For units equipped with IEEE488.2 (GPIB) Interface option,
refer to Manual IA586-04-01_.
For units equipped with LAN Interface option,
refer to Manual IA672-04-01_.
IA657-04-01-Rev. M
This information sheet was prepared based on People's Republic of China "Management Methods for Controlling Pollution Caused by
"SJ/T 11364—2006 Marking for Control of Pollution Caused by Electronic Information Products
As People's Republic of China "Management Methods for Controlling Pollution Caused by Electronic Information Products Regulatio
2002/95/EC
, inquiries concerning EU RoHS Directive
The date of manufacture
Part Name
GENESYS, GEN5KW POWER SUPPLY SERIESProduct Weight
16Kg
Lead (Pb)Mercury (Hg)Cadmium (Cd)Hexavalent
Chromium (Cr6+)
Polybrominated
Biphenyls (PBB)
Polybrominated Diphenyl
Ethers(PBDE)
0.1wt%0.1wt%0.01wt%0.1wt%0.1wt%0.1wt%
Case
OOOOOO
Plastic panel
OOOOOO
PCB's assemblyXOOOOO
Inner metal partsOOOOOO
Inner cablesOOOOOO
AccessoriesOOOOOOProvided in the package
○ : Indicates that the concentration values of toxic and hazardous substances in all "homogeneous materials" of respective parts and materials does not exceed the concentration limits
regulated by "SJ/T 11363-2006 Requirements for Concentration Limits for Certain Hazardous Substances in Electronic Information Products".
× : Indicates that the concentration value of a toxic or hazardous substance included in a "homogeneous part" of a respective part ot material exceeds the concentration limit regulated by
"SJ/T 11363-2006 Requirements for Concentration Limits for Certain Hazardous Substances in Electronic Information Products".
Information Concerning Inclusion of Toxic and Hazardous Substances
NotesConcentration Values of Toxic and Hazardous Substances/Elements (wt%)
Subpart Name
(2002/95/EC), inquiries concerning EU RoHS Directive (2002/95/EC) information should be done separately.
GENESYS, GEN5KW POWER SUPPLY SERIESProduct Weight
16Kg
Lead (Pb)Mercury (Hg)Cadmium (Cd)Hexavalent
0.1wt%0.1wt%0.01wt%0.1wt%0.1wt%0.1wt%
OOOO OO
Plastic panel
OOOO OO
PCB's assemblyXOOO OO
Inner metal partsOOOO OO
Inner cablesOOOO OO
AccessoriesOOOO OO
: Indicates that the concentration values of toxic and hazardous substances in all "homogeneous materials" of respective parts
regulated by "SJ/T 11363-2006 Requirements for Concentration Limits for Certain Hazardous Substances in Electronic Infor
: Indicates that the concentration value of a toxic or hazardous substance included in a "homogeneous part" of a respective p
"SJ/T 11363-2006 Requirements for Concentration Limits for Certain Hazardous Substances in Electronic Information Product
n"is a different legislation from EU RoHS Directive
Electronic Information Products Regulation"and
The date of manufacture
NotesConcentration Values of Toxic and Hazardous Substances/Elements (wt%)
Polybrominated Diphenyl
Provided in the package
Ethers(PBDE)
s".
art ot material exceeds the concentration limit regulated by
Polybrominated
Biphenyls (PBB)
mation Products".
and materials does not exceed the concentration limits
".
Chromium (Cr6+)
(2002/95/EC) information should be done separately.
)
(
Part Name
Subpart Name
Case
○
×
DECLARATION OF CONFORMITY
GEN5000W SERIES
We, TDK-Lambda Ltd., located at Haharoshet St. 56 Industrial Zone P.O.B. 500 Karmiel, Israel declare under our sole
responsibility that the GEN5000W series as detailed on the products covered sheet comply with the provisions of the
following European Directive and are eligible to bear the CE mark:
Restriction Of the use of certain Hazardous Substances Directive 2011/65/EU (RoHS2)
Low Voltage Directive 2006/95/EC
EMC Directive 2004/108/EC
Assurance of conformance of the described product with the provisions of the stated EC Directive is given through
compliance to the following standard:
Electrical Safety EN 60950-1:2006+A11+A1+A12
Electromagnetic Compatibility (EMC): EN 55022:1998+A1:2000+A2:2003
EN 55024:1998+A1:2001+A2:2003
EN 61000-3-3:1995+A2:2005
which cover testing to the following standards:
EN 55022:1998+A1:2000+A2:2003 Conducted Emissions Class A
Radiated Emissions Class A
EN 61000-3-3 :1995+A2:2005 Voltage Fluctuations
EN 61000-4-2 :1995+A1:1998+A2:2001 ESD AD: 8KV, CD:4KV
EN 61000-4-3 :2006 Radiated Immunity 3V/m
EN 61000-4-4 :2004 EFT/B Power leads: 2KV
Signal leads: 0.5KV
EN 61000-4-5 :2006 Conductive Surges Common mode: 2KV
Dierential mode 1KV
EN 61000-4-6 :2007 Conducted Disturbances 3Vrms
EN 61000-4-8 :1993+A1:2001 Immunity to Mag. Field 1A/m
EN 61000-4-11:2004 Voltage Dips
Our European Representative in the EU is TDK-Lambda UK Limited, located at Kingsley Avenue, llfracombe, Devon, EX34
8ES UK. Further, all products covered by this declaration are manufactured in accordance with ISO9000:2008 which
ensure continued compliance of the products with the requirements of the Low Voltage Directive and EMC Directive.
