TDK-Lambda GEN6-100, GEN300-5, GEN600-1.3, GEN8-90, GEN600-2.6 User Manual

...
Programmable DC Power Supplies
750W/1500W in 1U
Built in RS-232 & RS-485 Interface
Advanced Parallel Operation
Optional Interface:
Compliant LAN
IEEE488.2 SCPI (GPIB) Multi-Drop
Isolated Analog Programming
IA575-04-01-Rev. O
Manual Supplement
For units equipped with IEEE488.2 (GPIB) Interface option, refer to Manual IA586-04-01_.
For units equipped with LAN Interface option, refer to Manual IA672-04-01_.
GENESYS
TM
GEN 750W/1500W SERIES POWER
SUPPLIES
USER MANUAL
GENESYS
TM
GEN 750W/1500W SERIES POWER
SUPPLIES
USER MANUAL
This Manual Covers Models:
GEN6-100 GEN6-200 GEN8-90 GEN8-180 GEN12.5-60
GEN150-10 GEN300-2.5 GEN300-5 GEN600-1.3 GEN600-2.6
GEN80-9.5 GEN80-19 GEN100-7.5 GEN100-15 GEN150-5
GEN12.5-120 GEN20-38 GEN20-76 GEN30-25 GEN30-50
GEN40-19 GEN40-38 GEN50-30 GEN60-12.5 GEN60-25
WARRANTY ..........................................................................................................................................
SAFETY INSTRUCTIONS.....................................................................................................................
GERMAN SAFETY INSTRUCTIONS ...................................................................................................
....................................................................................
1.1 OPERATION MANUAL CONTENT .................................................................................................
1.2 INTRODUCTION .............................................................................................................................
1.2.1 General description ................................................................................................................
1.2.2 Models covered ......................................................................................................................
1.2.3 Features and options .............................................................................................................
1.2.4 Multiple output power system .................................................................................................
1.2.5 Control via the serial communication port ..............................................................................
1.2.6 Analog voltage programming and monitoring .................................................................. ......
1.2.7 Parallel operation ...................................................................................................................
1.2.8 Output connections ................................................................................................................
1.2.9 Cooling and mechanical construction ....................................................................................
1.3 ACCESSORIES ...............................................................................................................................
1.3.1 General ..................................................................................................................................
1.3.2 Serial link cable ......................................................................................................................
1.3.3 Misc. hardware .......................................................................................................................
1.3.4 AC cables ...............................................................................................................................
1.3.5 Serial Port Cables ..................................................................................................................
...................................................................................................
2.1 OUTPUT RATING ...........................................................................................................................
2.2 INPUT CHARACTERISTICS ..........................................................................................................
2.3 CONSTANT VOLTAGE MODE .......................................................................................................
2.4 CONSTANT CURRENT MODE ......................................................................................................
2.5 ANALOG PROGRAMMING AND MONITORING ............................................................................
2.6 PROGRAMMING AND READBACK ...............................................................................................
2.7 PROTECTIVE FUNCTIONS ...........................................................................................................
2.8 FRONT PANEL ................................................................................................................................
2.9 ENVIRONMENTAL CONDITIONS ..................................................................................................
2.10 MECHANICAL ..............................................................................................................................
2.11 SAFETY/EMC ...............................................................................................................................
2.12 SUPPLEMENTAL CHARACTERISTICS .......................................................................................
2.13 OUTLINE DRAWINGS .................................................................................................................
.......................................................................................................
3.1 GENERAL .......................................................................................................................................
3.2 PREPARATION FOR USE ..............................................................................................................
3.3 INITIAL INSPECTION .....................................................................................................................
3.4 RACK MOUNTING ..........................................................................................................................
3.4.1 To install the power supply in a rack .......................................................................................
3.4.2 Rack mount slides ..................................................................................................................
3.5 LOCATION MOUNTING AND COOLING .......................................................................................
3.6 AC SOURCE REQUIREMENTS .....................................................................................................
3.7 AC INPUT POWER CONNECTION ................................................................................................
3.7.1 AC input connector, 1500W models .......................................................................................
3.7.2 AC input connector, 750W models .........................................................................................
3.7.3 AC input cord ..........................................................................................................................
3.7.4 AC input wire connection, 1500W models ..............................................................................
3.8 TURN-ON CHECKOUT PROCEDURE ...........................................................................................
3.8.1 General ...................................................................................................................................
3.8.2 Prior to operation ...................................................................................................................
3.8.3 Constant voltage check ..........................................................................................................
3.8.4 Constant current check ..........................................................................................................
3.8.5 OVP check .............................................................................................................................
3.8.6 UVL check ..............................................................................................................................
3.8.7 Foldback check ......................................................................................................................
3.8.8 Address setting ......................................................................................................................
3.8.9 Baud rate setting ....................................................................................................................
CHAPTER 1 GENERAL INFORMATION
CHAPTER 2 SPECIFICATIONS
CHAPTER 3 INSTALLATION
TABLE OF CONTENTS
Pg.6 Pg.6 Pg.6 Pg.6 Pg.6 Pg.6 Pg.7 Pg.7 Pg.7 Pg.7 Pg.7 Pg.8 Pg.8 Pg.8 Pg.8 Pg.8 Pg.8 Pg.8
Pg.9 Pg.9 Pg.9 Pg.9 Pg.9 Pg.9 Pg.10 Pg.10 Pg.10 Pg.10 Pg.10 Pg.10 Pg.11 Pg.12
Pg.13 Pg.13 Pg.13 Pg.13 Pg.13 Pg.13 Pg.14 Pg.14 Pg.14 Pg.14 Pg.15 Pg.15 Pg.15 Pg.15 Pg.16 Pg.16 Pg.16 Pg.17 Pg.17 Pg.17 Pg.17 Pg.18 Pg.18 Pg.18
Pg.1 Pg.2 Pg.4
3.9 CONNECTING THE LOAD ..........................................................................................................
3.9.1 Load Wiring ..........................................................................................................................
3.9.2 Current Carrying Capacity ...................................................................................................
3.9.3 Wire termination .................................................................................................................
3.9.4 Noise and Impedance Effects ..............................................................................................
3.9.5 Inductive loads .....................................................................................................................
3.9.6 Making the load connections ................................................................................................
3.9.7 Connecting single loads, local sensing (default) ..................................................................
3.9.8 Connecting single loads, remote sensing ............................................................................
3.9.9 Connecting multiple loads, radial distribution method ..........................................................
3.9.10 Multiple loads connection with distribution terminals .........................................................
3.9.11 Grounding outputs .............................................................................................................
3.10 LOCAL AND REMOTE SENSING .............................................................................................
3.10.1 Sensing wiring ...................................................................................................................
3.10.2 Local sensing .....................................................................................................................
3.10.3 Remote sensing .................................................................................................................
3.10.4 J2 sense connector technical information ..........................................................................
3.11 REPACKAGING FOR SHIPMENT .............................................................................................
...............
4.1 INTRODUCTION ..........................................................................................................................
4.2 FRONT PANEL CONTROLS AND INDICATORS ........................................................................
4.3 REAR PANEL ...............................................................................................................................
4.4 REAR PANEL SW1 SETUP SWITCH .........................................................................................
4.4.1 SW1 positions functions ......................................................................................................
4.4.2 Resetting the switch .............................................................................................................
4.5 REAR PANEL J1 PROGRAMMING AND MONITORING CONNECTOR ....................................
4.5.1 Making J1 connections ........................................................................................................
.............................................................................................
5.1 INTRODUCTION ..........................................................................................................................
5.2 STANDARD OPERATION ............................................................................................................
5.2.1 Constant Voltage Mode .......................................................................................................
5.2.2 Constant Current Operation .................................................................................................
5.2.3 Automatic Crossover ............................................................................................................
5.3 OVER VOLTAGE PROTECTION (OVP) ......................................................................................
5.3.1 Setting the OVP level ..........................................................................................................
5.3.2 Activated OVP protection indications ...................................................................................
5.3.3 Resetting the OVP circuit .....................................................................................................
5.4 UNDER VOLTAGE LIMIT (UVL) ..................................................................................................
5.4.1 Setting the UVL level ...........................................................................................................
5.5 FOLDBACK PROTECTION ..........................................................................................................
5.5.1 Setting the Foldback protection ...........................................................................................
5.5.2. Resetting activated Foldback protection ............................................................................
5.6 OUTPUT ON/OFF CONTROL ......................................................................................................
5.7 OUTPUT SHUT-OFF (SO) CONTROL VIA REAR PANEL J1 CONNECTOR ..............................
5.8 ENABLE/DISABLE CONTROL VIA REAR PANEL J1 CONNECTOR ..........................................
5.9 CV/CC SIGNAL .............................................................................................................................
5.10 PS_OK SIGNAL ..........................................................................................................................
5.11 SAFE START AND AUTO-RESTART MODES ............................................................................
5.11.1 Automatic start mode .........................................................................................................
5.11.2 Safe start mode ..................................................................................................................
5.12 OVER TEMPERATURE PROTECTION (OTP) ..........................................................................
5.13 LAST SETTING MEMORY .........................................................................................................
5.14 SERIES OPERATION .................................................................................................................
5.14.1 Series connection for increased output voltage .................................................................
5.14.2 Series connection for positive and negative output voltage ...............................................
5.15 PARALLEL OPERATION ............................................................................................................
5.15.1 Basic parallel operation....................................................................................................
5.15.2 Advanced parallel operation...............................................................................................
CHAPTER 4 FRONT AND REAR PANEL CONTROLS AND CONNECT
ORS
CHAPTER 5 LOCAL OPERATION
TABLE OF CONTENTS
Pg.18 Pg.18 Pg.18 Pg.19 Pg.20 Pg.20 Pg.20 Pg.23 Pg.23 Pg.23 Pg.24 Pg.24 Pg.25 Pg.25 Pg.25 Pg.26 Pg.26 Pg.26
Pg.27 Pg.27 Pg.27 Pg.29 Pg.30 Pg.31 Pg.31 Pg.32 Pg.32
Pg.34 Pg.34 Pg.34 Pg.34 Pg.34 Pg.35 Pg.35 Pg.35 Pg.35 Pg.35 Pg.36 Pg.36 Pg.36 Pg.36 Pg.36 Pg.36 Pg.36 Pg.37 Pg.37 Pg.37 Pg.38 Pg.38 Pg.38 Pg.38 Pg.38 Pg.38 Pg.39 Pg.40 Pg.41 Pg.41 Pg.41
CHAPTER 6 REMOTE ANALOG PROGRAMMING
CHAPTER 7 RS232 & RS485 REMOTE CONTROL
CHAPTER 8 ISOLATED ANALOG PROGRAMMING OPTION
.................................................................
6.1 INTRODUCTION ...........................................................................................................................
6.2 LOCAL/REMOTE ANALOG CONTROLL.......................................................................................
6.3 LOCAL/REMOTE ANALOG INDICATION......................................................................................
6.4 REMOTE VOLTAGE PROGRAMMING OF OUTPUT VOLTAGE AND CURRENT LIMIT .............
6.5 RESISTIVE PROGRAMMING OF OUTPUT VOLTAGE AND CURRENT LIMIT ...........................
6.6 REMOTE MONITORING OF OUTPUT VOLTAGE AND CURRENT .............................................
...............................................................
7.1 INTRODUCTION ...........................................................................................................................
7.2 CONFIGURATION .........................................................................................................................
7.2.1 Default setting .......................................................................................................................
7.2.2 Address setting .....................................................................................................................
7.2.3 RS232 or RS485 selection ...................................................................................................
7.2.4 Baud rate setting ...................................................................................................................
7.2.5 Setting the unit into Remote or Local mode ..........................................................................
7.2.6 RS232/458 port at Local mode .............................................................................................
7.2.7 Front panel in Remote mode ................................................................................................
7.3 REAR PANEL RS232/485 CONNECTOR ......................................................................................
7.4 CONNECTING POWER SUPPLIES TO RS232 OR RS485 BUS .................................................
7.4.1 Single power supply ..............................................................................................................
7.4.2 Multi power supplies connection to RS232 or RS485 bus ....................................................
7.5 COMMUNICATION INTERFACE PROTOCOL ..............................................................................
7.5.1 Data format ...........................................................................................................................
7.5.2 Addressing ............................................................................................................................
7.5.3 End of message ....................................................................................................................
7.5.4 Command repeat .................................................................................................................
7.5.5 Checksum .............................................................................................................................
7.5.6 Acknowledge .........................................................................................................................
7.5.7 Error message ......................................................................................................................
7.5.8 Backspace ............................................................................................................................
7.6 ERROR MESSAGES .....................................................................................................................
7.7 COMMAND SET DESCRIPTION ..................................................................................................
7.7.1 General guides .....................................................................................................................
7.7.2 Command set categories ......................................................................................................
7.7.3 Initialization control commands .............................................................................................
7.7.4 ID control commands ............................................................................................................
7.7.5 Output control commands .....................................................................................................
7.7.6 Global output commands ....................................................................................................
7.7.7 Status control commands .....................................................................................................
7.8 STATUS, ERROR AND SRQ REGISTERS ...................................................................................
7.8.1 General .................................................................................................................................
7.8.2 Conditional registers .............................................................................................................
7.8.3 Service Request: Enabled and Event Registers ...................................................................
7.9 SERIAL COMMUNICATION TEST SET-UP ..................................................................................
..............................................
8.1 INTRODUCTION ...........................................................................................................................
8.2 SPECIFICATIONS .........................................................................................................................
8.2.1 0-5V/0-10V option .................................................................................................................
8.2.2 4-20mA option .......................................................................................................................
8.3 ISOLATED PROGRAMMING & MONITORING CONNECTOR ....................................................
8.4 SETUP AND OPERATING INSTRUCTIONS .................................................................................
8.4.1 Setting up the power supply for 0-5/0-10V Isolated Programming and Monitoring ...............
8.4.2 Setting up the power supply for 4-20mA Isolated Programming and Monitoring ..................
TABLE OF CONTENTS
Pg.44 Pg.44 Pg.44 Pg.44 Pg.45 Pg.46 Pg.47
Pg.43 Pg.43 Pg.43 Pg.43
Pg.48 Pg.48 Pg.48 Pg.48 Pg.48 Pg.48 Pg.48 Pg.48 Pg.49 Pg.49 Pg.49 Pg.50 Pg.50 Pg.51 Pg.51 Pg.51 Pg.51 Pg.51 Pg.51 Pg.51 Pg.51 Pg.52 Pg.52 Pg.52 Pg.52 Pg.52 Pg.52 Pg.53 Pg.53 Pg.53 Pg.55 Pg.56 Pg.57 Pg.57 Pg.57 Pg.58 Pg.61
Pg.62 Pg.62 Pg.62 Pg.62 Pg.62 Pg.63 Pg.64 Pg.64 Pg.64
5.16 DAISY-CHAIN CONNECTION......................................................................................................
5.17 FRONT PANEL LOCKING.............................................................................................................
5.17.1 Unlocked front panel ............................................................................................................
5.17.2 Locked front panel ...............................................................................................................
This information sheet was prepared based on People's Republic of China "Management Methods for Controlling Pollution Caused by Electronic Information Products Regulation"and
"SJ/T 11364—2006 Marking for Control of Pollution Caused by Electronic Information Products".
As People's Republic of China "Management Methods for Controlling Pollution Caused by Electronic Information Products Regulation"is a different legislation from EU RoHS Directive
2002/95/EC, inquiries concerning EU RoHS Directive (2002/95/EC information should be done separately.
The date of manufacture
Part Name
GENESYS, GEN1500W & GEN750W POWER SUPPLY SERIES Product Weight
GEN1500W: 8.5Kg
Product Weight
GEN750W: 7Kg
Lead (Pb) Mercury (Hg) Cadmium (Cd) Hexavalent Chromium
(Cr6+)
Polybrominated
Biphenyls PBB
Polybrominated Diphenyl
EthersPBDE
0.1wt% 0.1wt% 0.01wt% 0.1wt% 0.1wt% 0.1wt%
Case
O O O O O O
Plastic panel
O O O O O O
PCB's assembly X O O O O O
Inner metal parts O O O O O O
Inner cables O O O O O O
Accessories O O O O O O Provided in the package
: Indicates that the concentration values of toxic and hazardous substances in all "homogeneous materials" of respective parts and materials does not exceed the concentration limits
regulated by "SJ/T 11363-2006 Requirements for Concentration Limits for Certain Hazardous Substances in Electronic Information Products".
× : Indicates that the concentration value of a toxic or hazardous substance included in a "homogeneous part" of a respective part ot material exceeds the concentration limit regulated by
"SJ/T 11363-2006 Requirements for Concentration Limits for Certain Hazardous Substances in Electronic Information Products".
Information Concerning Inclusion of Toxic and Hazardous Substances
NotesConcentration Values of Toxic and Hazardous Substances/Elements (wt%)
Subpart Name
2002/95/EC, inquiries concerning EU RoHS Directive 2002/95/EC information should be done separately.
The date of manufacture
Part Name
GENESYS, GEN1500W & GEN750W POWER SUPPLY SERIES Product Weight
GEN1500W: 8.5Kg
Product Weight
GEN750W: 7Kg
Lead (Pb) Mercury (Hg) Cadmium (Cd) Hexavalent Chromium
(Cr6+)
Polybrominated
Biphenyls (PBB)
Polybrominated Diphenyl
EthersPBDE
0.1wt% 0.1wt% 0.01wt% 0.1wt% 0.1wt% 0.1wt%
Case
O O O O O O
Plastic panel
O O O O O O
PCB's assembly X O O O O O
Inner metal parts O O O O O O
Inner cables O O O O O O
Accessories O O O O O O Provided in the package
: Indicates that the concentration values of toxic and hazardous substances in all "homogeneous materials" of respective parts and materials does not exceed the concentration limits
regulated by "SJ/T 11363-2006 Requirements for Concentration Limits for Certain Hazardous Substances in Electronic Information Products".
× : Indicates that the concentration value of a toxic or hazardous substance included in a "homogeneous part" of a respective part ot material exceeds the concentration limit regulated by
"SJ/T 11363-2006 Requirements for Concentration Limits for Certain Hazardous Substances in Electronic Information Products".
NotesConcentration Values of Toxic and Hazardous Substances/Elements (wt%)
Subpart Name
WARRANTY
This Nemic-Lambda product is warranted against defects in materials and workmanship for a period of ve years from date of shipment .During the warranty period, Nemic-Lambda will, at it’s option,either repair or replace products which prove to be defective.
LIMITATION OF WARRANTY
The warranty shall not apply to defects resulting from improper or inadequate usage or maintenanceby the buyer, buyer supplied products or interfacing. The warranty shall not apply to defects resultingfrom unauthorized modications or from operation exceeding the environmental specications of the product or if the QA seal has been removed or altered by anyone other than Nemic-Lambda authorised personnel. Nemic-Lambda does not warrant the buyers circuitry or malfunctions of Nemic-Lambda products resulting from the buyer ’s circuitry. Furthermore, Nemic­Lambda does notwarrant any damage occurring as a result of the buyer ’s circuitry or the buyer ’s - supplied products.
