

5.11 SAFE START AND AUTO-RESTART MODES
5.12 OVER TEMPERATURE PROTECTION(OTP)
5.13 LAST SETTING MEMOR
5.14 SERIES OPERATION
When turning on the power supply AC On/Off,it can start to its last setting of Output Voltage and
Current limit with the output enabled (Auto-restart) or start with the output disabled (Safe mode).
Press and hold the OUT button to select between Safe start and Auto-restart modes. The VOLTAGE
display will continuously cycle between "SAF" and "AU7” every 3 seconds. Releasing OUT
pushbutton while one of the modes is displayed, selects that mode. The default setting at shipment
is Safe mode.
In this mode, the power supply restores its last operation setting. Upon start-up, the output is
enabled or disabled according to its last setting.
In this mode, the power supply restores its last operation setting and sets the Output to Offstate. At
start-up, the output is disabled and the output voltage and current are zero. To enable the output and
restore the last output voltage and current limit values, momentarily press OUT button.
The OTP circuit shuts down the power supply before the internal components can exceed their safe
internal operating temperature. When an OTP shutdown occurs, the display shows"O7P" and the
ALARM LED blinks.
Resetting the OTP circuit can be automatic (non-latched) or manual (latched) depending on the
Safe or Automatic restart mode.
In Safe start mode, the power supply stays offafter the over temperature
condition has been removed. The display continue to shows"O7P" and the ALARM LED
continues to blink. To reset the OTP circuit, press OUT button (or send OUT ON command via the
serial port).
InAuto-restart mode , the power supply recovers to it's last setting
automatically when the over temperature condition is removed.
The power supply is equipped with Last Setting Memory,which stores power supply parameters at
eachAC turn-off sequence.
1. OUT On or Off
2. Output voltage setting (PV setting)
3. Output current limit (PC setting)
4. OVP setting
5. UVL setting
6. FOLD setting
7. Start-up mode (Safe or Auto-rest
art)
8. Remote/Local:If the last setting was Local Lockout (latched mode), the supply will return to
Remote mode (non-latched).
9.Address setting
10. Baud rate
11. Locked /Unlocked front panel (LFP/UFP)
(Items8,9,10 are related to Remote digital control operation and explained in chapter 7)
12. Master/Slave setting
Power supplies of the SAME MODEL can be connected in series to obtain increased output voltage.
Split connection of the power supplies gives positive and negative output voltage.
5.11.1Automatic start mode (AU7)
5.11.2Safe start mode (SAF)
1. Safe start mode:
2. Auto-restart mode:
Y
STORED PARAMETERS:
Do not connect power supplies from different
manufacturers in series or in parallel.
CAUTION
When power supplies are connected in series, and
the load or one of the output terminals is grounded,
no point maybeatagreater potential of +/-60VDC
from ground for models up to 60VDCRated Output
and +/-600VDC from ground for models >60VDC
Rated Output. When using RS232/485 or IEEE, refer
to the OUTPUT TERMINALS GROUNDING
warning, section 3.9.11.
5.14.1 Series connection for increased output voltage
In this mode, two units are connected so that their outputs are summed. Set the current limit of
each power supply to the maximum that the load can handle without damage. It is
recommended that diodes be connected in parallel with each unit output to prevent reverse
voltage during start up sequence or in case one of the units shuts down. Each diode should be
rated to at least the power supply rated output voltage and output current. Refer to Fig.5-1 and
5-2 for series operation with local and remote sensing.
+S
+
-
-S
-LS
+LS
POWER
SUPPLY
+S
+
+
-
-
-S
-LS
+LS
POWER
SUPPLY
LOAD
+S
+
-
-S
-LS
+LS
POWER
SUPPLY
+S
+
+
-
-
-S
-LS
+LS
POWER
SUPPLY
LOAD
Fig.5-1: Series connection, local sensing
Fig.5-2: Series connection, remote sensing
Remote programming in series operation for increased output voltage:
1.Programming by external voltage:
2.Using the SO function and PS_OK signal:
The analog programming circuitsof this power supply
are referenced to the negative Sense (-S) potential.
Therefore, the circuits used to control each series
connected unit must be separated and floated from
each other.
The Shut-Off and PS_OK circuits are referenced to the
isolated interface common, IF_COM (J1-2,3). The
IF_COM terminals of different units can be connected
to obtainasingle control circuit for the power supplies
connected in series.
(*)
(*)
(*)
(*)
(*) Diodes are
user supplied.
WARNING

Fig.5-3: Series connection for positive/negative output voltages
3. Programming by external resistor:
1. Programming by external voltage:
Programming by external resistor is possible . Refer to
section 6-5 for details.
The analog programming circuitsof this power supply
are referenced to the negative Sense potential.
Therefore, the circuits used to control each series
connected unit must be separated and floated from
each other.
The communication port is referenced to the IF_COM
which is isolated from the power supply output
potential. Therefore power supplies connected in
series can be chained using the Remote-In and
Remote-Out connectors. Refer to chapter 7 for details.
The Shut-Off and PS_OK circuits are referenced to the
isolated interface common, IF_COM (J1-2,3). The
IF_COM terminals of the units can be connected to
obtain a single control circuit for the power supplies
connected in series.
4. Programming via the Serial
Communication port (RS232/RS485):
4. Programming via the Serial
Communication port (RS232/RS485):
5.14.2 Series connection for positive and negative output voltage
In this mode, two units are configured as a positive and negative output. Set the current limit of each
power supply to the maximum that the load can handle without damage. It is recommended that
diodes be connected in parallel with each unit output to prevent reverse voltage during start-up or in
case one of the units shuts down. Each diode should be rated to at least the power supply rated
output voltage and output current. Refer to Fig.5-3 for this operating mode.
+S
+
-
-S
-LS
+LS
POWER
SUPPLY
+S
+
+
-
-
-S
-LS
+LS
POWER
SUPPLY
COM.
Remote programming in series operation for positive and negative output voltage
2. Using the SO function and PS_OK
signal :
3. Programming by external resistor :
Programming by external resistor is possible. Refer
to section 6.5 for details.
The communication port is referenced to the IF_COM
which is isolated from the power supply output
potential. Therefore power supplies connected in
series can be chained using the Remote-In and
Remote-Out connectors. Refer to chapter 7 for details.
LOAD
(*)
(*)
(*) Diodes are user supplied.
5.15 PARALLEL OPERATION
Up to four units of the same VOLTAGE and CURRENT rating can be connected in parallel to provide
up to four times the output current capability. One of the units operates as a master and the
remaining units are slaves. The slave units are analog programmed by the master unit.
In remote digital operation, only the master unit can be programmed by the computer while the slave
units may be connected to the computer for voltage, current and status readback only.
There are two methods, basic and advanced, to configure multiple supplies for parallel operation.
With both methods, Power Supplies, should be connected in a Daisy-Chain configuration.
Refer to Sec. 5.15.1 , to Sec. 5.15.2 and to Sec.5.16 for detailed explanation.
In this method, setting the units as Master and Slaves is made by the rear panel J1 connections and
the setup switch SW1. Each unit displays its own output current and voltage. To program the load
current, the Master unit should be programmed to the total load current divided by the number of
units in the system. Refer to the following procedure to configure multiple supplies for simple parallel
operation.
5.15.1 Basic parallel operation
5.15.2 Advanced parallel operation
1. Basic configuration
In this method, multiple supplies can be configured to parallel operation as a single power supply.
The total load current and output voltage are displayed by the Master unit and can be readback
from the Master unit. The Slave units display only their operating status (On, Off or Fault
condition).
Refer to the following procedure to configure multiple supplies for Advanced parallel operation.
Repeat steps 1 to 5 in Sec. 5.15.1 (Basic parallel operation).
1. Setting up the Master unit
2. Setting up the slave units
3. Setting Over Voltage protection
4. Setting Foldback protection
5. Connection to the load
Set the master unit output voltage to the desired voltage. Program the current limit to the
desired load current limit divided by the number of parallel units. During operation, the master
unit operates in CV mode, regulating the load voltage at the programmed output voltage.
Connect the sensing circuit to local or remote sensing as shown in Fig.5-4 or Fig.5-5.
-1.The output voltage of the slave units should be programmed 2%~5% higher than the output
voltage of the master unit to prevent interference with the master unit's control.
The current limit of each unit should be programmed to the desired load current limit
divided by the number of parallel units.
-2.Set the rear panel setup switch SW1 position 2 to it's up position.
-3.Set the rear panel setup switch SW1 position 3 in the same position as
SW1 position 4 of the master.
-4.Connect short between J1-8 and J1-12 (refer to Table 4-4.)
-5. Connect J1 terminal 10(IPGM) of the slave unit to J1 terminal 25(P) of the master unit.
During operation the slave units operate as a controlled current source following the master
output current. It is recommended that the power system is designed so that each unit supplies
up to 95% of its current rating because of the imbalance which may be caused by cabling and
connections voltage drop.
The master unit OVP should be programmed to the desired OVP level. The OVP of the slave
units should be programmed to a higher value than the master OVP. When the master unit
shuts down, it programs the slave unit to zero output voltage. If a slave unit shuts down
(when its OVP is set lower than the master output voltage), only that unit would shut down
and the remaining slave units would supply all the load current.
Foldback protection if desired, may only be used with the master unit. When the master unit
shuts down it programs the slave units to zero output voltage.
In parallel operation, power supplies can be connected in local or remote sensing. Refer to
Fig.5-4 and 5-5 for typical connections of parallel power supplies. The figures show
connection of two units, however the same connection method applies up to 4 units.