Name of Authorized SignatoryMartin Southam
Signature of Authorized Signatory
Position of Authorized SignatoryMarketing Director EMEA
Date4
th
April 2013
Date Series rst CE marked7 January 2008
Place where signedIlfracombe, Devon, England
PRODUCTS COVERED SHEET FOR:
GEN5000W series
1. GEN5000W with three phase input 190-240VAC
2. GEN5000W with three phase input 380-415VAC
with rated output 0-8VDC/0-600A up to 0-600VDC/0-8.5A and total output power equial or less 5100W
Optional modules:
1. IEEE (GPIB) module
2. Isolated analog (V/I) module
3. LAN module
4. USB module
TDK-Lambda Ltd., Industrial Zone P.O.B 500 Karmiel, Israel
CHAPTER 9 GERMAN TRANSLATION.........................................................................................
.
......
.............
.......
This page intentionaly left blank
WARRANTY
This TDK-Lambda Ltd. product is warranted against defects in materials and workmanship for a period ofve
years from date of shipment. During the warranty period, TDK-Lambda Ltd. will, at it's option, either repair or
replace products which prove to be defective.
LIMITATION OF WARRANTY
The warranty shall not apply to defects resulting from improper or inadequate usage or maintenance by
the buyer, buyer supplied products or interfacing. The warranty shall not apply to defects resulting from
unauthorized modications or from operation exceeding the environmental specications of the product or
if the QA seal has been removed or altered by anyone other than TDK-Lambda Ltd. authorized personnel.
TDK-Lambda Ltd. does not warrant the buyers circuitry or malfunctions of TDK-Lambda Ltd. products
resulting from the buyer's circuitry. Furthermore, TDK-Lambda Ltd. does not warrant any damage occurring
as a result ofthe buyer's circuitry or the buyer's - supplied products. No other warranty is expressed or
implied.
WARRANTY SERVICE
This product must be returned to an authorized TDK-Lambda Ltd. service facility for repairs or other warranty
service. For products returned to TDK-Lambda Ltd. for warranty service, the buyer shall prepay shipping
charges to TDK-Lambda Ltd. and TDK-Lambda Ltd. shall pay the shipping charges to return the product to
the buyer. Refer to section 3.11 for repackaging for shipment.
DISCLAIMER
The information contained in this document is subject to change without notice. TDK-Lambda Ltd. shall not
be liable for errors contained in this document or for incidental or consequential damages in connection
with the furnishing, performance or use of this material. No part of this document may be photocopied,
reproduced or translated into another language without the prior written consent of TDK-Lambda Ltd..
TRADEMARK INFORMATION
Genesys™ power supply is a trademark of TDK-Lambda Ltd. & TDK- Lambda Americas Inc.
Microsoft™ and Windows™ are trademarks of Microsoft Corporation.
1
REGULATORY NOTICES
FCC Notice
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two
conditions: (1) this device may not cause harmful interference, and (2) this device must accept any
interference received, including interference that maycause undesired operation.
NOTE: This equipment has been tested and found to comply with the limits for a Class A digital
device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio frequency energy and, if not
installed and used in accordance with the instruction manual, may cause harmful interference to
radio communications. Operation of this equipment in a residential area is likely to cause harmful
interference in which case the userwill be required to correct the interference at his ownexpense.
WARNING: Modifications not expressly approved by the party responsible for compliance could
void the user’s authorityto operate the equipment under FCC Rules.
CE Notice (European Union)
Marking by the CE Symbol indicates compliance to the EMC Directive and the Low Voltage
Directive of the European Union. Such marking is indicative that the Genesysseries GEN5000W
meets thefollowing technical standards:
TM
A “Declaration of Conformity” in accordance with the preceding directives and standards has been
made and is on file at our EU representative TDK-Lambda Limited, located at Kingsley Avenue,
Ilfracombe, Devon EX34 8ES, UK.
EN 55022:2010 Information technology equipment - Radio disturbance characteristics Limits andmethods of measurement.
EN 55024:2010 Information thecnology equipment - Immunity characteristics - Limits and
methods of measurement.
EN 60950-1:2006+A11:2009 + A1:2010 + A12:2011 Information technology equipment Safety - Part 1: General requirements.
WARNING: This is a Class A product. On a domestic environment this product may cause radio
interference in which case user maybe required to take adequate measures.
