TDK-Lambda ESS 150-100 Operator Manual

OPERATOR MANUAL FOR
EMBEDDED IEEE-488
PROGRAMMING INTERFACE
Document: 83-468-007 Rev B
MODEL _______________________
SERIAL _________________
Tel: (732) 922-9300
Fax: (732) 922-9334
Web: www.lambda-emi.com
Table of Contents
1. THE DIGITAL PROGRAMMING OPTION................................................... 1
1.1 OVERVIEW: IEEE AND RS-232 PORTS ........................................................1
1.2 SCOPE
1.3 USING
OF MANUAL ......................................................................................2
DIGITAL PROGRAMMING .................................................................2
1.3.1 THE IEEE-488.2 INTERFACE............................................................2
1.3.2 THE RS-232 INTERFACE ..................................................................2
1.3.3 IEEE AND RS-232 INTERACTION ....................................................2
1.4 CONFIGURING
THE IEEE INTERFACE.........................................................3
1.4.1 CONFIGURING THE IEEE CONTROLLER .......................................3
1.4.2 CONFIGURING THE IEEE INTERFACE ...........................................3
1.5 GETTING
STARTED WITH THE SOFTWARE................................................4
1.5.1 EXAMPLE SESSION USING THE ‘IBIC’ CONSOLE.........................4
1.5.2 EXAMPLE PROGRAM WRITTEN IN VISUAL BASIC .......................4
1.5.3 EXAMPLE PROGRAM WRITTEN IN LABVIEW ................................5
1.6 PROGRAMMING
VOLTAGE AND CURRENT ...............................................6
1.6.1 PROGRAM OUTPUT VOLTAGE .......................................................6
1.6.2 PROGRAM OUTPUT CURRENT.......................................................6
1.6.3 DISABLE THE SUPPLY OUTPUT .....................................................6
1.6.4 ENABLE THE SUPPLY OUTPUT ......................................................7
1.6.5 READ PROGRAMMING MODE .........................................................7
1.7 MEASURING
VOLTAGE AND CURRENT......................................................8
1.7.1 MEASURE VOLTAGE ........................................................................8
1.7.2 MEASURE CURRENT........................................................................8
1.7.3 SET MEASUREMENT FILTERING ....................................................8
1.8 LIMITS
AND PROTECTIONS..........................................................................9
1.8.1 SET VOLTAGE LIMIT.........................................................................9
1.8.2 SET CURRENT LIMIT ........................................................................9
1.8.3 OVER-VOLTAGE PROTECTION......................................................9
1.8.4 OVER-CURRENT PROTECTION ...................................................10
1.9 COMMON
COMMANDS................................................................................12
1.9.1 READ DEVICE IDENTITY ................................................................12
1.9.2 GO TO LOCAL..................................................................................12
1.9.3 REMOTE ENABLE ...........................................................................12
1.9.4 READ STATUS BYTE REGISTER...................................................12
1.9.5 RESET THE POWER SUPPLY........................................................13
1.9.6 CHANGING THE POWER-UP DEFAULTS......................................13
1.10 USING
ERROR AND STATUS REGISTERS ................................................13
1.10.1 OVERVIEW: REGISTER FAN-OUT.................................................14
1.10.2 GLOSSARY OF REGISTER TERMS...............................................14
1.10.3 CLEAR ALL STATUS REGISTERS .................................................17
1.10.4 SERIAL POLL AND STATUS BYTE REGISTER ...........................17
1.10.5 STANDARD EVENT STATUS REGISTER .....................................18
1.10.6 THE OPERATIONAL REGISTERS ..................................................19
1.10.7 THE QUESTIONALBE REGISTERS................................................21
2. THE RS-232 INTERFACE ......................................................................... 22
Document: 83-468-007 Rev B
2.1 CONFIGURING
2.1.1 THE RS-232 CABLE.........................................................................22
2.1.2 DEFAULT RS-232 CONFIGURATION.............................................22
2.2 RS-232
2.2.1 CHANGE CHARACTER ECHO........................................................24
2.2.2 GO TO LOCAL COMMAND..............................................................25
2.2.3 CHANGE THE BAUD RATE.............................................................25
2.2.4 CHANGE THE DATA BITS...............................................................25
2.2.5 CHANGE THE PARITY BITS ...........................................................26
2.2.6 CHANGE THE STOP BITS...............................................................26
2.3 ERROR
COMMAND SET ...............................................................................24