5.15 PARALLEL OPERATION
Up to four units of the same VOLTAGE and CURRENT rating can be connected in parallel to provide
up to four times the output current capability. One of the units operates as a master and the
remaining units are slaves. The slave units are analog programmed by the master unit.
In remote digital operation, only the master unit can be programmed by the computer while the slave
units may be connected to the computer for voltage, current and status readback only.
There are two methods, basic and advanced, to configure multiple supplies for parallel operation.
With both methods, Power Supplies, should be connected in a Daisy-Chain configuration.
Refer to Sec. 5.15.1 , to Sec. 5.15.2 and to Sec.5.16 for detailed explanation.
In this method, setting the units as Master and Slaves is made by the rear panel J1 connections and
the setup switch SW1. Each unit displays its own output current and voltage. To program the load
current, the Master unit should be programmed to the total load current divided by the number of
units in the system. Refer to the following procedure to configure multiple supplies for simple parallel
operation.
5.15.1 Basic parallel operation
5.15.2 Advanced parallel operation
1. Basic configuration
In this method, multiple supplies can be configured to parallel operation as a single power supply.
The total load current and output voltage are displayed by the Master unit and can be readback
from the Master unit. The Slave units display only their operating status (On, Off or Fault
condition).
Refer to the following procedure to configure multiple supplies for Advanced parallel operation.
Repeat steps 1 to 5 in Sec. 5.15.1 (Basic parallel operation).
1. Setting up the Master unit
2. Setting up the slave units
3. Setting Over Voltage protection
4. Setting Foldback protection
5. Connection to the load
Set the master unit output voltage to the desired voltage. Program the current limit to the
desired load current limit divided by the number of parallel units. During operation, the master
unit operates in CV mode, regulating the load voltage at the programmed output voltage.
Connect the sensing circuit to local or remote sensing as shown in Fig.5-4 or Fig.5-5.
-1.The output voltage of the slave units should be programmed 2%~5% higher than the output
voltage of the master unit to prevent interference with the master unit's control.
The current limit of each unit should be programmed to the desired load current limit
divided by the number of parallel units.
-2.Set the rear panel setup switch SW1 position 2 to it's up position.
-3.Set the rear panel setup switch SW1 position 3 in the same position as
SW1 position 4 of the master.
-4.Connect short between J1-8 and J1-12 (refer to Table 4-4.)
-5. Connect J1 terminal 10(IPGM) of the slave unit to J1 terminal 25(P) of the master unit.
During operation the slave units operate as a controlled current source following the master
output current. It is recommended that the power system is designed so that each unit supplies
up to 95% of its current rating because of the imbalance which may be caused by cabling and
connections voltage drop.
The master unit OVP should be programmed to the desired OVP level. The OVP of the slave
units should be programmed to a higher value than the master OVP. When the master unit
shuts down, it programs the slave unit to zero output voltage. If a slave unit shuts down
(when its OVP is set lower than the master output voltage), only that unit would shut down
and the remaining slave units would supply all the load current.
Foldback protection if desired, may only be used with the master unit. When the master unit
shuts down it programs the slave units to zero output voltage.
In parallel operation, power supplies can be connected in local or remote sensing. Refer to
Fig.5-4 and 5-5 for typical connections of parallel power supplies. The figures show
connection of two units, however the same connection method applies up to 4 units.
41

Fig.5-5: Parallel operation with Remote sensing
With local sensing it is important to minimize the wire length and resistance. Also the
positive and negative wire resistance should be close as possible to each other to achieve
current balance between power supplies.
NOTE
5.16 DAISY-CHAIN CONNECTION
It is possible to configure amultiple power supply system to shut down all the unitswhen a fault
condition occurs in one of the units. When the fault is removed, the system recovers according to its
setting to Safe start mode or Automatic restart.
Setup switch SW1 position 5 should be set to itsDown position to enable the Daisy-chain operation.
Other SW1 positions can be set according to the application requirements.
Ifafault occurs in one of the unitsits PS_OK signal will be set to low level and the display will indicate
the fault. The other unitswill shut off and their display will indicate "SO”. When the fault condition is
removed, the unitswill recover to their last setting according to their Safe start orAuto-restart setting.
Fig.5-6 shows connection of three units, however the same connection method applies to systems
with a larger number of units.
Fig.5-6: Daisy-chain connection
POWER SUPPLY
#
1
J1-2,3
J1-16
J1-16
J1-16
J1-15
PS_OK
POWER SUPPLY
#
2
J1-2,3
J1-15
PS_OK
SO
POWER SUPPLY
#3
J1-2,3
J1-15
PS_OK
SO
SO
IF_COM
IF_COM
IF_COM
5.17 FRONT PANELLOCKING
The front panel controls can be locked to protect from accidental power supply parameter change.
Press and hold PREV button to toggle between “Locked front panel” and “Unlocked front panel”.
The display will cycle between “LFP” and “UFP”. Releasing the PREV button while one of the
modes is displayed, selects that mode.
In this mode, the front panel controls are enable to program and monitor the power supply
parameters.
In this mode the following front panel controls are disabled:
- VOLTAGE and CURRENT encoders.
- FOLD button.
- OUT button.
The power supply will not respond to attemptsto use these controls. The VOLT display will show
“LFP” to indicate that the front panel is locked.
OVP/UVL button is active to preview the OVP and UVL setting.
Use PREV button to preview the output voltage and current setting or to unlock the front panel.
5.17.1 Unlocked front panel
5.17.2 Locked front panel
+V
-V
+
V
-V
+S-S
+S-S
MASTER
POWER SUPPLY
SLAVE#1
POWER SUPPLY
+S
-S
+S
+S
-S
-S
+
-
LOAD
J1-25
J1-10
P
IPGM
As shortas possible
Twisted
pair
Twisted
pair
Twisted
pair
J1-8
J1-12
To J1-10
SLAVE#2
POWER SUPPLY
CAUTION
Make sure that the
connection between -Vo
terminals is reliable to
avoid disconnection
during operation.
Disconnection may cause
damage to the power
supply.
2. Setting the unitsasMaster or Slave
3. Master and Slave units default operation
4. CURRENT display accuracy
5. To release units from Slave mode
a) Depress and hold the FINE button for3seconds. The Master/Slave configuration will be
displayed on the Current Display.Rotate the CURRENT encoder to obtain the desired mode.
Refer to Table 5-4 for the CURRENT display and modes of operation.
b) When the desired configuration is obtained, depress and release the FINE button or wait
approx. 5 seconds.
a) When a unit is programmedto Slave mode it enters the Remote mode with Local Lockout. In
this mode, the front panel controls are disabled to prevent accidental setting change (refer to Sec.
7.2.7 for details).
b) The Slave unitsparameters will automatically set the following:
*Output voltage to approximate. 102% of rated output voltage.
*ProgrammedCurrent to zero.
*UVL to zero volts
*OVP to itsmaximum value
c) The Master and Slave modes are stored in the power supply EEPROM when the AC power is
Turned off. The system will return to the Master/Slave mode upon re-application of AC power.
In the advanced parallel mode, the total current is programmed and reported by the Master.In
this method, the CURRENT display accuracy is 2%+/- 1 count. In cases that higher accuracy is
required, it is recommended to use the basic parallel operation mode.
Slave units can be released using the following procedure:
a) Depress FINE button for3seconds. The Master/Slave configuration will be displayed on the
CURRENT display.
b) Select H1 mode using the CURRENT encoder.
c) Depress FINE button again or wait 5 seconds.
d) Turn the AC power Offto store the new setting.
e) After exiting from Slave operation the unit’s parameters will be set to:
CAUTION
Make sure that the connection between -Vo terminals is reliable to avoid disconnection during
operation. Disconnection may cause damage to the power supply.
CURRENT Display
H1
H2
H3
H4
S
Operating Mode
Singlesupply(default)
Mastersupplywith1Slave supply
Mastersupplywith2Slave supplies
Mastersupplywith3Slave supplies
Slave supply
Table 5-4: Setting mode of operation
Fig.5-4: Parallel connection with local sensing
+V
-V
+V
-V
+S
+LS
-S -LS
+S
+LS
-S -LS
MASTER
POWER SUPPLY
SLAVE#1
POWER SUPPLY
+
-
LOAD
J1-25
J1-10
P
IPGM
As shortas possible
Twisted
pair
To J1-10
SLAVE#2
POWER SUPPLY
J1-8
J1-12
*AST On
*OUT On
*Foldback protection Off
*Programmed Voltage to zero *AST OFF
*Programmed Current to zero *OUT OFF
*UVL to zero volts *Foldback protection OFF
*OVP to its maximum value *Locked Front Panel
42