SAFETY APPROVALS:
UL 60950-1 Second Edition, UL Listed, C-UL for Canada, IEC 60950-1 Second Edition, CE
marking, when applied to the GEN5000W product, indicates compliance with the Low Voltage
Directive 2006/95/EC in that it complieswith EN 60950-1 Second Edition.
2
SAFETY INSTRUCTIONS
CAUTION
The following safety precaution must be observed during all phases of operation, service and repair
of this equipment. Failure to comply with the safety precautions or warnings in this document
violates safety standards of design, manufacture and intended use of this equipment and may
impair the built-in protections within.
TDK-Lambda Ltd. shall not be liablefor user’s failure to comply with these requirements.
INSTALLATION CATEGORY
The Genesyspower supply series has been evaluated to INSTALLATION CATEGORY II.
Installation category (over voltage category) II:local level, appliances, portable equipment etc.. With
smaller transient over voltage than Installation Category (overvoltage category) III.
TM
GROUNDING
This product isaSafety Class1instrument. To minimize shock hazard, the instrument chassis must
be connected to an electrical ground. The instrument must be connected to the AC power supply
mains throughathree conductor power cable for Single Phase models and throughafour conductor
power cable for Three Phase models with the ground wire firmly connected to an electrical ground
(safety ground) at thepower outlet.
For instruments designed to be hard-wired t
be connected to the safety electrical ground before another connection is made. Any interruption of
the protective ground conductor, or disconnection of the protective earth terminal will cause a
potential shock hazard thatmight cause personal injury.
o the supply mains, the protective earth terminal must
WARNING
OUTPUT TERMINAL GROUNDING
There isapotential shock hazardat the RS232/485 and the IEEE ports when using power supplies
with rated or combined voltage greaterthan 400V and the Positive Output of the Power Supply is
grounded. Do Not connectthe Positive Output to ground when using the RS232/485 or IEEE.
FUSES
Fuses must be changed by authorized TDK-Lambda Ltd. service personnel only. For continued
protection against risk of fire, replace only with the same type and rating of fuse. Refer to
maintenance instructions in chapter9for fuses rating.
CAUTION MULTI POLE FUSING
The GenesysTM power supply units have fuses in all supply conductots. To prevent potential risk
of hazard during servicing, the unit shall be fully disconnected from the supply.
INPUT RATINGS
Do not use AC supply which exceeds the input voltage and frequency rating of this instrument. The
input voltage and frequency rating of the Genesys power supply series is:190-240V~, 50/60Hz for
Three Phase 200V models and 380-415V~, 50/60Hz for Three Phase 400V models
reasons, the mains supplyvoltage fluctuations should not exceed +/-10% of nominalvoltage.
TM
. For safety
LIVE CIRCUITS
Operating personnel must not remove the instrument cover. No internal adjustment or component
replacement is allowed by non-TDK-Lambda Ltd. qualified personnel. Never replace componentswith
power cable connected. To avoid injuries, always disconnect power,discharge circuits and remove
external voltage source before touching components.
PARTS SUBSTITUTIONS & MODIFICATIONS
Parts substitutions and modifications are allowed by authorized TDK-Lambda Ltd.service personnel
only. For repairs or modifications, theinstrument must be returned to TDK-Lambda Ltd.service facility.
3
SAFETY INSTRUCTIONS.
ENVIRONMENTAL CONDITIONS
The Genesyspower supply series safety approval applies to the following operating conditions:
*Indoor use*Ambient temperature: 0 C to 50 C
*Maximum relative humidity: 90% (no condensation)*Altitude: up to 3000m
*Pollution degree 2
CAUTION
!
TM
oo
Do not use this product in environments with strong Electromagnetic field, corrosive
gas and conductive materials.
CAUTION Risk of Electrical Shock.
Instruction manual symbol. The
instrument will be marked with this
symbol when it is necessary for the
user to refer to the instruction
manual.
Indicates hazardous voltage.
-
-
On (Supply)
Direct Current (DC)
-
Alternative Current (AC)
~
Indicates ground terminal.
3~
Three-PhaseAlternating Current
Protective Ground Conductor Terminal
Off (Supply)
WARNING
CAUTION
Standby (Supply)
The WARNING sign denotes a hazard.An attentionto a procedureis called.
Not following procedure correctly could resultin personal injury.
AWARNING signshould not be skipped and all indicatedconditions must be
fully understood and met.
The CAUTION sign denotes a hazard. An attention to a procedure is called. Not
following procedure correctly could result indamage to the equipment. Do not proceed
beyond a CAUTION sign until allindicated conditions arefully understood and met.
4
567
CHAPTER 1GENERAL INFORMATION
1.1 USER MANUAL CONTENT
This user’s manual contains the operating instructions, installation instructions and specifications of
the Genesys5000W power supply series. The instructions refer to the standard power supplies,
including the built-in RS232/485 serial communication. For information related to operation with the
optional IEEE programming, refer to UserManual for PowerSupply IEEE Programming Interface.