REGISTERS AND RS-232...............................................................27
THE RS-232 INTERFACE...................................................22
3. ADJUST THE IEEE CALIBRATION.......................................................... 28
3.1 INTRODUCTION ...........................................................................................28
3.2 CALIBRATE
3.3 CALIBRATE
3.4 CALIBRATE
3.5 CALIBRATE
THE VOLTAGE PROGRAMMING...........................................28
THE VOLTAGE MEASUREMENT...........................................30
THE CURRENT PROGRAMMING ..........................................31
THE CURRENT MEASUREMENT ..........................................32
4. SUMARY TABLE OF COMMANDS .......................................................... 35
List of Tables
Table 1. The *SAV 0 Command............................................ 13
Table 2. The Status Byte Register......................................... 17
Table 3. The Standard Event Status Register ....................... 18
Table 4. The Operational Registers....................................... 19
Table 5. Default RS-232 Configuration .................................. 22
Table 6. RS-232 Echo Settings ............................................. 24
List of Figures
Figure 1. IEEE Address Switch Settings ................................... 3
Figure 2. Status and Error Register Diagram.......................... 15
Figure 3. Status and Error Handler ......................................... 16
Figure 4. RS-232 Cable Construction ..................................... 23
Document: 83-468-007 Rev B
WARNING:
When a power supply with IEEE option is first powered ON, or when a “Go To Local” command is sent, the supply output will jump to whatever is set on the front panel knobs.
Therefore, it is recommended the front panel Voltage and Current knobs be turned counter-clockwise to ZERO before REMOTE programming.
1 THE DIGITAL PROGRAMMING OPTION
1.1 OVERVIEW: IEEE AND RS-232 PORTS
Most power supplies come standard with the Local and Analog Remote programming modes which use the front panel knobs or the back panel 25 pin ‘D’ connector. A third programming mode, Digital Remote, is available as an option. This option adds an em­bedded interface board with two extra connectors to the back of the supply.
The connectors allow cables to be run from the supply to a remotely located operator terminal or to a computer running an automation program. A terminal allows the operator to type commands to the power supply which take affect as soon as they are typed. An automation program will allow several power supplies to be ‘daisy chained’ together. It also allows other instruments, including relay switchers and measurement devices, to be synchronized with the power supplies in complex power systems.
When the supply is running in the digital programming mode, the front panel knobs are disabled but all the front panel indicators still show the status of the supply. The power supply output levels and operating states may be monitored through the computer port.
Commands that are standard with digital programming include:
Introduction
1
Program Voltage Program Current
Measure Voltage • Measure Current
Set Maximum Voltage Set Maximum Current
Over-Voltage Shutdown Over-Current Shutdown
Error and Status Messages
Computerized Calibration
IEEE-488.2 Compliant SCPI Compliant
Document: 83-468-007 Rev B
1.2 SCOPE OF MANUAL
This manual contains the information needed to setup and operate the embedded digital interface used in the Lambda EMI power supplies including the EMS and ESS models. The interface is contained on one circuit card. It may be optionally installed by Lambda facilities at the time of purchase.
This manual does NOT include specifications for digital accuracy and response rate. These values are only valid for the power supply in which the interface is installed, so the specifications are given in the User Manual for the power supply.
1.3 USING DIGITAL PROGRAMMING
1.3.1 THE IEEE-488.2 INTERFACE
The IEEE-488 digital programming interface (also called the GPIB interface) is a popular way to connect instruments to a computer. It uses a specialized 24-pin cable with con­nectors that allow cables to be ‘stacked’ together. There are eight data wires, eight con­trol wires and eight ground wires. If the system runs from a personal computer, there are numerous vendors of IEEE controller cards and software.
The IEEE-488 standard has gone through several upgrades. The IEEE-488.1 focused on the handshaking of the eight control lines. The IEEE-488.2 added status registers in­side each instrument and it added common commands to make programming groups of instrument easier. The latest specification, SCPI, adds guidelines for the command syn­tax so one vendor’s power supply will use the same commands as another’s. The Lambda interface follows all of these standards.
Because up to 15 instruments may be connected and independently controlled by a sin­gle IEEE controller, each instrument must have a unique address. On the power supply, the address is set by a DIP switch accessible through a slot in the back panel.