WARRANTY SERVICE
This product must be returned to an authorized Nemic-Lambda service facility for repairs or otherwarranty service. For products returned to Nemic_Lambda for warranty service, the buyer shall prepay shipping charges to Nemic­Lambda and Nemic-Lambda shall pay the shipping charges toreturn the product to the buyer. Refer to section 3.11 for repackaging for shipment.
DISCLAIMER
The information contained in this document is subject to change without notice. Nemic-Lambda shall not be liable for errors contained in this document or for incidental or consequential damages in connection with the furnishing, performance or use of this material. No part of this document may be photocopied, reproduced or translated into another language without the prior written consent of Nemic-Lambda.
TRADEMARK INFORMATION
Genesys™ power supply is a trademark of Nemic-Lambda & Lambda Americas Inc. Microsoft™ and Windows™ are trademarks of Microsoft Corporation.
1
REGULATORY NOTICES
FCC Notice
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
CE Notice (European Union)
Marking by the CE Symbol indicates compliance to the EMC Directive and the Low Voltage Directive of the European Union. Such marking is indicative that the Genesys series
GEN1500/750W meets the following technical standards:
EN 55022:1998+A1:2000+A2:2003 -”Limits and Methods of Measurement of Radio Interference Characteristics of Information Technology Equipment.” EN 55024:1998+A1:2001+A2:2003-”information thecnology equipment - Immunity characteristics - Limits and methods of measurement.” EN 60950-1:2006+A11:2009- “Safety of InformationTechnology Equipment.”
A “Declaration of Conformity” in accordance with the preceding directives and standards has been made and is on file at our EU representative TDK-Lambda Limited, located at Kingsley Avenue, Ilfracombe, Devon EX34 8ES, UK.
TM
NOTE: This equipment has been tested and found to comply with the limits for a Class A digital
device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
WARNING:
Modifications not expressly approved by the party responsible for compliance could
void the user’s authority to operate the equipment under FCC Rules.
WARNING: This is a Class A product. on a domestic environment this product may cause radio
interference in which case user may be required to takeadequate measures.
SAFETY APPROVALS: UL 60950-1:2007 Second Edition, UL Listed, C-UL for Canada, IEC
60950-1:2005 Second Edition, CE marking, when applied to the
GEN1500/750W
product, indicates compliance with the Low Voltage Directive 2006/95/EC in that it complies with EN 60950­1:2006/A11:2009 Second Edition.
2
SAFETY INSTRUCTIONS.
ENVIRONMENTAL CONDITIONS
The Genesys power supply series safety approval applies to the following operating conditions: *Indoor use *Ambient temperature: 0 C to 50 C *Maximum relative humidity: 90% (no condensation) *Altitude: up to 3000m *Pollution degree 2
TM
o o
FCC COMPLIANCE NOTICE:
Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
!
Instruction manual symbol. The instrument will be marked with this symbol when it is necessary for the user to refer to the instruction manual.
CAUTION Risk of Electrical Shock.
Indicates hazardous voltage.
Indicates ground terminal.
Protective Ground Conductor Terminal
Off (Supply)
On (Supply)
The WARNING sign denotes a hazard. An attention to a procedure is called. Not following procedure correctly could result in personal injury. AWARNING sign should not be skipped and all indicated conditions must be fully understood and met.
The CAUTION sign denotes a hazard. An attention to a procedure is called. Not following procedure correctly could result in damage to the equipment. Do not proceed beyond a CAUTION sign until all indicated conditions are fully understood and met.
WARNING
CAUTION
3
SICHERHEITS-INSTALLATIONS ANWEISUNGEN
Vorsicht
Betriebsbedingungen
Erdungskonzept
Vorsicht
Absicherung
Anschluss an Versorgungsstromkreis
Spannungsfuhrende Teile
Vor Anschluss an das Netz ist die Aufstellanleitung wie nachstehend beschrieben zu beachten. Die nachstehenden Sicherheitsanweisungen mussen während aller Phasen des Betriebes, des Services und der Reparatur dieser Ausrustung beachtet werden. Alle notwendigen Bedingungen die sicherstellen, dass die Einrichtung zu keiner Gefahr im Sinne dieser Norm fuhren kann, sind
in diesem Handbuch beschrieben. Nemic-Lambda ist nicht verantwortlich fur Fehler, die bei der Inbetriebnahme des Gerätes auf
Grundlage dieser Sicherheitsanweisungen durch den Betreiber entstehen können.
Die Genesys Stromversorgungs-Reihe ist zur Installation gemäss Uberspannungs-Kategorie 2 entwickelt worden.
Installations Kategorie (Uberspannungs-Kategorie) 2 bedeutet: Kleinindustrie, Geräte, bewegliche Ausrustung etc.. mit Uberspannungen kleiner als Installation Kategorie 3.
Dieses Produkt ist ein Gerät mit Schutzklasse1. Damit gefährliche Energieinhalte und Spannungen vermieden werden, ist das Gerätechassis an eine Schutzerde anzuschliessen. Das Gerät muss an die AC-Wechselspannungsversorgung mit 3 Leitern (L, N, PE) angeschlossen werden. Der PE-Anschluss ist an einen festen Erder anzuschliessen. Bei Festverdrahtung des Gerätes ist sicherzustellen, dass der PE Anschluss als erstes durchgefuhrt wird.
Jede mögliche Unterbrechung des PE-Leiters oder Trennung der PE Masse kann einen möglichen elektrischen Schlag hervorrufen, der Personenschäden zur Folge hätte.
Es besteht Energiegefahr am RS232/485 und IEEE Anschluss, falls die Ausgangsspannung des Gerätes grösser ist als 400V und der positive Ausgangsanschluss des Netzteiles geerdet wird. Dies gilt insbesondere auch bei Reihenschaltungen von unterschiedlichen Netzteilen. Wird die RS232/485 oder IEEE Schnittstelle verwendet, ist darauf zu achten, dass der
Plus-Ausgangsanschluss nicht geerdet wird.
Sicherungen durfen nur durch autorisierte Nemic-Lambda Service Personen ausgetauscht werden. Um Brandgefahr vorzubeugen, sind nur Sicherungen zu verwenden mit gleicher Bauart und Auslösecharakteristik. Siehe hierzu Wartungsanweisungen in Kapitel 9 bezuglich Sicherungen.
Der Betrieb des Gerätes ist nur fur den dafur spezifizierten Wechselspannungsbereich und der angegebenen Frequenz erlaubt. Der Nominaleingangsspannungsbereich der Genesys Serie liegt bei 100-240VAC mit 50/60Hz. Fur einen sicheren Betrieb des Gerätes ist eine Abweichung von max. +/-10% der Nominalspannung erlaubt.
Die Geräteabdeckung darf nur im stromlosen Zustand geöffnet werden. Interne Modifikationen, sowie Bauteileaustausch ist nur durch Nemic-Lambda qualifiziertes Personal erlaubt. Vor Austausch von Bauteilen ist das Netzkabel bzw
. die Versorgungsspannung zu trennen. Energieversorgungsanschlusse sind immer zu trennen um Personenverletzungen durch gefährliche Energieinhalte und Spannungen auszuschliessen. Die Stromkreise sind zu entladen, externe Spannunsquellensind zu entfernenbevor Bauteile bzw. Komponenten getauscht werden.
TM
TM
Erdung des DC-Ausgangs
!
4
Anderungen und Bauteileersatz
Umweltbedingungen
Sicherheits- und Warnsymbole
Ersatzteilaustausch - und Anderungen durfen nur von autorisiertem Nemic-Lambda SERVICE­PERSONEN durchgefuhrt werden. Fur Reparaturen oder Anderungen ist das Gerät zur Nemic­Lambda Service-Niederlassung zu retournieren.
Die Genesys -Stromversorgungs-Serie ist gemäss den Sicherheitsabnahmen fur folgende Betriebsbedingungen zugelassen.
* Stationäre Einrichtungen in Gebäuden. * Umgebungstemperaturbereich: 0-50 C.
* Maximale Relative Luftfeuchtigkeit: 90% (nicht kondensierend). * Betriebshöhe: bis zu 3000m. * Verschmutzungsgrad 2.
VORSICHT Spannungsfuhrende Teile - Gefahr durch elektrischen Schlag bzw. Energieinhalte.
Handbuch-Symbol. Das Gerät bzw. Geräteteile werden mit diesem Symbol gekennzeichnet, wenn es fur den Benutzer notwendig ist, sich auf die Anweisungen im Handbuch zu beziehen.
Zeigt "spannungsfuhrende Teile" mit gefährlicher Spannung an.
Zeigt Masse-Anschluss an, keine Schutzerde.( z.B. Masseanschluss an einen Verbraucher).
Schutzleiter-Anschlussklemme.
Symbol fur Schalter oder Druckknöpfe - Zeigt die "Ein"- Stellung hier an.
Symbol fur Schalter oder Druckknöpfe - Zeigt die "Aus"-Stellung hier an.
Dieses Warnaufschrift weist auf eine Gefahr hin, die eine Uberprufunganweisung nach
sich zieht. Nichteinhaltung kann zu Personenschäden fuhren. Dieser Warnhinweis darf nicht ubersprungen werden und die beschriebene Vorgehensweise muss
strikt verstanden werden und dementsprechend umgesetzt werden.
Diese "Vorsichtswarnung" weist auf eine Gefahr hin, die einer Vorkehrung bedarf.
Nichteinhaltung kann zur Zerstörung der Anlage oder des Gerätes fuhren. Bitte berucksichtigen
Sie Anweisungen, die dort beschrieben sind, bevor Sie mit Benutzung der Anlage bzw. des Gerätes fortfahren.
SICHERHEITS-HINWEISE
TM
o
alle
WARNING
CAUTION
!
MASCHINENLAERM
Maschinenlaerminformations Verordnung 3. GPSGV, der hoechste Schalldruckpegel betraegt 70 dB A) oder weniger gemass EN ISO 7779.
(
5
CHAPTER 1 GENERAL INFORMATION
1.1 USER MANUAL CONTENT
1.2 INTRODUCTION
This user’s manual contains the operating instructions, installation instructions and specifications of the Genesys 1500W and 750W power supply series. The instructions refer to the standard power supplies, including the built-in RS232/485 serial communication. For information related to operation with the optional IEEE programming, refer to User Manual for Power Supply IEEE Programming Interface.
Genesys power supplies are wide output range, high performance switching power supplies. The Genesys series is power factor corrected and operates from worldwide AC voltage range continuously . Output voltage and current are continuously displayed and LED indicators show the complete operating status of the power supply. The Front panel controls allow the user to set the output parameters, the protection levels (Over-Voltage protection, Under-Voltage limit and Foldback) and preview the settings. The rear panel includes the necessary connectors to control and monitor the power supply operation by remote analog signals or by the built-in serial communication (RS232/485). GPIB programming and Isolated-Analog programming/monitoring are optional.
Model Voltage Current Model Voltage Current
range(V) range(A) range(V) range(A) GEN6-100 0-6 0-100 GEN60-12.5 0-60 0-12.5 GEN6-200 0-6 0-200 GEN60-25 0-60 0-25 GEN8-90 0-8 0-90 GEN80-9.5 0-80 0-9.5 GEN8-180 0-8 0-180 GEN80-19 0-80 0-19 GEN12.5-60 0-12.5 0-60 GEN100-7.5 0-100 0-7.5 GEN12.5-120 0-12.5 0-120 GEN100-15 0-100 0-15 GEN20-38 0-20 0-38 GEN150-5 0-150 0-5 GEN20-76 0-20 0-76 GEN150-10 0-150 0-10 GEN30-25 0-30 0-25 GEN300-2.5 0-300 0-2.5 GEN30-50 0-30 0-50 GEN300-5 0-300 0-5 GEN40-19 0-40 0-19 GEN600-1.3 0-600 0-1.3 GEN40-38 0-40 0-38 GEN600-2.6 0-600 0-2.6 GEN50-30 0-50 0-30
Table1-1: Models covered by the manual
Constant Voltage / Constant Current with automatic crossover. * Active Power Factor correction. * Universal Input Voltage 85~265Vac, continuous operation. * Embedded Microprocessor Controller. * Built in RS232/485 Interface. * Voltage & Current high resolution adjustment by digital encoders. * High accuracy programming/readback-16 bit. * Software Calibration (no internal trimmers / potentiometers). * Last Setting Memory. * Independent Remote ON/OFF (opto-isolated) and Remote Enable/Disable.
TM
TM
TM
1.2.1 General description
1.2.2 Models covered by this manual
1.2.3 Features and options
*
6
* Parallel operation (Master/Slave) with Active current sharing. * Remote sensing to compensate for voltage drop of power leads.
* Cooling fan speed control for low noise and extended fan life. * Zero stacking- no ventillation holes at the top and bottom surface of the power supply. * Optional GPIB interface (SCPI compatible). * Optional Isolated Analog programming/monitoring (0-5V or 0-10V, user selectable
and 4-20mA).
The Genesys power supplies series can be configured into a programmable power system of up to 31 units using the built-in RS232/RS485 communication port in the power
supply and the RS485 linking cable provided with each power supply.
In a GPIB system, each power supply can be controlled using the optional GPIB controller
(factory installed).
The following parameters can be programmed via the serial communication port:
1. Output voltage setting.
2. Output current setting.
3. Output voltage measurement.
4. Output on/off control.
5. Output current measurement.
6. Foldback protection setting.
7. Over-voltage protection setting and readback.
8. Under-Voltage limit setting and readback.
9. Power-supply start up mode (last setting or safe mode)
Analog inputs and outputs are provided at the rear panel for analog control of the power supply. The output voltage and the current limit can be programmed by analog voltage or by resistor, and can be monitored by analog voltage. The power supply output can be remotely set to On or Offand analog signals monitor the proper operation of the power supply and the mode of operation (CV/CC).
Genesys powersupplies of the same output voltage and current rating can be paralleledin master-slave configuration with automatic current sharing to increase power available.
Output connections are made to rear panel bus-bars for models up to 60V and to a 4­terminal wire clamp connector for models above 60V rated output voltage. Either the positive or negative terminal may be grounded or the output may be floated. Models up to 60VDC Rated Output shall not float outputs more than +/- 60VDC above/below chassis ground. Models >60VDC Rated Output shall not float outputs more than +/-600VDC above/below chassis ground. Contact factory for assistance with higher float voltage applications.
Local or remote sense may be used.
In remote sense, the voltage drop on the load wires
should be minimized. Refer to the specifications for the maximum voltage drop value.
* External Analog Programming and Monitoring standard (0-5V or 0-10V, user selectable).
1.2.4 Multiple output power system
1.2.5 Control via the serial communication port
1.2.6 Analog voltage programming and monitoring
1.2.7 Parallel operation
TM
TM
1.2.8 Output connections
7
1.2.9 Cooling and mechanical construction
1.3.1 General
1.3.2 Serial link cable
1.3.4 AC cables
The Genesys series is cooled by internal fans. At the installation, care must be taken to allow free air flow into the power supply via the front panel and out of the power supply via the rear panel. The Genesys power supplies have a compact and lightweight package which allows easy installation and space saving in the application equipment.
Accessories are delivered with the power supply or separately upon ordering. The list below shows the possible accessories and ordering numbers.
S
TM
TM
1.3 ACCESSORIES
erial link cable, for linking power supplies by RS485 communication is provided with the power supply. Cable description: 0.5m length, shielded, RJ-45 type plugs, 8 contacts (P/N: GEN/RJ45).
* DB25 plug kit (AMP, 749809-9).
* Output terminal shield
AC cables are not provided with the power supply. If an AC cable is required, it should be ordered according to following:
Part no. Market Description
NC301 USA 13A125V, unshielded, 2m typical length, with IEC320 connector on
one end and NEMA-5-15P connector on the other end.
NC302 Europe 10A 250V, unshielded, 2m typical length, with IEC320 connector
on one end and INT’L 7 standard VII, dual earthing.
NC303 General 10A 250V, unshielded, 2m typical length, with IEC320 connector
on one end and unterminated stripped wires on the other end. Use the cable only with plug approved by the national safety standards of the country of usage.
NC305 Japan 13A 125V, unshielded, 2m typical length, with IEC320 connector
on one end and Japan type plug on the other end.
NC306 UK 10A 250V unshielded, 2m typical length, with IEC320 connector
on one end and UK type plug on the other end.
For 1500W Genesys power supplies the recommended AC cable (customer supplied) is:
25A 250V, 3x12AWG, outer diameter: 9-11mm, rated 60 C min., 3m max. length. Add a non-locking plug approved by the national safety standards of the country of usage.
Refer to section 7.4
1.3.3 Misc. hardware
1.3.5 Serial Port Cables
TM
O
(GEN/U)
(GEN/E)
(GEN/O)
(GEN )/J
(GEN/GB)
Observe all torque guidelines within this manual. Over torqueing may damage unit or accessories. Such damage is not covered under manufacturers warranty.
CAUTION
8
9
10
UL 60950-1:2007(Ed.2), IEC 60950-1:2005(Ed.2), EN 60950-1:2006(Ed.2)+A11:2009
*1: Minimum voltage is guaranteed to maximum 0.2% of the rated output voltage. *2: Minimum current is guaranteed to maximum 0.4% of the rated output current. *3: For cases where conformance to various safety standards (UL, IEC etc.) is required, to be
described as 100-240Vac (50/60Hz). *4: At 100/200V input voltage and maximum output power. *5: From 85~132Vac or 170~265Vac, constant load. *6: From No-load to Full-load, constant input voltage. Measured at the sensing point in Remote
Sense. *7: For load voltage change, equal to the unit voltage rating, constant input voltage. *8: For 6V models the ripple is measured at 2~6V output voltage and full output current. For
other models, the ripple is measured at 10~100% output voltage and full output current. *9: With rated, resistive load. *10:For 6V~300V models: Measured with JEITA RC-9131A (1:1) probe.
For 600V model: Measured with (10:1) probe.
The supplemental characteristics give typical but non-warranted performance characteristics. The supplemental characteristics are useful in assessing applications for the power supply. Several kinds of supplemental characteristics are listed below.
1.Evaluation Data: Typical performance of the power supply.
2.Reliability Data: Reliability performance of the power supply.
3.IEC1000 Data: Performance of the power supply under IEC1000 test conditions.
4.EMI Data: Typical EMI (conducted and radiated) performance of the power supply.
The supplemental characteristics data is held in each Lambda sales and service facility. For further details please contact the Lambda office nearest you.
NOTES:
2.12 SUPPLEMENTAL CHARACTERISTICS
11
2.13 GENESYS 750W & 1500W POWER SUPPLIES OUTLINE DRAWINGS
TM
482.8+/-1.0mm
43.6+/-0.3mm
24.5
A
A A
595.3+/-1.0mm
497.8+/-1.0mm
57.8+/-0.5
92.0+/-0.5
92.0+/-0.5
21.0
432.8+/-1.0mm
J2
AC INPUT
ON
OFF
OUT
IN
J3
J1
SW1
422.8+/-1.0mm
Note 1
Note 5
Note 2 (80V~600V)
Note 2
NOTES:
1.Mating plug supplied with power supply.
2.Bus-bars for 6V to 60V models. See detail. Wire clamp connector for 80V to 600V models (shown).
3. AC cable strain relief for 1500W models only (supplied
with power supply).