CHAPTER 6 REMOTE ANALOG PROGRAMMING
6.1 INTRODUCTION
The rear panel connector J1 allows the user to program the power supply output voltage and current
limit with an analog device. J1 also provides monitoring signals for output voltage and output current.
The programming range and monitoring signals range can be selected between 0-5V or 0-10V
using the setup switch SW1. When the power supply is in Remote Analog programming, the serial
communication port is active and can be used to read the power supply parameters.
CAUTION
COM (J1-12), VPGM_RTN (J1-22) and IPGM_ RTN (J1-23) terminals of J1
connect internally to the -Sense potential (-S). Do not connect these
terminals to any potential other than -Sense (-S), as it may damage the
power supply.
6.2 LOCAL /REMOTEANALOG CONTROL
Contact 8ofJ1 (Fig. 4-2, item 5) accepts TTL signal or Open-Short contact (referenced to J1-12) to
select between Local or Remote Analog programming of the output voltage and current limit.
In Local mode, the output voltage and current limit can be programmed via the front panel VOLTAGE
and CURRENT encoders or via the RS232/485 port. In Remote Analog mode, the output voltage
and current limit can be programmedby analog voltage or by programming resistors via J1 contacts
9 and 10 (refer to sec. 6.4 and 6.5). Refer to Table 6-1 for Local/Remote Analog control (J1-8)
function and Setup switch SW1-1, 2 setting.
6.3 LOCAL/REMOTEANALOGINDICATION
Contact 21 of J1 (Fig. 4-2, item 5) is an open collector output that indicates if the power supply is in
Local mode or in Remote Analog mode. To use this output, connect a pull-up resistor toavoltage
source of 30Vdc maximum.Choose the pull-up resistor so that the sink current will be less than 5mA
when the output is in low state. Refer to Table 6-2 for J1-21 function.
Table 6-1: Local/Remote Analog control function
Table 6-2: Local/Remote Analog indication
SW1-1,2 setting
Down (default)
Up
J1-8 function
Output voltage/
Current setting
No effect
"0" or Short
"1" or Open
Local
Remote Analog
Local
TTL "0" or short
TTL "1" or open
SW1-1
SW1-2
J1-8
J1-21 signal
Down
Down
Up
Up
Down or Up
Down
Up
Down
Up
Down or Up
Open
0~0.6V
0~0.6V
0~0.6V
Open
CAUTION
To maintain the isolation of power supply and prevent ground loops, use an
isolated programming source when operating the power supply via remote
analog programming at J1 connector.
6.4 REMOTE VOLTAGEPROGRAMMING OF OUTPUT VOLTAGE AND CURRENT LIMIT
SW1-3 setting
UP
DOWN
Output Voltage programming
VPGM (J1-9)
0-10V
0-5V
Current limit programming
IPGM (J1-10)
0-10V
0-5V
Table 6-3: SW1-3 setting and programming range
1
14
13
25
10
12
8
9
23
22
+
-
+
-
CURRENT LIMIT
PROGRAMMING
OUTPUT VOLTAGE
PROGRAMMING
J1 connector, rear panel view
Fig.6-1: Remote voltage programming connection
Perform the following procedure to set the power supply to Remote Voltage programming :
1. Turn the power supply AC On/Off switch to Off.
2. Set setup switch SW1-1 to itsUP position for output voltage external programming and
SW1-2 to itsUP position for Output Current limit external programming.
3. Set SW1 position3to select programming voltage range according to Table 6-3.
4. Ensure that SW1 positions7and8are at their Down (default) position.
5. Connect a short between J1-8 and J1-12 (refer to Table 4-4).
6. Connect the programming source to the mating plug of J1 as shownin Fig.6-1. Observe
correct polarity for the voltage source.
7. Set the programming sources to the desired levels and turn the power supply ON. Adjust the
programming sources to change the power supply output.
1. SW1 positions 4,5,6 and9are not required for remote programming. Their setting can be
determined according the application.
2. The control circuits allow the user to set the output voltage and current limit up to 5% over
the model-rated maximum value. The power supply will operate within the extended range,
however it is not recommended to operate the power supply over its voltage and current
rating and performance is not guaranteed.
NOTES:

6.5 RESISTIVE PROGRAMMING OF OUTPUT VOLTAGE AND CURRENT LIMIT
For resistive programming, internal current sources, for output voltage and/or output current control,
supply 1mA current through external programming resistors connected between J1-9&22 and J1-10
& 23. The voltage across the programming resistors is used asaprogramming voltage for the power
supply.Resistance of 0~5Kohm or 0~10Kohm can be selected to program the output voltage and
current limit from zero to full scale.
A variable resistor can control the output over its entire range, oracombination of variable resistor
and series/parallel resistors can control the output over restricted portion of its range.
Perform the following procedure to set the power supply to Resistive programming:
1. Turn the AC On/Off switch to Off.
2. Set setup switch SW1-1 to itsUP position for output voltage external programming and
SW1-2 to itsUP position for Output Current limit external programming.
3. Set SW1 position 3to select programming resistor range according to Table 6-4.
4. Set SW1-7 to itsUP position for output voltage resistive programming and
SW1-8 to itsUP position for Output Current limit resistive programming.
5. Connect a short between J1-8 and J1-12 (refer to Table 4-4).
6. Connect the programming resistors to the mating plug of J1 as shownin Fig.6-2.
7. Set the programming resistors to the desired resistance and turn the power supply ON.
Adjust the resistors to change the power supply output.
1. SW1 positions 4, 5, 6 and9are not required for remote programming. Their setting can be
determined according to the application requirements.
2. The control circuits allow the user to set the output voltage and current limit up to 5% over
the model-rated maximum value. The power supply will operate within the extended range,
however it is not recommended to operate the power supply over its voltage and current
rating and performance is not guaranteed.
3. To maintain the temperature stability specification of the power supply, the resistors used for
programming should be stable and low noise resistors, with temperature coefficient of less
than 50ppm.
4. When resistive programming is used, front panel and computer control (via serial communication
port)
of output voltage and current are disabled.
NOTES:
SW1-3 setting
UP
DOWN
Output Voltage programming
VPGM (J1-9)
0-10Kohm
0-5Kohm
Current limit programming
IPGM (J1-10)
0-10Kohm
0-5Kohm
Table 6-4: SW1-3 setting and programming range
1
14
13
25
10 9
23
22
CURRENT LIMIT
PROGRAMMING
OUTPUT VOLTAGE
PROGRAMMING
J1 connector, rear panel view
Fig.6-2: Remote resistive programming
PROGRAMMING
RESISTOR
PROGRAMMING
RESISTOR
OPTIONAL SETS
LOWER LIMIT
OPTIONAL SETS
LOWER LIMIT
OPTIONAL SETS
UPPER LIMIT
OPTIONAL SETS
UPPER LIMIT
12
8
6.6 REMOTE MONITORINGOF OUTPUTVOLTAGE AND CURRENT
The J1 connector, located on the rear panel provides analog signals for monitoring the output
voltage and output current. Selection of the voltage range between 0-5V or 0-10V is made by
setup switch SW1-4. The monitoring signals represent 0to 100% of the power supply output
voltage and output current.The monitor outputs have 500 ohm series output resistance. Ensure
that the sensing circuit has an input resistance of greater than 500 Kohm or accuracy will be
reduced.
Refer to Table 6-5 for required J1 connection, SW1-4 setting and monitoring voltage range.
Signal
name
VMON
IMON
VMON
IMON
Signal function
Vout monitor
Iout monitor
Vout monitor
Iout monitor
Signal (+)
J1-11
J1-24
J1-11
J1-24
J1-12
J1-12
0-5V
0-10V
Down
Up
Range
SW1-4
Return (-)
J1 connection
Table 6-5 Monitoring signals setting
FCC requirements for radiated emissions, use
shielded cable for the analog control signals. In case of
using unshielded cable, attach an EMI ferrite
suppressor to the cable, as close as possible to the
power supply.
1.Radiated emissions, FCC requirements:
Notes:
2. Front panel encoders operation:
3. Front panel PREV button:
4. Communication:
In Remote analog mode the output voltage and
current can’t be set by the VOLTAGE and CURRENT
encoders.
Use PREV button to display the output voltage and
current setting defined by the encoders or
communication.
In Remote analog mode, power supply parameters
can be programmed and readback via the
communication port except output voltage and current
setting.

CHAPTER 7 RS232&RS485 REMOTE CONTROL
7.1 INTRODUCTION
7.2 CONFIGURATION
This chapter describes the operation of the Genesys 750W and 1500W power supplies via the
serial communication port. Details of the initial set-up, operation via RS232 or RS485, the command
set and the communication protocol are described in this chapter.
The power supply is shipped with the following setting:
TM
7.2.1 Default setting
6
9600
RS232
0
Maximum
H1(Master)
-Output:
-Start up mode:
-OVP:
-UVL:
-Foldback:
-Front panel:
Off
Safe start
Maximum
0
Off
Unlocked (UFP)
7.2.2 Address setting
7.2.3 RS232 or RS485 selection
7.2.4 Baud rate setting
7.2.5 Setting the unit into Remote or Local mode
The power supply address can be set to any address between0and 30. Follow the instructions
described below to set the address.
1. If the unit is in Remote mode (front panel REM/LOC LED illuminates), press REM/LOC
button to put the unit into Local mode.
2. Press and hold for approximately 3sec. the REM/LOC button. The VOLTAGE display will
indicate the communication port address.
3. Using the VOLTAGE adjust encoder, select the address.
To preview the address at any time, press and hold the REM/LOC button for approx. 3sec. The
VOLTAGE display will indicate the power supply address.
To select between RS232 or RS485 set the rear panel setup switch SW1-6 position to:
-Down for RS232
-Up for RS485
Five optional rates are possible: 1200, 2400, 4800, 9600 and 19200. To select the desired rate,
the following steps should be taken:
1. If the unit is in Remote mode (front panel REM/LOC LED illuminates), press REM/LOC
button to put the unit into Local mode.
2. Press and hold for approx. 3sec. the REM/LOC button. The CURRENT display will show
the communication port Baud Rate.
3. Using the CURRENT adjust encoder, select the desired Baud Rate.
1. The unit will be put into Remote mode only via serial communication command.
Commands that will put the unit into Remote mode are:
RST PV n
OUT nPCn
RMT n
(for n values see Tables 7-3, 7-4 and 7-5)
-Address:
-Baud-rate:
-RS232/485:
-Vout setting:
-Iout setting:
-Master/Slave
2. There are two Remote modes:
1. Remote:
2. Local Lockout:
In this mode, return to local can be made by the front panel REM/LOC or via
serial port command RMT 0. Set the unit into Remote mode via serial port
RMT 1 command.
In this mode the unit can be returned to Remote mode via the serial port
RMT 1 command or by turning off the AC power until the display turns off
and then turn it to on again. In Local Lockout mode, the front panel
REM/LOC button is not active. Set the unit into Local Lockout mode via
serial port RMT 2 command.
7.2.6 RS232/485 port in Local mode
7.2.7 Front panel in Remote mode
When the power supply is in local mode, it can receive queries or commands. Ifa query is received,
the power supply will reply and remain in Local mode. Ifacommand that affects the output is
received, the power supply will perform the command and change to Remote mode.
Serial commands may be sent to set the status registers and read them while the unit is in Local
mode. If the Enable registers are set (refer to section 7.8) the power supply will transmit SRQ’s while
in Local.
Front panel control in Remote mode is disabled except for:
1. PREV: use to preview the Voltage and Current limit setting.
2. OVP/UVL: use to preview the OVP/UVL setting.
3. LOC/REM: use to set the unit into Local mode.
In Local Lockout mode, only PREV and OVP/UVL are active.
The RS232/485 interface is accessible through the rear panel RS232/485 IN and RS485 OUT
connectors. The connectors are 8 contact RJ-45. The IN and OUT connectors are used to connect
power supplies in a RS232 or RS485 chain to a controller. Refer to Fig.7-1 for IN/OUT connectors
7.3 REAR PANELRS232/485 CONNECTOR
Tx and Rx are used for RS232 communication. Txd +/- and Rxd +/- are used for RS485
communication. Refer to RS232 and RS485 cables description for connection details.
NOTE
NC
NC
RX
NC
NC
TXD
RXD
TXD
RXD
RXD
TXD
RXD
TXD
SG
SG
-
-
-
-
+
+
+
+
TX
OUT
IN
Fig.7-1: J3 rear panel IN/OUT connectors pinout
87654321
87654321
Shield
(connector enclosure)