1.2 INTRODUCTION
TM
1.2.1 General description
Genesyspower supplies are wide output range, high performance switching power supplies. The
Genesysseries is power factor corrected and operates from worldwide AC voltage range. Output
TM
TM
voltage and current are continuously displayed and LED indicators show the complete operating
status ofthe power supply. The Front panel controls allow the user to set the outputparameters, the
protection levels (Over-Voltage protection, Under-Voltage limit and Foldback) and preview the
settings. The rear panel includes the necessary connectors to control and monitor the power supply
operation by remote analog signals or by the built-in serial communication (RS232/485). GPIB
programming and Isolated-Analog programming/monitoring are optional.
1.2.2 Models covered by this manual
Models with rated output from 0-8VDC/0-600A to 0-600VDC/0-8.5A.
1.2.3 Features and options
Constant Voltage / Constant Current with automatic crossover.
*
* Active Power Factor correction.
* Single Phase or Three Phase options.
* Embedded Microprocessor Controller.
* Built in RS232/485 Interface.
* Voltage & Current high resolution adjustment by digital encoders.
* High accuracy programming/readback-16 bit.
* Software Calibration (no internal trimmers / potentiometers).
* Last Setting Memory.
* Independent Remote ON/OFF (opto-isolated) and Remote Enable/Disable.
* Parallel operation (Master/Slave) with Active current sharing.
* Remote sensing to compensate for voltage drop of power leads.
* External Analog Programming and Monitoring standard (0-5V or 0-10V, user selectable).
* Cooling fan speed control for low noise and extended fan life.
* Zero stacking- no ventillation holes at the top and bottom surface of the power supply.
* Optional GPIB interface (SCPI compatible).
* Optional Isolated Analog programming/monitoring (0-5V or 0-10V, user selectable
and 4-20mA).
1.2.4 Multiple output power system
The Genesyspower supplies series can be configured into a programmable power
TM
system of up to 31 units using the built-in RS232/RS485 communication port in the power
supply and the RS485 linking cable provided with each power supply.
In a GPIB system, each power supply can be controlled using the optional GPIB controller
(factory installed).
1.2.5 Control via the serial communication port
The following parameters can be programmed via the serial communication port:
1. Output voltage setting.
2. Output current setting.
3. Output voltage measurement.
4. Output on/off control.
5. Output current measurement.
6. Foldback protection setting.
7. Over-voltage protection setting and readback.
8. Under-Voltage limit setting and readback.
9. Power-supply start up mode (last setting or safe mode)
1.2.6 Analog voltage programming and monitoring
Analog inputs and outputs are provided at the rear panel for analog control of the power
supply. The output voltage and the current limit can be programmed by analog voltage or by
resistor, and can be monitored by analog voltage.The power supply output can be remotely
set to On or Off and analog signals monitor the proper operation of the power supply and the
mode of operation (CV/CC).
1.2.7 Parallel operation
Genesyspower supplies of the same output voltage and current rating canbe paralleled in
TM
master-slave configuration with automatic current sharingto increase power available.
1.2.8 Output connections
Output connections are made to rear panel bus-bars for models up to 100V and to a 4terminal wire clamp connector for models above 100V rated output voltage. Either the
positive or negative terminal may be grounded or the output may be floated. Models up to
60VDC Rated Output shall not float outputs more than +/- 60VDC above/below chassis
ground. Models >60VDC Rated Output shall not float outputs more than +/-600VDC
above/below chassis ground. Contact factory for assistance with higher float voltage
applications.
Local or remote sense may be used. In remote sense, the voltage drop on the load wires
should be minimized. Refer to the specifications for the maximum voltage drop value.
8
1.2.9 Cooling and mechanical construction
The Genesysseries is cooled by internal fans. At the installation, care must be taken to
allow free air flow into the power supply via the front panel and out of the power supply via
the rear panel. The Genesyspower supplies have a compact and lightweight package
TM
TM
which allows easy installation and space saving inthe application equipment.
CAUTION
Observe all torque guidelines within this manual. Over torqueing may damage
unit or accessories. Such damage is not covered under manufacturers warranty.
1.3 ACCESSORIES
1.3.1 General
Accessories are delivered with the power supply or separately upon ordering. The list below
shows the possible accessories and ordering numbers.
1.3.2 Serial link cable
S
erial link cable,for linking power suppliesby RS485 communication is provided with the
power supply.
Cable description: 0.5m length,shielded, RJ-45 type plugs, 8 contacts (P/N: GEN/RJ45).
1.3.3 Misc. hardware
*AC Input plug connector(Phoenix Contact, PC 6/4-STF-10,16)
* Strain relief for AC cord
* Output terminalshield
* DB25 plugkit (AMP, 749809-9).
* Plastic legsfor bench mounting.
1.3.4 AC cables
AC cables arenot provided with thepower supply.
Refer to Table1-1 for recommended AC input cables (customer supplied). Add a non-locking
plug approved bythe national safety standards of the country of usage.
AC Input Range
190-240V~ , Three Phase
Min 4x12AWG (3 wire plus safety ground),
stranded copper, 300V, 60 c minimum, rated for
AC Input Cable
O
25A. 3m max. length, outer diameter: 9~11mm.