4. IEC connector for 750W models. Wire clamp terminal for 1500W models (shown).
5. Chassis slides, GENERAL DEVICES P/N: CC3001-00-S160
or equivalent, mounting holes #10-32 marked "A".
6. Bus Bars output connector enclosure for 60V to 600V.
7. Mounting holes for 19” rack. Uae M6x16
screws to fix the unit to the rack.
104+/-2.0mm
Note 4
Note 7
Note 3
Note 6
39.5+0.5mm
22.0mm
3.0mm
30.0mm
Bus-Bar Detail
6V to 60V Models
8.5mm
T
D
L
a
m
b
d
a
-
I
T
D
L
amb
d
a
-
I
0-8V 0-300A
GEN8-300
12
CHAPTER 3 INSTALLATION
3.1 GENERAL
3.2 PREPARATION FOR USE
3.3 INITIAL INSPECTION
3.4 RACK MOUNTING
This chapter contains instructions for initial inspection, preparation for use and repackaging for shipment. Connection to PC, setting the communication port and linking Genesys power supplies are described in Chapter 7.
Genesys power supplies generate magnetic fields which might affect the operation of other instruments. If your equipment is susceptible to magnetic fields, do not position it adjacent to the power supply.
n order to be operational the power supply must be connected to an appropriate AC source. The AC source voltage should be within the power supply specification. Do not apply power before reading, Section 3.6 and 3.7. Table 3-1 below, describes the basic setup procedure. Follow the instructions in Table 3-1 in the sequence given to prepare the power supply for use.
Stepno. Item Description Reference
Prior to shipment this power supply was inspected and found free of mechanical or electrical
defects. Upon unpacking of the power supply, inspect for any damage which may have occured in transit. The inspection should confirm that there is no exterior damage to the power supply such as broken knobs or connectors and that the front paneland meters face are not scratched or cracked. Keep all packing material until the inspection has been completed. If damage is detected, file a claim with carrier immediately and notify the Lambda sales or service facility nearest you.
The Genesys power supply series is designed to fit in a standard 19” equipment rack.
1. Use the front panel rack-mount brackets to install the power supply in the rack.
2. Use a support bar to provide adequate support for the rear of the power supply. Do not obstruct the air exhaust at the rear panel of the unit.
TM
TM
TM
I
3.4.1 Toinstall the Power Supply in a rack:
NOTE
1
2
3
4
5
6
Inspection
Installation
AC source
Test
Load connection
Default setting
Initial physical inspection of the power supply
Section 3.3
Installing the power supply, Ensuring adequate ventillation.
AC source requirements Connecting the power supply to the AC source.
Turn-on checkout procedure.
The power supply setting at shipment.
Wire size selection. Local /Remote sensing. Single or multiple loads.
Section 3.4 Section 3.5
Section 3.6 Section 3.7
Section 3.8
Section 3.9
Section 7.2.1
Table 3-1: Basic setup procedure
13
3.4.2 Rack Mount Slides (optional):
Use rack mount slides: General Devices P/N: CC3001-00-S160 (ordering P/N: C-300-S-116-RH­LH) or equivalent to install the unit in a standard 19” equipment rack. Refer to Fig. 3-1 for slides assembly instructions. Use three #10-32x0.38"(max.) screws at each side. To prevent internal damage, use the specified screw length only.
This power supply is fan cooled. The air intake is at the front panel and the exhaust is at the rear panel. Upon installation allow cooling air to reach the front panel ventilation inlets. Allow minimum 10cm (4 Inch) of unrestricted air space at the front and the rear of the unit. The power supply should be used in an area that the ambient temperature does not exceed +50 C.
The Genesys series can be operated from a nominal 100V to 240V, single phase, 47~63Hz. The input voltage range and current required for each model is specified in Chapter 2. Ensure that under heavy load, the AC voltage supplied to the power supply does not fall below the specifications described in Chapter 2.
3.5 LOCATION, MOUNTING AND COOLING
3.6 AC SOURCE REQUIREMENTS
3.7 AC INPUT POWER CONNECTION
o
TM
Ensure that the screws used to attach the slides to the unit do not penetrate more than 6mm into the sides of the unit.
CAUTION
CAUTION
WARNING
Connection of this power supply to an AC power source should be made by an electrician or other qualified personnel.
There is a potential shock hazard if the power supply chassis (with cover in place) is not connected to an electrical safety ground via the safety ground in the AC input connector
Fig.3-1: Rack-mount slides assembly
#10-32x0.38"(max.)
screws
T
D
L
amb
d
a
-
I
14
3.7.1 AC Input Connector, 1500W models
3.7.2 AC Input Connector, 750W models
3.7.3 AC Input Cord
3.7.4 AC Input Wire Connection, 1500W models
TheAC input connector is a 3-Terminal wire clamp located on the rear panel: Phoenix Contact P/N: FRONT4-H-7.62/3
Use suitable wires and tightening torque as follows:
1. Wire diameter: 12AWG or 10AWG.
2. Tightening torque: 4.4-5.3Lb-inch. (0.5-0.6Nm).
An IEC connector is provided on the rear panel for connecting the unit to the AC power source with an AC cord. The IEC connector also provides the safety ground connection while the AC cord is plugged into an appropriate AC receptacle.
Refer to section 1.3.4 for details of the AC input cords recommended for the 750W and the 1500W models.
1.Stripthe outside insulation of the AC cable approx. 10cm. Trim the wires so that the ground wire is 10mm longer than the other wires. Strip 14mm at the end of each of the wires.
2.Unscrew the base of the strain relief from the helix-shaped body. Insert the base through the outside opening in the AC input cover and screw the locknut securely (11-14 Lb-inch.) into the base, from the inside.
3.Slide the helix-shaped body onto theAC cable. Insert the stripped wires through the strain relief base until the outer cable jacket is flush with the edge of the base. Tighten (16-18 Lb-inch.) the body to the base while holding the cable in place. Now the cable is securely fastened inside the
WARNING
The AC input cord is the disconnect device of the power supply. The plug must be readily identifiable and accessible to the user.The AC input cord must be no longer than 3m.
Fig.3-2: Stripped Wires installed in Strain Relief
WARNING
Some components inside the power supply are at AC voltage even when the On/Off switch is in the “Off” position. To avoid electric shock hazard, disconnect the line cord and load and wait two minutes
before removing cover.
Screw-on
Locknut
CAUTION
AC Input Wires No Conductor Pretreatment: Phoenix Contact clamping parts are designed so
that all kinds of copper conductors can be clamped without pretreatment. It is forbidden to solder the conductors. The solder tin yields and fractures under high pressure. The result is increased contact resistance and an excessive temperature rise. In addition, corrosion caused by pickling or fluxes has been observed on soldered conductor ends. Notch fractures at the transition point from the rigid to the flexible conductor area are also possible.
15
Fig.3-3: AC input cover and strain relief, 1500W models
4.Route the AC wires to the input connector terminals as required. To connect the wires, loosen the terminal screw, insert the stripped wire into the terminal and tighten the screw securely (4.4-5.3 Lb-inch.).
5.Route the wires inside the cover to prevent pinching. Fasten the cover to the unit using the M3x8 Flat Head screws are provided. Strain relief cover could be opened for inspection.
Refer to Fig.3-3 for details.
3.8 TURN-ON CHECKOUT PROCEDURE
3.8.1 General
3.8.2 Prior to Operation
The following procedure ensures that the power supply is operational and may be used as a basic incoming inspection check. Refer to Fig.4-1 and Fig.4-2 for the location of the controls indicated in the procedure.
1. Ensure that the power supply is configured to the default setting:
-AC On/Off switch at Off position.
-Dip switch : All positions at Down (”Off”) position.
-Sense connector : Configured to Local Sense as shown in Fig.3-4:
1 Remote (+) sense 2 Local (+) sense 3 Not connected 4 Local (-) sense 5 Remote (-) sense
-For units equipped with IEEE option, ensure that the IEEE_En switch is in Up (default) position (Refer to Fig.4-2, item 8 for location), if checkout is to be done in IEEE mode.
Fig.3-4: Sense connector default connection
Plug P/N: MC 1.5/5-ST-3.81
(Phoenix)
Removable cover. Remove only to inspect AC input wires connection. Reinstall cover
after inspection.
Assembled Strain Relief
M3x8
Flat Head screws
(2 places)
16
2. Connect the unit to an AC source as described in section 3.7.
3. Connect a DVM with appropriate cables for the rated voltage to the output terminals.
4. Turn the front panel AC power switch to On.
1. Turn on the output by pressing OUT pushbutton so the OUT LED illuminates.
2. Observe the power supply VOLTdisplay and rotatethe Voltage encoder. Ensure that the output voltage varies while the VOLT encoder is rotated. The minimum control range is from zero to the maximum rated output for the power supply model. Compare the DVM reading with the front panel VOLT display to verify the accuracy of the VOLT display. Ensure that the front panelVOLTLED is on.
3. Turn off the front panelAC power switch.
1. Ensure that the front panel AC power switch is at Offposition and the DVM connected to the output terminals shows zero voltage.
2. Connect a DC shunt across the output terminals. Ensure that the shunt and the wires' current ratings are higher than the power supply rating. Connect a DVM to the shunt.
3. Turn the front panel AC power switch to On position.
4. Turn on the output by pressing OUTpushbutton so the OUTLED illuminates.
5. Observe the power supply CURRENT display and rotate the CURRENT encoder. Ensure that the output current varies while the CURRENT encoder is rotated. The minimum control range is from zero to the maximum rated output for the power supply model. Compare the DVM reading with the front panel CURRENT display to verify the accuracy of the CURRENT display. Ensure that the front panel CURRENT LED is on.
6. Turn off the front panel AC power switch.
7. Remove the shunt from the power supply output terminals.
Refer to Section 5.3 for explanation of the OVP function prior to performing the procedure below.
1. Turn the front panel AC power switch to On position and turn on the output by pressing OUT pushbutton.
2. Using the VOLTencoder,adjust the output voltage to approx. 10% of the unit voltagerating.
3. Momentarily press
the OVP/UVL button so that the CURRENT display shows “OUP”. The
VOLTAGE display will show the last setting of the OVPlevel.
4. Rotate the VOLT encoder CCW to adjust the OVP setting to 50% of the unit voltage rating.
5. Waita few seconds until the VOLT display returns to show the output voltage.
6. Adjust the output voltage toward it’smaximum and check that the output voltage cannot be increased more than the OVP setting.
7. Adjust OVP limit to the maximum by repeating step 3 and rotating the VOLT encoder CW.
Refer to Section 5.4 for explanation of the UVL function prior to performing the procedure below.
1. Press the OVP/UVL button TWICE so that the CURRENT display shows "UUL". The VOLTAGE display will show the last setting of the UVL level.
2. Rotate the VOLT encoder to adjust the UVL level to approx. 10% of the unit voltage rating.
3. Waita few seconds until the VOLT display returns to show the output voltage.
4. Adjust the output voltage toward it’sminimum and check that the output voltage cannot be decreased below the UVL setting.
5. Adjust the UVLlimit to the minimum by repeating step1 and rotatingthe VOLTencoder CCW.
3.8.3 Constant Voltage Check
3.8.4 Constant Current Check
3.8.5 OVP Check
3.8.6 UVL Check
17
Refer to Section 5.5 for explanation of the FOLD function prior to performing the procedure below.
1. Ensure that the output voltage is set to approx. 10% of the unit rating.
2. Adjust the CURRENT encoder to set the current limit to approx. 10% of the unit rating.
3. Momentarily press the FOLD button. Ensure that the FOLD LED illuminates. The output voltage remains unchanged.
4. Short the output terminals momentarily (approx. 0.5 sec.). Ensure that the output voltage falls to zero, the VOLT display shows “Fb” and the ALARM LED blinks.
5. Press the FOLD button again to cancel the protection. The output voltage remains zero.
6. Press OUT button. Ensure that the output voltage returns to it’s last setting.
7. Turn the output off by pressing OUT button. Ensure that the VOLT display shows “OFF”.
1. Press and hold the REM/LOC button for approx. 3sec. The VOLT display will show the communication port address.
2. Using the VOLT adjust encoder, check that the address can be set within the range of 0 to 30.
1. Press and hold the REM/LOC button for approx. 3sec. The CURRENT display will show the communication port Baud Rate.
2. Using The CURRENT adjust encoder, check that the Baud Rate can be set to 1200, 2400, 4800, 9600 and 19200.
3.8.8 Address Setting
3.8.9 Baud Rate Setting
3.9 CONNECTING THE LOAD
Shorting the output may expose the user to hazardous voltages. Observe proper safety procedures.
Turn off the AC input power before making or changing any rear panel connection. Ensure that all connections are securely tightened before applying power.There is a potential shock hazard when using a power supply with a rated output greater than 40V.
WARNING
WARNING
3.9.1 Load Wiring
3.9.2 Current Carrying Capacity
at least
The following considerations should be made to select wiring for connecting the load to the power supply:
* Current carrying capacity of the wire (refer to 3.9.2) * Insulation rating of the wire should be at least equivalent to the maximum output voltage of
the power supply. * Maximum wire length and voltage drop (refer to 3.9.2) * Noise and impedance effects of the load wiring (refer to 3.9.4).
Twofactors must be considered when selecting the wire size:
1. Wires should be heavy enough not to overheat while carrying the power supply load current at the rated load, or the current that would flow in the event the load wires were shorted, whichever is greater.
3.8.7 Foldback Check
18
CAUTION
When local sensing, a short from +LS or +S to -V or -S or -LS, will cause damage to the power supply. Reversing the sense wires might cause damage to the power supply in local and remote sensing. (Do not connect -S to +V or +S to -V.)
Table 3-2: Maximum wire length for 1V drop on lead (in feet)
Table 3-3: Maximum wire length for 1V drop on lead (in meters)
2. Wire size should be selected to enable voltage drop per lead to be less than 1.0V at the rated current. Although units will compensate for up to 5V in each load wire, it is recommended to minimize the voltage drop (1V typical maximum) to prevent excessive output power consum­ption from the power supply and poor dynamic response to load changes. Please refer to Tables 3-2 and 3-3 for maximum wire length to limit voltagedrop in American and European dimensions respectively.
Wire size
AWG
14 12 10
8 6 4 2 0
2.526
1.589
0.9994
0.6285
0.3953
0.2486
0.1564
0.0983
5A
80 120 200 320 500 800
1200 2000
10A
40
60 100 160 250 400 600
1000
20A
20 30 50
80 125 200 300 500
50A
8 12 20 32 50 80
125 200
150A
2
3.4 6
10 16 26 40 68
Resistivity
Ohm/1000ft
Maximum length in Feet to limit
voltage drop to 1V or less
Cross sect.
area
(mm )
2
2.5 4 6
10 16 25 35
8.21
5.09
3.39
1.95
1.24
0.795
0.565
5A
24.0
39.2
59.0
102.6
160.0
250.0
354.0
10A
12.0
18.6
29.4
51.2
80.0
125.0
177.0
20A
6.0
9.8
14.8
25.6
40.0
62.0
88.0
50A
2.4
4.0
5.8
10.2
16.0
25.2
35.4
150A
0.8
1.4
2.0
3.4
5.4
8.4
11.8
Resistivity
Ohm/Km
Maximum length in meters to limit
voltage drop to 1V or less
For currents not shown in Table 3-2 and 3-3, use the formula:
Maximum length=1000/(current x resistivity)
where current is expressed in Amperes and resistivity in ohms/km or ohms/1000ft.
3.9.3 Wire termination
The wires should be properly terminated with terminals securely attached. DO NOT use unter­minated wires for load connection at the power supply.
19
3.9.4 Noise and Impedance Effects
3.9.5 Inductive loads
3.9.6 Making the load connections
To minimize the noise pickup or radiation, the load wires and remote sense wires should be twisted- pairs to the shortest possible length. Shielding of sense leads may be necessary in high noise environments. Where shielding is used, connect the shield to the chassis via a rear panel Ground screw. Even if noise is not a concern, the load and remote sense wires should be twisted-pairs to reduce coupling, which might impact the stability of power supply. The sense leads should be separated from the power leads. Twisting the load wires reduces the parasitic inductance of the cable which could produce high frequency voltage spikes at the load and the output of power supply, because of current variation in the load itself. The impedance introduced between the power supply output and the load could make the ripple and noise at the load worse than the noise at the power supply rear panel output.Additional filtering with bypass capacitors at the load terminals may be required to bypass the high frequency load current.
Inductive loads can produce voltage spikes that may be harmful to the power supply.A diode should be connected across the output. The diode voltage and current rating should be greater than the power supply maximum output voltage and current rating. Connect the cathode to the positive output and the anode to the negative output of the power supply. Where positive load transients such as back EMF from a motor may occur, connect a surge suppressor across the output to protect the power supply. The breakdown voltage rating of the suppressor must be approximately 10% higher than the maximum output voltage of the power supply.
CAUTION
Ensure that the load wiring mounting hardware does not short the output terminals. Heavy connecting cables must have some form of strain relief to prevent loosening the connections or bending the bus-bars.
6V to 60V Models
Refer to Fig.3-5 for connection of the load wires to the power supply bus-bars and to Fig.3-6 for mounting the bus-bars enclosure to the chassis.
WARNING
Hazardous voltages may exist at the outputs and the load connections when using a power supply with a rated output greater than 40V. To protect personnel against accidental contact with hazardous voltages, ensure that the load and its connections have no accessible live parts. Ensure that the load wiring insulation rating is greater than or equal to the maximum output voltage of the power supply.
20
WARNING
Hazardous voltages exist at the outputs and the load connections. To protect personnel against accidental contact with hazardous voltages, ensure that the load and its connections have no accessible live parts. Ensure that the load wiring insulation rating is greater than or equal to the maximum output voltage of the power supply.
80V to 600V Models
Output Load Wires No Conductor Pretreatment: Phoenix Contact clamping parts are designed
so that all kinds of copper conductors can be clamped without pretreatment. It is forbidden to solder the conductors. The solder tin yields and fractures under high pressure. The result is increased contact resistance and an excessive temperature rise. In addition, corrosion caused by pickling or fluxes has been observed on soldered conductor ends. Notch fractures at the transition point from the rigid to the flexible conductor area are also possible.
CAUTION
Fig. 3-5: Load wires connection , 6V to 60V models.
M8x15 screw (2 places)
Hex Nut (2 places)
Flat washer (2 places)
Spring washer (2 places)
Wire terminal lug (2 places)
Flat washer
(2 places)
Screws tightening torque: 104-118 Lb-inch.
Fig. 3-6 Bus-bars
cover 6V to 50V
Fig. 3-7 Bus-bars
enclosure 60V
(Refer to Fig.3-8, 3-9 for installation instructions.)
Fix the bus-bars enclosure top cover using the screws marked “A”. Tighten the
screws after fixing.
Enclosure top cover
Enclosure
bottom cover
Fix the bus-bars enclosure top cover using the screws marked “A”. Loosen screw “B” to release the shutter. Insert load wires through enclosure bottom cover
opening and connect load wires.
Assemble the enclosure bottom
cover by using screw C. Tighten
screws “B” after sliding down the
shutter.
