3.7.1 PARALLEL OPERATION IN MASTER/SLAVE
CONFIGURATION
3.11 INTERLOCK
4 RSTL CONTROLLER BOARD
1
11.1 INTRODUCTION
11.1 SAFETY PRECAUTIONS
31.3 SPECIFICATIONS
51.4 DESCRIPTION
61.5 INPUT VOLTAGE
81.6 RETURNING EQUIPMENT
81.7 CLAIM FOR DAMAGE IN SHIPMENT
9
92.1 UNPACKING
92.2 VISUAL INSPECTION
92.3 LOCATION
92.4 ELECTRICAL INSTALLATION
92.5 ELECTRICAL INSPECTION
11
113.1 CONTROLS, INDICATORS (LEDS) AND CONNECTORS
143.2 GENERAL OPERATION
143.3 OVERVOLTAGE PROTECTION
153.4 CONNECTING THE LOAD
153.5 MODES OF OPERATION
163.5.1 NORMAL OPERATION MODE
163.5.2 REMOTE PROGRAMMING BY EXTERNAL RESISTANCE
173.5.3 REMOTE PROGRAMMING BY EXTERNAL VOLTAGE
183.5.4 REMOTE PROGRAMMING BY EXTERNAL CURRENT
193.6 REMOTE SENSING
203.7 PARALLEL OPERATION
21
253.8 SERIES OPERATION
253.9 REMOTE METERS
253.10 VOLTAGE AND CURRENT MONITOR, 0-5 VDC OUTPUT
263.10.1 REMOTE PROGRAMMING BOTH VOLTAGE AND CURRENT
32
324.1 INTRODUCTION TO THE RSTL CONTROLLER BOARD
324.2 RSTL CONNECTION TO COMPUTER
324.3 CONTROLLING THE POWER SUPPLY
334.4 GENERAL DESCRIPTION
334.5 ELECTRICAL SPECIFICATIONS
344.6 MECHANICAL SPECIFICATIONS
344.7 OPERATING INSTRUCTIONS
344.7.1 GPIB AND RS232 INTERFACES
354.7.2 SET-UP COMMANDS
364.7.3 INQUIRY COMMANDS
384.7.4 MEASUREMENT COMMANDS
394.7.5 PROGRAMMING AND SOFT LIMIT COMMANDS
Page 3
4.7.6 TRIM PROGRAM COMMANDS (SOFT PROGRAMMING
CALIBRATION)
4.7.7 TRIM MEASURE COMMANDS (SOFT READBACK
CALIBRATION)
5 THEORY OF OPERATION
6 MAINTENANCE
6.8 MAIN RECTIFIER ASSEMBLY
40
41
414.8 SERVICE PROCEDURES
414.8.1 GENERAL
424.8.2 CALIBRATION
454.8.3 DEMONSTRATION GWBASIC PROGRAM
464.8.4 DEMONSTRATION QUICK-C PROGRAM
494.8.5 DEMONSTRATION LAB WINDOWS FOR DOS PROGRAM
52
525.1 REFERENCE
525.2 POWER FLOW
525.3 INVERTER MODULE
535.4 SIGNAL FLOW
535.5 REFERENCE GENERATION
535.6 ERROR AMPLIFIERS
535.7 PULSE WIDTH MODULATOR
545.8 SUPERVISORY FUNCTIONS
545.9 REMOTE TURN ON CIRCUIT
545.10 INRUSH CURRENT LIMITING CIRCUIT
545.11 MODE DETECT
545.12 THERMAL SHUTDOWN
555.13 PHASE LOSS CIRCUIT
555.13.1 PHASE LOSS CIRCUIT FOR THE 220 VAC
555.13.2 PHASE LOSS CIRCUIT FOR THE 380, 415 AND 480 VAC
555.14 OVERVOLTAGE PROTECTION
56
566.1 MAINTENANCE
566.2 INTRODUCTION
566.3 TROUBLESHOOTING GUIDE
576.4 FIELD REPLACEABLE UNITS (FRUS)
576.5 INVERTER A200
576.5.1 INVERTER A200 TEST
576.6 A100 CONTROL BOARD
586.7 FAN ASSEMBLY
58
586.9 A900 OVP BOARD
586.10 CALIBRATION
596.11 SCHEMATICS AND COMPONENTS
Page 4
LIST OF TABLES
LIST OF FIGURES
Figure 3.14: Paralleled Operation in Master/Slave Configuration with OVP
Master/Slave
Figure 3.20: Remote Programming by External Resistance for Constant Current
and Constant Voltage
Figure 3.21: Remote Programming by External Voltage for Constant Current and
Constant Voltage
3Table 1.1: Nominal Input Current/Circuit Breaker for the 10 KW Series
3Table 1.2: Nominal Input Current/Circuit Breaker for the 15 KW Series
5Table 1.3: Regulation 10 KW
5Table 1.4: Regulation 15 KW
6Table 1.5: Model Number
7Table 1.6: AC Input Configuration
11Table 3.1: Front Panel Controls and LEDs
13Table 3.2: Rear Panel Controls and Connections
15Table 3.3: Programming J1 Connector
34Table 4.1: Dip Switch Settings
56Table 6.1: Troubleshooting Guide
57Table 6.2: FRUs
2Figure A Outline Drawing
7Figure 1.1: Delta to Wye Conversion
12Figure 3.1: Front Panel
13Figure 3.2 Rear Panel
14Figure 3.3: Operating Modes
16Figure 3.4: Normal Operation Mode
16Figure 3.5: Remote Programming By External Resistance for Constant Voltage
17Figure 3.6: Remote Programming by External Resistance for Constant Current
17Figure 3.7: Remote Programming by External Voltage for Constant Voltage
17Figure 3.7.1: Voltage Program 0806
18Figure 3.8: Remote Programming by External Voltage for Constant Current
19Figure 3.9: Remote Programming by External Current for Constant Voltage
19Figure 3.10: Remote Programming by External Current for Constant Current
20Figure 3.11: Remote Sensing
21Figure 3.12: Parallel Operation
22Figure 3.13: Parallel Operation in Master/Slave Configuration
22 - 24
25Figure 3.15: Series Operation
26Figure 3.16: Remote Meter Across Output
26Figure 3.17: Remote Meter Across Load
27Figure 3.18: Remote Meter Across Shunt
27Figure 3.19: Voltage and Current Monitor
28
28
29Figure 3.22 Remote Interlock and Dry Contact
30Figure 3.23 Rear Panel Reference
31Figure 3.24 Series Operation with Opto Isolators
Page 5
Page 6
MANUFACTURER'S PRODUCT DECLARATION
INTENDED PURPOSE (USE)
The Power Supplies described by this manual are defined by Lambda EMI as a component for
use in the composition of an apparatus as defined in Article 1 (1) of the EMC Directive
(89/336/EEC). These products, as individual components, do not perform in themselves a direct
function for the user of the end product. They are not intended to be placed on the market with
a direct function to a final user! As such, the products described by this manual are not subject
to the provisions of the EMC Directive (89/336/EEC, with amendment 92/31/EEC). The
products described by this manual are intended for incorporation into a final product by a
professional assembler. It is the responsibility of the assembler to ensure that the final
apparatus or system incorporating our products complies with all relevant EMC standards for
that final product.
OPERATING ENVIRONMENT
The operating environment as defined by Lambda EMI, for the products described by this
manual is stated as follows:
The Power Supplies described by this manual are intended for use in a protected industrial
environment or in proximity to industrial power installations. These locations are often referred
to as industrial locations containing establishments that are not connected to the low voltage
public mains network.
Industrial locations are characterized by the existence of one or more of the following
conditions:
1) industrial, scientific and medical (ISM) apparatus are present;
2) heavy inductive or capacitive loads are frequently switched;
3) currents and associated magnetic fields are high;
4) location supplied by their own transformer.
These components are not intended for connection to a public mains network, but are intended
to be connected to a power network supplied from a high or medium-voltage transformer
dedicated for the supply of an installation feeding manufacturing or similar operations. They are
suitable for use in all establishments other than domestic and those directly connected to a low
voltage power supply network which supplies buildings used for domestic purposes.
83-000-006 Revision C
Page 7
Description of symbols used in product labeling.
DESCRIPTIONPUBLICATIONSYMBOL
EC Council
directive 93/68/EEC
European Community
Conformity Assessment
Product Mark
IEC 348
IEC 60417-1-5019
IEC 60417-1-5017
IEC 60417-1-5134
Attention, consult
accompanying documents
Dangerous voltageIEC 60417-1-5036
Protective earth
(e.g. power line earth ground)
Functional earth
(e.g. chassis ground)
Electrostatic Discharge
(ESD) Sensitive Device
Page: 83-000-007 Rev D
Page 8
1GENERAL INFORMATION
1.1INTRODUCTION
This series of high frequency switching power supplies is designed to operate as a source of
constant current/constant voltage power with automatic crossover. The ESS series exhibits
excellent transient response, excellent regulation, high efficiency, low ripple and low noise.
NOTE: This manual contains information, instructions and diagrams which apply to a
variety of standard constructions. If special features or modifications have been
installed, the specific instructions peculiar to that special are contained in addenda
and take precedence where conflicts exist. Take care to refer to the correct information for your unit.
1.2SAFETY PRECAUTIONS
All EMI power supplies are designed to minimize risk of fire or shock hazards. This instrument received comprehensive mechanical and electrical inspection prior to shipment. Nevertheless, certain safety precautions must be observed. Only technically competent personnel
familiar with the principles of electrical safety should operate this supply. To prevent fire or
shock hazard, the power supply should not be exposed to water or moisture. Electrical safety
should be maintained at all times.
Lethal voltages are developed within the power supply's enclosure. Therefore, the power
supply must always be unplugged prior to removing the cover. If the input to the power
supply is hard-wired, the circuit breaker must be secured and the line fuses removed.
Of course, dangers are inherent in high voltage equipment. However, a power supply with a
low voltage output is also potentially dangerous considering the amount of energy (current)
the supply is capable of delivering. In addition to the steady state energy available,
power supplies are typically terminated by very large capacitors, which can deliver
huge surge currents capable of vaporizing metallic objects such as screwdrivers or
jewelry. This could result in molten metal being sprayed. Proper care and judgment
must always be observed.
1) Ensure all covers are in place and securely fastened and the required grounding is
connected before supplying input AC power.
2) Proper grounding from the input AC power is required to reduce the risk of electric shock.
Insure that the ground connection has at least the same gauge as the supply leads.
3) Use extreme caution when connecting input AC power and never apply the incorrect input
voltage. Refer to ratings label.
4) Use extreme caution when connecting the high voltage output cable including the
separate ground connecting the supply to the load.
5) Ensure all load capacitors are completely discharged prior to connection. Never
handle the output cable when the power supply is operating.
83-481-004
Page 1 of 59 Rev. Z
Page 9
6) Always replace fuses with the same type and Volt/Amp ratings.
7) Never attempt to operate the power supply in any manner not described in this manual.
8) Never remove DANGER or WARNING labels from the power supply, and replace lost or
damaged labels immediately.