Introduction
2
1.3.2 THE RS-232 INTERFACE
The second connector on the interface board is for the RS-232 serial port. It uses a 9-pin “D” connector. Only three wires are used: transmit data, receive data, and ground. Compared to the IEEE port, the RS-232 is slower and it has limited status and error re­porting. Also, there is no instrument addressing so only one power supply can be run from each controller port. The advantage of RS-232 is the cable is easy to make and every personal computer and terminal comes standard with it.
The RS-232 specification does not include any requirements for command syntax. For this port, a “short form” command set is available where each command has only a cou­ple of characters. The short form commands are easy to type into a terminal program.
1.3.3 IEEE AND RS-232 INTERACTION
When the power supply is first powered up, the RS-232 serial port is active. If a com­mand is sent over the IEEE bus, the IEEE port becomes enabled and the RS-232 port will no longer function. To restore the function to the RS-232 port, the power supply must be cycled off and on.
Document: 83-468-007 Rev B
1.4 CONFIGURING THE IEEE INTERFACE
1.4.1 CONFIGURING THE IEEE CONTROLLER
A typical IEEE controller is a personal computer with a IEEE interface card. Each card vendor supplies its own configuration instructions and interface software.
Each time the software is executed, the controller must be configured as follows:
Controller Address = 0. This is factory default for all controllers.
EOI Flag = TRUE. The “End or Identify” is a control line in the IEEE cable that
is asserted when the last character of a message string is sent. It is required for Lambda EMI supplies
EOS Flag = FALSE: The “End of String” is used in some instruments to say a
character, such as a linefeed, marks the last character of a message. The Lambda EMI supply does not require an end of string character.
1.4.2 CONFIGURING THE IEEE INTERFACE
The power supply is connected to the controller using a standard IEEE-488 cable. Stan­dard connecting requirements are as follows:
Verify the power supply is switched OFF before connecting any cables to it.
ConfiguringBeginning Software
3
A maximum of 15 devices may be connected to any one IEEE bus. Maximum
cable length between any two devices should be six feet. Total cable length should be less than 65 feet.
Before powering up the supply, set the IEEE address on its back panel switch.
It is labeled “IEEE ADDRESS”. Each device on the IEEE bus must have a unique address. The controller is normally at address = 0 and address = 31 is reserved, so the available addresses are from 1 to 30. See Figure 1.
Before powering up the supply, verify the FORCED LOCAL switch on IEEE
address switch is downward for OFF. Setting this switch ON will disable re­mote programming over the IEEE and RS-232 busses. See Figure 1.
Figure 1. IEEE Address Switch Settings
Document: 83-468-007 Rev B
1.5 GETTING STARTED WITH THE SOFTWARE
A computer can use a variety of controllers, programs, and programming languages for the IEEE bus. Here are three examples showing minimal programs to set the voltage, set the current and measure the voltage from a Lambda EMI power supply.
1.5.1 EXAMPLE SESSION USING THE ‘IBIC’ CONSOLE
A popular console program is National Instruments “Win32 Interactive Control” (file: ibic.exe). As the operator types each command on the computer, at the colon prompt, it is immediately sent to the power supply. This example works only for computers with National Instruments and compatible IEEE controller cards.
Win32 Interactive Control Copyright 1996 National Instruments Corporation All rights reserved.
Type 'help' for help or 'q' to quit.
: ibdev Controller address enter board index: 0 enter primary address: 4 enter secondary address: 0 enter timeout: 13 enter 'EOI on last byte' flag: 1 enter end-of-string mode/byte: 10
ud0: ibwrt "sour:volt 100" [0100] ( cmpl ) count: 12
Program supply to
ud0: ibwrt "sour:curr 5" [0100] ( cmpl ) count: 11
ud0: ibwrt "meas:volt?" output voltage?” [0100] ( cmpl ) count: 10
ud0: ibrd 50 [2100] ( end cmpl ) count: 11 31 30 30 2e 30 38 33 31 1 0 0 . 0 8 3 1 30 31 0a 0 1 .