380-415V~ , Three Phase
Min 4x14AWG (3 wire plus safety ground),
stranded copper, 600V, 60 c minimum, rated for
O
15A. 3m max. length, outer diameter: 9~11mm.
Table 1-1: Recommended AC input cable
9
CHAPTER 2SPECIFICATIONS
1.Vout voltage programming
2.Iout voltage programming (*13)
3.Vout resistor programming
4.Iout resistor programming (*13
5.On/off control
6.Output current monitor (*13)
7.Output voltage monitor
8.Power supply OK signal
9.Parallel operation
10.Series operation
11.CV/CC indicator
12.Enable/Disable
13.Local/Remote analog control
14.Local/Remote analog indicator
)
2.5 ANALOG PROGRAMMING AND MONITORING
---
---
---
---
---
---
---
---
---
---
---
---
---
---
0~100%, 0~5V or 0~10V, user selectable. Accuracy and linearity: +/-0.5% of rated Vout.
0~100%, 0~5V or 0~10V, user selectable. Accuracy and linearity: +/-1% of rated Iout.
0~100%, 0~5/10Kohm full scale, user selectable. Accuracy and linearity: +/-1% of rated Vout.
0~100%, 0~5/10Kohm full scale, user selectable. Accuracy and linearity: +/-1.5% of rated Iout.
By electrical Voltage: 0~0.6V/2~15V or dry contact, user selectable logic.
0~5V or 0~10V, user selectable. Accuracy: +/-1%.
0~5V or 0~10V, user selectable. Accuracy : +/-1%.
4~5V-OK, 0V-Fail. 500ohm series resistance.
Possible , up to 4 units in master/slave mode with two wires current balance connection.
Possible (with external diodes), up to 2 units. 600Vdc max.from chassis ground.
Open collector. CC mode: On, CV mode: Off. Maximum voltage : 30V, maximum sink current: 10mA
Dry contact. Open: Off, Short: On. Max. voltage at Enable/Disable in: 6V.
By electrical signal or Open/Short: 0~0.6V or short: Remote, 2~15V or open: Local.
Open collector. Local: Open, Remote: On. Maximum voltage: 30V, maximum sink current: 10mA.
2.1 OUTPUT RATING
1.Rated output voltage(1*)
2.Rated output current (*2)
3.Rated output power
V
A
W
MODEL
GEN
8-600
8
600
4800
10-500
10
500
5000
16-310
16
310
4960
20-250
20
250
5000
30-170
30
170
5100
40-125
40
125
5000
60-85
60
85
5100
80-65
80
65
5200
100-50
100
50
5000
150-34
150
34
5100
200-25
200
25
5000
300-17
300
17
5100
400-13
400
13
5200
500-10
500
10
5000
600-8.5
600
8.5
5100
2.2 INPUT CHARACTERISTICS
3-Phase, 200V models:
3-Phase, 400V models:
---
--%
0.94 @200/380Vac, rated output power.
3-Phase, 200V models: 170~265Vac, 47~63Hz
3-Phase, 400V models: 342~460Vac, 47~63Hz
3-Phase 200V models: Less than 50A
3-Phase 400V models: Less than 20A
V
8
10
16
20
30
60
40150
200
300
500
100
80
600
400
21
10.5
22
11
22
11
22
12
22
11
22
11
22
11
22
11
22
11
22
11
22
11
22
11
22
11
22
11
22
11
3.Power Factor (Typ)
4.Efficiency (*4)
5.Inrush current (*5)
2.Maximum
Input current
at 100% load
1.Input voltage/freg. (*3)
---
A
83
84
84
86
88
86
88
88
90
88
88
88
88
88
88
8
10
16
30
20
40
60
80
150
100
200
300
400500
600
2.3 CONSTANT VOLTAGE MODE
1.Max. Line regulation (*6)
2.Max. Load regulation (*7)
3.Ripple and noise (p-p , 20MHz) (*8)
4.Ripple r.m.s., 5Hz~1MHz
5.Temperature coefficient
6.Temperature stability
7.Warm-up drift
8.Remote sense compensation/wire
9.
11.Transient response time
12.Hold-up time (Typ)
Up-prog. response time, 0~Vomax.(*9)
10.Down-prog. response time
Full load(*9)
No load(*10)
V
---
--mV
mV
---
---
V
mS
PPM/ C
o
mS
mS
mS
0.01% of rated output voltage
0.015% of rated output voltage +5mV
75
8
70
10
75
8
75
10
70
8
80
15
120
20
200
60
300
70
350
70
450
100
70
10
70
8
90
15
200
45
50PPM/ C from rated output voltage, following 30 minutes warm-up.
O
0.01% of rated Vout over 8 hrs interval following 30 minutes warm-up. Constant line, load & temp.
Less than 0.05% of rated output voltage +2mV over 30 minutes following power on.