9) The power supply should only be serviced by Lambda-EMI factory qualified personnel, or
authorized service centers.
Figure A Outline Drawing
83-481-004
Page 2 of 59 Rev. Z
Page 10
1.3SPECIFICATIONS
This series of high frequency switching power supplies is designed to operate as a source of
constant current/constant voltage power with automatic crossover. All ESS power supplies
are fully remote programmable via our RSTL-488 interface, allowing for systems integration
to meet the customer's specific requirements.
Table 1.2: Nominal Input Current/Circuit Breaker for the 15 KW Series
GENERAL:
Power Factor:
.9 Passive
Efficiency:
85-91%
Dielectric withstanding voltage:
Primary to Secondary: 2500 VDC
Primary to Case: 2500 VDC
Secondary to Case: 1500 VDC*
(Sensing removed)
83-481-004
Page 3 of 59 Rev. Z
Page 11
Operating Temperature:
All ESS power supplies are capable of continuous duty performance within their specifications
in ambient temperature between 0 ºC and 50 ºC. Units may be safely stored at temperatures
of -55 ºC to 85 ºC.
Humidity:
95% non-condensing
Transient Response
For a 30% load step below 20V, the transient response is 650 µS. For units above 20V, use
Vmax/20 for transient response.
Dimensions:
Rack mount standard - 19 inches (see Figure A)
Weight:
105 lbs (48 kg)
Stability:
Maximum deviation in either voltage or current mode for an eight (8) hour period is up to
0.05% under conditions of constant line, load and temperature.
Temperature Coefficient:
The output voltage temperature coefficient is 0.02% per 1ºC of rated output voltage. The
output current temperature coefficient is 0.03% per 1ºC of the rated output current.
Regulation:
Constant Voltage Mode :
An output current load change of 100% will cause an output voltage variation of less than
0.1%.
Constant Current Mode :
An output voltage load change of 100% will cause an output current change variation of less
than 0.1%.
All ESS models are capable of being remotely started or stopped by means of an external AC
or DC voltage source. NOTE: When remote is OFF or interlock is open, control failure LED
will be ON, this is normal.
Programming:
The ESS series of power supplies will respond either to the setting of the front panel controls
or to an external control signal. This control signal may be in the form of either a resistance, a
current, or a voltage. Full scale output is signaled by 5000 ohms, by 5 Vdc, or 1mA.
Proper ESD precautions must be taken when taking off the cover and making connections to
J1, RS-232 and IEEE connection when used.
Remote Sensing:
Separate sense and power terminals are provided to enable specified regulation directly at
the terminals of the load. This feature provides automatic compensation for the voltage drop
in the power distribution system. Voltage drop of sensing lead should be no more than 5V
total. Over 10 ft. of Remote Sensing, contact Lambda-EMI.
83-481-004
Page 5 of 59 Rev. Z
Page 13
Controls:
All ESS models are provided with a UL listed circuit breaker which provides primary circuit
protection and serves as a power on/off control. Output voltage and current are adjusted by
the 10 turn, front panel mounted, controls. Simultaneous indication of output current and
voltage is provided by front panel meters. The voltmeter is connected across the sense
terminals so that the meter will read either the voltage at the load or the voltage at the power
supply terminals, depending on whether local or remote sense is selected.
Overvoltage:
Overvoltage protection, adjustable from the front panel, is standard on all ESS models. This
circuit will soft discharge the power supply output to protect the load when the output voltage
reaches the OVP set value. The adjustment is from 0% to 105% of Full Vout. This protection
is effective regardless of the cause of the overvoltage. Events which will trigger the OVP
include, but are not limited to the OVP knob being turned inadvertently, broken remote sense
lead, voltage applied from external source, and servo failure in the power supply.
1.5SETTING INPUT VOLTAGE
The following chart explains the model number for the ESS power supply series.
ESSXX-XXX- XX-XX-XX
DC Output Volt.
DC Output Current
2
3 PHASE, 4 WIRE
190-253 Vac 400 Hz
3
3 PHASE, 4 WIRE
8
3 PHASE, 5 WIRE
0
3 PHASE, 5 WIRE
10
11
12
400 Vac 50/60 Hz
3 PHASE, 5 WIRE
480 Vac 50/60 Hz
3 PHASE, 5 WIRE
440 Vac 50/60 Hz
3 PHASE, 5 WIRE
FEATURESPANEL METERS AC INPUT VOLTS
OMIT220 Vac 50/60 Hz
METERS
D380 Vac 50/60 Hz
DIGITAL
METERS
LOCK BUSHINGLB ANALOG
X
X
TEST POINTSTP415 Vac 50/60 Hz
CE1950
XX
TL
PROGRAMMING
Table 1.5: Model Number
83-481-004
Page 6 of 59 Rev. Z
Page 14
The input voltage for the ESS is determined by the option number. The options are:
2 = 190-250 Vac Three Phase 4 Wires 50/60 Hz.
3 = 190-250 Vac Three Phase 4 Wires 400 Hz.
4 = 190-250 Vac Three Phase 4 Wires 60/400 Hz.
7 = 180-220 Vac Three Phase 4 Wires 50/60 Hz.
8 = 348-418 Vac Three Phase 5 Wires 50/60 Hz.
9 = 374-452 Vac Three Phase 5 Wires 50/60 Hz.
10 = 360-440 Vac Three Phase 5 Wires 50/60 Hz.
11 = 432-528 Vac Three Phase 5 Wires 50/60 Hz.
12 = 396-484 Vac Three Phase 5 Wires 50/60 Hz.
13 = 380-460 Vac Three Phase 5 Wires 50/60 Hz.
14 = 380, 415, 440 Vac Three Phase 5 Wires 50 Hz.
15 = 190-253 Vac One Phase 6 Wires 47/64 Hz.
16 = 380 Vac Three Phase 4 Wires
17 = 415 Vac Three Phase 4 Wires
18 = 480 Vac Three Phase 4 Wires
19 = 400 Vac Three Phase 4 Wires
20 = 440 Vac Three Phase 4 Wires
21 = 460 Vac Three Phase 4 Wires
The Power Supply must be properly connected to an approved AC distribution box with the
correctly rated over current protection. Input voltages above 230VAC should be supplied from
a grounded neutral Wye connected AC power source. For nominal input voltages of 380 Vac
and higher, a Wye connection of the input is required in order to provide a neutral connection.
Refer to the following diagram below. Lambda-EMI provides two auto transformers (28-004890-2 set type or 28-004-952-1 set type) for delta to Wye conversion.
Figure 1.1: Delta to Wye Conversion
Phase rotation sequence need not be observed when connecting the power lines to the input
terminals of the power supply. A neutral connection (marked N) is required for the 380, 400,
415 and 480 VAC rated units. For safety, the chassis ground terminal should be connected to
earth ground. The input wires must be of the proper gauge size to minimize impedance. The
wiring of the AC input connector is dependent upon the rated input voltage of the power
supply. Refer to the below table for the appropriate connections.
83-481-004
Page 7 of 59 Rev. Z
Page 15
PIN
195-253 Vac
CONNECTIONS
342-418, 373-456, 432-528, 360-440,
400-480 Vac CONNECTIONS
PHASE APHASE AL1
PHASE BPHASE BL2
PHASE CPHASE CL3
NEUTRALNO CONNECTIONN
GROUNDGROUNDG
Table 1.6: AC Input Configuration
Both POS and NEG output terminals are floating (not connected to ground). Either may be
grounded or operated at any voltage less than 600 VDC with respect to chassis ground.
RSTL Controller Board:
This is an optional board that can be installed at the customer's request. The board is
designed for remote computer control, functionally duplicating the controls on the front panel
of the power supply. These controls select the programming levels (Voltage and Current),
and provide metering of the supply's output. The RSTL, when set in the REMOTE mode,
disables the front panel control pots (but the meters still read), and asserts control of the
power supply. For detailed information, refer to Section 4.
1.6RETURNING EQUIPMENT
Before returning any equipment to the factory, the following steps should be taken.
1) Notify Lambda-EMI, at telephone number (732)-922-9300. Give a full description of the
difficulty, including the model and serial number of the unit in question. Upon receipt of
this information, Lambda-EMI will assign a Return Material Authorization number (RMA)
and provide shipping instructions.
2) Equipment returned to Lambda-EMI must be packed in such a manner as to arrive
without incurring any damage. The shipping container must be marked with the RMA
number in legible numbers near the shipping label. Any returned unit must have its RMA
number clearly displayed on the outside of the container in order to be accepted.
3) For non-warranty repairs, Lambda-EMI will submit a cost estimate for the customer's
approval prior to proceeding.
1.7CLAIM FOR DAMAGE IN SHIPMENT
This instrument received comprehensive mechanical and electrical inspection before
shipment. Immediately upon receipt from the carrier, and prior to operation, this instrument
should be visually inspected for any damage that may have been incurred during shipment.
If such inspection reveals internal or external damage in any way, a claim should be filed with
the carrier. A full report of the damage should be furnished to the claim agent and forwarded
to Lambda-EMI noting the model and serial number of the equipment. Lambda-EMI will
determine the proper course of action and arrange for repair or replacement.
83-481-004
Page 8 of 59 Rev. Z
Page 16
2INSPECTION AND INSTALLATION
2.1 UNPACKING
Carefully open the top of the box and remove the packing material. The supply can then be
lifted from the box. This power supply is intended for rack mounting. The blades of the forklift
must extend fully under the base of the power supply. Both sides must be supported. The
power supply may be hoisted with a suitable sling, using the specially provided side lifting
plates. If the plates interfere with the application installation, they may be removed. The
holding screws should be reinstalled into power supply.
2.2VISUAL INSPECTION
Immediately inspect the power supply for any shipping damage. Verify the following:
A) Check the operation (knobs should rotate smoothly) of the front panel controls.
B) Verify that the circuit breaker latches in the ON and OFF positions.
C) Confirm that there are no dents or scratches on the panel surfaces.
D) Check front panel meters and LEDs for any broken or cracked glass.
If any damage is found, follow the "Claim for Damage in Shipment" instructions in Section
1.7.
2.3LOCATION
Make sure that adjacent equipment does not block air intake or exhaust openings of the
power supply. Air enters at the front panel and is forced out of the rear panel. This power
supply is intended for rack mounting. A conventional 19-inch rack panel can be used.
2.4ELECTRICAL INSTALLATION
This power supply should not be operated with covers removed. Please refer to safety
precautions detailed in section 1.2. After the supply has been installed in a location with sufficient space for ventilation, the appropriate AC input can be applied. Refer to Section 1.5
(Option) for the required AC input voltage and wiring configuration of the AC input connector.
2.5ELECTRICAL INSPECTION
To ensure that no internal damage was incurred during shipment, a preliminary test should be
performed as follows:
A) Rotate Voltage and Current knobs completely counter clockwise.
B) Apply appropriate AC input power to the supply. With no load connected to the output
terminals, flip ON the circuit breaker of the supply. The internal fans should start
immediately. The power supply should turn on after an approximate ten second delay.