7.5.7 Error message
7.5.8 Backspace
If an error is detected inacommand or query, the power supply will respond with an error
message. Refer to section 7.6 for details.
The backspace character (ASCII 8) clears the last character sent to the power supply.
The power supply will return error messages for illegal commands and illegal programming
parameters. Refer to Table 7-1 for programming error messages and Table 7-2 for commands
error messages.
Table 7-1: Programming error messages
7.6 ERRORMESSAGES
Table 7-2: Commands error messages
7.7 COMMAND SET DESCRIPTION
7.7.1 General guides
7.7.2 Command set categories
1. Any command or argument maybein capital letters or small letters.
2. In commands with an argument, aspace must be between the command and the argument.
3. For any command that setsanumeric value, the value maybeupto12 characters long.
4. Carriage Return: If the CR character (ASCII 13) is received by itself, the power supply will
respond with "OK" and CR.
The Genesys 750W and 1500W series command set is divided into four categories as follows:
1. Initialization control
2. ID control
3. Output control
4. Status control
TM
E01
E02
E04
E06
E07
Description
Returned when program voltage (PV) is programmed above acceptable range.
Example: PV value is above '105% of supply rating'or 'PV above 95% of OVP setting'.
Returned when programming output voltage below UVL setting.
Returned when OVP is programmed below acceptable range.
Example:OVP value is less than '5% of supply voltage rating' plus 'voltage setting'.
Returned when UVL value is programmed above the programmed output voltage.
Returned when programming the Output to ON during a fault shut down.
Error
Code
C01
C02
C03
C04
C05
Description
Illegal command or query
Missing parameter
Illegal parameter
Checksum error
Setting out of range
Error
Code
7.7.3 Initialization control commands
ADR is followed by address which can be0to30 and is used to access the
power supply .
Clear status. Sets FEVE and SEVE registers to zero (refer to section 7-8).
Reset command. Brings the power supply toasafe and knownstate:
Output voltage: zero, Remote: non-latched remote,
Output current: zero, Auto-start: Off,
Output: Off, OVP: maximum,
FOLD:Off,UVL: zero
The conditional registers (FLT and STAT) are updated, the other registers are
not changed.
Command
Sets the power supply to local or remote mode:
1. RMT0or RMT LOC, sets the power supply into Local mode.
2. RMT1or RMT REM, sets the unit into remote mode.
3. RMT2or RMT LLO, sets the unit into Local Lockout mode (latched remote mode).
#
Description
1
ADR n
2
CLS
3
RST
4
RMT
Returns the Remote mode setting:
1. "LOC"- The unit is in Local mode.
2. "REM"- The unit is in Remote mode.
3. "LLO"- The unit is in Local Lockout (latched remote) mode.
Returns MD MODE OPTION Status.1indicates installed and0indicates not
installed.
Repeat last command. If \<CR> is received, the power supply will repeat the
last command.
5
6
7
RMT?
MDAV?
\
7.7.5 Output control commands
7.7.4 ID control commands
Command
#
Description
Returns the power supply model identification as an string
Returns the software version as an ASCII string.
Returns the unit serial number.Upto12 characters.
Returns date of last test. Date format: yyyy/mm/dd
ASCII
: LAMBDA, GENX-Y
1
2
3
4
IDN?
REV?
SN?
DATE?
Command
#
Description
Sets the output voltage value in Volts. The range of voltage value is described in
Table7-3. The maximum number of characters is 12. See the following examples
for PV n format: PV 12, PV 012, PV 12.0, PV 012.00, etc...
Reads the output voltage setting. Returns the string "n" where "n" is the exact
string sent in the PVncommand. When in Local mode, returns the PREVIEW
(front panel) settings ina5digits string.
Reads the actual output voltage. Return5digits string.
Example: 60V supply sends 01.150, 15.012, 50.000, etc...
1
PV n
2
PV?
3
MV?
Reads the output current setting. Returns the string "n" where "n" is the exact
string sent in the PCncommand. When in Local mode, returns the
PREVIEW (front panel) settings ina5digits string.
4
PC n
(See Note 1)
5
PC?
Sets the output current value in Amperes. The range of current values is
described in Table 7-4 and 7-5. The maximum number of characters is 12. See
the following examples for PCnformat: PC 10, PC 10.0, PC 010.00, etc...

7.7.3 Initialization control commands
ADR is followed by address which can be0to30 and is used to access the
power supply .
Clear status. Sets FEVE and SEVE registers to zero (refer to section 7-8).
Reset command. Brings the power supply toasafe and knownstate:
Output voltage: zero, Remote: non-latched remote,
Output current: zero, Auto-start: Off,
Output: Off, OVP: maximum,
FOLD:Off,UVL: zero
The conditional registers (FLT and STAT) are updated, the other registers are
not changed.
Command
Sets the power supply to local or remote mode:
1. RMT0or RMT LOC, sets the power supply into Local mode.
2. RMT1or RMT REM, sets the unit into remote mode.
3. RMT2or RMT LLO, sets the unit into Local Lockout mode (latched remote mode).
#
Description
1
ADR n
2
CLS
3
RST
4
RMT
Returns the Remote mode setting:
1. "LOC"- The unit is in Local mode.
2. "REM"- The unit is in Remote mode.
3. "LLO"- The unit is in Local Lockout (latched remote) mode.
Returns MD MODE OPTION Status.1indicates installed and0indicates not
installed.
Repeat last command. If \<CR> is received, the power supply will repeat the
last command.
5
6
7
RMT?
MDAV?
\
7.7.5 Output control commands
7.7.4 ID control commands
Command
#
Description
Returns the power supply model identification as an string
Returns the software version as an ASCII string.
Returns the unit serial number.Upto12 characters.
Returns date of last test. Date format: yyyy/mm/dd
ASCII
: LAMBDA, GENX-Y
1
2
3
4
IDN?
REV?
SN?
DATE?
Command
#
Description
Sets the output voltage value in Volts. The range of voltage value is described in
Table7-3. The maximum number of characters is 12. See the following examples
for PV n format: PV 12, PV 012, PV 12.0, PV 012.00, etc...
Reads the output voltage setting. Returns the string "n" where "n" is the exact
string sent in the PVncommand. When in Local mode, returns the PREVIEW
(front panel) settings ina5digits string.
Reads the actual output voltage. Return5digits string.
Example: 60V supply sends 01.150, 15.012, 50.000, etc...
1
PV n
2
PV?
3
MV?
Reads the output current setting. Returns the string "n" where "n" is the exact
string sent in the PCncommand. When in Local mode, returns the
PREVIEW (front panel) settings ina5digits string.
4
PC n
(See Note 1)
5
PC?
Sets the output current value in Amperes. The range of current values is
described in Table 7-4 and 7-5. The maximum number of characters is 12. See
the following examples for PCnformat: PC 10, PC 10.0, PC 010.00, etc...
53