2
2
2
2
5
5
5
5
5
5
5
5
5
65
135
5
80
170
5
100
200
15
30
50
400
500
600
700
80
800
900
100
50
1000
1200
1500
2000
2500
3000
3000
3000
Time for output voltage to recover within 0.5% of its rated output for a load change 10~90% of rated output
current. Output set-point: 10~100%, Local sense.
Less than 1mS, for models up to and including 100V. 2mS, for models above 100V.
5mSec Typical. Rated output power.
V
8
10
16
20
40
30
60
80
100
150
300
400
500
600
200
2.4 CONSTANT CURRENT MODE
1.Max. Line regulation (*6)
2.Max. Load regulation (*11)
3.Load regulation thermal drift
4.Ripple r.m.s. 5Hz~1MHz (*12)
5.Temperature coefficient
6.Temperature stability
7.Warm-up drift
---
---
---
---
---
mA
PPM/ C
o
0.05% of rated output current
0.1% of rated output current
70PPM/ C from rated output current, following 30 minutes warm-up.
0.01% of rated Iout over 8hrs interval following 30 minutes warm-up. Constant line, load & temperature.
O
Less than 0.1% of rated output current over 30 minutes following load change.
1600
1000
700
1700
180
350
50
50
120
80
50
20
10
10
15
8~16V model: Less than +/-0.5% of rated output current over 30 minutes following power on.
20V~600V model: Less than +/-0.25% of rated output current over 30 minutes following power on.
10
2.6 PROGRAMMING AND READBACK (RS232/485, Optional LAN/IEEE Interface)
1.Vout programming accuracy (*14)
2.Iout programming accuracy (*13)
3.Vout programming resolution
4.Iout programming resolution
5.Vout readback accuracy
6.Iout readback accuracy (*13)
7.Vout readback resolution
8.Iout readback resolution
---
---
---
---
---
---
% of rated
output voltage
% of rated
output current
0.05% of rated output voltage
0.1% of actual output current +0.3% of rated output current
0.002% of rated output voltage
0.002% of rated output current
0.05% of rated output voltage
0.3% of rated output current
2.7 PROTECTIVE FUNCTIONS
1.Foldback protection
2.Over-voltage protection (OVP)
3.Over-voltage trip point
4.Output under voltage limit (UVL)
5.Over temperature protection
---
---
---
---
V
Output shut-down when power supply change from CV to CC User presetable.
Inverter shut-down, manual reset by AC input recycle or by OUT button or by communication port command.
Preset by front panel or communication port. Prevents from adjusting Vout below limit. Does not affect analog
programming.
User selectable, latched or non latched.
0.5~10
0.5~12
2~36
1~24
1~19
2~44
5~66
5~165
5~110
5~88
5~220
5~330
5~440
5~550
5~660
V
8
16
2010
30
40
60
80
100
150
200
300
400
500
600
0.002%
0.002%
0.007%
0.006%0.011%
0.004%
0.003%
0.002%
0.002%
0.011%
0.007%
0.006%
0.004%
0.003%
0.003%
0.002%
0.004%
0.005%0.003%
0.006%
0.009%
0.002%
0.002%
0.003%
0.004%
0.005%
0.006%
0.008%
0.011%
0.002%
V
8
16
2010
30
40
60
80
100
150
200
300
400
500
600
2.8 FRONT PANEL
---
---
---
---
---
---
---
---
---
---
---
---
---
Vout/Iout manual adjust by separate encoders (coarse and fine adjustment).
OVP/UVL manual adjust by Vout. Adjust encoder.
Address selection by Voltage Adjust encoder. No of addresses:31.
Go to local control.
Output on/off
AC on/off
Front panel Lock
Foldback control
Baud rate selection: 1200, 2400, 4800, 9600 and 19200.
Re-start modes (automatic restart, safe mode).
Vout: 4 digits, accuracy: 0.05% of rated output voltage +/-1count.
Iout:4 digits, accuracy: 0.2% of rated output current +/-1count.
VOLTAGE, CURRENT, ALARM, FINE, PREVIEW, FOLDBACK, REMOTE(RS232,RS485,IEEE), OUTPUT ON,
FRONT PANEL LOCK.
1.Control functions
2.Display
3.Indications
2.9 ENVIRONMENTAL CONDITIONS
1.Operating temperature
2.Storage temperature
3.Operating humidity
4.Storage humidity
5.Altitude
---
--%
%
---
0~50 C, 100% load.
-20~85 C
20~90% RH (no condensation).
10~95% RH (no condensation).
Maximum 3000m. Derate output current by 2%/100m above 2000m.
o
o
2.10 MECHANICAL
1.Cooling
2.Weight
3.Dimensions (WxHxD)
4.Vibration
5.Shock
---
Kg
mm
---
---
Forced air cooling by internal fans.
Less than 16Kg.
W: 423, H: 88, D: 442.5 (Refer to Outline drawing).
MIL-810F, method 514.5
Less than 20G, half sine, 11mS. Unit is unpacked.
Models with Vout 50V: Output is SELV, all communication/control interfaces (RS232/485, IEEE, Isolated Analog,
LAN, Sense, Remote Programming and Monitoring) are SELV.