The status of the indicators is as follows:
Power On indicator is glowing.
Phase Loss indicator is off
Control Failure indicator is on (Will turn off as control is achieved)
Inverter Failure indicators are off
Overvoltage indicator is off
83-481-004
Page 9 of 59 Rev. Z
Page 17
C) Rotate the current knob clockwise.
D) Rotate the voltage knob completely clockwise. The front panel's voltmeter should
display the maximum output voltage of the supply. The voltage indicator should glow.
E) Rotate the current knob completely counter clockwise; the output voltage should drop to
zero.
F) Rotate the current knob clockwise. The output voltage should rise to its original value.
Rotate the OVP potentiometer counter clockwise. The output voltage shoulddrop to
zero volts.
G) Since the OVP circuitry latches on itself, rotate the OVP potentiometer completely
clockwise. Flip the circuit breaker OFF and then ON to disable the OVP. The voltmeter
should display the output voltage.
H) Rotate the voltage knob completely counter clockwise and monitor the front panel
voltmeter. The output voltage should gradually decrease to zero. Flip OFF the circuit
breaker of the supply.
I)Apply a short wire, that can sustain the maximum output current, across the output
terminals of the supply.
J) Flip ON the circuit breaker of the supply. Rotate the voltage knob clockwise. Rotate
the current knob completely clockwise. The front panel ammeter should display the
maximum output current of the supply. The current indicator should glow.
K) Rotate Current knob completely counter clockwise. The output current should drop to
zero.
Flip OFF circuit breaker.
If any inconsistency from the above test procedure is noted, please do not hesitate to call
Lambda-EMI for assistance.
83-481-004
Page 10 of 59 Rev. Z
Page 18
3OPERATING INSTRUCTIONS
3.1CONTROLS, INDICATORS (LEDS) AND CONNECTORS
This section gives a brief description of the controls and indicators and also describes
the different operational methods of the ESS power supply. Refer to figures 3.1 and
3.2.
REFERENCE
NUMBER
FRONT PANEL
CONTROL/INDICATOR
Power On LED 1
Phase Loss LED2
Inverter Failure LEDs 3
Overvoltage LED5
Voltage LED6
Circuit Breaker 7
FUNCTION
When glowing, indicates that the supply is
on and in the Normal Operation Mode.
When glowing, indicates that the supply is
off and not in Operation Mode.
Four LEDs corresponding to four
inverters. The number of the LED that
glows indicates which inverter has failed.
Indicates constant current mode.Current LED4
Indicates supply has exceeded the
voltage that was set by the OVP Control.
Indicates that the supply is in the constant
Voltage mode.
Connects and disconnects AC input to
supply.
Displays output voltage of power supply.Voltmeter8
Displays output current of power supply.Ammeter 9
Indicates system failure in the supply. Control Failure LED10
NOTE: will go out when supply has soft
started and is on when remote is turned
off.
Voltage control11
Current Control12
OVP Voltage Adjust13
Adjusts the output voltage from zero to full
scale.
Adjust the output current from zero to full
scale.
Adjust Overvoltage from Zero to 105% of
Vout
Table 3.1: Front Panel Controls and LEDs
83-481-004
Page 11 of 59 Rev. Z
Page 19
Figure 3.1: Front Panel
83-481-004
Page 12 of 59 Rev. Z
Page 20
REFERENCE
NUMBER
FUNCTIONCONTROL/
CONNECTOR
Programming Connector J1 Connector1
AC Input TB1 Terminal Strip2
IEEE 4883
Output Terminals6
RS2327
Table 3.2: Rear Panel Controls and Connections
Provides interfacing between a computer and the power
supply.
Selects the IEEE488 address. Address Switch4
Allows the panel to be conveniently connected to ground. Ground Stud5
The load is connected to these 2 terminals. The output
terminals supply power to the load.
Provides interfacing between computer and the power
supply.
Figure 3.2 Rear Panel
83-481-004
Page 13 of 59 Rev. Z
Page 21
3.2GENERAL OPERATION
Iset
When shipped from the factory, each supply is configured for constant voltage,
constant current and local sensing operation. This is the default or typical operating
mode of the supply. All performance specifications, unless otherwise stated, are
defined in this configuration. The voltage and current controls set the boundary limits
for the load voltage and current respectively. The relationship between the control
settings and the load resistance determines whether the power supply operates in
constant voltage or constant current mode. Automatic crossover between modes
depends on the following:
The load connected to the output terminals of the power supply RL .
The front panel voltage control setting Vset .
The front panel current control setting Iset .
Constant Voltage Mode: The power supply will operate in this mode whenever the
current demanded by the load is less than that defined by front panel current control.
In this mode, the output voltage of the power supply is set by the front panel voltage
control. The output current is determined by the load and the Vset .
Constant Current Mode: The power supply will operate in this mode whenever the
current demanded by the load is greater than that defined by front panel current
control. In this mode, the output current of the power supply is set by the front panel
current control. The output voltage is determined by the load and Iset.
..
Vmax.
Vset.
Open Circuit Load
R >R
L
cr s
R =R
L
R =R
L
crsL
crs
Figure 3.3: Operating Modes
The front panel provides all controls and indicators necessary to operate the power
supply.
3.3OVERVOLTAGE PROTECTION
An adjustable internal overvoltage protection (OVP) circuit trips between 0% and
105% of output. When the circuit is tripped, the front panel Overvoltage LED will
glow, and the OVP circuitry will latch on. To reset the OVP circuit, rotate the OVP
potentiometer completely clockwise, and flip the circuit breaker to the OFF and then to
the ON position.
Iset
Pt.
Voltage Mode Line
Crossover Point
Current Mode
Short Circuit Load
Imax.
Line
Pt.
Rcrs= Vset
83-481-004
Page 14 of 59 Rev. Z
Page 22
3.4CONNECTING THE LOAD
Ensure that the power supply is off and disconnected from the input power and
that all load capacitors are discharged and shorted to ground before making
any connections. Never handle the output cable during operation.
Each resistive load must be connected to the power supply output terminals using
separate pairs of connecting wires. Make sure that the connecting wires are of
suitable gauge to sustain maximum rated current. Separate pairs of wires minimize
mutual coupling effects between loads and maintain the low output impedance of the
power supply. Each pair of connecting wires must be as short as possible. If strong
AC or RF fields are present, the connecting wires should be twisted or shielded. If a
shield is used, connect the supply end of the shield to earth ground. Do not terminate
the shield at the load end.
ProperESD precautions must be taken when taking off the J1 cover and
makingmaking connections to J1, RS-232, IEEE connectors when used.
3.5MODES OF OPERATION
A 25 pin Sub-D female Connector (J1) is used for configuring the operating mode of
the power supply. Depending on the configuration of the J1 programming connector,
an external resistance, voltage or current can be used to control the power supply in
the remote operation mode. Remote programming can be applied to either voltage
channel (voltage regulation circuit) or current channel (current regulation circuit). If
strong AC or RF fields are present, use a twisted pair or shielded cable to connect the
remote terminals of J1 to the programming source. The following table provides a
description of the J1 connector and J18 connector.
J18 PIN PIN DESCRIPTION
1 +V
2 +V REMOTE SENSE
J1 PINPIN DESCRIPTION
1+V (+ Buss Bar of Power Supply up to 300V)
2+V REMOTE (+ sense of control board up to 300V)
3V PROG I (Current source for voltage channel)
4V AMP IN (Voltage programming input)
5V PROG R (Front panel voltage pot +)
6V PROG R COM (Front panel voltage pot -)
7-V REMOTE (-Sense of control board)
8-V (Output of Power Supply and common of A100)
9I PROG I (Current source of current channel)
10I AMP IN (Current programming input)
11I PROG R (Front panel current pot +)
12- SHUNT
13I MON REMOTE (Buffered current monitor )
14REMOTE V IN (Internal VAC for interlock)
15REMOTE V SW (Return connection, internal VAC)
16REMOTE V SW ( Interlock contact )
17OVP M/S IN ( Logic port in for OVP)
18I PROG SLAVE (Output of Difference Amp.)
19V MONITOR (Voltage monitor )
20I MON OUT TO SLAVE ESS (50X internal shunt Amp)
21-V OUT TO SLAVE (common of A100 control Bd)
22-V IN FROM MASTER (-Input of Difference Amp)
83-481-004
Page 15 of 59 Rev. Z
Page 23
23I MON IN FROM MASTER (+ input of Difference Amp)
123456789
20
22
J1 PROGRAMMING CONNECTOR
24OVP M/S OUT (logic output of OVP)
25+ SHUNT
Table 3.3: Programming J1ConnectorNormal operation mode
In the Normal Operation mode, the power supply is controlled by the front panel
potentiometers. The supply is configured for constant voltage, constant current and
local sensing. When shipped from the factory, the supply is configured for this mode.
Figure 3.4 illustrates the configuration of J1 for the Normal Operation mode. When
using RSTL program, voltage and current programming are not applicable.
NOTE: If the unit has the "RSTL" option, you cannot perform any remote analog
programming in the voltage or current mode.
NOTE: If the unit has a 0-10Volt Programming option, you cannot perform external
resistive or external current programming in the voltage or current mode.
10 11 12 13 21 14 15 16
Removed for RSTL
Figure 3.4: Normal Operation Mode
CAUTION: IF THE REMOTE PROGRAMMING RESISTOR OPENS, THE LOAD
VOLTAGE OR LOAD CURRENT CAN INCREASE TO THE MAXIMUM RATING OF
THE POWER SUPPLY. THEREFORE, USE MAKE-BEFORE- BREAK SWITCH
CONTACTS BETWEEN EXTERNAL PROGRAMMING SOURCE AND THE
PROGRAMMING J1 CONNECTOR.
3.5.1REMOTE PROGRAMMING BY EXTERNAL RESISTANCE
Voltage Channel
A 5000 ohm potentiometer programs the supply output voltage from zero to full
rated voltage. Front panel Voltage control is disabled. Front panel Current
control remains active.
Desired Output Voltage
=
Full Rated Output Voltage
5000 ohms
83-481-004
Page 16 of 59 Rev. Z
Page 24
Figure 3.5: Remote Programming By External Resistance for Constant Voltage
Current Channel
A 5000 ohm potentiometer programs the supply output current from zero to full
rated current. Front panel Current control is disabled. Front panel Voltage
control remains active.
Desired Output Current
=
Full Rated Output Current
5000 ohms
Figure 3.6: Remote Programming by External Resistance for Constant Current
3.5.2REMOTE PROGRAMMING BY EXTERNAL VOLTAGE
Voltage Channel
A 0 to 5 Vdc variable power supply programs the supply output from zero to full
rated voltage. Front panel Voltage control is disabled. Front panel Current
control remains active.