A
A
A
B
A
C
21
The 80V to 600V models have a four terminal wire clamp output connector: Phoenix Contact P/N: FRONT4-H-7.62/4. The two left terminals are the positive outputs and the other two right terminals are the negative outputs. Max. 30A per terminal. The connector requirements are as follows:
1. Wires: AWG18 to AWG10.
2. Tightening torque: 4.4-5.3Lb-inch. (0.5-0.6Nm).
Follow the below instructions for connection of the load wires to the power supply:
1. Strip approx.10mm at the end of each of the load wires.
2. Loosen the connector terminal screws.
3. Loosen screw “B” from enclosure bottom cover to release the shutter.
4. Insert stripped wires into enclosure bottom cover opening and then to the terminals, tighten the terminals screws securely (see fig.3-8)
5. Loosen the two chassis screws marked “A” halfway.
6. Assemble the enclosure top cover to the chassis and tighten screws “A” (tightening torque:
4.8 - 5.3 Lb-inch).
7. Assemble the enclosure bottom cover to it’s place, as shown in Fig.3-9,using screw “C”, (tightening torque 4.8-5.3 Lb-inch).
8. Slide down the shutter to secure load wires in place, and tighten screw “B”.
Fig.3-9: Enclosure assembly
B
Fig.3-8: Load wires connection to the output connector
Load wires
Negative (-)
Output/Return
Positive output (+)
Shutter
Enclosure bottom cover
Enclosure top cover
C
B
A
A
22
3.9.7 Connecting single loads, local sensing (default).
Fig.3-10 shows recommended load and sensing connections for a single load. The local sense lines
shown are default connections at the rear panel J2 sense connector. Local sensing is suitable for
applications where load regulation is less critical.
-
-
Rem.sense
Local sense
Local sense
Rem.sense
+ +
Load lines, twisted pair, shortest length possible.
+V
-V
Load
+
-
Power Supply
Fig.3-10: Single load connection, local sensing
3.9.8 Connecting single loads, remote sensing
Fig.3-11 shows recommended remote sensing connection for single loads. Remote sensing is used when, in Constant Voltage mode, the load regulation is important at the load terminals. Use twisted or shielded wires to minimize noise pick-up. If shielded wires are used, the shield should be connected to the ground at one point, either at the power supply chassis or the load ground. The optimal point for the shield ground should be determined by experimentation.
-
-
Rem.sense
Local sense
Local sense Rem.sense
+ +
Sense lines. Twisted pair or shielded.
+V
-V
Load
+
-
Power Supply
Load lines. Twisted pair
shortest length possible.
Fig.3-11: Remote sensing, single load
3.9.9 Connecting multiple loads, radial distribution method
Fig.3-12 shows multiple loads connected to one supply. Each load should be connected to the power supply’s output terminals using separate pairs of wires. It is recommended that each pair of wires will be as short as possible and twisted or shielded to minimize noise pick-up and radiation. The sense wires should be connected to the power supply output terminals or to the load with the most critical load regulation requirement.
23
-
-
Rem.sense
Local sense
Local sense Rem.sense
+ +
Load lines, twisted pair, shortest length possible.
+V
-V
Load#1
+
-
Load#3
+
-
Load#2
+
-
Power Supply
Fig.3-12: Multiple loads connection, radial distribution, local sense
-
-
Rem.sense
Local sense
Local sense
Rem.sense
+ +
Distribution terminal
+V
+V
-V
-V
Load#1
+
-
Load#3
+
-
Load#2
+
-
Power Supply
Fig.3-13: Multiple loads connection with distribution terminal
3.9.10 Multiple load connection with distribution terminals
If remotely located output distribution terminals are used, the power supply output terminals should be connected to the distribution terminals by a pair of twisted and/or shielded wires. Each load should be separately connected to the remote distribution terminals (see Fig.3-13). If remote sensing is required, the sensing wires should be connected to the distribution terminals or at the most critical load.
3.9.11Grounding outputs
Either the positive or negative output terminals can be grounded. To avoid noise problems caused by common-mode current flowing from the load to ground, it is recommended to ground the output terminal as close as possible to the power supply chassis ground. Always use two wires to connect the load to the power supply regardless of how the system is grounded.
WARNING
Models up to 60VDC Rated Output shall not float outputs more than +/-60VDC above/below chassis ground. Models > 60VDC Rated Output shall not float outputs more than +/-600VDC above/below chassis ground.
24
WARNING
OUTPUT TERMINAL GROUNDING
There is a potential shock hazard at the RS232/485 and the IEEE ports when using power supplies with rated or combined voltage greater than 400V with the Positive Output of the power supplies is grounded. Do not connect the Positive Output to ground when using the RS232/485 or IEEE under the above conditions.
3.10 LOCAL AND REMOTE SENSING
The rear panel J2 sense connector is used to configure the power supply for local or remote sensing of the output voltage. Refer to Fig.3-14 for sense connector location.
WARNING
There is a potential shock hazard at the sense connector when using a power supply with a rated output voltage greater than 40V. Local sense and remote sense wires should have a minimum insulation rating equivalent or greater than the maximum output voltage of the power supply. Ensure that the connections at the load end are shielded to prevent accidentalcontact with hazardous voltages.
3.10.2 Local sensing
The power supply is shipped with the rear panel J2 sense connector wired for local sensing of the output voltage. See Table 3-4 for J2 terminals assignment. With local sensing , the output voltage regulation is made at the output terminals. This method does not compensate for voltage drop on the load wires, therefore it is recommended only for low load current applications or where the load regulation is less critical.
3.10.1 Sense wiring
Table 3-4: J2 terminals
Fig.3-14: Sense connector location
Function Remote positive sense (+S). Local positive sense. Connected internally to the positive output terminal (+LS). Not connected (NC). Local negative sense. Connected internally to the negative output terminal (-LS). Remote negative sense (-S).
Terminal J2-1 J2-2 J2-3 J2-4 J2-5
+S +LS
NC
-LS
-S
1
2
3
4
5
6
7
8
9
ON
OFF
SW1
J2
25
WARNING
There is a potential shock hazard at the sense point when using power supply with a rated output voltage greater than 40V. Ensure that the connections at the load end are shielded to prevent accidental contact with hazardous voltages.
CAUTION
When using shielded sense wires, ground the shield in one place only. The location can be the power supply chassis or one of the output terminals.
3.10.3 Remote sensing
Use remote sense where the load regulation at the load end is critical. In remote sense, the power supply will compensate for voltage drop on the load wires. Refer to the power supply specifications
for the maximum voltage drop on load wires. The voltage drop is subtracted from the total voltage available at the output. Follow the instructions below to configure the power supply for remote sensing:
1. Ensure that the AC On/Off is in the Off position.
2. Remove the local sense jumpers from J2.
3. Connect the negative sense lead to terminal J2-5 (-S) and the positive sense lead to terminal J2-1(+S) of the J2 mating connector. Ensure that the J2 mating connector is plugged securely
into the rear panel sense connector,J2.
4. Turn On the power supply.
1. If the power supply is operating in remote sense and either the positive or negative load wire is not connected, an internal protection circuit will activate and shut down the power supply. To resume operation, turn the AC On/Off to the Off position, connect the open load wire, and turn On the power supply.
2. If the power supply is operated without the remote sense lines or local sense jumpers, it will
continue to work, but the output voltageregulation will be degraded. Also, the OVP circuit may activate and shut down the power supply.
- J2 connector type: MC 1.5/5-G-3.81, Phoenix.
- Plug type: MC 1.5/5-ST-3.81, Phoenix.
- Wire AWG; 28 up to 16.
- Strippinglength: 7mm.
- Tightening torque:1.95-2.21Lb-Inch. (
To ensure safe transportation of the instrument, contact the Lambda sales or service facility near you for Return Authorization and shipping information. Please attach a tag to the power supply describing the problem and specifying the owner, model number and serial number of the power supply. Refer to Warranty Information for further instructions.
Notes:
3.10.4 J2 sense connector technical information
3.11 REPACKAGING FOR SHIPMENT
0.22- 0.25Nm)
26
CHAPTER 4 FRONT AND REAR PANEL CONTROLS
AND CONNECTORS
4.1 INTRODUCTION
4.2 FRONT PANEL CONTROLS AND INDICATORS
The Genesys Power Supply series has a full set of controls, indicators and connectors that allow the user to easily setup and operate the unit. Before starting to operate the unit, please read the following sections for explanation of the functions of the controls and connectors terminals.
- Section 4.2: Front panel controls and indicators.
- Section 4.3: Rear panel controls and connectors.
See Fig.4-1 to review the controls, indicators and meters located on the power supply front panel.
TM
Fig.4-1: Front panel controls and indicators
1
Number
Control/Indicator
Description
Section
High resolution rotary encoder for adjusting the Output Voltage. Also adjusts the OVP/UVL levels and selects theAddress.
VOLTAGE control
VOLTAGE indicator
Green LED , lights for Constant-Voltage mode
operation.
2
3
VOLTAGE display
4 digit, 7-segment LED display. Normally displays the output voltage. When the PREV button is pressed, the display indicates the programmed setting of the output voltage. When the OVP/UVL button is pressed, the Voltage display indicates the OVP/UVL setting.
Table 4-1: Front Panel controls and indicators
VOLTAGE
ALARM
FINE
PREV/
OVP UVL
FOLD
REM/LOC
OUT
DC AMPS
CURRENT
'
'
'
'
'
'
'
'
DC VOLTS
POWER
1
14
17
18
19
2
15
16
3
13
10
4
11
5
12
9
6
7
8
5.2.1
5.3.1
5.4.1
7.2.2
27
4
Number Control/Indicator Description
Section
4 digit, 7-segment LED display. Normally displays the output current. When the PREV button is pressed, the display indicates the programmed setting of output current.
CURRENT display
6
CURRENT control
High resolution rotary encoder for adjusting the Output Current. Also selects the Baud-Rate of the communication port.
Table 4-1: Front Panel controls and indicators
5
CURRENT indicator
Green LED, lights for Constant-Current mode operation.
Main function
Auxiliary function
: Output ON/OFF control. Press OUT to set the output On or Off. Press to reset and turn On the output after OVP or FOLD alarm events have occurred.
: Selects between "Safe-Start" and "Auto-Restart" modes. Press and hold OUT button to toggle between "Safe-Start" and "Auto-Restart".The VOLT display will cycle between "SAF" and "AU7”. Releasing the OUT button while one of the modes is displayed, selects that mode.
OUT button
OUT indicator
Green LED, lights when Foldback protection is On.
Over VoltageProtection and Under Voltage limit setting.
- Press once to set OVPusing VOLTAGE encoder ( the
current display shows “OUP” )
- Press again to set the UVL using VOLTAGE encoder
( the current display shows “UUL” ).
Main function
Auxiliary function
: Go to local. Press REM/LOC to put the unit into Local (REM/LOC button is disabled at Local Lockout mode).
: Address and Baud Rate setting. Press and hold REM/LOC for 3sec. to set the Address with the VOLTAGE encoder and the Baud Rate with the CURRENT encoder.
Green LED, lights when the unit is in Remote mode.
Foldback protection control.
- Press FOLD to set Foldback protection to On.
- To release Foldback alarm event, press OUT to
enable the output and re-arm the protection.
- Press FOLD again to cancel the Foldback protection.
Main function
Auxiliary function
: Press PREV to display the output voltage and current limit setting. For 5 sec. the display will show the setting and then it will return to show the actual output voltage and current.
: Front Panel Lock. Press and hold PREV button to toggle between “Locked front panel” and “Unlocked front panel”. The display will cycle between “LFP” and “UFP”. Releasing the PREV button while one of the modes is displayed, selectsthat mode.
REM/LOC button
REM/LOC indicator
FOLD button
FOLD indicator
OVP/UVL button
PREV/ button
Green LED, lights when the DC output is enabled.
7
8
9
10
11
12
13
14
5.2.2
7.2.4
5.6
7.2.5
5.11
7.2.2
7.2.4
5.5
5.3
5.4
5.17
28
Table 4-1: Front Panel controls and indicators
4.3 REAR PANEL
See Fig.4-2 to review the connections and controls located on the power supply rear panel. Refer to Table 4-2 for explanations about the rear panel connections and controls.
Fig.4-2: Rear panel connections and controls
1
Number
Item
Description
Section
AC input connector
2
DC output
Table 4-2: Rear panel connections and controls
3
Wire clamp connector for 1500W units. IEC connector for 750W units.
3.7.1
3.7.2
Bus-bars for 6V to 60V models. Wire clamp connector for 80V to 600V models.
3.9.6
RJ-45 type connector, use for connecting power supplies to RS232 or RS485 port of computer for remote control purposes. When using several power supplies in a power system, the first unit Remote-In is connected to the computer and the remaining units are chained, Remote-In to Remote-Out.
Remote-In connector
7.3
7.4
J2
AC INPUT
ON
OFF
OUT
IN
J3
J1
SW1
10
5
7
3
8
9
4
6
1
2
750W
1500W
6~60V
Models
80~600V
Models
16
Number Control/Indicator Description
Section
FINE button
18
ALARM indicator
17
FINE indicator
AC Power switch
19
Voltage and Current Fine/Coarse adjustment control. Operates as a toggle switch. In Fine mode, the VOLTAGE and CURRENT encoders operate with high resolution and in Coarse mode with lower resolution (approx. 6 turns).
: Advanced Parallel Operation
Mode setting.
Auxiliary function
Green LED, lights when the unit is in Fine mode. Red LED, blinks in case of fault detection. OVP, OTP
Foldback, Enable and AC fail detection will cause the ALARM LED to blink.
AC On/Off control.
Green LED, lights when PREV button is pressed.
PREV indicator
15
5.15.2
29
Table 4-2: Rear panel connections and controls
RJ-45 type connector, used for chaining power supplies to form a serial communication bus.
Connector for remote analog interface. Includes output voltage and current limit programming and monitoring signals, Shut-off control (electrical signal), Enable/Disable control (dry-contact), power supply ok (PS_OK) signal and operation mode (CV/CC) signal.
Nine position DIP switch for selecting remote programming and monitoring modes for Output Voltage, Current Limit and other control functions.
Blank sub-plate for standard units. Isolated Remote Analog programming connector for units equipped with Isolated Analog control option. IEEE connector for units equipped with IEEE programming option (shown).
M4x8 screw for chassis ground connection.
Two position DIP switch for selecting IEEE mode or RS232/485 mode when IEEE option is installed.
Number
Item
Description
Section
4.5
Connector for making remote sensing connections to the load for regulation of the load voltage and compensation of load wire drop.
4.4
4.4.1
4.4.2
3.8.2
3.10.2
3.10.3
4
5
6
7
8
10
9
Remote Out connector
Programming and Monitoring connector
SW1 Setup switch
Remote sense connector
Blank Sub-plate
Ground screw
IEEE switch
7.3
7.4
4.4 REAR PANEL SW1 SETUP SWITCH
The SW1 Setup switch (see Fig.4-3) is a 9-position DIP switch that allows the user to choose the following:
- Internal or remote programming for Output Voltage and Current Limit.
- Remote voltage or resistive programming of Output Voltage and Output Current limit.
- Select range of remote voltage and resistive programming.
- Select range of Output Voltage and Output Current monitoring.
- Select the Remote Shut-Off control logic.
- Select between RS232 or RS485 communication interface.
- Enable or disable the rear panel Enable/Disable control (dry contact).
Fig.4-3: SW1 setup DIP switch
1
2
3
4
5
6
7
8
9
30
31
4.5 REAR PANEL J1 PROGRAMMING AND MONITORING CONNECTOR
The J1 Programming and Monitoring connector is a DB25 subminiature connector located on the power supply rear panel. Refer to Table 4-4 for description of the connector functions. The power supply default configuration is Local operation which does not require connections to J1. For remote operation using J1 signals use the plug provided with power supply or equivalent type. It is essential to use plastic body plug to conform with Safety Agency requirements. If a shield is required for J1 wires, connect the shield to a power supply chassis ground screw.
- J1 connector type: AMP, P/N: 5747461-3
- J1 plug description: AMP, P/N: 745211-7
- Wire dimension range: AWG26-22
- Extraction tool: AMP, 91232-1 or equivalent.
- Manual Pistol grip tool: Handle:AMP, P/N: 58074-1 Head:AMP, P/N: 58063-2
Before making any connection, turn the AC On/Off switch to the Off position and wait until the front panel display has turned Off.
4.5.1 Making J1 connections
To prevent ground loops and to maintain the isolation of the power supply when programming from J1, use an ungrounded programming source.
CAUTION
Terminals 12, 22 and 23 of J1 are connected internally to the negative sense(-S) potential of the power supply. Do not attempt to bias any of these terminals relative to the negative sense. Use the Isolated Programming interface option to allow control from a programming source at a different potential relative to the power supply negative
CAUTION
There is a potential shock hazard at the output when using a power supply with rated output greater than 40V. Use wires with minimum insulation rating equivalent to the maximum output voltage of the power supply.
WARNING
32
Fig.4-4: J1 connector terminals and functions
Table 4-4: J1 connector terminals and functions
Enable /Disable the power supply output by dry-contact (short/open) with ENA_OUT.
Isolated Interface Common. Return for the SO control, PS_OK signal and communication interface RS232/485 IEEE optional.
No Connection
Input for selecting between Local or Remote analog programming of output voltage and output current.
Input for remote analog voltage/resistance programming of the Output Voltage.
Input for remote analog voltage/resistance programming of the Output Current.
Output for monitoring the power supply Output Voltage.
Output for Constant-Voltage / Constant-Current mode indication.
Enable/Disable the power supply output by dry-contact (short/open) with ENA_IN.
Input for Shut-Off control of the power supply output.
Output for indication of the power supply status.
No Connection.
Output for indicating if the unit is in Local or Remote analog programming mode.
Output for monitoring the power supply Output Current.
Output for current balance in parallel operation.
Control Common. Return for VMON, IMON, CV/CC, LOC/REM.
(-S).
Connected internally to the negative sense potential
Return for VPGM input. Connected internally to the " -S".
Return for IPGM input. Connected internally to the " -S".
J1-1
J1-2 J1-3
J1-4~7
J1-8
J1-17~20
J1-22
J1-21
J1-23
J1-24
J1-25
J1-16
J1-15
J1-14
J1-13
J1-9
J1-10
J1-11
J1-12
Sec. 5.8
Sec. 5.7, 5.10
Sec. 6.1~6.4
Sec. 6.1~6.4
Sec. 6.6
Sec. 6.2
Sec. 5.9
Sec. 5.8
Sec. 5.7
Sec. 5.10
Sec. 6.3
Sec. 6.1, 6.4,
6.5
Sec. 6.1, 6.4,
6.5
Sec. 6.6
Sec. 5.15
ENA_IN
IF_COM
N/C
LOC/REM SELECT
VPGM
IPGM
VMON
COM
CV/CC
ENA_OUT
SO
PS_OK
N/C
LOC/REM SIGNAL
VPGM_RTN
IPGM_RTN
IMON
P
J1
contact
Signal name
Function
Reference
14
15
16
17
18
19
20
21
22
23
24
25
1
2
3
4
5
6
7
8
10
11
12
13
9
Same ground
as P/S negative
sense (-S)
Isolated from
PS outputs,
same ground
as RS232/485
IMON
IPGM_RTN
VPGM_RTN
LOC/REM SIGNAL
IF_COM IF_COM ENA_IN
VMON
COM
CV/CC
IPGM VPGM
LOC/ REM
P
ENA_OUT SO PS_OK
33
CHAPTER 5 LOCAL OPERATION
5.1 INTRODUCTION
5.2 STANDARD OPERATION
This Chapter describes the operating modes that are not involved in programming and monitoring the power supply via its serial communication port (RS232/RS485) or by remote analog signals. Ensure that the REM/LOC LED on the front panel is Off, indicating Local mode. If the REM/LOC LED is On, press the front panel REM/LOC button to change the operating mode to local.