7.7.5 Output control commands-cont
#
Command
Description
Sets the Foldback protection to ON or OFF.
FLD1(or FOLD ON) - Arms the Foldback protection.
FLD0(or FOLD OFF)- Cancels the Foldback protection.
When the Foldback protection has been activated, OUT 1 command will release the
protection and re-arm it, while FLD0will cancel the protection.
Returns the Foldback protection status string:
“ON”- Foldback is armed, “OFF”- Foldback is canceled.
Add (nnx0.1) seconds to the Fold Back Delay. This delay is in addition to the standard
delay. The range of nn is0to 255. The value is stored in eprom at AC power down and
recovered at AC power up.
Supply returns the value of the added Fold Back Delay.
Reset the added Fold Back Delay to zero.
Returns the output On/Offstatus string.
ON- output on. OFF- output off.
Display Voltage and Current data. Data will be returned asastring of ASCII characters. A
comma will separate the different fields. The fields, in order, are: Measured Voltage,
Programmed Voltage, Measured Current, Programmed Current, Over Voltage Set point
and Under Voltage Set Point.
Example: 5.9999, 6.0000, 010.02, 010.00, 7.500, 0.000
10
FLD n
11
12
13
14
FLD?
FBD nn
FBD?
FBDRST
9
8
OUT?
Sets the OVP level. The OVP setting range is given in Table 7-6. The number of characters
after OVP is up to 12.
The minimum setting level is approx. 105% of the set output voltage, or the value in Table
7-6, whichever is higher. The maximum setting level is shown in Table 5-1. Attempting to
program the OVP below this level will result in execution error response (”E04”). The OVP
setting stays unchanged.
15
OVP n
Returns the power supply operation mode. When the power supply is On (OUT 1) it will
return “CV” or “CC”. When the power supply is OFF (OUT 0) it will return “OFF”.
Returns the Master/Slave setting. Master: n=1,2,3,or4 Slave: n=0
Saves present settings. The settings are the same as power-down last settings.
These settings are erased when the supply power is switched off and the new “last settings”
are saved.
Sets Under Voltage Limit. Value of “n” may be equal to PV setting, but returns “E06” if
higher. Refer to Table 7-7 for UVL programming range.
Sets OVP level to the maximum level. Refer to Table 7-6.
Returns the setting “n” where “n” is the exact string in the user’s “UVL n”. When in Local
mode, returns the last setting from the front panel ina4digit string.
Returns the setting “n” where “n” is the exact string in the user’s “OVP n”. When in Local
mode, returns the last setting from the front panel ina4digit string.
Returns the string auto-restart mode status.
Recalls last settings. Settings are fromthe last power-down or from thelast“SAV”
command.
16
OVP?
17
OVM
18
UVL n
19
UVL?
21
AST?
22
SAV
23
RCL
24
25
MODE?
MS?
Sets the auto-restart mode to ON or OFF.
AST 1 (or AST ON)- Auto restart on.
AST 0 (or AST OFF)- Auto restart off.
20
AST n
Reads the actual output current. Returns5digits string.
Example: 200A supply sends 000.50, 110.12, 200.00, etc...
Turns the output to ON or OFF. Recover from Safe-Start, OVP or FLD fault.
OUT 1 (or OUT ON)-Turn On.
6
MC?
(See Note 2)
7
OUT n
DVC?
Table 7-3: Voltage programming range
Model
Rated Output Voltage(V)
Minimum
(V)
Maximum
(V)
8
10
15
20
30
40
50
60
80
100
150
300
600
0.000
00.000
00.000
00.000
00.000
00.000
00.000
00.000
00.00
000.00
000.00
000.00
000.00
8.000
10.000
15.000
20.000
30.000
40.000
50.000
60.000
80.00
100.00
150.00
300.00
600.00
NOTE:
The power supply can accept values higher by 5% than
the table values, however it is not recommended to
program the power supply over the rated values.
7.7.6 Global output commands
1. General
All supplies, even if not the currently addressed supply, receivingaglobal command will execute
the command. No response to the PC issuing the command will be returned to the PC. The PC
issuing the command will be responsible to delay and any other communications until the
command is execute. 200 Ms minimum is the suggested delay.
If the command contains an error, out of range values for example, no error report will be sent to
the issuing PC.
Reset. Brings the Power Supply toasafe and known state:
Output voltage: 0V, output current: 0A, OUT:Off, Remote: RMT 1’
AST:Off OVP:Max, UVL:0.
The conditional register (FLT and STAT) are updated. Other registers are not changed.
Non-Latching faults (FB, OVP, SO) are cleared, OUT fault stays.
Sets the output voltage value in volts. The range of voltage values is shown in Table 7-3.
‘n’ may be up to 12 char plus dec. pt
Program the output current value in amperes. The range of current values is shown in
Table 7-4. ‘n’ may be up to 12 char plus dec. pt
Turns the output to ON or OFF:
“OUT 1/ON”=turn on
“OUT 0/OFF”= turn off, clears CV and CC bitsin the Status Condition (STAT)
OUT ON will respond with “E07’if the output cannot be turned on because ofalatching
fault (OTP< AC, ENA, SO) shutdown.
1.
GRST
2.
3.
4.
GPV n
GPC n
GOUT
Save present settings. Same settings as power-down last settings listed in Error!
Reference source not found. Except the address and Baud rate are not saved
Saves to the RAM. These settings are erased when
the supply power is switched off and
the new ‘last settings’ are saved.
5.
GSAV
Recall last settings. Settings are from last power-down or from last ‘SAV’ or ‘GSAV’
command. Address and Baud rate are not recalled so communication is not interruped.
6.
GRCL
NOTES:
1. In Advanced parallel mode (refer to Sec. 5.15.2), “n” is the total system current.
2. In Advanced parallel mode, “MC?” returns the Master unit current multiplied by the number of
slave units+1.

Minimum
(A)
Model
Maximum
(A)
GENH6-100
GENH8-90
GENH12.5-60
GENH20-38
GENH30-25
GENH40-19
GENH60-12.5
GENH80-9.5
GENH100-7.5
GENH150-5
GENH300-2.5
GENH600-1.3
000.00
00.00
00.000
00.000
00.000
00.000
00.000
0.000
0.000
0.000
0.000
0.000
100.00
90.00
60.000
38.000
25.000
19.000
12.500
9.500
7.500
5.000
2.500
1.300
NOTE:
The power supply can accept values higher by 5% than the table values, however it
is not recommended to program the power supply over the rated values.
GENH models
Current programming range
7.7.7 Status control commands
Refer to section 7-8 for definition of the registers.
Command
#
Description
1
STT?
Reads the complete power supply status.
Returns ASCII characters representing the following data, separated by commas:
Table 7-6: OVP programming range
Table 7-7: UVL programming range
Model
RatedOutput Voltage(V)
Minimum
(V)
Maximum
(V)
6
8
12.5
20
30
40
50
60
80
100
150
300
600
0.5
0.5
1.0
1.0
2.0
2.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
7.50
10.0
15.0
24.0
36.0
44.0
57.0
66.0
88.0
Model
Rated Output Voltage(V)
Minimum
(V)
Maximum
(V)
6
8
12.5
20
30
40
50
60
80
100
150
300
600
0
0
0
0
0
0
0
0
0
0
0
0
0
5.70
7.60
11.9
19.0
28.5
38.0
47.5
57.0
76.0
95.0
142
285
570
MV<actual (measured) voltage>
PV<programmed (set) voltage>
MC<actual (measured) current>
PC<programmed (set) current>
SR<status register, 2-digit hex>
FR<fault register, 2-digit hex>
Example response: MV(45.201),PV(45),MC(4.3257),PC(10),SR(30),FR(00)
Reads Fault Conditional Register.Return 2-digit hex.
Set Fault Enable Register using 2-digit hex.
Reads Fault Enable Register.Returns 2-digit hex.
Reads Fault Event Register. Returns 2-digit hex. Clears bitsof Fault Event Register.
Reads Status Conditional Register.Returns 2-digit hex.
SetsStatus Enable Register using 2-digit hex.
Reads Status Enable Register.Returns 2-digit hex.
Reads Status Event register. Returns 2-digit hex. Clears bitsofStatus Event register.
2
3
4
5
6
7
8
9
FLT?
FENA
FENA?
FEVE?
STAT?
SENA
SENA?
SEVE?
Table 7-4:
Table 7-5: not used)
110
165
330
660
OR
OR
OR
SRQ
Messages
Address
Changed
Response
messages
Command Error (”Cnn”)
Execution Error (”Enn”)
Query Response (”message”)
Command Response (”OK”)
CV
CC
NFLT
FLT
AST
FDE
0
LCL
CV
CC
NFLT
FLT
0
0
0
LCL
0
0
0
OR
Status Registers
Condition
Enable
Event
Constant Voltage
Constant Current
No Fault
Fault
Auto Start
Fold Enabled
Spare
Local Mode
0
1
2
3
4
5
6
7
“STAT?”
“SENA xx”
“SENA?”
“SEVE?”
0
AC
OTP
FLD
OVP
SO
OFF
ENA
Fault Registers
Condition
Enable
Spare
AC Fail
Over Temperature
Foldback (tripped)
Over Volt Prot
Shut Off (rear panel)
Output Off (front panel)
Enable Open
0
1
2
3
4
5
6
7
“FLT?”
“FENA xx”
“FENA?”
0
AC
OTP
FLD
OVP
SO
OFF
ENA
OR
Event
“FEVE?”
MSB
MSB
LSB
Serial
TXD
LSB
One response for every command
or query received.
One SRQ when SEVE goes
from all zeroes to any bit set.
Setting more SEVE bits does
not cause more SRQs.
Positive Logic:
0=No Event
1=Event Occured
7.8 STATUS,ERROR AND SRQREGISTERS
This section describes the various status error and SRQ registers structure. The registers can be
read or set via the RS232/485 commands. When using the IEEE option, refer to the user manual
for Genesys Power Supply IEEE Programming interface.
Refer to Fig.7-7 for the Status and Error Registers Diagram.
7.8.1 General
TM
Fig.7-7: Status and Error Registers Diagram
7.8.2 Conditional registers
The fault Condition Register and the St atus Condition Register are read only registers that the user
may read to see the condition of the supply. Refer to table 7-8 for description of the Fault Condition
Register bits and Table 7-9 for the Status Condition register bits.
SRQ=“!nn”,
nn=address