83-481-004
Page 17 of 59 Rev. Z
Page 25
0806 Option 0-10V Program
J1 PROGRAMMING CONNECTOR
2345678
9
20
22
VOLTAGE PROG 0806
1
10 11 12 13 14 15
16
+
0 - 10V
Figure 3.7.1: Voltage Prog 0806
Current Channel
A 0 to 5 Vdc variable power supply programs the supply output from zero to full rated
current. Front panel Current control is disabled. Front panel Voltage control remains
active
0 – 5V=
0 – FS
CURRENT
J1 PROGRAMMING CONNECTOR
0-10V
NOTE:
place of J1-20 for
I Monitor.
J1-13 used in
.
Figure 3.8: Remote Programming by External Voltage for Constant Current
83-481-004
Page 18 of 59 Rev. Z
Page 26
3.5.3REMOTE PROGRAMMING BY EXTERNAL CURRENT
J1 PROGRAMMING CONNECTOR
Voltage Channel
A 0 to 1 mA Variable Current Source programs the supply output from zero to full
rated voltage. The current source is placed in parallel with a 5000 ohm variable
resistor. Front panel Voltage control is disabled. Front panel Current control
remains active.
Figure 3.9: Remote Programming by External Current for Constant Voltage
Current Channel
J18
1122
Figure 3.10: Remote Programming by External Current for Constant Current
A 0 to 1 mA variable current source programs the supply output from zero to full rated
current. The current source is placed in parallel with a 5000 ohm variable resistor.
Front panel current control is disabled. Front panel Voltage control remains active.
3
56
4
7
89 10
11 12
5K
+
0 - 1mA
13
21 14
15 16 20
22
–
83-481-004
Page 19 of 59 Rev. Z
Page 27
3.6 REMOTE SENSING
In applications where the voltage drop across the wires connecting the load cannot be
ignored, the output voltage can be sensed directly across the load. The front panel
voltmeter indicates the voltage directly at the power supply. Remote sensing
minimizes the effect of the power distribution system on load voltage and current.
With remote sensing, the maximum output voltage of the power supply equals the
rated output voltage, minus the total voltage drop across the connecting wires. Figure
3.11 illustrates the strapping and connections required for remote sensing. Note that
the sensing wires are polarized.
NOTE: The RSTL voltage sensing points remain at the output busbars. It will
not sense voltage at the load.
+
+
Figure 3.11: Remote Sensing
3.7 PARALLEL OPERATION
NOTE: Lambda-EMI does not recommend connecting more than two ESS
power supplies in parallel. Contact the factory before connecting three or more
supplies in parallel.
1) The J1 programming connector should be configured before connecting the two
power supplies in parallel.
Caution: Verify that step 1 is done properly before proceeding.
2) Advance the Current control of each supply one half turn clockwise.
3) Use the Voltage control on each unit to set the required output voltage.
4) Turn off both power supplies and rotate each Current control to its maximum
counterclockwise position.
5) Connect each positive load terminal to the positive side of the load. Connect each
negative load terminal to the negative side of the load. NOTE: Individual leads
83-481-004
Page 20 of 59 Rev. Z
Page 28
between the power supply and load must be equal in length and of sufficient
gauge to provide a low impedance.
6) Turn both power supplies on.
7) Use the Voltage controls to ensure that each power supply delivers approximately
the same load current.
8) Slowly adjust each Current control to limit supply output current just above the
value required by the load.
Figure 3.12: Parallel Operation
Recall that the ESS power supply has a variable OVP trip point from about 0 to
110% of output voltage. Consult Lambda-EMI, Inc. for overvoltage protection
using parallel supply connections.
3.7.1 PARALLEL OPERATION IN MASTER/SLAVE CONFIGURATION
A) Maintain the same connections used for parallel operation (Figure 3.12).
Adjust the strapping of each (master and slave supply) J1 programming
connector as shown in Figure 3.13. The power supply designated master
controls the voltage and current output of the slave supply.
B) Figure 3.14 for Master/Slave with OVP Master/Slave. In this configuration
both Master and Slave will shut down with an OVP Function.
NOTE: RSTL can only be used in Master Supply, and the P1/J1 should be
configured according to Fig. 3.13 and 3.14. Please contact the factory to
configure a unit with RSTL for Slave Operation.
83-481-004
Page 21 of 59 Rev. Z
Page 29
Advance the Voltage and Current controls of the slave supply to maximum clockwise
position. Use the Voltage and Current controls of the master supply to set load
voltage and current.
Figure 3.13: Parallel Operation in Master/Slave Configuration
NOTE: The Slave power supply should be set at 1% to 5% higher in the voltage
channel than the master (otherwise the master will lose control of the slave and the
slave will seek the voltage setting of the front panel setting).
Figure 3.14: Paralleled Operation in Master/Slave Configuration with OVP
Master/Slave
Note: See Figure 3.14.3 and 3.14.4 for units with the 0-10V Option.
83-481-004
Page 22 of 59 Rev. Z
Page 30
Advance the Voltage and Current controls of the slave supply to maximum clockwise position.
NOTE: 13 can be used
in place of 20 for noise
J1 PROGRAMMING CONNECTOR
NOTE: 13 CAN BE USED
IN PLACE OF 20 FOR A
Use the Voltage and Current controls of the master supply to set load voltage and current.
MASTER
SLAVE
NOISE REDUCTION
5.2K
Figure 3.14.1: Parallel Operation in Master/Slave Configuration Total Control
with Higher Slave Voltage
NOTE: The Slave power supply is set at 1% to 5% higher in the voltage channel than the
master (otherwise the master will lose control of the slave and the slave will seek the voltage
setting of the front panel setting).
13
5.2K
reduction.
Figure 3.14.2: Paralled Operation in Master/Slave Configuration with OVP with Master
On/Off Total Control Master/Slave and Higher Voltage Slave
83-481-004
Page 23 of 59 Rev. Z
Page 31
Advance the Voltage and Current controls of the slave supply to maximum clockwise
J1 PROGRAMMING CONNECTOR
NOTE: 13 can be used
in place of 20 for noise
reduction.
position. Use the Voltage and Current controls of the master supply to set load voltage
and current.
MASTER
SLAVE
5.2K
Figure 3.14.3: Parallel Operation in Master/Slave Configuration 0806 Total Master
Control On/Off Local Control Note: Figure 4 for External 3.15 & 3.8 For Master only.
NOTE: The Slave power supply is set at 1% to 5% higher in the voltage channel than the
master (otherwise the master will lose control of the slave and the slave will seek the voltage
setting of the front panel setting).
13
5.2K
Figure 3.14.4: Paralled Operation in Master/Slave Configuration with OVP Total
Control Master/Slave Local Control Note: Figure 3.78 and 3.8 for Voltage Current for
Master on.
83-481-004
Page 24 of 59 Rev. Z
Page 32
3.8 SERIES OPERATION
600V +UP ONLY
NOTE: Lambda-EMI, does not recommend more than two ESS power supplies
connected in series. Contact the factory before connecting three or more
supplies in series.
No external programming can be conducted between power supplies other than
Isolated Programming. (See Figure 3.24 for alternate series operation). The output of
each power supply is connected to A100 control board. Damage will occur if bothcommons are wired together.
Two ESS supplies are connected in series by connecting the negative output terminal
of one supply directly to the positive output terminal of the second supply. In local
Voltage and Current controls of each supply are adjusted independently. Total output
or load voltage equals the sum of the individual supply outputs. Although the supply
output terminals are floating, the maximum voltage at any one terminal must not
exceed 600 volts with respect to chassis ground. NOTE: Individual leads between the
power supply and load must be equal in length and of sufficient gauge to provide a
low impedance. The leads between output terminals of the supply must be of equal
gauge.
Figure 3.15: Series Operation
3.9 REMOTE METERS
If strong AC or RF fields are present, remote meter leads should be shielded. Connect
the supply end of the shield to J1-25. Do not terminate the load side of the shield.
A remote voltmeter is connected between J18-2 (positive) and J1-7 (negative). The
voltmeter reads the voltage at the load in conjunction with remote sensing. To read
voltage at the supply output terminals, connect the voltmeter across J18-1 (positive)
and J1-8 (negative).
Figure 3.16 illustrates a remote voltmeter that indicates voltage across the output
terminals of the power supply. Remote sensing is not used. Figure 3.16 illustrates a
remote voltmeter that indicates voltage across the load.
83-481-004
Page 25 of 59 Rev. Z
Page 33
J18
J1 PROGRAMMING CONNECTOR
POWER SUPPLY
POWER SUPPLY
J1 PROGRAMMING CONNECTOR
REM VM
J18
LOAD
Figure 3.16: Remote Meter Across Output
TERMINALS
REM VM
LOAD
TWISTED
PAIR
Figure 3.17: Remote Meter Across Load
83-481-004
Page 26 of 59 Rev. Z
TERMINALS
Page 34
A) To measure load current, use a remote millivolt meter (100 mV full scale
J1 PROGRAMMING CONNECTOR
OPTIONAL CURRENT
sensitivity), rated output current calibrated in amperes. Connect the meter
across J1-12 (negative) and J1-25 (positive). The power supply generates
100 mV across J1 pins 12 and 25 at full rated output current. See Figure
3.18.
B) Connect 0-5 Vdc meter from J1-20(+) to J1-8 (-V). Full output current, will
generate a full scale reading of 5 Vdc. See Figure 3.19.
Figure 3.18: Remote Meter Across Shunt
Use a higher sensitivity meter movement with a series calibration resistor to compensate for IR drops generated across long remote leads.
VOLTAGE AND CURRENT MONITOR, 0-5 VDC OUTPUT
0-5VDC
REMOTE V MONITOR
0-5V = 0-FS VOLTAGE
REMOTE I MONITOR
0-5V = 0-FS CURRENT
MONITOR
Figure 3.19: Voltage and Current Monitor
83-481-004
Page 27 of 59 Rev. Z
Page 35
3.5.1REMOTE PROGRAMMING BOTH VOLTAGE AND CURRENT
Figure 3.20:
Remote Programming by External Resistance for Constant Current and Constant Voltage
NOTE: You cannot Remote program with external resistance in units with an RSTL or 0-10V
Program.
Figure 3.21:
Remote Programming by External Voltage for Constant Current and Constant Voltage
83-481-004
Page 28 of 59 Rev. Z
Page 36
3.13.11 REMOTE INTERLOCK AND DRY CONTACT
AC Source 24V to 115VAC
18-24VDC Source
16
15
14
Figure 3.22
In normal configuration. Interlock is jumpered as shown in Figure 3.22. An opto
coupler switch, relay contact or other closure device can replace Link 15 to 16. The
interlock when opened disables the power supply output and indicates a control failure
on front panel. Pin 14 can be used with an ac source of a range of 24V to 115VAC
50-400Hz or an 18-24VDC source. Connection hookups are shown in the following
figures.