- For information regarding remote analog programming refer to Chapter 6.
- For information regarding usage of the serial communication port refer to Chapter 7.
The power supply has two basic operating modes: Constant Voltage Mode and Constant Current Mode. The mode in which the power supply operates at any given time depends on the output voltage setting, output current limit setting and the load resistance.
1. In constant voltage mode, the power supply regulates the output voltageat the selected value, while the load current varies as required by the load.
2. While the power supply operates in constantvoltage mode, the VOLTAGE LED on the front panel
illuminates.
3.Adjustment of the output voltage can be made when the power supply output is enabled (Output On) or disabled (Output Off).When the output is enabled, simply rotate the VOLTAGE encoder knob to program the output voltage. When the output is disabled, press the PREV button and then rotate the VOLTAGE encoder knob. The VOLTAGE meter will show the programmed output voltage for 5 seconds after the adjustment has been completed.Then the VOLTAGE meter will display "OFF".
4.Adjustment resolution can be set to coarse or fine resolution.
Press FINE button to select between the lower and higher resolution. The FINE LED turns On when the resolution is set to FINE.
5.2.1 Constant Voltage Mode
If after completing the adjustment, the display shows a different value than the setting, the power supply may be at current limit. Check the load condition and the power supply current limit setting.
The maximum and minimum setting values of the output voltage are limited by the Over Volt
age protection and Under Voltage limit setting.
Refer to Sec.5.3 and 5.4 for more details.
NOTE
NOTE
5.2.2 Constant Current Operation
1. In constant current mode, the power supply regulates the output current at the selected value, while the voltage varies with the load requirement.
2. While the power supply is operating in constant current mode, the CURRENTLED on the front
panel illuminates.
3.Adjustment of the output current limit can be made when the power supply output is enabled
(Output On) or disabled (Output Off).
- Disabled output (Off): Press PREV button and then rotate the Current encoder knob. The CURRENT meter will show the programmed current limit for 5 seconds after the adjustment has been completed. Then the VOLTAGE meter will display "OFF".
34
- Enabled output, power supply in Constant Voltage mode: Press the PREV button and then rotate the CURRENT encoder knob. The CURRENT meter will show the programmed current limit for 5 seconds after the adjustment has been completed, and then will return to show the actual load current.
- Enabled output, power supply in Constant Current mode: Rotate the CURRENT encoder knob to adjust the current limit.
4. Adjustment resolution can be set to Coarse or Fine adjustment. Press the FINE button to select between the Coarse and Fine resolution. The FINE LED turns On when the resolution is set to FINE.
If the power supply operates in Constant Voltage mode, while the load current is increased to greater than the current limit setting, the power supply will automatically switch to Constant Current mode. If the load is decreased to less than the current limit setting, the power supply will automatically switch back to Constant Voltage mode.
The OVP circuit protects the load in the event of a remote or local programming error or a power supply failure. The protection circuit monitors the voltage at the power supply sense points and thus providing the protection level at the load. Upon detection of an Over Voltage condition, the power supply output will shut down.
The OVP can be set when the power supply output is Enabled (On) or Disabled (Off). To set the OVP level, press the OVP/UVL button, so that the CURRENT meter shows "OUP".
The VOLTAGE meter shows the OVP setting level. Rotate the VOLTAGE encoder knob to adjust the OVP level. The display will show "OUP" and the setting value for 5 seconds after the adjustment has been completed and then will return to it's previous state.
The minimum setting level is approx. 105% of the set output voltage, or the value in Table 7-6, whichever is higher.The maximum setting level is shown in Table5-1.
5.2.3 Automatic Crossover
5.3.1 Setting the OVP level
5.3 OVER VOLTAGE PROTECTION (OVP)
Table 5-1: Maximum OVP setting levels
5.3.2 Activated OVP protection indications
5.3.3 Resetting the OVP circuit
When the OVP is activated the power supply output
shuts down. The VOLTAGE display shows
"OUP" and the ALARM LED blinks.
To reset the OVP circuit afterit activates:
1. Reduce the power supply Output Voltage setting below the OVP set level.
2. Ensure that the load and the sense wiring is connected properly.
3. There are four methods to reset the OVPcircuit.
3.1 Press OUT button.
3.2 Turn the power supply Off using theAC On/Off switch, wait until the front panel display turns
Off, then turn the power supply On using theAC On/Off switch.
3.3 Turn the power supply output Offand then On using the SO control (refer to sect.5.7). In this
method the power supply should be set to Auto-Restart mode.
3.4 Send OUT1 command via the RS232/485 communication port.
60V
80V 100V 150V 300V 600V
66.0V
88.0V
110.0V
165.0V
330.0V
660.0V
Model
Max. OVP
6V 8V
12.5V 20V 30V 40V 50V
7.5V
10.0V
15.0V
24.0V
36.0V
44.0V
57.0V
Model
Max. OVP
To preview the OVP setting, press OVP/UVL pushbutton so that the CURRENT display will show "OUP". At this time, the VOLTAGE display will show the OVP setting. After 5 seconds, the display will return to it's previous state.
35
5.4 UNDER VOLTAGE LIMIT (UVL)
5.5 FOLDBACK PROTECTION
5.6 OUTPUT ON/OFF CONTROL
5.7 OUTPUT SHUT-OFF (SO) CONTROL VIA REAR PANEL J1 CONNECTOR
The UVL prevents adjustment of the output voltage below a certain limit.The combination of UVL and OVP functions, allow the user to create a protection window for sensitive load circuitry.
Setting the UVL can be made when the power supply output is Enabled (On) or Disabled (Off). To set the UVL level, press the OVP/UVL button TWICE, so that the CURRENT meter shows “UUL”. The VOLTAGE meter shows the UVL setting level. Rotate the VOLTAGE encoder knob to adjust the UVL level. The display will show “UUL” and the setting value for 5 seconds after the adjustment has been completed and then will return to it’s previous state. UVL setting values are limited at the maximum level to approximately 95% of the Output Voltage setting. Attempting to adjust the UVL above this limit will result in no response to the adjustment attempt. The minimum UVL setting is zero.
5.4.1 Setting the UVL level
Foldback protection will shut down the power supply output if the load current exceeds the current limit setting level. This protection is useful when the load circuitry is sensitive to an over current condition.
To arm the Foldback protection, the FOLD button should be pressed so that the FOLD LED illuminates. In this condition, transition from Constant Voltage to Constant Current mode will activate the Foldback protection. Activation of the Foldback protection disables the power supply output, causes the ALARM LED to blink and display " Fb" on the VOLTAGE meter.
There are four methods to reset an activated Foldback protection.
1. Press the OUT button. The power supply output is enabled and the Output Voltage and current will return to their last setting. In this method, the Foldback protection remains armed, therefore if the load current is higher than the current limit setting, the Foldback protection will be activated again.
2. Press the FOLD button to cancel the Foldback protection. The power supply output will be disabled
and the VOLTAGE display will show “OFF”. Press the OUTbutton to enable the power supply output.
3. Turn the power supply output Off and then On using the SO control (refer to sect. 5.7). In this method the foldback protection remains armed, therefore if the load current is higher than the current limit setting the Foldback protection will be activated.
4. Turn the power supply Offusing the AC On/Off switch, wait until the front panel display turns Off, then turn the unit back ON again. The power supply output is enabled and the Output Voltage and Current will return to their last setting. In this method, the Foldback protection remains armed, therefore if the load current is higher than the current limit setting, the Foldback protection will be activated again.
The Output On/Off enables or disables the power supply output. Use this function to make adjustments to either the power supply or the load without shutting off the AC power. The Output On/Off can be activated from the front panel using the OUT button or from the rear panel J1 connector.The OUT button can be pressed at any time to enable or disable the power supply output. When the output is disabled, the output voltage and current fall to zero and the VOLTAGE display shows “OFF”.
Contacts 2,3 and 15 of J1 (Fig.4-2, Item 5) serve as Output Shut-Off (SO) terminals. The SO terminals
accept a 2.5V to 15V signal or Open-Short contact to disable or enable the power supply output. The SO function will be activated only when a transition from On to Off is detected after applying AC power
to unit. (Thus , inAuto-Restart mode, the output will be enabled after applying AC power, even if SO is in Off level.). After On to Off transition is detected, the SO will enable or disable the power supply output according to the signal level or the short/open applied to J1.This function is useful for connecting power supplies in a “Daisy-chain” (refer to section 5.16). The SO control can be used also to reset the OVP and Fold Protection. Refer to sect. 5.3 and 5.5 for details.
5.5.1 Setting the Foldback protection
5.5.2 Resetting activated Foldback protection
36
When the unit is shut-off by J1 signal, the VOLTAGE display will show “SO” to indicate the unit state. J1 contact 15 is the SO signal input and contacts 2 and 3, IF_COM, are the signal return (connected internally). Contacts 2,3 and 15 are optically isolated from the power supply output. The SO control logic can be selected by the rear panel SW1 Setup switch. Refer to Table 5-2 for SW1 setting and SO control logic.
Table 5-2: SO logic selection
SW1-5 setting
Down (default)
Up
SO signal level J1-2(3), 15 2-15V or Open 0-0.6V or Short 2-15V or Open 0-0.6V or Short
Power supply output On Off Off On
Display
Voltage/Current “SO” “SO” Voltage/Current
5.8 ENABLE/DISABLE CONTROL VIA REAR PANEL J1 CONNECTOR
Contacts 1 and 14 of J1 (Fig.4-2, Item 5) serve as Output Enable/Disable terminals by switch or relay. This function is enabled or disabled by the SW1 Setup switch position 9. Refer to Table 5-3 for Enable/Disable function and SW1 setting.
Table 5-3: Enable/Disable function and SW1 setting
SW1-9 setting
Down (Default)
Enable/Disable inputs
Open or Short
Open Short
Power supply output
On Off On
Display
Voltage/Current
“ENA”
Voltage/Current
ALARM LED
Off
Blinking
Off
Up
5.9 CV/CC SIGNAL
5.10 PS_OK SIGNAL
CV/CC signal indicates the operating mode of the power supply, Constant Voltage or Constant Current. CV/CC signal is an open collector output with a 30V parallel zener, at J1-13, referenced to the COM potential at J1-12 (connected internally to the negative sense potential). When the power supply operates in Constant Voltage mode, CV/CC output is open. When the power supply operates in Constant Current mode, CV/CC signal output is low(0-0.6), with maximum 10mA sink current.
PS_OK signal indicates fault condition in the power supply. PS_OK is a TTL signal output at J1-16, referenced to IF_COM at J1-2,3 (Isolated Interface Common)). When a fault condition occurs, PS_OK level is low, with maximum sink current of 1mA, when no fault condition occurs, PS_OK level is high with maximum source current of 2mA. The following faults will set the PS_OK to Fault state:
Safe Startmode-If the Enable/Disable fault condition clears when units in safe start mode
recovery is by pressing OUT button or by sending a ‘OUT 1’ serial command.
Auto Restart mode-The output will return back ON automatically when the Enable/Disable
fault conditions clears.
To prevent possible damage to the unit, do not connect any of the Enable/Disable inputs to the positive or negative output potential.
CAUTION
Do not connect CV/CC signal to a voltage source higher than 30VDC. Always connect CV/CC signal to the voltage source with a series resistor to limit the sink current to less than 10mA.
CAUTION
*OTP *OVP *Foldback *AC fail
*Enable/Disable open (Power supply is disabled) *SO (Rear panel Shut-Off - Power supply is shut off)) *IEEE failure (with optional IEEE interface) *Output Off
NOTE
37
5.11 SAFE START AND AUTO-RESTART MODES
5.12 OVER TEMPERATURE PROTECTION (OTP)
5.13 LAST SETTING MEMOR
5.14 SERIES OPERATION
When turning on the power supply AC On/Off, it can start to its last setting of Output Voltage and
Current limit with the output enabled (Auto-restart) or start with the output disabled (Safe mode).
Press and hold the OUT button to select between Safe start and Auto-restart modes. The VOLTAGE
display will continuously cycle between "SAF" and "AU7” every 3 seconds. Releasing OUT
pushbutton while one of the modes is displayed, selects that mode. The default setting at shipment
is Safe mode.
In this mode, the power supply restores its last operation setting. Upon start-up, the output is
enabled or disabled according to its last setting.
In this mode, the power supply restores its last operation setting and sets the Output to Off state. At
start-up, the output is disabled and the output voltage and current are zero. To enable the output and restore the last output voltage and current limit values, momentarily press OUTbutton.
The OTP circuit shuts down the power supply before the internal components can exceed their safe internal operating temperature. When an OTP shutdown occurs, the display shows "O7P" and the ALARM LED blinks. Resetting the OTP circuit can be automatic (non-latched) or manual (latched) depending on the Safe or Automatic restart mode.
In Safe start mode, the power supply stays off after the over temperature condition has been removed. The display continue to shows "O7P" and theALARM LED continues to blink. To reset the OTP circuit, press OUT button (or send OUT ON command via the serial port).
InAuto-restart mode , the power supply recovers to it's last setting
automatically when the over temperature condition is removed.
The power supply is equipped with Last Setting Memory, which stores power supply parameters at eachAC turn-off sequence.
1. OUT On or Off
2. Output voltage setting (PV setting)
3. Output current limit (PC setting)
4. OVP setting
5. UVL setting
6. FOLD setting
7. Start-upmode (Safe orAuto-rest
art)
8. Remote/Local:If the last setting was Local Lockout (latched mode), the supply will return to Remote mode (non-latched).
9.Address setting
10. Baud rate
11. Locked /Unlocked front panel (LFP/UFP) (Items 8, 9, 10 are related to Remote digital control operation and explained in chapter 7)
12. Master/Slave setting
Power supplies of the SAME MODEL can be connected in series to obtain increased output voltage. Splitconnection of the power supplies gives positive and negative output voltage.
5.11.1Automatic start mode (AU7)
5.11.2Safe start mode (SAF)
1. Safe start mode:
2. Auto-restart mode:
Y
STORED PARAMETERS:
38
Do not connect power supplies from different manufacturers in series or in parallel.
CAUTION
When power supplies are connected in series, and the load or one of the output terminals is grounded, no point may be at a greater potential of +/-60VDC from ground for models up to 60VDC Rated Output and +/-600VDC from ground for models >60VDC Rated Output. When using RS232/485 or IEEE, refer to the OUTPUT TERMINALS GROUNDING warning, section 3.9.11.
5.14.1 Series connection for increased output voltage
In this mode, two units are connected so that their outputs are summed. Set the current limit of each power supply to the maximum that the load can handle without damage. It is recommended that diodes be connected in parallel with each unit output to prevent reverse voltage during start up sequence or in case one of the units shuts down. Each diode should be rated to at least the power supply rated output voltage and output current. Refer to Fig.5-1 and 5-2 for series operation with local and remote sensing.
+S
+
-
-S
-LS
+LS
POWER SUPPLY
+S
+
+
-
-
-S
-LS
+LS
POWER SUPPLY
LOAD
+S
+
-
-S
-LS
+LS
POWER SUPPLY
+S
+
+
-
-
-S
-LS
+LS
POWER SUPPLY
LOAD
Fig.5-1: Series connection, local sensing
Fig.5-2: Series connection, remote sensing
Remote programming in series operation for increased output voltage:
1.Programming by external voltage:
2.Using the SO function and PS_OK signal:
The analog programming circuits of this power supply are referenced to the negative Sense (-S) potential. Therefore, the circuits used to control each series connected unit must be separated and floated from each other.
The Shut-Off and PS_OK circuits are referenced to the isolated interface common, IF_COM (J1-2,3). The IF_COM terminals of different units can be connected to obtain a single control circuit for the power supplies connected in series.
(*)
(*)
(*)
(*)
(*) Diodes are user supplied.
WARNING
39
Fig.5-3: Series connection for positive/negative output voltages
3. Programming by external resistor:
1. Programming by external voltage:
Programming by external resistor is possible . Refer to section 6-5 for details.
The analog programming circuits of this power supply are referenced to the negative Sense potential. Therefore, the circuits used to control each series connected unit must be separated and floated from each other.
The communication port is referenced to the IF_COM which is isolated from the power supply output potential. Therefore power supplies connected in series can be chained using the Remote-In and Remote-Out connectors. Refer to chapter 7 for details.
The Shut-Off and PS_OK circuits are referenced to the isolated interface common, IF_COM (J1-2,3). The IF_COM terminals of the units can be connected to obtain a single control circuit for the power supplies connected in series.
4. Programming via the Serial Communication port (RS232/RS485):
4. Programming via the Serial Communication port (RS232/RS485):
5.14.2 Series connection for positive and negative output voltage
In this mode, two units are configured as a positive and negative output. Set the current limit of each power supply to the maximum that the load can handle without damage. It is recommended that diodes be connected in parallel with each unit output to prevent reverse voltage during start-up or in case one of the units shuts down. Each diode should be rated to at least the power supply rated
output voltage and output current. Refer to Fig.5-3 for this operating mode.
+S
+
-
-S
-LS
+LS
POWER SUPPLY
+S
+
+
-
-
-S
-LS
+LS
POWER SUPPLY
COM.
Remote programming in series operation for positive and negative output voltage
2. Using the SO function and PS_OK signal :
3. Programming by external resistor :
Programming by external resistor is possible. Refer to section 6.5 for details.
The communication port is referenced to the IF_COM which is isolated from the power supply output potential. Therefore power supplies connected in series can be chained using the Remote-In and Remote-Out connectors. Refer to chapter 7 for details.
LOAD
(*)
(*)
(*) Diodes are user supplied.
40
5.15 PARALLEL OPERATION
Up to four units of the same VOLTAGE and CURRENT rating can be connected in parallel to provide up to four times the output current capability. One of the units operates as a master and the remaining units are slaves. The slave units are analog programmed by the master unit.
In remote digital operation, only the master unit can be programmed by the computer while the slave units may be connected to the computer for voltage,current and statusreadback only.
There are two methods, basic and advanced, to configure multiple supplies for parallel operation. Refer to Sec. 5.15.1 and to Sec. 5.15.2 for detailedexplanation.
In this method, setting the units as Master and Slaves is made by the rear panel J1 connections and the setup switch SW1. Each unit displays its own output current and voltage. To program the load current, the Master unit should be programmed to the total load current divided by the number of units in the system. Refer to the following procedure to configure multiple supplies for simple parallel operation.