7.8.2 Conditional registers
7.8.3 Service Request: Enable and Event Registers
The conditional Registers arecontinuously monitored. Whenachange is detectedina
registerbit which is enabled, the power supplywill generate an SRQ message.
The SRQ message is: "!nn" terminated by CR, wherethe nn is thepower supply address.
The SRQ will be generatedeither in Local or Remote mode.
Output is ON and the supplyis not in
CV.
Output is On and the
supplyinCV.
Output is ON and the supplyis not in
CC.
Output is ON and the
supplyin CC.
The power supply is
operating normally or
fault reporting is not
enabled.
See “OUT n”
command in Section
7.7.5.
One or morefaults are active and
faultreportingis enabled (using
“FENA xx”).
1
2
Constant
Voltage
Constant
Current
No Fault
Table7-8: Fault Condition Register
BIT
Fault name
Fault symbol
Bit Set condition
Bit Reset condition
Fixed to zero
Fixed to zeroSPARESparebit
0 (LSB)
The AC input returnsto normal.
AC fail has occurred.
OTP shutdown has
occurred.
The power supply cools down.
Foldback shutdown
has occurred.
The supply output is turned On by
front panel buttonor OUT 1
command.
The supply output is turned On by
front panel buttonor OUT 1
command.
The supply output is turned On by
front panel buttonor OUT 1
command.
OVP shutdown has
occurred.
Rear panelJ"Shut
Off" condition has
occurred.
Rear panel J1 "Shut Off" condition
removed.
Front panel OUT
button pressed to Off.
Rear panel J1 Enable
terminals(J1-1&J1-14)
opened.
Rear panel J1 Enableterminalsclosed.
1
2
3
4
5
6
7(MSB)
AC Fail
Over
temperature
Foldback
Over
voltage
Shut Off
Output Off
Enable
AC
OTP
FOLD
OVP
SO
OFF
ENA
Table7-9:Status Condition Register
BIT
Status name
Status symbol
Bit Set condition
Bit Reset condition
0 (LSB)
CV
CC
NFLT
One or more faults are
enabled and occur.
Fault Event Register cleared (FEVE?).
Supplyisin Auto-
Restart mode (from
Front Panel or serial
command).
Supplyisin Safe-Startmode (from
Front Panelorserialcommand).
Foldprotection
enabled (fromFront
Panel or serial
command).
Foldprotectiondisabled (fromFront
Panel or serial command).
Fixed to zero.
Fixed to zero.
Supplyin Local mode.
Supplyin Remote mode or LocalLockout mode.
3
4
5
6
7 (MSB)
Fault
active
Fold
Enabled
Sparebit
Local Mode
FLT
FDE
SPARE
LCL
AST
Auto-
Restart
Enabled
Refer to Tables 7-10 to 7-13 for details of the Enable and Event registers.
The Fault Enable Register is set to the enable faults SRQs.
1.Fault Enable Register
2.Fault Event Register
The Fault Event will setabit ifacondition occurs and it is enabled. The register is cleared when
FEVE?, CLS or RST commands are received.
Table 7-10: Fault Enable Register
BIT
Enable
bit name
Fault symbol
0 (LSB)
1
2
3
4
5
6
7(MSB)
Spare bit
AC Fail
Over Temperature
Foldback
Over Voltage
Shut Off
Output Off
Enable
SPARE
AC
OTP
FOLD
OVP
SO
OFF
ENA
Bit Set condition
Bit reset condition
User command:
"FENA nn" where
nn is hexadecimal
User command: "FENA nn"
where nn is hexadecimal (if
nn="00", no fault SRQs will
be generated).
Table 7-11: Fault Event Register
0 (LSB)
1
2
3
4
5
6
7(MSB)
Spare bit
AC Fail
Over Temperature
Foldback
Over Voltage
Shut Off
Output Off
Enable
SPARE
AC
OTP
FOLD
OVP
SO
OFF
ENA
Entire Event Register is
cleared when user sends
"FEVE?" command to read
the register.
"CLS" and power-up also
clear the Fault Event
Register. (The Fault Event
Register is not cleared by
RST)
BIT
Event
bit name
Fault symbol
Bit Set condition
Bit reset condition
Fault condition
occurs and it is
enabled.
The fault can set
a bit, but when
the fault clears
the bit remains
set.

Table 7-12: Status Enable Register
BIT
Status symbol
0 (LSB)
1
2
3
4
5
6
7(MSB)
Constant Voltage
Constant Current
No Fault
Fault active
Auto-Restart enabled
Fold enabled
Spare
Local Mode
CV
CC
NFLT
FLT
AST
FDE
Spare
LCL
Bit Set condition
Bit reset condition
User command:
"SENA nn" is
received,
where nn is
hexadecimal bits.
User command: "SENA nn"
is received, where nn is
hexadecimal bits.
If "nn"=00, no SRQis sent
when there isachange in
Status Condition Register.
Table 7-13: Status Event Register
0 (LSB)
1
2
3
4
5
6
7(MSB)
Constant Voltage
Constant Current
No Fault
Fault active
Not used
Not used
Not used
Local Mode
CV
CC
NFLT
FLT
0
0
0
LCL
Entire Event Register is
cleared when user sends
"SEVE?" command to read
the register.
"CLS" and power-up also
clear the Status Event
Register. (The Fault Event
Register is not cleared by
RST)
BIT
Status
name
Status
symbol
Bit Set condition
Bit reset condition
Changes in status
occurs and it is
enabled.
The change can
set a bit, but when
the change clears
the bit remains
set.
3.Status Enable register
The Status Enable Register is set by the user to enable SRQs from changes in power supply
status.
Status name
Always zero
Always zero
Always zero
Always zero
Always zero
Always zero
"SENA nn"
command
"SENA nn"
command
4.Status Event Register
The Status Event Register will setabit ifachange in the power supply status occurs and it is
enabled. The register is cleared when the "SEVE?" or "CLS" commands are received. A change
in this register will generate SRQ.
Always zero
Always zero
Always zero
Unit is set to Local
by pressing front
panel REM/LOC
button.
7.9 SERIAL COMMUNICATION TEST SET-UP
Use the following instructions as basic set-up to test the serial communication operation.
1.Equipment:
2.PC set-up:
3.Power supply set-up:
4.Communication Test:
PC with Windows Hyper Terminal, private edition, software installed, Genesys
power supply, RS232 cable.
TM
2.1 Open Hyper Terminal.......................New Connection.
2.2 Enter a name
2.3 Connect to.......................................Direct to Com1 or Com2
2.4 Configure port properties:
2.5 Open Properties in the program File...........................Properties
2.6 Setting: ASCII Set Up
Select Echo characters locally, select send line ends with line feed.
On somePC systems, pressing the number keypad "Enter" will
distort displayed messages. Use the alphabetic "Enter" instead.
Bits per second .......9600
Data bits ..................8
Parity .......................None
Stop bits....................1
Flow control..............None
3.1 Connect the power supply to the PC using the RS232 cable.
3.2 Set via the front panel: Baud Rate: 9600, Address: 06.
3.3 Set via the rear panel: RS232/485 to RS232 (refer to section: 4-4).
4.1 Model identification:
PC:write: ADR06
Power supply response: "OK"
4.2 Command test:
PC write: OUT 1
Power supply response: "OK"
PC write: PV n
Power supply response: "OK"
PC write: PC n (for n values see Tables7-3 and 7-4)
Power supply response: "OK"
The power supply should turn on and the display will indicate the output voltage
and the actual output current.