14
15
1415
16
Opto
14
15
16
Switch
1415
83-481-004
Page 29 of 59 Rev. Z
Page 37
Figure 3.23 Rear Panel Reference
83-481-004
Page 30 of 59 Rev. Z
Page 38
Figure 3.24 Series Operation with Opto Isolators
83-481-004
Page 31 of 59 Rev. Z
Page 39
4RSTL CONTROLLER BOARD
4.1INTRODUCTION TO THE RSTL CONTROLLER BOARD
This board is factory-installed for remote computer control of ESS power systems manufactured by Lambda-EMI. The RSTL is designed to functionally duplicate the voltage and
current controls on the front panel of a power supply. These controls select the programming
levels and provide metering of the supply output. The RSTL, when set for REMOTE mode,
disables the front panel control pot but (the meters still read), and asserts control of the
power supply. The RSTL also disables the analog program when in control.
4.2RSTL CONNECTION TO COMPUTER
The RSTL is designed to be connected to a computer via a GPIB or RS232 cable. The
switch on the back of the RSTL (red DIP switch) is used to set the GPIB address and RS232
data rate. The default setting when shipped from the factory is address #6 and 9600 bits per
second (see section 4.7.1 for details).
4.3CONTROLLING THE POWER SUPPLY
This section explains programming the supply, reading back its output and querying its
status.
Each command sent to the RSTL must be followed by a CR LF (ASCII 13 and 10). Normally
this is taken care of during the configuration of the IEEE-488 card installed in your computer.
For example, the National Instruments cards have an End Of String (EOS) byte that is
controlled by the user. Try using the default setting of the IEEE-488 card, if you have
problems then look to see if the end of string terminator is set correctly.
Send the command "?M" and read the result using either the GPIB or RS232 interface. The
RSTL will return the firmware revision, model and serial numbers. In addition, the voltage
and current of the power supply will be returned. If they do not match your unit then they will
need to be changed using the following commands:
"Set * Voltage dddd" = "S*Vdddd" = Set scaling voltage to dddd Volts.
"Set * Current dddd" = "S*Cdddd" = Set scaling current to dddd Amps.
dddd = 0000 to 1000 (must use four digits).
After the voltage and current are correctly identified, the following commands will be sufficient
to test out the basic functionality of the RSTL control of the power supply:
The RSTL is designed to functionally duplicate the voltage and current controls on the front
panel of a power supply.
"SR" tells the RSTL to put the supply in REMOTE operating mode. In this mode the front
panel controls are switched out of the control circuit and the RSTL digital to analog converters
provide the control signal to the supply. These D/A converters are controlled by the following
two programming commands (among others - see Section 4.7.4 for other commands):
"PV%50" tells the RSTL to program the voltage output of the supply to 50% of full
scale (see 4.7.5 for further details).
83-481-004
Page 32 of 59 Rev. Z
Page 40
"PC%100" tells the RSTL to program the current output of the supply to 100% of full
scale (see 4.7.4 for further details).
"MV" tells the RSTL to measure the voltage output of the supply (see 4.7.4 for further
details).
"MC" tells the RSTL to measure the current output of the supply (see 4.7.5 for further
details).
4.4GENERAL DESCRIPTION
The RSTL board is factory installed within the ESS power supply. The RSTL communicates
via the General Purpose Interface Bus (GPIB) or the RS232C serial communications link.
The RSTL allows remote duplication of the power supply manual operating modes. Front
panel controls are locked out when the user places the power supply in REMOTE mode.
Programming of the Voltage and Current channels is via 12 bit D/A converters. The offset
(zero) and gain (span) trimming of the programming signals is accomplished by 4 8-bit D/A's
pumping current into the programming loop. The values used to trim the unit are stored in
EEPROM in the microcontroller. At power up the trim levels are restored.
Readback is via a 21-bit A/D converter. The software routines used for calibration "use up"
some of this resolution, leaving an apparent 16-bit resolution. This is more accurate than
needed for the great majority of supplies. Trim adjustments for OFFSET and GAIN, in both
Voltage and Current channels, for PROGRAM and READBACK are implemented in software.
Readback trim settings may be disabled at any time, the default mode at power up is TRIM
ON. Trim settings are stored in nonvolatile EEPROM address space.
4.5ELECTRICAL SPECIFICATIONS
OPERATING TEMPERATURE: 0 TO 40 DEGREES CENTIGRADE.
ISOLATION from IEEE(RS232) to POWER SUPPLY: 1000Vac.
AC INPUT:95-130 VAC or 190-260 VAC 1Ø 47-63 Hz
IEEE-488.1: SWITCH SELECTABLE PRIMARY ADDRESS.
The RSTL is contained in a printed circuit board assembly mounted internally in the ESS
power supply unit.
4.7OPERATING INSTRUCTIONS
The following subsections describe the operation of the RSTL in detail.
4.7.1 GPIB AND RS232 INTERFACES
The RSTL interfaces to a computer using either GPIB or RS232 data transfer
methods. See IEEE Std 488.1 for mechanical details of the GPIB connection.
The RS232 port follows the 9-pin IBM AT serial port standard for DCE devices.
The RSTL accepts a command string from either port and processes that string.
If any messages are generated by the command string (e.g. Voltage Readback)
the message is placed in an output buffer.
After the command string is processed the contents of the output buffer are
transmitted over the RS232 lines. At any time the output buffer may be read
using the GPIB. All messages are terminated with a carriage-return and a linefeed character.
The RSTL may be a Talker or a Listener.
The response of the RSTL to a Device Clear Command is to zero the voltage
and current programming DACs. If the power supply is in remote mode it will be
zeroed. If in local mode there will be no change in supply output. However,
unless new voltage and current values are programmed in, the power supply will
be zeroed upon returning to remote operation. The GPIB address and the
RS232 baud rate are selected using the 8-position DIP switch on the rear of the
supply. The settings are as follows:
The baud rate is user selectable. However, the RSTL requires an 8-bit word, 1 stop, and 1
start bit for proper communications. There is no hardware handshaking, a properly received
character will be echoed back over the RS232 line, assuming that the echo function is
enabled. The default is to echo all characters, modifiable using the SET BACKTALK
command:
SB1 = echo on, SB0 = echo off.
Since there is a finite amount of time required to perform a command, the user should not
send a second command until the first command is complete. The unit is ready for the
second command when bit 4 in the serial poll register is set.
The serial poll register is used as follows:
b0 set = Not Used.
b1 set = Not Used.
b2 set = Not Used.
b3 set = Not Used.
b4 set = supply ready to accept commands, when this bit is set after a command the results
of the command (e.g. MV results) are now in the output buffer.
b5 set = Not Used.
b6 set = service request sent.
b7 set = power on initialization, reset by CLR or device clear finish. This bit simply indicates
that the unit has been turned on. This bit is reset by a device clear command. If the bit then
becomes set again, it is because the controller has reinitialized for some reason.
As an alternative method, the RSTL is able to assert a service request upon the implementation of a command that results in some return message. The command "SQ1" will enable this
feature, "SQ0" will disable it. The default is NO service request.
"SQ0" = Don't assert SRQ when ready for next command (def).
"SQ1" = Assert SRQ when ready for next command.
4.7.2 SET-UP COMMANDS
There are several commands that may be issued to the RSTL to select operating
conditions. Each must be followed by a CR LF (ASCII 13, 10).
The following two commands set the scaling values used by the RSTL in calcu-
lating correct programming and readback values. These have no effect in the
HEX or %FULL SCALE modes. If not set properly the RSTL will return erroneous readback data and will program the supply incorrectly. The result is stored
in nonvolatile memory.
"Set * Voltage dddd" = "S*Vdddd" = Set scaling voltage to dddd Volts.
"Set * Current dddd" = "S*Cdddd" = Set scaling current to dddd Amps.
dddd = 0000 to 1000 (must use four digits).
The set commands are as follows:
"Set Local" = "SL" = local operation (def)
"Set Remote" = "SR" = remote operation
83-481-004
Page 35 of 59 Rev. Z
Page 43
"Set Backtalk 0" = "SB0" = RS232 echo off
"Set Backtalk 1" = "SB1" = RS232 echo on (def)
"Set Trim 0" = "ST0" = disable trim adjustments
"Set Trim 1" = "ST1" = enable trim adjustments (def)
These commands may be explicitly spelled out in the command string sent to the ESS
RSTL, but only those letters that are capitalized are actually needed. The rest are
ignored.
e.g. "Set Message 0" is the same as "SM0"
"Set Remote" is the same as "SR"
Due to the limited WRITE/ERASE endurance of the EEPRO< in the RSTL’s microcontroller,
EMI cautions users from executing any of the following commands more than 10,000 times.
4.7.3 INQUIRY COMMANDS
There are several inquiry commands used to check the operating conditions of
the RSTL. Each command must have as its first character a question mark (?).
Each must be followed by a CR LF (ASCII 13, ASCII 10). Each of these
commands will result in a message being placed in the output buffer. The length of
the returned message is determined by the setting of the BACKTALK bit (see 4.7.2)
The inquiry commands are as follows:
"? Model" = "?M" = Place Software Revision, Model and Serial number in output buffer
"? String" = "?S" = Previous command string ?
"? Operation" = "?O" = Local or remote operation?
"? Voltage channel " = "?V" = Voltage DAC programming value (decimal)?
"? Voltage channel heX" = "?VX" = Voltage DAC programming value (hex)?
"? Voltage channel Limit" = "?VL" = Voltage programming soft limit (decimal)?
"? Voltage channel Limit heX" = "?VLX" = Voltage programming soft limit (hex)?
NOTE: Models over 1000 volts, the limit will not set above 999.9 volts.
"? Current channel" = "?C" = Current DAC programming value (decimal)?
"? Current channel heX" = "?CX" = Current DAC programming value (hex)?
"? Current channel Limit" = "?CL" = Current programming soft limit (decimal)?
83-481-004
Page 36 of 59 Rev. Z
Page 44
"? Current channel Limit heX" = "?CLX" = Current programming soft limit (hex)?
NOTE: Models over 1000 Amps, the limit will not set above 999.9 Amps.
"? Trim Voltage " = "?TV" = Trimming values for voltage channel?
"? Trim Current" = "?TC" = Trimming values for current channel?
These commands may be explicitly spelled out in the command string sent to the RSTL
controller, but only those letters that are capitalized are actually needed. The rest are
ignored.
"?M" will put a message in the output buffer of the following form:
"Rev 3.0 RSTL 10-1000 Serial 91A-1234"
This is of the form : Rev #1 RSTL voltage-current Serial #2, where #1 is the firmware
revision number and #2 is the unit's serial number.
"?S" will return the last command string sent to the RSTL. This can be useful for debugging command sequences or verifying correct command reception.
"?O" will put one of the following messages in the output buffer:
"L operation" or "L"
"R operation" or "R"
if unit is in SHUTDOWN mode:
"R operation SHUTDOWN" or
"R SHUTDOWN"
"?V" will put the following message in the output buffer: "PVoltage = ddd.d Volts"
"?C" will put the following message in the output buffer: "PCurrent = ddd.d Amps"
"?VL" will put the following message in the output buffer: "PVoltage Limit = ddd.d Volts"
"?CL" will put the following message in the output buffer: "PCurrent Limit = ddd.d Amps"
"?VX" will put the following message in the output buffer: "Voltage = xxx"
"?CX" will put the following message in the output buffer: "Current = xxx"
"?VLX" will put the following message in the output buffer: "PVoltage Limit = xxx"
"?CLX" will put the following message in the output buffer: "PCurrent Limit = xxx"
xxx = the hex programming values of 000 to FFF.