5.15.1 Basic parallel operation
5.15.2 Advanced parallel operation
1. Basic configuration
In this method, multiple supplies can be configured to parallel operation as a single power supply. The total load current and output voltage are displayed by the Master unit and can be readback from the Master unit. The Slave units display only their operating status (On, Off or Fault condition). Refer to the following procedure to configure multiple supplies for Advanced parallel operation.
Repeat steps 1 to 5 in Sec. 5.15.1 (Basic parallel operation).
1. Setting up the Master unit
2. Setting up the slave units
3. Setting Over Voltage protection
4. Setting Foldback protection
5. Connection to the load
Set the master unit output voltage to the desired voltage. Program the current limit to the desired load current limit divided by the number of parallel units. During operation, the master unit operates in CV mode, regulating the load voltage at the programmed output voltage. Connect the sensing circuit to local or remote sensing as shown in Fig.5-4 or Fig.5-5.
-1.The output voltage of the slave units should be programmed 2%~5% higher than the output voltage of the master unit to prevent interference with the master unit's control. The current limit of each unit should be programmed to the desired load current limit divided by the number of parallel units.
-2.Set the rear panel setup switch SW1 position 2 to it's up position.
-3.Set the rear panel setup switch SW1 position 3 in the same position as
SW1 position 4 of the master.
-4.Connect short between J1-8 and J1-12 (refer to Table 4-4.)
-5. Connect J1 terminal 10(IPGM) of the slave unit to J1 terminal 25(P) of the master unit.
During operation the slave units operate as a controlled current source following the master output current. It is recommended that the power system is designed so that each unit supplies up to 95% of its current rating because of the imbalance which may be caused by cabling and connections voltage drop.
The master unit OVP should be programmed to the desired OVP level. The OVP of the slave
units should be programmed to a higher value than the master OVP. When the master unit shuts down, it programs the slave unit to zero output voltage. If a slave unit shuts down (when its OVP is set lower than the master output voltage), only that unit would shut down and the remaining slave units would supply all the load current.
Foldback protection if desired, may only be used with the master unit. When the master unit shuts down it programs the slave units to zero output voltage.
In parallel operation, power supplies can
be connected in local or remote sensing. Refer to Fig.5-4 and 5-5 for typical connections of parallel power supplies. The figures show connection of two units, however the same connection method applies up to 4 units.
41
2. Setting the units as Master or Slave
3. Master and Slave units default operation
4. CURRENT display accuracy
5. To release units from Slave mode
a) Depress and hold the FINE button for 3 seconds. The Master/Slave configuration will be displayed on the Current Display. Rotate the CURRENT encoder to obtain the desired mode. Refer to Table 5-4 for the CURRENT display and modes of operation.
b) When the desired configuration is obtained, depress and release the FINE button or wait approx. 5 seconds.
a) When a unit is programmed to Slave mode it enters the Remote mode with Local Lockout,
then all the front panel controls are disabled to prevent accidental setting change.
b) The Slave units parameters will automatically set the following:
*Output voltage to approximate. 102% of rated output voltage. *Programmed Current to zero. *UVL to zero volts *OVP to its maximum value
c) The Master and Slave modes are stored in the power supply EEPROM when the AC power is
Turned off. The system will return to the Master/Slave mode upon re-application of AC power.
In the advanced parallel mode, the total current is programmed and reported by the Master. In this method, the CURRENT display accuracy is 2%+/- 1 count. In cases that higher accuracy is required, it is recommended to use the basic parallel operation mode.
Slave units can be released using the following procedure: a) Depress FINE button for 3 seconds. The Master/Slave configuration will be displayed on the
CURRENT display. b) Select H1 mode using the CURRENT encoder. c) Depress FINE button again or wait 5 seconds. d) Turn the AC power Off to store the new setting. e) After exiting from Slave operation the unit’s parameters will be set to:
CAUTION
Make sure that the connection between -Vo terminals is reliable to avoid disconnection during operation. Disconnection may cause damage to the power supply.
CURRENT Display
H1 H2 H3 H4
S
Operating Mode Single supply (default) Master supply with 1 Slave supply Master supply with 2 Slave supplies Master supply with 3 Slave supplies Slave supply
Table 5-4: Setting mode of operation
Fig.5-4: Parallel connection with local sensing
+V
-V
+V
-V
+S
+LS
-S -LS
+S
+LS
-S -LS
MASTER POWER SUPPLY
SLAVE#1 POWER SUPPLY
+
-
LOAD
J1-25
J1-10
P IPGM
As short as possible
Twisted
pair
To J1-10
SLAVE#2
POWER SUPPLY
J1-8
J1-12
*AST On *OUT On *Foldback protection Off
*Programmed Voltage to zero *AST OFF *Programmed Current to zero *OUT OFF *UVL to zero volts *Foldback protection OFF *OVP to its maximum value *Locked Front Panel
42
Fig.5-5: Parallel operation with Remote sensing
With local sensing it is important to minimize the wire length and resistance. Also the positive and negative wire resistance should be close as possible to each other to achieve current balance between power supplies.
NOTE
5.16 DAISY-CHAIN CONNECTION
It is possible to configure a multiple power supply system to shut down all the units when a fault condition occurs in one of the units. When the fault is removed, the system recovers according to its setting to Safe start mode or Automatic restart. Setup switch SW1 position 5 should be set to its Down position to enable the Daisy-chain operation. Other SW1 positions can be set according to the application requirements. If a fault occurs in one of the units its PS_OK signal will be set to low level and the display will indicate the fault. The other units will shut off and their display will indicate "SO”. When the fault condition is removed, the units will recover to their last setting according to their Safe start or Auto-restart setting. Fig.5-6 shows connection of three units, however the same connection method applies to systems with a larger number of units.
Fig.5-6: Daisy-chain connection
POWER SUPPLY
#
1
J1-2,3
J1-16
J1-16
J1-16
J1-15
PS_OK
POWER SUPPLY
#
2
J1-2,3
J1-15
PS_OK
SO
POWER SUPPLY
#3
J1-2,3
J1-15
PS_OK
SO
SO
IF_COM
IF_COM
IF_COM
5.17 FRONT PANEL LOCKING
The front panel controls can be locked to protect from accidental power supply parameter change. Press and hold PREV button to toggle between “Locked front panel” and “Unlocked front panel”. The display will cycle between “LFP” and “UFP”. Releasing the PREV button while one of the modes is displayed, selects that mode.
In this mode, the front panel controls are enable to program and monitor the power supply parameters.
In this mode the following front panel controls are disabled:
- VOLTAGE and CURRENT encoders.
- FOLD button.
- OUT button. The power supply will not respond to attempts to use these controls. The VOLT display will show “LFP” to indicate that the front panel is locked. OVP/UVL button is active to preview the OVPand UVL setting. Use PREV button to preview the output voltageand current setting or to unlock the front panel.
5.17.1 Unlocked front panel
5.17.2 Locked front panel
+V
-
V
+
V
-V
+S-S
+S-S
MASTER POWER SUPPLY
SLAVE#1 POWER SUPPLY
+S
-S
+S
+S
-S
-S
+
-
LOAD
J1-25
J1-10
P IPGM
As short as possible
Twisted
pair
Twisted
pair
Twisted
pair
J1-8
J1-12
To J1-10
SLAVE#2
POWER SUPPLY
CAUTION
Make sure that the connection between -Vo terminals is reliable to avoid disconnection during operation. Disconnection may cause damage to the power supply.
43
NOTE
CHAPTER 6 REMOTE ANALOG PROGRAMMING
6.1 INTRODUCTION
The rear panel connector J1 allows the user to program the power supply output voltage and current limit with an analog device. J1 also provides monitoring signals for output voltage and output current. The programming range and monitoring signals range can be selected between 0-5V or 0-10V using the setup switch SW1. When the power supply is in Remote Analog programming, the serial communication port is active and can be used to read the power supply parameters.
CAUTION
COM (J1-12), VPGM_RTN (J1-22) and IPGM_ RTN (J1-23) terminals of J1 connect internally to the -Sense potential (-S). Do not connect these terminals to any potential other than -Sense (-S), as it may damage the power supply.
6.2 LOCAL /REMOTE ANALOG SELECTION
Contact 8 of J1 (Fig. 4-2, item 5) accepts TTL signal or Open-Short contact (referenced to J1-12) to select between Local or Remote Analog programming of the output voltage and current limit. In Local mode, the output voltage and current limit can be programmed via the front panel VOLTAGE and CURRENT encoders or via the RS232/485 port. In Remote Analog mode, the output voltage and current limit can be programmed by analog voltage or by programming resistors via J1 contacts 9 and 10 (refer to sec. 6.4 and 6.5). Refer to Table 6-1 for Local/Remote Analog control (J1-8) function and Setup switch SW1-1, 2 setting.
6.3 LOCAL/REMOTE ANALOG INDICATION
Contact 21 of J1 (Fig. 4-2, item 5) is an open collector output that indicates if the power supply is in Local mode or in Remote Analog mode. To use this output, connect a pull-up resistor to a voltage source of 30Vdc maximum. Choose the pull-up resistor so that the sink current will be less than 5mA when the output is in low state. Refer toTable 6-2 for J1-21 function.
Table 6-1: Local/Remote Analog control function
Table 6-2: Local/Remote Analog indication
SW1-1,2 setting
Down (default)
Up
J1-8 function
Output voltage/
Current setting
No effect
"0" or Short
"1" or Open
Local
Remote Analog
Local
TTL "0" or short
TTL "1" or open
SW1-1
SW1-2
J1-8
J1-21 signal
Down Down
Up Up
Down or Up
Down
Up
Down
Up
Down or Up
Open 0~0.6V 0~0.6V 0~0.6V
Open
44
CAUTION
To maintain the isolation of power supply and prevent ground loops, use an
isolated programming source when operating the power supply via remote analog programming at J1 connector.
6.4 REMOTE VOLTAGE PROGRAMMING OF OUTPUT VOLTAGE AND CURRENT LIMIT
SW1-3 setting
UP
DOWN
Output Voltage programming
VPGM (J1-9)
0-10V
0-5V
Current limit programming
IPGM (J1-10)
0-10V
0-5V
Table 6-3: SW1-3 setting and programming range
1
14
13
25
10
12
8
9
23
22
+
-
+
-
CURRENT LIMIT PROGRAMMING
OUTPUT VOLTAGE
PROGRAMMING
J1 connector, rear panel view
Fig.6-1: Remote voltage programming connection
Perform the following procedure to set the power supply to Remote Voltage programming :
1. Turn the power supply AC On/Off switch to Off.
2. Set setup switch SW1-1 to its UP position for output voltage external programming and SW1-2 to its UP position for Output Current limit external programming.
3. Set SW1 position 3 to select programming voltage range according to Table 6-3.
4. Ensure that SW1 positions 7 and 8 are at their Down (default) position.
5. Connect a short between J1-8 and J1-12 (refer to Table 4-4).
6. Connect the programming source to the mating plug of J1 as shown in Fig.6-1. Observe correct polarity for the voltage source.
7. Set the programming sources to the desired levels and turn the power supply ON. Adjust the programming sources to change the power supply output.
1. SW1 positions 4,5,6 and 9 are not required for remote programming. Their setting can be determined according the application.
2. The control circuits allow the user to set the output voltage and current limit up to 5% over the model-rated maximum value. The power supply will operate within the extended range, however it is not recommended to operate the power supply over its voltage and current rating and performance is not guaranteed.
NOTES:
45
6.5 RESISTIVE PROGRAMMING OF OUTPUT VOLTAGE AND CURRENT LIMIT
For resistive programming, internal current sources, for output voltage and/or output current control, supply 1mA current through external programming resistors connected between J1-9 & 22 and J1-10 & 23. The voltage across the programming resistors is used as a programming voltage for the power supply. Resistance of 0~5Kohm or 0~10Kohm can be selected to program the output voltage and current limit from zero to full scale. A variable resistor can control the output over its entire range, or a combination of variable resistor and series/parallel resistors can control the output over restricted portion of its range.
Perform the following procedure to set the power supply to Resistive programming:
1. Turn the AC On/Off switch to Off.
2. Set setup switch SW1-1 to its UP position for output voltage external programming and SW1-2 to its UP position for Output Current limit external programming.
3. Set SW1 position 3 to select programming resistor range according to Table 6-4.
4. Set SW1-7 to its UP position for output voltage resistive programming and SW1-8 to its UP position for Output Current limit resistive programming.
5. Connect a short between J1-8 and J1-12 (refer to Table 4-4).
6. Connect the programming resistors to the mating plug of J1 as shown in Fig.6-2.
7. Set the programming resistors to the desired resistance and turn the power supply ON.
Adjust the resistors to change the power supply output.
1. SW1 positions 4, 5, 6 and 9 are not required for remote programming. Their setting can be determined according to the application requirements.
2. The control circuits allow the user to set the output voltage and current limit up to 5% over the model-rated maximum value. The power supply will operate within the extended range, however it is not recommended to operate the power supply over its voltage and current rating and performance is not guaranteed.
3. To maintain the temperature stability specification of the power supply, the resistors used for programming should be stable and low noise resistors, with temperature coefficient of less than 50ppm.
4. When resistive programming is used, front panel and computer control (via serial communication port)
of output voltage and current are disabled.
NOTES:
SW1-3 setting
UP
DOWN
Output Voltage programming
VPGM (J1-9)
0-10Kohm
0-5Kohm
Current limit programming
IPGM (J1-10)
0-10Kohm
0-5Kohm
Table 6-4: SW1-3 setting and programming range
1
14
13
25
10 9
23
22
CURRENT LIMIT PROGRAMMING
OUTPUT VOLTAGE
PROGRAMMING
J1 connector, rear panel view
Fig.6-2: Remote resistive programming
PROGRAMMING
RESISTOR
PROGRAMMING
RESISTOR
OPTIONAL SETS
LOWER LIMIT
OPTIONAL SETS
LOWER LIMIT
OPTIONAL SETS
UPPER LIMIT
OPTIONAL SETS
UPPER LIMIT
12
8
46
6.6 REMOTE MONITORING OF OUTPUT VOLTAGE AND CURRENT
The J1 connector, located on the rear panel provides analog signals for monitoring the output voltage and output current. Selection of the voltage range between 0-5V or 0-10V is made by setup switch SW1-4. The monitoring signals represent 0 to 100% of the power supply output voltage and output current.The monitor outputs have 500 ohm series output resistance. Ensure that the sensing circuit has an input resistance of greater than 500 Kohm or accuracy will be reduced. Refer to Table 6-5 for required J1 connection, SW1-4 setting and monitoring voltage range.
Signal
name
VMON
IMON
VMON
IMON
Signal function
Vout monitor
Iout monitor
Vout monitor
Iout monitor
Signal (+)
J1-11
J1-24
J1-11
J1-24
J1-12
J1-12
0-5V
0-10V
Down
Up
Range
SW1-4
Return (-)
J1 connection
Table 6-5 Monitoring signals setting
FCC requirements for radiated e missions, use shielded cable for the analog control signals. In case of using unshielded cable, attach an EMI ferrite suppressor to the cable, as close as possible to the power supply.
1.Radiated emissions, FCC requirements:
Notes:
2. Front panel encoders operation:
3. Front panel PREV button:
4. Communication:
In Remote analog mode the output voltage and current can’t be set by the VOLTAGE and CURRENT encoders.
Use PREV button to display the output voltage and current setting defined by the encoders or communication.
In Remote analog mode, power supply parameters can be programmed and readback via the communication port except output voltage and current setting.
47
CHAPTER 7 RS232 & RS485 REMOTE CONTROL
7.1 INTRODUCTION
7.2 CONFIGURATION
This chapter describes the operation of the Genesys 750W and 1500W power supplies via the serial communication port. Details of the initial set-up, operation via RS232 or RS485, the command set and the communication protocol are described in this chapter.
The power supply is shipped with the following setting:
TM
7.2.1 Default setting
6 9600 RS232 0 Maximum H1(Master)
-Output:
-Start up mode:
-OVP:
-UVL:
-Foldback:
-Front panel:
Off Safe start Maximum 0 Off Unlocked (UFP)
7.2.2 Address setting
7.2.3 RS232 or RS485 selection
7.2.4 Baud rate setting
7.2.5 Setting the unit into Remote or Local mode
The power supply address can be set to any address between 0 and 30. Follow the instructions described below to set the address.
1. If the unit is in Remote mode (front panel REM/LOC LED illuminates), press REM/LOC button to put the unit into Local mode.
2. Press and hold for approximately 3sec. the REM/LOC button. The VOLTAGE display will indicate the communication port address.
3. Using the VOLTAGE adjust encoder, select the address.
To preview the address at any time, press and hold the REM/LOC button for approx. 3sec. The VOLTAGE display will indicate the power supply address.
To select between RS232 or RS485 set the rear panel setup switch SW1-6 position to:
- Down for RS232
- Up for RS485
Five optional rates are possible: 1200, 2400, 4800, 9600 and 19200. To select the desired rate, the following steps should be taken:
1. If the unit is in Remote mode (front panel REM/LOC LED illuminates), press REM/LOC button to put the unit into Local mode.
2. Press and hold for approx. 3sec. the REM/LOC button. The CURRENT display will show the communication port Baud Rate.
3. Using the CURRENT adjust encoder, select the desired Baud Rate.
1. The unit will be put into Remote mode only via serial communication command. Commands that will put the unit into Remote mode are:
RST PV n OUT n PC n RMT n (for n values see Tables 7-3, 7-4 and 7-5)
-Address:
-Baud-rate:
-RS232/485:
-Vout setting:
-Iout setting:
-Master/Slave
48
2. There are two Remote modes:
1. Remote:
2. Local Lockout:
In this mode, return to local can be made by the front panel REM/LOC or via serial port command RMT 0. Set the unit into Remote mode via serial port
RMT 1 command.
In this mode the unit can be returned to Remote mode via the serial port RMT 1 command or by turning off the AC power until the display turns off and then turn it to on again. In Local Lockout mode, the front panel REM/LOC button is not active. Set the unit into Local Lockout mode via serial port RMT 2 command.
7.2.6 RS232/485 port in Local mode
7.2.7 Front panel in Remote mode
When the power supply is in local mode, it can receive queries or commands. If a query is received, the power supply will reply and remain in Local mode. If a command that affects the output is received, the power supply will perform the command and change to Remote mode. Serial commands may be sent to set the status registers and read them while the unit is in Local mode. If the Enable registers are set (refer to section 7.8) the power supply will transmit SRQ’s while in Local.
Front panel control in Remote mode is disabled except for:
1. PREV: use to preview the Voltage and Current limit setting.
2. OVP/UVL: use to preview the OVP/UVL setting.
3. LOC/REM: use to set the unit into Local mode.
In Local Lockout mode, only PREV and OVP/UVLare active.
The RS232/485 interface is accessible through the rear panel RS232/485 IN and RS485 OUT connectors. The connectors are 8 contact RJ-45. The IN and OUT connectors are used to connect power supplies in a RS232 or RS485 chain to a controller. Refer to Fig.7-1 for IN/OUT connectors
7.3 REAR PANEL RS232/485 CONNECTOR
Tx and Rx are used for RS232 communication. Txd +/- and Rxd +/- are used for RS485 communication. Refer to RS232 and RS485 cables description for connection details.