NOTE
SW1 position 3 and 4must be in their Up position for operation
with 4-20mA Isolated Programming and Monitoring.
CAUTION
To prevent damage to the unit, do not program the output voltage and current
to higher then the power supply rating.
Perform the following procedure to configure the power supply:
1. Turn the power supply AC power switch to Off.
2. Connect a short between J1-8 and J1-12 (refer to Table 4-4).
3. Set Setup switch SW1-1 to itsUP position for Output Voltage external programming
and SW1-2 to itsUP position for Output Current limit external programming.
4. Set SW1 position 3to select the programming voltage range: Down=0-5V,Up=0-10V.
5. Set SW1 position 4to select the monitoring range: Down=0-5V,Up=0-10V.
6. Ensure that SW1 positions 7 and 8 are in the their down position.
7. Connect the programming sources to the mating plug of the Isolated Programming
connector.Observe for correct polarity of the voltage source.
8. Set the programming sources to the desired levels and turn the power supply ON.
Perform the following procedure to configure the power supply:
1. Turn the power supply AC power switch to Off.
2. Connect a short between J1-8 and J1-12 (refer to Table 4-4).
3.Set setup switch SW1-1 to itsUP position for Output Voltage external programming and
SW1-2 to itsUP position for Output Current limit external programming.
4. Set SW1 position 3to it's Up position.
5. Set SW1 position 4to it's Up position.
6. Ensure that SW1 positions 7 and 8 are in their Down position.
7. Connect the programming source to the mating plug of the Isolated Programming
connector.Observe for correct polarity of the voltage source.
8. Set the programming sources to the desired levels and turn the power supply ON.
8.4.2 Setting up the power supply for 4-20mA Isolated Programming and Monitoring
8.4.1 Setting up the power supply for 0-5/0-10V Isolated Programming and Monitoring
8.4 SETUP AND OPERATINGINSTRUCTIONS
J1-8 and J1-12 must be shorted together withajumper.
NOTE
J1-8 and J1-12 must be shorted together withajumper.
NOTE
9.1 INTRODUCTION
9.2 UNITS UNDER WARRANTY
9.3 PERIODIC MAINTENANCE
9.4 ADJUSTMENTS AND CALIBRATION
9.5 PART SREPLACEMENT AND REPAIRS
This chapter provides information about maintenance, calibration and troubleshooting.
Units requiring repair during the warranty period should be returned toaLambda authorized service
facility. Refer to the addresses listing on the back cover of this manual. Unauthorized repairs
performed by other than the authorized service facilities may void the warranty.
No routine maintenance of the power supply is required except for periodic cleaning. To clean,
disconnect the unit from the AC supply and allow 30sec. for discharging internal voltage. The front
panel and the metal surfaces should be cleaned using mild solution of detergent and water. The
solution should be applied onto a soft cloth, and not directly to the surface of the unit. Do not use
aromatic hydrocarbons or chlorinated solvents for cleaning. Use low pressure compressed air to
blow dust from the unit.
No internal adjustment or calibration is required. There is NO REASON to open the power supply
cover.
As repairs are made only by the manufacturer or by authorized service facilities, no parts
replacement information is provided in the manual. In case of failure, unusual or erratic operation of
the unit, contact a Lambda sales or service facility nearest you. Please refer to the Lambda sales
offices addresses listing on the back cover of this user manual.
If the power supply appears to operating improperly, use the troubleshooting guide to determine
whether the power supply, load or external control circuit are the cause.
Configure the power supply for basic front panel operation and perform the testsof section 3.8 to
determine if the problem is with the supply.
Table 9-1 provides the basic checks that can be performed to diagnose problems, and references to
sections of this manual for further information.
9.6 TROUBLESHOOTING
Table 9-1: Troubleshooting guide
Check continuity, replace
if necessary.
Does the AC source voltage
sag when load is applied?
No output. All displays and
indicators are blank.
Is the AC power cord
defective?
SYMPTOM
CHECK
ACTION
REF.
Is the AC input voltage
within range?
Check input AC voltage.
Connect to appropriate
voltage source.
Check input AC voltage.
Connect to appropriate
voltage source.
Output is present momentarily
but shutsoff quickly.The display
indicates "AC".
3.7
3.6
3.7
3.6
CHAPTER 9 MAINTENANCE

9.7 FUSE RATING
There are no user replaceable fuses in the power supply. Internal fuses are sized for fault
protection and ifafuse was opened it would indicate that service is required. Fuse replacement
Table 9-2: Internal fuses
Fuse designation
GENH model
F301
F302, F304
F31,F32
20A 250VAC, FAST
2A 400VDC, NORMAL
NOT USED
Check if the positive or
negative load wire is loose.
Output is present momentarily
but shutsoff quickly. the display
indicates "OUP".
SYMPTOM
CHECK
ACTION
REF.
3.9.6
3.9.8
Is the power supply
configured to Remote
sense?
Output voltage will not adjust.
Front panel CC LED is on.
Is the unit in constant current
mode?
Check current limit setting
and load current.
5.2.1
5.2.2
Output voltage will not adjust.
Front panel CV LED is on.
Check if output voltage is
adjusted above OVP setting
or below UVL setting.
Set OVP or UVL so they
will not limit the output.
Output current will not adjust.
Front panel CV LED is on.
Is the unit in constant voltage
mode?
Check current limit and
voltage setting.
5.3
5.4
5.2
Check load and sense
wires connection for noise
and impedance effects.
Minimize the drop on the
load wires.
Turn off the AC power
switch. Check load
connections. If analog
programming is used,
check if the OVPis set
lower than the output.
Check rear panel J1
ENABLE connection.
Setup switch SW1 setting.
Check rear panel J1
Output Shut-Off connection.
Check if air intake or
exhaust are blocked.
Check if the unit is
installed adjacent to heat
generating equipment.
Check Foldback setting
and load current.
Connect the sense wires
according to User's
manual instructions.
Turn Off the AC power
and wait until the display
turns off. Turn on the AC
power and press front
panel REM/LOC button.
Is the power supply in remote
sense?
Is the voltage drop on the
load wire high?
Display indicates "ENA"
Display indicates "SO"
Over Voltage Protection
circuit is tripped.
Display indicates "O7P"
Display indicates "Fb"
Are sensing wires
connected properly?
Is the power supply in
Local-Lockout mode?
3.9.4
3.9.8
5.3
5.8
4.4
5.7
5.5
5.12
3.9.8
7.2.5
The front panel controls are
nonfunctional.
Poor Load regulation
Front panel CV LED is on.
No output. Front panel ALARM
LED is blinking.
No output. Display indicates
"OUP"
Large ripple present in output.
USER MANUAL INDEX
A
B
C
D
E
F
G
H
ac cables
ac fail
accessories
acknowledge
address
adjustment
auto-restart
back space
baud rate
bipolar voltage
calibration
configuration
checksum
communication
constant current
constant voltage
cooling
cv indicator
cc indicator
daisy-chain
display
enable
error message
external resistor
external voltage
fine
foldback
fuse
front panel control
front panel locking
grounding
global output command 55
humidity
hyper terminal
I
J
L
M
O
P
R
S
ID control
initialization
installation
isolated
J1
J2
J3
last setting memory
linking power supplies
linefeed
local operation
local sensing
lock front panel
maintenance
otp
outline
over voltage
parallel operation
parity
ps_ok
preview
rack mounting
rear panel
remote sensing
remote/local
registersstructure
RS232
RS485
RXD
RX(RS232)
safestart
safety
series operation
shield
specifications
status control
SRQ
shut-off
SW1
T
U
V
W
TXD
TX(RS232)
under voltage limit
volts display
warranty
wire size
8, 15
29
8
51
18, 48
65
38
52
18, 48
40
65
48
51
51, 61
17, 34
17, 34
8, 10
27, 37
27, 37
43, 51
27
33
52
46
45
29
18, 36
66
27
43
24
10
61
52
53
13
62
32, 45, 46
16, 25
49
28, 38
51
51
34
25
43
65
41
51
38
12
27,35
41
61
37, 43
28
13
29
26
28
57
48, 49, 50
48, 49, 50
49, 50
49, 50
38
3
38
49
9, 62
56, 57
57
36
30, 31
49, 50
49, 50
17, 36
27
1, 65
19
Master/Slave
MD