"?TV" will put the following message in the output buffer: "1 ww xx yyyy zzzz"
Where the first character indicates whether or not the trim adjustments are disabled:
(1 = enabled, 0 = disabled).
ww = the hexadecimal value of the voltage programming offset trim value.
xx = the hexadecimal value of the voltage programming gain trim value.
yyyy = the hexadecimal value of the voltage readback offset trim value.
zzzz = the hexadecimal value of the voltage readback gain trim value.
"?TC" will put the following message in the output buffer: "1 ww xx yyyy zzzz"
This gives the same result for the current channel as "?TV" gives for the voltage channel.
83-481-004
Page 37 of 59 Rev. Z
Page 45
4.7.4 MEASUREMENT COMMANDS
The RSTL is capable of measuring the output voltage and output current of the
power supply. The optional A/D converter provides approximately 16-bit resolution. The readback message is returned as a measure of Voltage, Amperage or,
for fastest operation, simply the hexadecimal output of the A/D converter. The
length of the returned message is determined by the setting of the BACKTALK
bit (see 4.7.2)
The measurement commands are as follows:
"Measure V" = "MV" = measure output voltage and return result in Volts format.
"Measure V heX" = "MVX" = measure output voltage and return result in hex
format.
"Measure C" = "MC" = measure output current and return result in Amps format.
“Measure C heX" = "MCX" = measure output current and return result in hex
format.
These commands may be explicitly spelled out in the command string sent to the
RSTL controller, but only those letters that are capitalized are actually needed.
The rest are ignored.
83-481-004
Page 38 of 59 Rev. Z
Page 46
Assuming a 10 Volt, 1000 Amp ESS supply at 10 Volts and 500 Amps, the
following messages would be returned using the following commands:
"MV" will put one of the following messages in the output buffer:
"Voltage = +10.000 Volts" or "+10.000"
"MC" will put one of the following messages in the output buffer:
"Current = 500.0 Amps" or "500.0"
"MCX" will put one of the following messages in the output buffer:
"Current = 8000" or "8000"
Note the value of the hex string:Zero = 0000 hex
Full Scale = ffff hex
4.7.5 PROGRAMMING AND SOFT LIMIT COMMANDS
The Voltage and Current programming channels have resolutions of 12-bits. In
addition to these two channels there are two corresponding "soft limit" values
that can be programmed. The soft limit is simply a programmed maximum or
limit point. If, for example, the Voltage channel is programmed to some value in
excess of the soft limit, the voltage output will not be allowed to exceed the soft
limit. If the soft limit is increased then the output will increase until the initial
programming level is reached. The default soft limit for both channels is full
scale.
NOTE: Soft limits will not set above 999.9 Volts or 999.9 Amps.
There are several methods available to program the control and limit channels,
these are:
Programming in Volts or Amps.
Programming as a percentage of full scale.
Programming the DAC directly in hexadecimal.
The programming channel commands are of the following forms:
Direct programming (Volts or Amps):
"Program Voltage 10.000" = "PV10.000" = Program Voltage to 10.000 Volts.
"Program Current 485" = "PC485" = Program Current to 485 Amps.
"Program Voltage Limit 10.000" = "PVL10.000" = Program Voltage Limit to
10.000 Volts.
"Program Current Limit 485" = "PCL485" = Program Current Limit to 485 Amps.
NOTE: Soft limits will not set above 999.9 Volts or 999.9 Amps.
Percentage full scale programming ( 0 to +%99.99):
"Program Voltage %50.00" = "PV%50" = Program Voltage to %50 of full scale.
"Program Current %99.99" = "PC%99.99" = Program Current to %99.99 of full
scale.
"Program Current -%0.25" = "PC-%.25" = Program Current to negative %0.25
full scale.
83-481-004
Page 39 of 59 Rev. Z
Page 47
"Program Voltage Limit %50.00" = "PVL%50" = Program Voltage Limit to %50 of
FS.
"Program Current Limit %99.99" = "PCL%99.99" = Program Current Limit to
%99.99 FS.
"Program Current Limit -%0.25" = "PCL-%.25" = Program Current Limit to neg.
%0.25 FS.
Hexadecimal programming (0000h to ffffh):
"Program Voltage heX 0000" = "PVX0" = Program Voltage DAC to 000h (zero).
"Program Voltage heX 7ff" = "PVX7ff" = Program Voltage DAC to 7ffh (half
scale).
"Program Current heX fff" = "PCXfff" = Program Current DAC to fffh (full scale).
"Program Voltage heX Limit 0000" = "PVXL0" = Program Voltage Limit to 000h (zero).
"Program Voltage heX Limit 7ff" = "PVXL7ff" = Program Voltage Limit to 7ffh (half
scale).
"Program Current heX Limit fff" = "PCXLfff" = Program Current Limit to fffh (full scale).
4.7.6 TRIM PROGRAM COMMANDS (SOFT PROGRAMMING CALIBRATION)
The RSTL does not have any potentiometers to adjust the zero and full scale
programming levels of the current and voltage channels. The calibration, or
"trimming" function is accomplished by using TRIMDACS to adjust these
parameters. The four trim levels are programmed using hexadecimal input
coding. The adjustment range is between 00h and ffh. The nomenclature of the
four trim programming parameters is (hh = hex programming level):
TRIM VOLTAGE CHANNEL OFFSET hh
TRIM VOLTAGE CHANNEL GAIN hh
TRIM CURRENT CHANNEL OFFSET hh
TRIM CURRENT CHANNEL GAIN hh
The trim programming commands are of the following forms:
"Trim Program Voltage Offset 80" = "TPVO80"=
Set voltage offset programming D/A to hex 80 (1/2 scale).
"Trim Program Voltage Gain ff" = "TPVGff"=
Set voltage gain programming D/A to hex ff (full scale).
"Trim Program Current Offset 40" = "TPCO40"=
Set current offset programming D/A to hex 40 (1/4 scale).
"Trim Program Current Gain c0" = "TPCGc0"=
Set current gain programming D/A to hex c0 (3/4 scale).
83-481-004
Page 40 of 59 Rev. Z
Page 48
4.7.7 TRIM MEASURE COMMANDS (SOFT READBACK CALIBRATION)
The measurement, or readback, of the power supply's output voltage and current
is accomplished by a high resolution A/D converter. To allow for software
trimming of the readback levels the input to the A/D is pulled up slightly above
zero and the full scale range slightly exceeds the actual signal to be measured.
By taking a "snapshot" of the voltage and current sense signal at their zero and
full scale points the RSTL can calculate all measured values. There are four
commands used to take this snapshot; they must only be used when the output
of the supply is at the appropriate level. The four trim readback parameters are:
"Trim Read Voltage Offset" = "TRVO" = Set voltage read zero point
"Trim Read Voltage Gain" = "TRVG" = Set voltage read full scale point
"Trim Read Current Offset" = "TRCO" = Set current read zero point
"Trim Read Current Gain" = "TRCG" = Set current read full scale point
The procedure to use these commands is as follows:
VOLTAGE READBACK ZERO:
Set the voltage output of the supply to zero using the "PV" command or
equivalent.
Send the command "TRVO". This will store the voltage readback offset value in
the EEPROM for later use in readback calculations.
VOLTAGE READBACK FULL SCALE:
Set the voltage output of the supply to full scale using the "PV" command or
equivalent.
Send the command "TRVG". This will store the voltage read gain value in the EEPROM
for later use in readback calculations
CURRENT READBACK ZERO:
Set the current output of the supply to zero using the "PC" command or equivalent.
Send the command "TRCO". This will store the current readback offset value in the
EEPROM for later use in readback calculations.
CURRENT READBACK FULL SCALE:
Set the current output to full scale using the "PC" command or equivalent.
Send the command "TRCG". This will store the current read gain value in the EEPROM
for later use in readback calculations.
If the readback seems to be correct toward the full scale end but erroneous toward thezero end, then repeat the zero procedure.
If the readback seems to be correct toward the zero end but erroneous toward the fullscale end, then repeat the full scale procedure.
4.8 SERVICE PROCEDURES
4.8.1 GENERAL
The RSTL controller board is factory-installed; there are no user serviceable
parts on it. Any operational difficulty with the board should be reported to
Electronic Measurements Inc. The RSTL controller is shipped precalibrated from
the factory; if it becomes necessary to recalibrate the operating parameters
(Programming, Readback, etc.) this may be done by the user.
83-481-004
Page 41 of 59 Rev. Z
Page 49
4.8.2 CALIBRATION
There are several end-user calibrations that may be made, these include:
Programming Voltage Zero
Programming Voltage Gain (full scale)
Programming Current Zero
Programming Current Gain (full scale)
Readback Voltage Zero
Readback Voltage Gain
Readback Current Zero
Readback Current Gain
The programming channels may be trimmed by approximately ± 10% using the
8-bit trim adjustments DACs. The DACs can be programmed in two ways, either
directly using a hexadecimal input (00 to ff), or as a percentage of full scale (0%
to 99%). Direct hex programming provides greater resolution and is the
preferred method.
The trim setting should only be adjusted after the unit under test has fully
warmed up.
The readback channels are trimmed quite differently from the programming
channels. Internal to the RSTL is an AD7710 21-bit A/D converter. the input to
this converter is slightly offset in the positive direction to force a zero input to
cause some slight reading. the gain of the buffer-amplifier stage before A/D is
set to provide a full-scale signal manipulation to “normalize” the readback data to
the actual supply output levels. Readback trimming is limited to about +10%
max on offset adjustments, and 20% max on gain adjustments.
Items needed for RSTL controller calibration:
RSTL Controller installed in a power supply.
4 1/2 digit voltmeter.
Calibrated external shunt (optional - internal shunt is very accurate).
Shorting strap or other load capable of handling the full current of the power
supply.
Computer with IEEE-488 or RS232 port (see 4.8.3 for demonstration programs).
INITIAL SETUP:
Turn circuit breaker to OFF position.
Disconnect AC power from the power supply.
Connect IEEE or RS232 ports to computer or other IEEE-488 Controller.
Connect the AC power source to the supply and the RSTL (the RSTL will now
be powered up if it is a separate unit).
Turn the power supply's AC circuit breaker to the ON position.
Establish communications between the computer and the RSTL.
Turn the power supply's AC circuit breaker to the OFF position.
VOLTAGE CHANNEL CALIBRATION:
Either disconnect the load from the power supply (open circuit) or adjust it such
that the supply will be able to put out its full voltage.
83-481-004
Page 42 of 59 Rev. Z
Page 50
Place meter across output terminals, observing proper polarity.
Turn the circuit breaker to ON position.
Send command "SR" (see 4.7.2).
VOLTAGE PROGRAM ZERO:
Send commands "PVX005" and "PCXFFF" (see 4.7.5).
Calculate the proper output voltage by dividing the full scale voltage of the
power supply by 4096 and multiplying the result by 5 ( (Vfs/4096) * 5 = zero
calibration point).