Supply reported output voltage
Supply Address on DIP Switch
Program supply to 100 volts output
5 amps output
Query: “What is
Read response
4
1.5.2 EXAMPLE PROGRAM WRITTEN IN VISUAL BASIC
Microsoft’s Visual Basic is a windows programming language that may be used to create “virtual instruments” and automation programs. Here is a simple program which sends commands to a Lambda EMI power supply to set the voltage, set the current and meas­ure the voltage. The program’s window only conatains two items: a “Start” button and a text box to show the measured voltage. The syntax of the CALLed functions are correct only for National Instruments and compatible IEEE controllers. Don’t forget to add the forms “Ni-global.bas” and “Vbib-32.bas” to you project.
Document: 83-468-007 Rev B
Beginning Software
Example Program Written in Visual Basic
Option Explicit Dim LambdaUD As Integer 'supply device descriptor Dim strMeasVolt As String * 50 'buffer for reading input message
Private Declare Function GetTickCount Lib "kernel32" () As Long
Private Sub cmdStart_Click() 'start program here after "Start" button clicked 'open IEEE port, get "User Device Description" = LambdaUD 'assume power supply address is set to "4" on DIP switch Call ibdev(0, 4, 0, T3s, 1, 10, intLambdaUD)
Call ibwrt(LambdaUD, "volt 100") 'program output to 100 volts Call ibwrt(LambdaUD, "curr 2") 'program output to 2 amps Wait 500 'wait 0.5 sec for output to settle Call ibwrt(LambdaUD, "meas:volt?") 'ask "What is output voltage?" Call ibrd(LambdaUD, strMeasVolt) 'read back output voltage txtOutVolt.Text = strMeasVolt 'display output voltage on window End Sub
Private Sub Wait(mSecWait As Long) 'subroutine to wait "mSecWait" milliseconds Dim StartTime As Long StartTime = GetTickCount Do Loop While (GetTickCount - StartTime < mSecWait) End Sub
5
1.5.3 EXAMPLE PROGRAM WRITTEN IN LABVIEW
The National Instruments LabVIEW programming language is a popular language which is optimized for instrument control and data analysis. It is a graphical language where functions are shown as icons with connection points and data flows along drawn lines. Here is a simple program which sends commands to a Lambda EMI power supply to set the voltage, set the current and measure the voltage. The program’s window only cona­tains two items: a numeric control for the supply IEEE address and a text indicator to show the measured voltage.
Document: 83-468-007 Rev B
Program OutputBeginning Software
1.6 PROGRAMMING VOLTAGE AND CURRENT
1.6.1 PROGRAM OUTPUT VOLTAGE
The output voltage can be programmed by sending the command:
SOURCE:VOLTAGE:AMPLITUDE <nn.nn>
where <nn.nn> is any valid voltage with or without decimal places. There must be a space before the number.
Per the Summary Table in Section 4, the command can be abbreviated in any of the fol­lowing ways:
SOUR:VOLT:AMPL <nn.nn> SOUR:VOLT <nn.nn> VOLT:AMPL <nn.nn> VOLT <nn.nn>
The power supply output will not reach the programmed voltage until a Program Current command is also sent. To get the sharpest transition from zero to programmed output, disable the output (Section 1.6.3), program voltage and current, then enable the output.
If the voltage is more than the supply output or less than zero, the command will be ig­nored and the Command Error bit of the Standard Event Status Register will be set. If the voltage is higher than the limit set by the SOURCE:VOLTAGE:LIMIT value, the command will be ignored and the Execution Error bit of the Standard Event Status Reg­ister will be set.
To read what voltage the supply was programmed to, regardless of the actual voltage, send query SOUR:VOLT:AMPL? and read the response message.
The short form of “program voltage” is: PV <nn.nn>
6
1.6.2 PROGRAM OUTPUT CURRENT
The output current is programmed by sending the command:
SOURCE:CURRENT:AMPLITUDE <nn.nn> or “CURR” <nn.nn>
where <nn.nn> is any valid current with or without decimal places. There must be a space before the number.
The power supply output will not reach the programmed current until a program voltage command is also sent. To get the sharpest transition from zero to programmed output, disable the output (Section 1.6.3), program voltage and current, then enable the output.
If the <nn.nn>is more than the supply output or less than zero, the command will be ig­nored and the Command Error bit of the Standard Event Status Register will be set. If the current is higher than the limit set by the SOURCE:CURRENT:LIMIT value, the command will be ignored and the Execution Error bit of the Standard Event Status Reg­ister will be set.
To read what current the supply was programmed to, regardless of the actual output cur­rent, send query SOUR:CURR:AMPL? and read the response message.