Models with 60V Vout 400V: Output is Hazardous, communication/control interfaces: RS232/485, IEEE,
Isolated Analog, LAN, Remote Programing and Monitoring (pins 1-3, pins14-16) are SELV, Sense, Remote
Programming and Monitoring (pins 8-13, pins 21-25) are Hazardous.
Models with 400V Vout 600V: Output is Hazardous, all communication/control interfaces (RS232/485, IEEE,
Isolated Analog, LAN, Sense, Remote Programming and Monitoring) are Hazardous.
Vout 50V models : Input-Output (SELV): 4242VDC 1min, Input-communication/control (SELV): 4242VDC 1min,
Input-Ground: 2828VDC 1min,
60V Vout 100V models: Input-Output (Hazardous): 2600VDC 1min, Input-communication/control (SELV):
4242VDC 1min, Output(Hazardous)-SELV: 1900VDC 1min, Output(Hazardous)-Ground: 1200VDC 1min,
UL 60950-1, CSA22.2 No.60950-1, IEC 60950-1, EN 60950-1
EN55022, EN55024, EN61000-3-3, FCC part 15, VCCI.
Conducted emmision - EN55022 class A, FCC part 15 class A, VCCI class A.
Radiated emmision - EN55022 class A, FCC part 15 class A, VCCI class A.
Immunity - EN55024
11
NOTES:
*1: Minimum voltage is guaranteed to maximum 0.2% of the rated output voltage.
*2: Minimum current is guaranteed to maximum 0.4% of the rated output current.
*3: For cases where conformance to various safety standards (UL, IEC etc.) is required, to be
described as 190~240Vac (50/60Hz) for 3-Phase 200V models, and 380~415Vac (50/60Hz)
for 3-Phase 400V models.
*4: 3-Phase 200V models: at 200Vac input voltage.
3-Phase 400V: at 380Vac input voltage. With rated output power.
*5: Not including EMI filter inrush current, less than 0.2mSec.
*6: 3-Phase 200V models: 170~265Vac, constant load.
3-Phase 400V models: 342~460Vac, constant load.
*7: From No-load to Full-load, constant input voltage. Measured at the sensing point in Remote
Sense.
*8: For 8V~300V models: measured with JEITA RC-9131A (1:1) probe.
For 600V model: measured with 10:1probe.
*9: From10% to 90% or 90% to 10% of rated output voltage, with rated , resistive load.
*10: From 90% to 10% of rated output voltage.
*11: For load voltage change, equal to the unit voltage rating, constant input voltage.
*12: For 8V~16V models the ripple is measured at 2V to rated output voltage and rated output
current. For other models, the ripple is measured at 10~100% of rated output voltage and
rated output current.
*13: The Constant Current programming, readback and monitoring accuracy does not include
the warm-up and Load regulation thermal drift.
*14: Measured at the sensing point.
2.12 SUPPLEMENTAL CHARACTERISTICS
The supplemental characteristics give typical but non-warranted performance characteristics.
The supplemental characteristics are useful in assessing applications for the power supply.
Several kinds of supplemental characteristics are listed below.
1.Evaluation Data: Typical performance of the power supply.
2.Reliability Data: Reliability performance of the power supply.
3.EN61000 Data: Performance of the power supply under EN61000 test conditions.
4.EMI Data: Typical EMI (conducted and radiated) performance of the power supply.
The supplemental characteristics data is held in each Lambda sales and service facility. For further
details please contact the Lambda office nearest you.
12
2.13 GENESYS5000W POWERSUPPLIES
TM
Table 1
Dimension/Model
8V-10V
16V-100V
517.5mm
L
497.5mm
Note 7
50.0
19.0
Note 6
104+/-2.0mm
60.5
92.0
92.0
442.5 1.0mm
642.5 1.0mm
L 1.0 (See Table 1)
35.5 1.0mm
Note 5
Note 3
42.0
A
A
A
86+/-0.3
OUTLINE DRAWINGS
-
I
D
a
d
T
amb
L
76.2
88.0mm 0.3
482.0 1.0mm
423.0 1.0mm
Note 1
Note 2
Note 4
NOTES:
1.Analog programming connector. Mating plug supplied with power supply.
2.Bus-bars for 8V to 100V models. See detail.
Wire clamp connector for 150V to 600V models (shown).
3. AC cable strain relief (supplied with power supply).
4. AC input connector (supplied with plug-in connector).
Header P/N: PC6-16/4-GF-10,16 Phoenix Contact
5. Chassis slides mounting holes #10-32 marked "A". GENERAL DEVICES
P/N: CC3001-00-S160 or equivalent.
6. Bus Bar enclosure for 60V to 600V.
7. Mounting holes for 19” rack. Use M6x16 screws to fix the unit to the rack.
13
Note 2: Bus-Bar Detail
16V to 100V Models
5.0mm
40.0mm
50.0mm
Note 2:Bus-Bar Detail
8V to 10V Models
5.0mm
60.0mm
50.0mm
30.0mm
10.5mm
30.0mm
10.5mm
CHAPTER 3INSTALLATION
3.1 GENERAL
This chapter contains instructions for initial inspection, preparation for use and repackaging for
shipment. Connection to PC, setting the communication port and linking Genesyspower supplies
are described in Chapter 7.