The Meter should read the calculated zero calibration value ± 0.1% F.S.
Adjust TRIM PROGRAM VOLTAGE OFFSET until meter reads correct voltage
(see 4.7.7)
VOLTAGE PROGRAM FULL SCALE:
Send command "PVXFFF" and "PCXFFF" (see 4.7.5).
Meter should read F.S. Voltage ± 0.1% F.S.
Adjust TRIM PROGRAM VOLTAGE GAIN until meter reads correct voltage (see
4.7.7).
VOLTAGE READBACK ZERO:
Program the supply to zero voltage (e.g. "PV0").
When the output voltage is zero ± 0.1 %, send the command: "TRVO". This will
store the voltage read offset value in the EEPROM for later use in readback
calculations (see 4.7.7).
Send command "MV" to initiate a read of the voltage channel (assuming the
readback is calibrated).
Check to make sure the reading is now correct (voltage should equal zero).
VOLTAGE READBACK FULL SCALE:
Program the supply to full-scale voltage.
When the output voltage is at full-scale ± 0.1 %, send the command : "TRVG".
This will store the voltage read gain value in the EEPROM for later use in
readback calculations.
Send command "MV" to initiate a read of the voltage channel.
Check to make sure the reading is now correct (voltage should equal full scale).
Program and measure the voltage for several points throughout the supply's
range. The programming and readback should track closely.
83-481-004
Page 43 of 59 Rev. Z
Page 51
CURRENT CHANNEL CALIBRATION:
Turn circuit breaker to OFF position.
Either connect the load to the power supply and adjust it such that the supply will
be able to put out its full current or connect the shorting strap to the power
supply. If using an external shunt connect the shunt in series with the load or
shorting strap.
Turn circuit breaker to ON position.
Send command "SR".
CURRENT PROGRAM ZERO:
Send the commands "PCX005" and "PVXFFF".
Calculate the proper output current by dividing the full scale current of the power
supply by 4096 and multiplying the result by 5 ( (Ifs/4096) * 5 = zero calibration
point). NOTE: The full scale current value corresponds the voltage across the
shunt being measured when the output current is at full scale. The typical E/M
internal shunt will measure 100 milliVolts at full output current. The zero calibra-
tion point is therefore equal to (100/4096)*5 = 0.122 milliVolts. The meter
should read the calculated zero calibration value ± 0.1% F.S. Adjust TRIM
PROGRAM CURRENT OFFSET until meter reads correct current (see 4.7.7).
CURRENT PROGRAM FULL SCALE:
Send command "PCXFFF".
Meter should read F.S. Current ± 0.1% F.S.
Adjust TRIM PROGRAM CURRENT GAIN until meter reads correct current.
CURRENT READBACK ZERO:
Program the supply to zero current.
When the output current is zero ± 0.1 %, send the command: "TRCO". This will
store the current read offset value in the EEPROM for later use in readback
calculations.
Send command "MC" to initiate a read of the voltage channel.
Check to make sure the reading is now correct.CURRENT READBACK FULL
SCALE:
Program the supply to full-scale current.
When the output current is at full-scale ± 0.1 %, send the command : "TRCG".
This will store the current read gain value in the EEPROM for later use in
readback calculations.
Send command "MC" to initiate a read of the current channel.
Check to make sure the reading is now correct.
Program and measure the current for several points throughout the supply's
range. The programming and readback should track closely.
83-481-004
Page 44 of 59 Rev. Z
Page 52
4.8.3 DEMONSTRATION GWBASIC PROGRAM
The following is a GWBASIC program to operate the RSTL controller card. This
program requires the use of a National Instruments GPIB interface card in an
AT-type PC. In addition, the Universal Language Interface program (ULI -
included with National Card) should be run prior to running this GWBASIC
program. See the National Instruments manual for proper installation and setup
of the IEEE-488 Interface Card.
Line 2000 is the serial poll wait routine. After a command is sent the program
looks for b4 to be set in the serial poll output register.
10 CLS
20 OPEN "GPIB0" FOR OUTPUT AS #1
30OPEN "GPIB0" FOR INPUT AS #2
40PRINT #1, "ABORT"
50PRINT #1, "GPIBEOS CR LF"
60 PRINT "ESS TEST......"
70 PRINT "UNIT UNDER TEST MUST BE AT ADDRESS 6"
80 PRINT:PRINT "Enter Command..."
90 INPUT CMD$
110IF CMD$ = "S" THEN GOSUB 1005
111IF CMD$ = "C" THEN GOSUB 3000
120PRINT #1,"OUTPUT 6 ;",CMD$
125GOSUB 2000
140PRINT #1, "ENTER 6"
150INPUT #2, RD$
160PRINT RD$
170GOTO 80
1005 PRINT#1,"SPOLL 6"
1006 INPUT#2,SPR%
1007 PRINT SPR%
1009 GOTO 1005
1010 RETURN
2000 PRINT#1,"SPOLL 6"
2010 INPUT#2,SPR%
2015 PRINT HEX$(SPR%)
2020 IF SPR% AND 16 THEN 2040
2030 GOTO 2000
2040 RETURN
3000 PRINT#1,"CLEAR 6"
3010 RETURN
Table 4.2 Demonstration GWBasic Program
83-481-004
Page 45 of 59 Rev. Z
Page 53
4.8.4 DEMONSTRATION QUICK-C PROGRAM
The following is a Quick-C program to operate the RSTL controller card. This
program requires the use of a National Instruments GPIB interface card in an
AT-type PC. See the National Instruments manual for proper installation and
setup of the IEEE-488 Interface Card.
/*
SIMPLE INTERACTIVE RSTL PROGRAM USING
MICROSOFT QUICK-C & NATIONAL INSTRUMENTS PCII-A CARD
*/
#include <c:\qc25\include\stdio.h>
#include <c:\qc25\include\math.h>
#include <c:\qc25\include\ctype.h>
#include <c:\qc25\include\dos.h>
#include <c:\qc25\include\graph.h>
#include <c:\qc25\include\time.h>
#include <c:\qc25\include\sys\types.h>
#include <c:\qc25\include\sys\timeb.h>
/* The following is provided on the National Instruments distribution disk */
#include <c:\gpib-pc\decl.h>
/*-----------------------------------------*/
/* IEEE functions and definitions */
/*-----------------------------------------*/
/*-----------------------------------------------------------------------------*/
/* initialize the National Controller at address 0 on the GPIB */
/*-----------------------------------------------------------------------------*/
brd0 = ibfind ("GPIB0");
if(brd0 < 0)
{
printf("Didn't find brd0\r\n");
finderr("GPIB0");
}
ibeos(brd0,"\n");
/*------------------------------------------------------------*/
/* initialize the RSTL at address 6 on the GPIB */
/*------------------------------------------------------------*/
/*--------------------------------------------------------------------*/
/* The following routine will write a string to the RSTL */
/*---------------------------------------------------------------------*/
int
write_rstl(char message[])
{
if (ibwrt (rstl,message,strlen(message)) & ERR)
error();
if (ibwrt (rstl,"\r\n",2) & ERR)
error();
ibcmd (brd0,"_?",2); /* UNT UNL */
}
/*--------------------------------------------------------*/
/* The following routine will read a string from the RSTL */
/*--------------------------------------------------------*/
void
read_rstl()
{
if (ibrd(rstl,rd,40) & ERR)
error();
ibcmd (brd0,"_?",2); /* UNT UNL */
}
/*--------------------------------*/
/* National error routines */
/*--------------------------------*/
int
finderr(char device[]) /* ibfind failure error routine */
{
printf("Ibfind error on %s; does device or board\n",device);
printf("name given match configuration name?\n");
}
int
error() /* general error handling routine */
{
printf("GPIB function call error:\n");
printf("ibsta=0x%x, iberr=0x%x,",ibsta,iberr);
printf(" ibcnt=0x%x\n",ibcnt);
}
int
rstlerr() /* device error handling routine */
{
printf("Device error\n");
printf("ibsta=0x%x, iberr=0x%x,",ibsta,iberr);
printf(" ibcnt=0x%x\n",ibcnt);
}
83-481-004
Page 48 of 59 Rev. Z
Page 56
4.8.5 DEMONSTRATION LAB WINDOWS FOR DOS PROGRAM
The following is a LabWindows for DOS program to operate the RSTL controller
card. This program requires the use of a National Instrument LabWindows
software package and a National Instruments GPIB interface card in an AT-type
PC. See the National Instruments manual for proper installation and setup of
the IEEE-488 Interface Card.
/*
/* SIMPLE INTERACTIVE LAB WINDOWS FOR DOS PROGRAM
/*
/*
#include "C:\LW\INCLUDE\lwsystem.h"
#include "C:\LW\INCLUDE\utility.h"
#include "C:\LW\INCLUDE\gpib.h"
#include "C:\LW\INCLUDE\formatio.h"
#include "C:\LW\INCLUDE\userint.h"
#include "C:\LW\INCLUDE\graphics.h"
#include "C:\LW\INCLUDE\analysis.h"
#include "C:\LW\INCLUDE\vxi.h"
#include "C:\LW\INCLUDE\rs232.h"
/*----------------------------------------------------------------*/
/* The following are IEEE functions and definitions */
/*----------------------------------------------------------------*/
#define ERR (1<<15) /* Error detected */
#define TIMO (1<<14) /* Timeout */
#define RQS (1<<11) /* Device needs service */
int ibsta,
iberr,
ibcnt;
/*---------------------------------------------------------------------------*/
/* Application program variables passed to GPIB functions */
/*---------------------------------------------------------------------------*/
char command[80]; /* command input buffer */
int rstl, /* RSTL */
brd0; /* National GPIB board */
int spr; /* serial poll response byte */
int status;
long stptme,strtme;
long pretme,eltme;
long strtime,ptime;
main()
{
/*------------------------------------*/
83-481-004
Page 49 of 59 Rev. Z
Page 57
/* Local variable assignment */
/*------------------------------------*/
void supply_init();
char *read_rstl();
/*-----------------------------------------------------------------------------*/
/* initialize the National Controller at address 0 on the GPIB */
/*-----------------------------------------------------------------------------*/
brd0 = ibfind ("GPIB0");
if (brd0 < 0)
{
FmtOut("Didn't find board and GPIB0\r\n");
finderr("GPIB0");
}
/*-------------------------------------------------------------*/
/* Set end of string character to LineFeed, 0x0a */
/*-------------------------------------------------------------*/
ibeos(brd0,0x0a);
/*-------------------------------------------------------*/
/* initialize the RSTL at address 6 on GPIB */
/*-------------------------------------------------------*/
The 220 Vac version works with 3 phase four wire systems. The Input AC is rectified by
CR1. A raw DC bus is created with a parallel combination of C1 and C2. Refer to main
schematic. The power is processed by four high frequency transformers coupled with full
bridge buck converters. The raw DC bus is connected to the input of a full bridge inverter.
The output from the bridge is controlled by the duty cycle of the PWM. For 220 Vac input, all
four modules are connected to the parallel combination of C1 and C2.