The short form of “program current” is: PC <nn.nn>
1.6.3 DISABLE THE SUPPLY OUTPUT
Document: 83-468-007 Rev B
The power supply output can be shut off by sending this command:
SOURCE:VOLTAGE:OUTPUT OFF or VOLT:OUT OFF
This command will not disconnect the supply output. It is equivalent to programming the output to zero volts.
To read if the supply output is disabled, send query VOLT:OUTP?. A “0” (zero) will be returned if the output is disabled.
The short form for “supply off” is: SF
1.6.4 ENABLE THE SUPPLY OUTPUT
After the supply output has been shut off with the SOUR:VOLT:OUTP OFF command, the output can be turned back on by sending this command:
SOURCE:VOLTAGE:OUTPUT ON or VOLT:OUTP ON
The output will immediately jump to the last programmed voltage and current.
To read if the supply output is enabled, send query VOLT:OUTP?. A “1” (one) will be re­turned if the output is enabled.
The short form for “supply on” is: SN
1.6.5 READ PROGRAMMING MODE
7
The power supply may be programmed in two modes. In Local Mode, the front panel knobs or back panel analog connections set the supply output. In Remote Mode, the IEEE/RS232 interface sets the output. The mode is indicated by the front panel REMOTE LED (if it is installed). The mode may be read by sending this query:
SYSTEM:PROGMODE? or SYST:PROG?
The response will be one of three choices: LOCAL, REMOTE, OR FORCED_LOCAL. Since sending a query takes the supply out of Local Mode, that response will not be re­ceived. The Forced Local Mode is set by the first rocker on the IEEE address switch (see Figure 1).
The short form for this command is: MH?
Document: 83-468-007 Rev B
1.7 MEASURING VOLTAGE AND CURRENT
1.7.1 MEASURE VOLTAGE
The output voltage can be measured by sending the command:
MEASURE:VOLTAGE? or MEAS:VOLT?
When the controller does the next IEEE Read, the supply will send the measured volt­age to it. The measurement is always given to six decimal places even if the measure­ment is not so accurate. See the Specifications Section in the power supply User Manual for actual measurement accuracy. If the back panel analog connector is wired for Re­mote Voltage Sensing, the measured value will be the voltage at the sense lines, not the voltage at the supply output.
The short form for “measure voltage” is MV?
1.7.2 MEASURE CURRENT
The output current can be measured by sending the SCPI command:
MEASURE:CURRENT? or MEAS:CURR?
When the controller does the next IEEE Read, the supply will return the amperes of cur­rent being produced. The measurement is always given to six decimal places even if the measurement is not so accurate. See the Specifications Section in the power supply User Manual for actual measurement accuracy.
The short form for “measure current” is: MC?
Measure Output
8
1.7.3 SET MEASUREMENT FILTERING
The output voltage or current may be queried with MEAS:VOLT? or MEAS:CURR?. Be­cause of noise, the measurements may have unacceptable random variations. There­fore, a routine is implemented so the board makes measurements every 16 milliseconds and keeps a running average of the output.
The number of samples in the running average may be adjusted. A higher number will “smooth” constant output readings but it will slow down the reported response to actual changes in output.
The voltage measurement averaging is set by the command:
AFV nnn
Where nnn is a number between 1 and 250. The default is 20.
The current measurement averaging is set by the command:
AFC nnn
Where nnn is a number between 1 and 250. The default is 20.
Changing the averaging value will not slow down the bus speed or slow down the re­sponse time to an over-voltage and over-current shutdown.
Any changes in AFV or AFC may be made the power-up default by sending the *SAV 0 command.
Document: 83-468-007 Rev B
1.8 LIMITS AND PROTECTIONS
1.8.1 SET VOLTAGE LIMIT
The maximum voltage that may be programmed to the power supply is set by the follow­ing command. It does not monitor the actual output voltage. It only inspects the numeric value in a voltage programming command.:
SOURCE:VOLTAGE:LIMIT <nn.nn> or VOLT:LIM <nn.nn>
where <nn.nn> is a number between zero and the maximum supply output voltage. The decimal is optional.. A space is required before the number.
By default, the voltage limit equals the power supply maximum voltage. A new voltage limit will remain in effect until the supply power is switched off. A new voltage limit can be made to be the power-up default by following VOLT:LIM with the *SAV 0 command. See Section 1.9.6 for a description of the *SAV 0 command.