WARNING
The Genesysseries is intended only for installation in
Restricted Access Location (RAL). Access to Hazardous
parts (rear side of the power supply) shall be prevented after
installation.
Genesyspower supplies generate magnetic fields which
might affect the operation of other instruments. If your
equipment is susceptible to magnetic fields, do not position
it adjacent to the power supply
TM
TM
NOTE
WARNING
TM
.
through the front panel slits.
3.2 PREPARATION FOR USE
To avoid electric shock hazard, do not insert conductive parts
I
n order to be operational the power supply must be connected to an appropriate AC source. The
AC source voltage should be within the power supply specification. Do not apply power before
reading, Section 3.6 and 3.7.
Table 3-1 below, describes the basic setup procedure. Follow the instructions in Table 3-1 in the
sequence given to prepare the power supply for use.
Step no.
1
2
3
4
5
6
ItemDescriptionReference
Inspection
Installation
AC source
Test
Load connection
Default setting
Initial physical inspection of the power supply
Installing the power supply,
Ensuring adequate ventillation.
AC source requirements
Connecting the power supply to the AC source.
Turn-on checkout procedure.
Wire size selection. Local /Remote sensing.
Single or multiple loads.
The power supply setting at shipment.
Section 3.3
Section 3.4
Section 3.5
Section 3.6
Section 3.7
Section 3.8
Section 3.9
Section 7.2.1
Table 3-1: Basic setup procedure
3.3 INITIAL INSPECTION
Prior to shipment this power supply was inspected and found free of mechanical or electrical
defects. Upon unpacking of the power supply, inspect for any damage which may have occured in
transit.
The inspection should confirm that there is no exterior damage to the power supply such as broken
knobs or connectors and that thefront panel and meters face arenot scratched or cracked. Keep all
packing material until the inspection has been completed. If damage is detected, file a claim with
carrier immediately and notify the Lambdasales or servicefacility nearest you.
3.4 RACK MOUNTING
The Genesys power supply seriesis designed to fit in a standard 19” equipment rack.
TM
3.4.1 To install thePower Supply in a rack:
1. Use the front panel rack-mount brackets to install the power supply in the rack.
2. Use a support bar toprovide adequate supportfor the rear of the power supply. Do notobstruct
the air exhaust at the rearpanel of the unit.
14
15
WARNING
Some components inside the power supply are at AC voltage even when the On/Off switch is in the
“Off”position. To avoid electric shock hazard, disconnect the line cord and load and wait two
minutes before removing cover.
CAUTION
AC Input Wires No Conductor Pretreatment: Phoenix Contact clamping parts are designed so
that all kindsof copper conductors can be clamped withoutpretreatment.
It is forbidden to solder the conductors. The solder tin yields and fractures under high pressure. The
result is increased contact resistance and an excessive temperature rise. In addition, corrosion
caused by pickling or fluxes has been observed on soldered conductor ends. Notch fractures at the
transition point from the rigid tothe flexible conductorarea are also possible.
The power supply ON/OFFswitch is not the main disconnect device and does not completely
disconnect all the circuits from the AC source.
An appropiately rated disconnect device such as circuit breaker, type B plug on power cord, ...etc.,
shall be provided in the final installation. The disconnect device shall comply with UL/IEC 60950-1
requirements andshall be easily accessible.
3.7.1 AC Input Connector
TheAC input connector is a header (Phoenix Contact P/N:PC6-16/4-GF-10, 16) with a screw
plug in connector (Phoenix Contact P/N: PC 6/4-STF-10,16), locatedon the rearpanel.
Use suitablewires and tightening torque as follows:
1. Wire diameter: 12AWG for three-phase 200V models and
14AWG for three-phase 400V models. Refer to Table 1-1 for details.
Refer to section 1.3.4 for details of the recommendedAC input cords and to section 3.7 for
disconnected device requirement.
3.7.3 AC Input Wire Connection
1.Stripthe outside insulationof theAC cable approx. 10cm. Trimthe wires so that the ground wireis
10mm longer than the other wires.Strip 10mmat the endof each of the wires.
2.Unscrew the base of the strainrelief from thehelix-shaped body. Insert the base through the
outside openingin theAC input cover and screw the locknut securely (11-14 Lb-inch.)into the
base, from the inside.
3.Slide the helix-shaped body onto theAC cable. Insert thestripped wires through the strain relief
base until the outer cable jacketis flush withthe edge of the base. Tighten (16-18 Lb-inch.) the
body to the base while holdingthe cable inplace. Now the cable is securely fastenedinside the
strain relief. Refer to Fig.3-2.
Screw-on
Locknut
Fig.3-2: Stripped Wires installed in Strain Relief
16
Loading...
+ 57 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.