NOTE
NC
NC
RX
NC
NC
TXD
RXD
TXD
RXD
RXD
TXD
RXD
TXD
SG
SG
-
-
-
-
+
+
+
+
TX
OUT
IN
Fig.7-1: J3 rear panel IN/OUT connectors pinout
8 7 6 5 4 3 2 1
8 7 6 5 4 3 2 1
Shield
(connector enclosure)
49
50
7.4.2 Multi power supply connection to RS232 or RS485 bus
Daisy-chain up to 31 units can be connected to RS232 or RS485 bus. The first unit connects to the controller via RS232 or RS485 and the other units are connected with RS485 bus.
1. First unit connection: Refer to section 7.4.1 for connecting the first unit to the controller.
2. Other units connection: The other units on the bus are connected via their RS485 interface. Refer to fig.7-5 for typical connection.
- Set rear panel setup switch SW1-6 to it's UP position
- Using the Linking cable supplied with each unit (refer to Fig.7-6), connect each unit OUT
connector to the next unit IN connector.
* I
120 ohm resistive termination at the last unit’s RS485 OUT connector. 120 W between TXD and TXD
+ -
t is recommended when using several power supplies in Daisy-chain system to connect a
120 W between RXD and RXD
+ -
7.5 COMMUNICATION INTERFACE PROTOCOL
7.5.1 Dataformat
7.5.2 Addressing
7.5.3 End of Message
7.5.4 Command Repeat
7.5.5 Checksum
7.5.6 Acknowledge
Serial data format is 8 bit, one start bit and one stop bit. No paritybit.
The Address is sent separately from the command. It is recommended to add a 100 msec software delay between query or sent command to next unit addressing.
Refer to section 7.7.3 for details.
The end of message is the Carriage Return character (ASCII 13). The power supply ignores the Line Feed (ASCII 10) character.
The backslash character “\” will cause the last command to be repeated.
The user may optionally add a checksum to the end of the command. The checksum is "$" followed by two hex characters. If a command or a query has checksum, the response will also have one. There is no CR between the command string and the "$" sign. Example: STT?$3A
STAT?$7B
The power supply acknowledges received commands by returning "OK" message. If an error is detected, the power supply will return an error message. The rules of checksum apply also to the acknowledge.
IN
OUT
POWER SUPPLY
#1
IN
OUT
POWER SUPPLY
#2
IN
OUT
POWER SUPPLY
#3
RS232/485
RS485
RS485
RS485
IN
OUT
RS485 120 OHM TERMINATION
POWER SUPPLY
#31
RS485
Fig7-5: Multi power supplies RS232/485 connection
1 6 3 5 4
1 6 3 5 4
PIN NO.
HOUSING
HOUSING
PIN NO.NAME
NAME SHIELD SG TXD TXD RXD RXD
SHIELD SG RXD RXD TXD TXD
8 PIN CONNECTOR (IN)
8 PIN CONNECTOR (OUT)
-
+
+
+
+
-
-
-
Serial link cable with RJ-45 shielded connectors (P/N: GEN/RJ45)
Fig.7-6:
8
1
1
8
L=0.5m typ.
The address (ADR n) command must return an “OK” response before any other commands are accepted.
NOTE
51
7.5.7 Error message
7.5.8 Backspace
If an error is detected in a command or query, the power supply will respond with an error message. Refer to section 7.6 for details.
The backspace character (ASCII 8) clears the last character sent to the power supply.
The power supply will return error messages for illegal commands and illegal programming parameters. Refer to Table 7-1 for programming error messages and Table 7-2 for commands error messages.
Table 7-1: Programming error messages
7.6 ERROR MESSAGES
Table 7-2: Commands error messages
7.7 COMMAND SET DESCRIPTION
7.7.1 General guides
7.7.2 Command set categories
1. Any command or argument may be in capital letters or small letters.
2. In commands with an argument, a space must be between the command and the argument.
3. For any command that sets a numeric value, the value may be up to 12 characters long.
4. Carriage Return: If the CR character (ASCII 13) is received by itself, the power supply will respond with "OK" and CR.
The Genesys 750Wand 1500W series command set is divided into four categories as follows:
1. Initialization control
2. ID control
3. Output control
4. Statuscontrol
TM
E01
E02
E04
E06
E07
Description
Returned when program voltage (PV) is programmed above acceptable range.
Example: PV value is above '105% of supply rating' or 'PV above 95% of OVP setting'.
Returned when programming output voltage below UVL setting.
Returned when OVP is programmed below acceptable range.
Example:OVP value is less than '5% of supply voltage rating' plus 'voltage setting'.
Returned when UVL value is programmed above the programmed output voltage.
Returned when programming the Output to ON during a fault shut down.
Error Code
C01
C02
C03
C04
C05
Description
Illegal command or query
Missing parameter
Illegal parameter
Checksum error
Setting out of range
Error Code
52
7.7.3 Initialization control commands
ADR is followed by address which can be 0 to 30 and is used to access the
power supply .
Clear status. Sets FEVE and SEVE registers to zero (refer to section 7-8).
Reset command. Brings the power supply to a safe and known state: Output voltage: zero, Remote: non-latched remote, Output current: zero, Auto-start: Off, Output: Off, OVP: maximum, FOLD: Off, UVL: zero The conditional registers (FLT and STAT) are updated, the other registers are not changed.
Command
Sets the power supply to local or remote mode:
1. RMT 0 or RMT LOC, sets the power supply into Local mode.
2. RMT 1 or RMT REM, sets the unit into remote mode.
3. RMT 2 or RMT LLO, sets the unit into Local Lockout mode (latched remote mode).
#
Description
1
ADR n
2
CLS
3
RST
4
RMT
Returns the Remote mode setting:
1. "LOC"- The unit is in Local mode.
2. "REM"- The unit is in Remote mode.
3. "LLO"- The unit is in Local Lockout (latched remote) mode.
Returns MD MODE OPTION Status. 1 indicates installed and 0 indicates not installed.
Repeat last command. If \<CR> is received, the power supply will repeat the last command.
5
6
7
RMT?
MDAV?
\
7.7.5 Output control commands
7.7.4 ID control commands
Command
#
Description Returns the power supply model identification as an string Returns the software version as an ASCII string. Returns the unit serial number. Up to 12 characters. Returns date of last test. Date format: yyyy/mm/dd
ASCII
: LAMBDA, GENX-Y
1 2 3 4
IDN? REV? SN? DATE?
Command
#
Description
Sets the output voltage value in Volts. The range of voltage value is described in Table7-3. The maximum number of characters is 12. See the following examples for PV n format: PV 12, PV 012, PV 12.0, PV 012.00, etc...
Reads the output voltage setting. Returns the string "n" where "n" is the exact string sent in the PV n command. When in Local mode, returns the PREVIEW (front panel) settings in a 5 digits string.
Reads the actual output voltage. Return 5 digits string. Example: 60V supply sends 01.150, 15.012, 50.000, etc...
1
PV n
2
PV?
3
MV?
Reads the output current setting. Returns the string "n" where "n" is the exact string sent in the PC n command. When in Local mode, returns the PREVIEW (front panel) settings in a 5 digits string.
4
PC n
(See Note 1)
5
PC?
Sets the output current value in Amperes. The range of current values is described in Table 7-4 and 7-5. The maximum number of characters is 12. See the following examples for PC n format: PC 10, PC 10.0, PC 010.00, etc...
53
7.7.5 Output control commands-cont
#
Command
Description
Sets the Foldback protection to ON or OFF. FLD 1 (or FOLD ON) - Arms the Foldback protection. FLD 0 (or FOLD OFF)- Cancels the Foldback protection. When the Foldback protection has been activated, OUT 1 command will release the
protection and re-arm it, while FLD 0 will cancel the protection. Returns the Foldback protection status string:
“ON”- Foldback is armed, “OFF”- Foldback is canceled.
Add (nn x 0.1) seconds to the Fold Back Delay. This delay is in addition to the standard delay. The range of nn is 0 to 255. The value is stored in eprom at AC power down and recovered at AC power up.
Supply returns the value of the added Fold Back Delay.
Reset the added Fold Back Delay to zero.
Returns the output On/Off status string. ON- output on. OFF- output off.
Display Voltage and Current data. Data will be returned as a string of ASCII characters. A comma will separate the different fields. The fields, in order, are: Measured Voltage, Programmed Voltage, Measured Current, Programmed Current, Over Voltage Set point and Under Voltage Set Point.
Example: 5.9999, 6.0000, 010.02, 010.00, 7.500, 0.000
10
FLD n
11
12
13
14
FLD?
FBD nn
FBD? FBDRST
9
8
OUT?
Sets the OVP level. The OVP setting range is given in Table 7-6. The number of characters after OVP is up to 12. The minimum setting level is approx. 105% of the set output voltage, or the value in Table 7-6, whichever is higher. The maximum setting level is shown in Table 5-1. Attempting to program the OVP below this level will result in execution error response (”E04”). The OVP setting stays unchanged.
15
OVP n
Returns the power supply operation mode. When the power supply is On (OUT 1) it will return “CV” or “CC”. When the power supply is OFF (OUT 0) it will return “OFF”.
Returns the Master/Slave setting. Master: n = 1, 2, 3, or 4 Slave: n = 0
Saves present settings. The settings are the same as power-down last settings. These settings are erased when the supply power is switched off and the new “last settings”
are saved.
Sets Under Voltage Limit.The Max. setting level is approx. 95% of the set output voltage, or the value in Table 7-7, whichever is higher. The maximum setting level is shown in Table 7-6. Attempting to program the UVL equal or higher this level will result in execution error response (”E06”). The UVL setting stays unchanged.
Sets OVP level to the maximum level. Refer to Table 7-6.
Returns the setting “n” where “n” is the exact string in the user’s “UVL n”. When in Local mode, returns the last setting from the front panel in a 4 digit string.
Returns the setting “n” where “n” is the exact string in the user’s “OVP n”. When in Local mode, returns the last setting from the front panel in a 4 digit string.
Returns the string auto-restart mode status.
Recalls last settings. Settings are from the last power-down or from the last “SAV”
command.
16
OVP?
17
OVM
18
UVL n
19
UVL?
21
AST?
22
SAV
23
RCL
24
25
MODE?
MS?
Sets the auto-restart mode to ON or OFF. AST 1 (or AST ON)- Auto restart on. AST 0 (or AST OFF)- Auto restart off.
20
AST n
Reads the actual output current. Returns 5 digits string. Example: 200A supply sends 000.50, 110.12, 200.00, etc...
Turns the output to ON or OFF. Recover from Safe-Start, OVP or FLD fault. OUT 1 (or OUT ON)-Turn On.
6
MC?
(See Note 2)
7
OUT n
DVC?
54
Table 7-3: Voltage programming range
Model
Rated Output Voltage(V)
Minimum
(V)
Maximum
(V)
8 10 15 20 30 40 50 60 80
100 150 300 600
0.000
00.000
00.000
00.000
00.000
00.000
00.000
00.000
00.00
000.00
000.00
000.00
000.00
8.000
10.000
15.000
20.000
30.000
40.000
50.000
60.000
80.00
100.00
150.00
300.00
600.00
NOTE:
The power supply can accept values higher by 5% than the table values, however it is not recommended to program the power supply over the rated values.
7.7.6 Global output commands
1. General
All supplies, even if not the currently addressed supply, receiving a global command will execute the command. No response to the PC issuing the command will be returned to the PC. The PC issuing the command will be responsible to delay and any other communications until the command is execute. 200 Ms minimum is the suggested delay.
If the command contains an error, out of range values for example, no error report will be sent to the issuing PC.
Reset. Brings the Power Supply to a safe and known state: Output voltage: 0V, output current: 0A, OUT: Off, Remote: RMT 1’ AST: Off OVP:Max, UVL:0. The conditional register (FLT and STAT) are updated. Other registers are not changed. Non-Latching faults (FB, OVP, SO) are cleared, OUT fault stays.
Sets the output voltage value in volts. The range of voltage values is shown in Table 7-3. ‘n’ may be up to 12 char plus dec. pt
Program the output current value in amperes. The range of current values is shown in Table 7-4. ‘n’ may be up to 12 char plus dec. pt
Turns the output to ON or OFF: “OUT 1/ON” = turn on “OUT 0/OFF”= turn off, clears CV and CC bits in the Status Condition (STAT) OUT ON will respond with “E07’ if the output cannot be turned on because of a latching fault (OTP< AC, ENA, SO) shutdown.
1.
GRST
2.
3.
4.
GPV n
GPC n
GOUT
Save present settings. Same settings as power-down last settings listed in Error! Reference source not found. Except the address and Baud rate are not saved Saves to the RAM. These settings are erased when the supply power is switched off and the new ‘last settings’ are saved.
5.
GSAV
Recall last settings. Settings are from last power-down or from last ‘SAV’ or ‘GSAV’ command. Address and Baud rate are not recalled so communication is not interruped.
6.
GRCL
NOTES:
1. In Advanced parallel mode (refer to Sec. 5.15.2), “n” is the total system current.
2. In Advanced parallel mode, “MC?” returns the Master unit current multiplied by the number of slave units+1.
55
Minimum
(A)
Model
Maximum
(A)
GEN6-100 GEN8-90 GEN12.5-60 GEN20-38 GEN30-25 GEN40-19 GEN60-12.5 GEN80-9.5 GEN100-7.5 GEN150-5 GEN300-2.5 GEN600-1.3
000.00
00.00
00.000
00.000
00.000
00.000
00.000
0.000
0.000
0.000
0.000
0.000
100.00
90.00
60.000
38.000
25.000
19.000
12.500
9.500
7.500
5.000
2.500
1.300
Minimum
(A)
Model
Maximum
(A)
GEN6-200 GEN8-180 GEN12.5-120 GEN20-76 GEN30-50 GEN40-38 GEN50-30 GEN60-25 GEN80-19 GEN100-15 GEN150-10 GEN300-5 GEN600-2.6
000.00
000.00
000.00
00.00
00.000
00.000
00.000
00.000
00.000
00.000
00.000
0.000
0.000
200.00
180.00
120.00
76.00
50.000
38.000
30.000
25.000
19.000
15.000
10.000
5.000
2.600
NOTE:
The power supply can accept values higher by 5% than the table values, however it is not recommended to program the power supply over the rated values.
GEN750W models Current programming range
GEN1500W models Current programming range
7.7.7 Status control commands
Refer to section 7-8 for definition of the registers.
Command
#
Description
1
STT?
Reads the complete power supply status. Returns ASCII characters representing the following data, separated by commas:
Table 7-6: OVP programming range
Table 7-7: UVL programming range
Model
Rated Output Voltage (V)
Minimum
(V)
Maximum
(V)
6 8
12.5 20 30 40 50 60 80
100 150 300 600
0.5
0.5
1.0
1.0
2.0
2.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
7.50
10.0
15.0
24.0
36.0
44.0
57.0
66.0
88.0
Model
Rated Output Voltage (V)
Minimum
(V)
Maximum
(V)
6 8
12.5 20 30 40 50 60 80
100 150 300 600
0 0 0 0 0 0 0 0 0 0 0 0 0
5.70
7.60
11.9
19.0
28.5
38.0
47.5
57.0
76.0
95.0 142 285 570
MV<actual (measured) voltage> PV<programmed (set) voltage> MC<actual (measured) current>
PC<programmed (set) current> SR<status register, 2-digit hex> FR<fault register, 2-digit hex>
Example response: MV(45.201),PV(45),MC(4.3257),PC(10),SR(30),FR(00)
Reads Fault Conditional Register. Return 2-digit hex. Set Fault Enable Register using 2-digit hex. Reads Fault Enable Register. Returns 2-digit hex.
Reads Fault Event Register. Returns 2-digit hex. Clears bits of Fault Event Register.
Reads Status Conditional Register. Returns 2-digit hex. Sets Status Enable Register using 2-digit hex. Reads Status Enable Register. Returns 2-digit hex.
Reads Status Event register. Returns 2-digit hex. Clears bits of Status Event register.
2 3 4
5 6
7 8
9
FLT? FENA FENA?
FEVE? STAT? SENA SENA?
SEVE?
Table 7-4:
Table 7-5:
110 165 330 660
56
OR
OR
OR
SRQ
Messages
Address Changed
Response messages
Command Error (”Cnn”)
Execution Error (”Enn”)
Query Response (”message”)
Command Response (”OK”)
CV CC
NFLT
FLT AST FDE
0
LCL
CV CC
NFLT
FLT
0 0 0
LCL
0 0 0
OR
Status Registers
Condition
Enable
Event
Constant Voltage
Constant Current No Fault Fault
Auto Start Fold Enabled
Spare Local Mode
0
1
2
3
4 5
6 7
“STAT?”
“SENA xx” “SENA?”
“SEVE?”
0
AC OTP FLD OVP
SO OFF ENA
Fault Registers
Condition
Enable
Spare AC Fail Over Temperature Foldback (tripped)
Over Volt Prot
Shut Off (rear panel)
Output Off (front panel)
Enable Open
0
1
2 3 4 5 6 7
“FLT?”
“FENA xx” “FENA?”
0
AC OTP FLD OVP
SO OFF ENA
OR
Event
“FEVE?”
MSB
MSB
LSB
Serial
TXD
LSB
One response for every command
or query received.
One SRQ when SEVE goes from all zeroes to any bit set. Setting more SEVE bits does not cause more SRQs.
Positive Logic: 0 = No Event 1 = Event Occured
7.8 STATUS, ERROR AND SRQ REGISTERS
This section describes the various status error and SRQ registers structure. The registers can be read or set via the RS232/485 commands. When using the IEEE option, refer to the user manual
for Genesys Power Supply IEEE Programming interface. Refer to Fig.7-7 for the Status and Error Registers Diagram.
7.8.1 General
TM
Fig.7-7: Status and Error Registers Diagram
7.8.2 Conditional registers
The fault Condition Register and the Status Condition Register are read only registers that the user may read to see the condition of the supply. Refer to table 7-8 for description of the Fault Condition Register bits and Table 7-9 for the Status Condition register bits.
SRQ = “!nn”, nn = address
57
7.8.2 Conditional registers
7.8.3 Service Request: Enable and Event Registers
The conditional Registers are continuously monitored. When a change is detected in a register bit which is enabled, the power supply will generate an SRQ message. The SRQ message is: "!nn" terminated by CR, where the nn is the power supply address. The SRQ will be generated either in Local or Remote mode.
Output is ON and the supply is not in CV.
Output is On and the supply in CV.
Output is ON and the supply is not in CC.
Output is ON and the supply in CC.
The power supply is operating normally or fault reporting is not enabled. See “OUT n” command in Section
7.7.5.
One or more faults are active and fault reporting is enabled (using “FENA xx”).
1
2
Constant Voltage
Constant Current
No Fault
Table 7-8: Fault Condition Register
BIT
Fault name
Fault symbol
Bit Set condition
Bit Reset condition
Fixed to zero
Fixed to zeroSPARESpare bit
0 (LSB)
The AC input returns to normal.
AC fail has occurred. OTP shutdown has occurred.
The power supply cools down.
Foldback shutdown has occurred.
The supply output is turned On by front panel button or OUT 1 command.
The supply output is turned On by front panel button or OUT 1 command.
The supply output is turned On by front panel button or OUT 1 command.