If a command is sent to set the supply to a voltage higher than the voltage limit, the command will be ignored and the Execution Error bit of the Standard Event Status Reg­ister will be set.
To read what voltage limit has been set, send query VOLT:LIM? and read the response message.
The short form for “set voltage limit” is: SVL <nn.nn>
Limit Output
9
1.8.2 SET CURRENT LIMIT
The maximum current that may be programmed to the power supply is set by the follow­ing command. It does not monitor the actual output current. It only inspects the numeric value in a current programming command.
SOURCE:CURRENT:LIMIT <nn.nn> or CURR:LIM <nn.nn>
where <nn.nn> is a number between zero and the maximum supply output current in amperes. The decimal is optional.. A space is required before the number.
By default, the current limit equals the power supply maximum current. A new current limit will remain in effect until the supply power is switched off. A new current limit can be made to be the power-up default by following CURR:LIM with the *SAV 0 command. See Section 1.9.6 for a description of the *SAV 0 command.
If a command is sent which sets the supply to a current higher than the current limit, the command will be ignored and the Execution Error bit of the Standard Event Status Reg­ister will be set.
To read what current limit has been set, send query CURR:LIM? and read the response message.
The short form for “set current limit” is: SCL <nn.nn>
1.8.3 OVER-VOLTAGE PROTECTION
Lambda supplies feature two types of over-voltage protection that shuts down the output if the output exceeds some settable voltage level. The analog method uses the Over­Voltage Adjustment potentiometer on the front panel. The digital method uses the IEEE board to constantly sample the supply output voltage. The analog pot setting always takes priority over any digital programmed level. Therefore, for digital over-voltage pro­tection, it is recommended the potentiometer be turned clockwise to maximum.
Document: 83-468-007 Rev B
Using IEEE protection, the time between an over-voltage occurring and the supply shut­ting down is typically 20 milliseconds. This is the time for two successive readings to ex­ceed the limit. The analog protection responds much faster. There is no analog over­current protection.
IEEE over-voltage protection is implemented with four commands:.
1.8.3.1 Set the over-voltage threshold:
SOURCE:VOLTAGE:LEVEL <nn.nn> or VOLT:LEV <nn.nn>
where <nn.nn> is a number between zero and the maximum supply output voltage. The decimal is optional.The voltage may be more or less than the limit set by the SOURCE:VOLTAGE:LIMIT command described in the previous paragraphs.
The set voltage level may be read by sending the query VOLT:LEV? and reading the re­sponse number.
The short form for “set voltage protection level” is: SVPL <nn.nn>
1.8.3.2 Enable the protection:
SOURCE:VOLTAGE:STATE ON or VOLT:STAT ON
The protection can be disabled by specifying OFF instead of ON.
The state of the protection may read by sending the query VOLT:STAT? and reading the response. A “1” (one) means the protection is enabled..
The short form for “set voltage protection state” is: SVPS ON (or OFF)
Limit Output
10
1.8.3.3 Query for over-voltage shutdown:
SOURCE:VOLTAGE:TRIPPED? or VOLT:TRIP?
Read the response number. The normal response is “0” (zero). If a “1” (one) is returned, it means an over-voltage has occurred and the output is shut down.
The response number is actually the value of the Operational Condition Register Bit 0. Because an over-voltage can set bits in four IEEE registers, it is recommended that a *CLS be sent to clear them after an over-voltage occurs. See the Section 0 on Status and Error Register Programming for more details.
The short form for “set voltage protection tripped?” is: SVPT?
1.8.3.4 Reset after shutdown:
SOURCE:VOLTAGE:CLEAR or VOLT:CLE
After an over-voltage shut down has occurred, this command must be sent to clear the error status before any new voltage commands will be accepted.
If and over-voltage is not cleared, and a new voltage command is sent, the command will be ignored and the Command Error bit in the Standard Event Status Register will be set.
The short form for “set voltage protection clear” is: SVPC
1.8.4 OVER-CURRENT PROTECTION
The IEEE Interface board constantly measures the power supply output current and the board can be set to shut down the supply if the output current exceeds a settable level. The time between an over-current occurring and the supply shutting down is typically 20 milliseconds.
Document: 83-468-007 Rev B
Loading...
+ 29 hidden pages