OVP shutdown has occurred.
Rear panel J "Shut Off" condition has occurred.
Rear panel J1 "Shut Off" condition removed.
Front panel OUT button pressed to Off.
Rear panel J1 Enable terminals(J1-1&J1-14)
opened.
Rear panel J1 Enable terminals closed.
1 2
3
4
5
6
7(MSB)
AC Fail Over
temperature
Foldback
Over voltage
Shut Off
Output Off
Enable
AC
OTP
FOLD
OVP
SO
OFF
ENA
Table 7-9: Status Condition Register
BIT
Status name
Status symbol
Bit Set condition
Bit Reset condition
0 (LSB)
CV
CC
NFLT
One or more faults are enabled and occur.
Fault Event Register cleared (FEVE?).
Supply is in Auto­Restart mode (from Front Panel or serial command).
Supply is in Safe-Start mode (from Front Panel or serial command).
Fold protection enabled (from Front Panel or serial command).
Fold protection disabled (from Front Panel or serial command).
Fixed to zero.
Fixed to zero.
Supply in Local mode.
Supply in Remote mode or Local­Lockout mode.
3
4
5
6
7 (MSB)
Fault active
Fold Enabled
Spare bit
Local Mode
FLT
FDE
SPARE
LCL
AST
Auto­Restart Enabled
58
Refer to Tables 7-10 to 7-13 for details of the Enable and Event registers.
The Fault Enable Register is set to the enable faults SRQs.
1.Fault Enable Register
2.Fault Event Register
The Fault Event will set a bit if a condition occurs and it is enabled. The register is cleared when FEVE?, CLS or RST commands are received.
Table 7-10: Fault Enable Register
BIT
Enable
bit name
Fault symbol
0 (LSB)
1
2
3
4
5
6
7(MSB)
Spare bit
AC Fail
Over Temperature
Foldback
Over Voltage
Shut Off
Output Off
Enable
SPARE
AC
OTP
FOLD
OVP
SO
OFF
ENA
Bit Set condition
Bit reset condition
User command: "FENA nn" where nn is hexadecimal
User command: "FENA nn" where nn is hexadecimal (if nn="00", no fault SRQs will be generated).
Table 7-11: Fault Event Register
0 (LSB)
1
2
3
4
5
6
7(MSB)
Spare bit
AC Fail
Over Temperature
Foldback
Over Voltage
Shut Off
Output Off
Enable
SPARE
AC
OTP
FOLD
OVP
SO
OFF
ENA
Entire Event Register is cleared when user sends "FEVE?" command to read the register. "CLS" and power-up also clear the Fault Event Register. (The Fault Event Register is not cleared by RST)
BIT
Event
bit name
Fault symbol
Bit Set condition
Bit reset condition
Fault condition occurs and it is enabled. The fault can set a bit, but when the fault clears the bit remains set.
59
Table 7-12: Status Enable Register
BIT
Status symbol
0 (LSB)
1
2
3
4
5
6
7(MSB)
Constant Voltage
Constant Current
No Fault
Fault active
Auto-Restart enabled
Fold enabled
Spare
Local Mode
CV
CC
NFLT
FLT
AST
FDE
Spare
LCL
Bit Set condition
Bit reset condition
User command: "SENA nn" is received, where nn is hexadecimal bits.
User command: "SENA nn" is received, where nn is hexadecimal bits. If "nn"=00, no SRQ is sent when there is a change in Status Condition Register.
Table 7-13: Status Event Register
0 (LSB)
1
2
3
4
5
6
7(MSB)
Constant Voltage
Constant Current
No Fault
Fault active
Not used
Not used
Not used
Local Mode
CV
CC
NFLT
FLT
0
0
0
LCL
Entire Event Register is cleared when user sends
"SEVE?" command to read the register. "CLS" and power-up also clear the Status Event Register. (The Fault Event Register is not cleared by RST)
BIT
Status
name
Status
symbol
Bit Set condition
Bit reset condition
Changes in status occurs and it is enabled.
The change can set a bit, but when the change clears the bit remains set.
3.Status Enable register
The Status Enable Register is set by the user to enable SRQs from changes in power supply
status.
Status name
Always zero
Always zero
Always zero
Always zero
Always zero
Always zero
"SENA nn" command
"SENA nn" command
4.Status Event Register
The Status Event Register will set a bit if a change in the power supply status occurs and it is enabled. The register is cleared when the "SEVE?" or "CLS" commands are received. A change in this register will generate SRQ.
Always zero
Always zero
Always zero
Unit is set to Local by pressing front panel REM/LOC button.
60
7.9 SERIAL COMMUNICATION TEST SET-UP
Use the following instructions as basic set-up to test the serial communication operation.
1.Equipment:
2.PC set-up:
3.Power supply set-up:
4.Communication Test:
PC with Windows Hyper Terminal, private edition, software installed, Genesys
power supply, RS232 cable.
TM
2.1 Open Hyper Terminal.......................New Connection.
2.2 Enter a name
2.3 Connect to.......................................Direct to Com1 or Com 2
2.4 Configure port properties:
2.5 Open Properties in the program File...........................Properties
2.6 Setting: ASCII Set Up Select Echo characters locally, select send line ends with line feed. On some PC systems, pressing the number keypad "Enter" will distort displayed messages. Use the alphabetic "Enter" instead.
Bits per second .......9600
Data bits ..................8
Parity .......................None
Stop bits....................1
Flow control..............None
3.1 Connect the power supply to the PC using the RS232 cable.
3.2 Set via the front panel: Baud Rate: 9600, Address: 06.
3.3 Set via the rear panel: RS232/485 to RS232 (refer to section: 4-4).
4.1 Model identification: PC:write: ADR 06 Power supply response: "OK"
4.2 Command test:
PC write: OUT 1 Power supply response: "OK" PC write: PV n Power supply response: "OK" PC write: PC n (for n values see Tables 7-3, 7-4 and 7-5 ) Power supply response: "OK"
The power supply should turn on and the display will indicate the output voltage and the actual output current.
61
CHAPTER 8 ISOLATED ANALOG PROGRAMMING OPTION
8.1 INTRODUCTION
Isolated Analog Programming is an internal option card for analog programming of the Genesys power supply series. The option is factory installed and cannot be obtained with GPIB (IEEE) Interface. Output Voltage and Current Limit can be programmed and readback through optically isolated signals which are isolated from all other ground references in the power supply. There are two types of Isolated Analog programming cards:
1. 0-5V/0-10V option (PN: IS510): Using 0-5V or 0-10V signals for programming and readback.
2. 4-20mA option (PN: IS420): Using current signals for programming and readback.
TM
NOTE:
Use 100Kohm minimum input impedance for the monitoring circuits to minimize the readback error.
Programming Inputs
Output voltage programming accuracy Output current programming accuracy Output voltage programming temperature coefficient
Output current programming temperature coefficient Input impedance Absolute maximum voltage Max. voltage between program inputs and supply outputs Output voltage monitoring accuracy Output current monitoring accuracy Output Impedance (see note) Max. voltage between monitoring outputs and supply outputs
% %
PPM/ C
PPM/ C
Ohm
Vdc Vdc
% %
Ohm
Vdc
o
o
+/-1
+/-1 +/-100 +/-100
1M
0-15
600
+/-1.5 +/-1.5
100
600
Programming Inputs
Output voltage programming accuracy Output current programming accuracy Output voltage programming temperature coefficient
Output current programming temperature coefficient Input impedance Absolute maximum input current Max. voltage between program inputs and supply outputs Output voltage monitoring accuracy Output current monitoring accuracy Maximum load impedance Max. voltage between monitoring outputs and supply outputs
% %
PPM/ C
PPM/ C
Ohm
mA
Vdc
% %
Ohm
Vdc
o
o
+/-1
+/-1 +/-200 +/-200
50
0-30
600
+/-1.5 +/-1.5
500
600
8.2.2 4-20mA option (PN: IS420)
8.2.1 0-5V/0-10V option (PN: IS510)
8.2 SPECIFICATIONS
Monitoring Outputs
Monitoring Outputs
62
8.3 ISOLATED PROGRAMMING & MONITORING CONNECTOR
Refer to Table 8-1 for detailed description of the rear panel Isolated Programming & Monitoring connector. To provide the lowest noise performance, it is recommended to use shielded-twisted pair wiring. Refer to Fig.8-1 for description of the connector.
1
2
3
4
5
6
7
8
Shield
+VPROG_ISO
+IPROG_ISO
GND
Shield
+IMON_ISO
+VMON_ISO
GND
+VPROG_ISO
Terminal
Signal name
Function
Shield, connected internally to chassis of the supply.
0-5/0-10V
0-5/0-10V
0-5/0-10V
0-5/0-10V
4-20mA
4-20mA
4-20mA
4-20mA
Range 0-5/0-10V
IS510 option
Range 4-20mA
IS420 option
Chassis ground
Chassis ground
SHLD
1
Output voltage programming input
Output current programming input
2
+IPROG_ISO
3
Ground for programming signals.
Ground for programming signals.
Output voltage monitoring output
Output current monitoring output
Shield, connected internally to chassis of the supply.
GND
GND
+VMON_ISO
+IMON_ISO
SHLD
4
5
6
7
8
Ground
Ground
Ground
Ground
Table 8-1: Detailed description of Isolated programming & Monitoring connector
Fig.8-1: Isolated Programming & Monitoring connector
Isolated programming plug P/N: MC1.5/8-ST-3.81, Phoenix.
When the Isolated Analog Option is installed, do not apply any signals to the non-isolated VPGM and IPGM (J1-9 and J1-10) pins. All other J1 features may be used normally. Refer to Section 4.5 for a description of J1 features.
CAUTION
63
NOTE
SW1 position 3 and 4 must be in their Up position for operation with 4-20mA Isolated Programming and Monitoring.
CAUTION
To prevent damage to the unit, do not program the output voltage and current to higher then the power supply rating.
Perform the following procedure to configure the power supply:
1. Turn the power supply AC power switch to Off.
2. Connect a short between J1-8 and J1-12 (refer to Table 4-4).
3. Set Setup switch SW1-1 to its UP position for Output Voltage external programming and SW1-2 to its UP position for Output Current limit external programming.
4. Set SW1 position 3 to select the programming voltagerange: Down=0-5V,Up=0-10V.
5. Set SW1 position 4 to select the monitoring range: Down=0-5V,Up=0-10V.
6. Ensure that SW1 positions 7 and 8 are in the their down position.
7. Connect the programming sources to the mating plug of the Isolated Programming connector.Observe for correct polarity of the voltage source.
8. Set the programming sources to the desired levels and turn the power supply ON.
Perform the following procedure to configure the power supply:
1. Turn the power supplyAC power switch to Off.
2. Connect a short between J1-8 and J1-12 (refer toTable 4-4).
3.Set setup switch SW1-1 to its UP position for Output Voltage external programming and
SW1-2 to its UP position for Output Current limit external programming.
4. Set SW1 position 3 to it's Up position.
5. Set SW1 position 4 to it's Up position.
6. Ensure that SW1 positions 7 and 8 are in their Down position.
7. Connect the programming source to the mating plug of the Isolated Programming
connector.Observe for correct polarity of the voltage source.
8. Set the programming sources to the desired levels and turn the power supply ON.
8.4.2 Setting up the power supply for 4-20mA Isolated Programming and Monitoring
8.4.1 Setting up the power supply for 0-5/0-10V Isolated Programming and Monitoring
8.4 SETUP AND OPERATING INSTRUCTIONS
J1-8 and J1-12 must be shorted together with a jumper.
NOTE
J1-8 and J1-12 must be shorted together with a jumper.
NOTE
64
9.1 INTRODUCTION
9.2 UNITS UNDER WARRANTY
9.3 PERIODIC MAINTENANCE
9.4 ADJUSTMENTS AND CALIBRATION
9.5 PARTS REPLACEMENT AND REPAIRS
This chapter provides information about maintenance, calibration and troubleshooting.
Units requiring repair during the warranty period should be returned to a Lambda authorized service facility. Refer to the addresses listing on the back cover of this manual. Unauthorized repairs performed by other than the authorized service facilities may void the warranty.
No routine maintenance of the power supply is required except for periodic cleaning. To clean, disconnect the unit from the AC supply and allow 30sec. for discharging internal voltage. The front panel and the metal surfaces should be cleaned using mild solution of detergent and water. The solution should be applied onto a soft cloth, and not directly to the surface of the unit. Do not use aromatic hydrocarbons or chlorinated solvents for cleaning. Use low pressure compressed air to blow dust from the unit.
No internal adjustment or calibration is required. There is NO REASON to open the power supply cover.
As repairs are made only by the manufacturer or by authorized service facilities, no parts replacement information is provided in the manual. In case of failure, unusual or erratic operation of the unit, contact a Lambda sales or service facility nearest you. Please refer to the Lambda sales offices addresses listing on the back cover of this user manual.
If the power supply appears to operating improperly, use the troubleshooting guide to determine whether the power supply, load or external control circuit are the cause.
Configure the power supply for basic front panel operation and perform the tests of section 3.8 to determine if the problem is with the supply.
Table 9-1 provides the basic checks that can be performed to diagnose problems, and references to sections of this manual for further information.
9.6 TROUBLESHOOTING
Table 9-1: Troubleshooting guide
Check continuity, replace if necessary.
Does the AC source voltage sag when load is applied?
No output. All displays and indicators are blank.
Is the AC power cord defective?
SYMPTOM
CHECK
ACTION
REF.
Is the AC input voltage within range?
Check input AC voltage. Connect
to appropriate
voltage source.
Check input AC voltage. Connect to appropriate voltage source.
Output is present momentarily but shuts off quickly. The display indicates "AC".
3.7
3.6
3.7
3.6
CHAPTER 9 MAINTENANCE
65
66
USER MANUAL INDEX
A
B
C
D
E
F
G
H
ac cables ac fail accessories acknowledge address adjustment auto-restart
back space baud rate bipolar voltage
calibration configuration checksum communication constant current constant voltage cooling cv indicator cc indicator
daisy-chain display
enable error message external resistor external voltage
fine foldback fuse front panel control front panel locking
grounding global output command 55
humidity hyper terminal
I
J
L
M
O
P
R
S
ID control initialization installation isolated
J1 J2 J3
last setting memory linking power supplies line feed local operation local sensing lock front panel
maintenance
otp outline over voltage
parallel operation parity ps_ok preview
rack mounting rear panel remote sensing remote/local registers structure RS232 RS485 RXD RX(RS232)
safe start safety series operation shield specifications status control SRQ shut-off
SW1
T
U
V
W
TXD TX(RS232)
under voltage limit
volts display
warranty wire size
8, 15 29 8 51 18, 48 65 38
52 18, 48 40
65 48 51 51, 61 17, 34 17, 34 8, 10 27, 37 27, 37
43, 51 27
33 52 46 45
29 18, 36 66 27 43
24
10 61
52 53 13 62
32, 45, 46 16, 25 49
28, 38 51 51 34 25 43
65 41 51
38 12 27,35
41 61 37, 43 28
13 29 26 28 57 48, 49, 50 48, 49, 50 49, 50 49, 50
38 3 38 49 9, 62 56, 57 57 36 30, 31
49, 50 49, 50
17, 36
27
1, 65 19
Master/Slave MD
67
NOTES
68
NOTES
69
NOTES
70
NOTES
71
NOTES
72
NOTES
73
NOTES
74
NORTH AMERICA
TDK-Lambda Americas Inc 405 Essex Rd. Neptune, NJ 07753 Tel: +1-732-922-9300 Fax: +1-732-922-1441 E-mail: sales@us.tdk-lambda.com www.us.tdk-lambda.com/hp
UK
TDK-Lambda UK Ltd. Kingsley Avenue Ilfracombe, Devon EX 34 8ES United Kingdom Tel: +44-1271-856666 Fax: +44-1271-864894 E-mail: powersolutions@emea.tdk-lambda.com www.uk.tdk-lambda.com
FRANCE
TDK-Lambda France SAS ZAC des Delaches BP 1077 - Gometz le Chatel 91940 LES ULIS Tel: +33 1 60 12 71 65 Fax: +33 1 60 12 71 66 E-mail: france@fr.tdk-lambda.com www.fr.tdk-lambda.com
GERMANY
TDK-Lambda Germany GmbH Karl-Bold-Str.40, D-77855 Achern, Germany Tel: +49-7841-666-0 Fax: +49-7841-500-0 E-mail: info.germany@de.tdk-lambda.com www.de.tdk-lambda.com
AUSTRIA
TDK-Lambda Austria Sales Office Aredstrasse 22, A - 2544 Leobersdorf, Austria Tel: +43-2256-65584 Fax: +43-2256-64512 E-mail: info.germany@de.tdk-lambda.com www.de.tdk-lambda.com
ITALY
TDK-Lambda Italy Via dei Lavoratori 128/130 IT20092 Cinisello Balsamo, Milano, Italy Tel: +39-02-6129-3863 Fax: +39-02-6129-0900 E-mail: info.italia@lambda-europe.com www.it.tdk-lambda.com
ISRAEL
Nemic Lambda Ltd. Sales Office: Kibbutz Givat Hashlosha Tel-Aviv 48800, Israel Tel: +972-3-9024-333 Fax: +972-3-9024-777 Plant: POB 500 Karmiel Industrial Zone 21651, Israel Tel: +972-4-9887-491 Fax: +972- 4-9583-347 www.nemic.co.il E-mail: info@nemic.co.il
JAPAN
TDK-Lambda Corporation International Sales Divison Nittetsu Bldg. 6F, 1-13-1 Nihonbashi, Chuo-ku, Tokyo 103-0027, Japan Tel: +81-3-5201-7175 Fax: +81-3-5201-7287 www.tdk-lambda.com
CHINA
Shanghai Branch of Wuxi TDK-Lambda Electronic Co. Ltd. 28F, Xingyuan Technology Building No.418, Guiping Road, Shanghai, China 200233 Tel: +86-21-6485-0777 Fax: +86-21-6485-0666 www. cn.tdk-lambda.com
Beijing Branch of Wuxi TDK-Lambda Electronic Co. Ltd. Room 12B11-12B12, Unit 7 DACHENG SQUARE, No.28 Xuanwumenxi Street, Xuanwu District Beijing, 100053, CHINA Tel: +86-10-6310-4872 Fax: +86-10-6310-4874 www. cn.tdk-lambda.com
Shenzhen Branch of Wuxi TDK-Lambda Electronics Co.Ltd. Room 4302, Excellence Times Square Building, 4068 Yi Tian Road, Futian District, Shenzhen, China 518048 Tel: +86 -755-83588261 Fax: +86 -755-83588260 www. cn.tdk-lambda.com
KOREA
TDK-Lambda Corporation Seoul Office 6F Songok Bldg. 4-1 Soonae-Dong Pundang-Gu, Songnam-Shi Kyonggi-Do, 463-020 Korea Tel: +82-31-717-7051 +82-31-726-9137 www.tdk-lambda.com
SINGAPORE
TDK-Lambda Singapore Pte.Ltd. Blk 1008 Toa Payoh North # 07-01/03 Singapore 318996 Tel: +65-6251-7211 Fax: +65-6250-9171 www.tdk-lambda.com.sg