5.2POWER FLOW
The AC power enters through TB1 on the rear of the unit and passes through the A300 line
filter board. The load side of the line filter is connected to the front panel circuit breaker. The
raw DC bus is created by the series or parallel combination of C1 and C2. L1 controls the
peak charging current which is inherent in capacitive input filters. Additionally, L1 also
increases the conduction angle, thereby improving the power factor of the system.
The inverter board consists of four full bridge inverters. The output of the inverter is a 33 kHz
PWM square wave, which is fed to the primary of transformers T1A to T1D. The secondaries
of the transformers are connected to a full wave rectifier and an LC averaging filter. Each
module is connected to the output bus bar. The output has preload resistors mounted on the
heatsink assembly. The output filter consists of L2A-2D, L3, C7, C8, C9, and C10. An RC
snubber is used to minimize the voltage spike across the diodes.
5.3INVERTER MODULE
The full bridge inverter consists of four IGBTs. T1 is designed such that Q1 and Q4 are
turned on simultaneously while Q2 and Q3 are turned off. T2 senses the switching of the
IGBTs and the switching of the HF power transformer's primary current. CR9, CR10, CR11,
and CR12 rectify the signal from T2 and generate a voltage across the burden resistor R14.
The signal across R14 is connected to the A100 card for control purposes. C5 snubs the
spikes generated by the primary leakage inductance of the HF power transformer. CR2,
CR4, CR6 and CR8 are the anti-parallel diodes across the switches. The RC snubber across
the device limits the dv/dt so that latching of the IGBTs is prevented. L1, C13 and C14 form a
bypass circuit which delivers the entire pulse current of the inverter, thereby reducing the
area of high frequency pulse current. The signal from TS1 shuts the PWM down in case of
over heating. The A100 board controls steady state volt-second balance across the high
frequency power transformer to prevent saturation of T1.
83-481-004
Page 52 of 59 Rev. Z
Page 60
5.4SIGNAL FLOW
A100 BOARD: This board generates 15 volts and +5 volts for "Housekeeping" purposes.
Other functions of the A100 control board:
1) Reference Generation
2) CC/CV Control
3) Control of PWM
4) Supervisory Functions
5) Over current protection
5.5REFERENCE GENERATION
Separate constant current references are provided for voltage and current channels. The
collector current of Q1 drives the voltage channel. The collector current of Q2 drives the
current channel. The current sources are referenced by U6, a highly stable voltage source.
The current through the sources is adjustable by R6 and R8. The current sources are factory
adjusted to 1 mA, and terminate at J1-3 and J1-9 on rear panel programming connector.
5.6ERROR AMPLIFIERS
Constant voltage control and error amplification are implemented by U7. The reference
(0-5 Volts) is connected to the non-inverting terminal of U7. An attenuated version of
the output voltage is connected to the inverting terminal of U7. A voltage of 0 to 5 volts
across R136 is the equivalent of 0 to 100% of the output voltage. The output of the voltage
channel amplifier can be measured at A1. It should be -0.7 volts for the shutdown condition
and 6 volts for maximum duty cycle. The offset null is adjusted by R15. Constant current is
implemented by U8 and U9. The references are connected to the non-inverting inputs of U9.
The output current is sensed by shunt R12 mounted in the power supply. The output of the
current channel can be measured at B1. It should be -0.7 volts shutdown or 6 volts. Voltage
and current channels are "ORed" via diodes CR41 and CR31, and thus provide automatic
crossover from current to voltage control and vice versa.
5.7PULSE WIDTH MODULATOR
The "core" of the A100 board consists of the four UC 3825 controllers. U15, U16, U17 and
U18 are synchronized by the clock consisting of U4, U20, U21, U22, U23, and output drivers
U22A-B, which comprise the sync needed to control the point at which the oscillator ramp
begins.
All error amplifiers of U15, U16, U17 and U18 have a unity gain. Their inputs are tied
together and receive their signal from U7 and U9. Q4, Q6, Q8, and Q10 isolate the clock
signal from the oscillators to provide slope compensation for U15, U16, U17 and U18.
83-481-004
Page 53 of 59 Rev. Z
Page 61
Signals are fed through diodes CR62, CR70, CR63 and CR71 to pin 7. At pin 7, the clock
signal and the current signal are combined. C54, C64, C74 and C84 block DC from Q4, Q6,
Q8 and Q10 from appearing on pin 7 of each PWM.
The duty cycle of the PWM is controlled by comparing the output of the error amplifiers (U15,
U16, U17 and U18) to the ramp of the oscillator and the current sense signal of the high
frequency transformers.
Q5, Q9, Q7 and Q11 make up the soft start. When their bases are pulled low or their
emitters are pulled low, the PWM shuts down. When the bases or the emitters are released,
the PWMs will slowly widen pulse width and then are controlled by error amps.
5.8SUPERVISORY FUNCTIONS
U14, U11, and U12 and the associated components form the supervisory circuit. These
functions include: undervoltage lockout, phase loss detection, overvoltage protection, control
failure, inrush current suppression, mode detect and over- temperature lockout. Inrush
current limitation and mode detection are implemented by U12. The other functions are
implemented by the power supply's supervisor chip U14 (UC3544).
5.9REMOTE TURN ON CIRCUIT
This feature allows the user to control the power supply from a remote location with a 12-24
Vdc, 24-115 Vac or a dry contact closure. U4 provides isolation from the power supply
ground. When using a dry contact closure, the power is supplied by the bias transformer,
rectified on the A100 board, and then routed to J14 to CR47. The interlock side is opened or
closed by J1 15 and J1 16.
5.10INRUSH CURRENT LIMITING CIRCUIT
The soft start is controlled by the A100 board and works in conjunction with the K1 that is on
the input rectifier assembly. When power is applied to the supply, the output of U12 is low.
The input bus capacitors are charged via K1 with a resistor to limit the inrush current. After
the elapsed time, which is determined by R47, R49 and C42, the output of U12 switches to
high, closing both poles of the relay (K1). The soft start pins of U15, U16, U17, and U18 go
high, enabling the PWMs.
5.11MODE DETECT
The output of the voltage channel and current channel are compared by the second op-amp
of U12. The output of the comparator switches between plus and minus 15 volts, depending
on the magnitude of its input signal. If the output is positive, the voltage LED on the front
panel lights; if it is negative, the current LED lights.
5.12THERMAL SHUTDOWN
The heatsink’s temperature is sensed by individual thermostats wired in parallel. The thermostats are normally open but they close when the temperature exceeds 70 degrees Celsius. A
closed thermostat will pull the soft start pins of U15, U16, U17, and U18 low, disabling the
PWMs.
83-481-004
Page 54 of 59 Rev. Z
Page 62
5.13PHASE LOSS CIRCUIT
The phase loss circuit is the same for all the models, except that the 220 Vac model does not
detect a neutral loss.
5.13.1PHASE LOSS CIRCUIT FOR THE 220 VAC
The incoming AC line is rectified (on the PCB A600 assembly) and optically
coupled to the control section. The output of the opto-coupler is controlled by
R602 and R601. The output of the opto-coupler is connected to pin 9 of U14 (on
the A100 board) and is compared to the 2.5 volts reference on pin 8. For
normal operation, pin 11 is high (15 volts). When a phase loss or a low line
occurs, pin 11 switches to low causing the soft start pins of U15, U16, U17, and
U18 to go low, thus disabling the PWMs and turning the phase loss LED on.
5.13.2PHASE LOSS CIRCUIT FOR THE 380, 415 AND 480 VAC
The incoming AC line is rectified (on the PCB A600 assembly) and optically
coupled to the control section. The output of the opto-coupler is controlled by
R4, R6 and R7. The output of the opto-coupler is connected to pin 9 of U14 (on
the A100 board) and is compared to the 2.5 volts reference on pin 8. For normal
operation, pin 11 is high (15 volts). When a phase loss or a low line occurs, pin
11 switches to low, causing the soft start pins of U15, U16, U17, and U18 to go
low, thus disabling the PWMs and turning the phase loss LED on. The neutral
loss circuit is comprised of R1, R2, R3, CR7, CR9, CR1 and U1. If the neutral
line is disconnected, a voltage will develop across R5 causing U1 to disable U2.
Therefore, the soft start pins of U15, U16, U17, and U18 will go low disabling the
PWMs.
5.14 OVERVOLTAGE PROTECTION
This feature allows the user to control the power supply's overvoltage trip point. The overvoltage control (R16) located on the front panel controls an adjustable 2.5 volt reference which is
fed to the U14 on the A100 board. An attenuator on the A100 board also couples the DC
signal to U14. When the signal of the attenuator is higher than the adjustable 2.5 volt reference, U14, drives a DC signal to the A900 board. U801 (SCR optocoupler) drives Q601,
which crowbars the output of the power supply. At the same time, U14 pulls the (SS line)
low, which shuts off the PWM.
83-481-004
Page 55 of 59 Rev. Z
Page 63
6MAINTENANCE
6.1MAINTENANCE
To be performed only by qualified service personnel. Prior to removing the cover, refer to
Section 1.2, page 1 for safety warnings.
6.2INTRODUCTION
This section provides a troubleshooting guide, module replacement procedures and a calibration procedure. The troubleshooting guide addresses the most common symptoms and their
causes. The replacement procedure outlines the removal and replacement of the Field
Replaceable Units (FRUs). The calibration procedure outlines the adjustment of the A100
board. Whenever any troubleshooting, replacement or calibration is done, the schematics
and components listed in section 6.10 should be used for reference.
6.3TROUBLESHOOTING GUIDE
POSSIBLE CAUSE SYMPTOMS
Remote on/off is disconnected.No Output. Control Failure LED is on.
A100 board failure, inverter failure or neutral
disconnected on 380, 414, 480 Vac input models,
or OVP fired.
NOTE: When remote is OFF, control failure will be
ON. This is a normal condition.
AC line low or phase/neutral is disconnected.Phase Loss LED is on
LED not glowing
Inverter LED is glowing
Unit output goes too high. Voltage and current
are unadjustable.
Overheating
Table 6.1: Troubleshooting Guide
Faulty Power On LED.Supply working, but Power On LED is not glowing.
F1 fuse blown. Bias supply failure or fan(s) failure.Supply not working and Power On
Inverter failed (replace inverter), check diodes on
output assembly.
Check address switch.RSTL doesn't work
Input rectifier failed or inverter failed. Circuit breaker trips
Wires to voltage or current pots are disconnected.
Voltage or current pot is broken.
One or two inverters have failed.Cannot reach full output
One of the output caps has failed.High ripple
One of the fans have failed or an inverter is
overheating.
83-481-004
Page 56 of 59 Rev. Z
Page 64
6.4FIELD REPLACEABLE UNITS (FRUS)
This supply is comprised of several modules (assemblies). If a module fails, simply replace it
with an identical one. A front panel LED will glow to indicate which module (assembly) has
failed. FRUs (modules) are replaced by removing the screws on the top cover which allows
access to the modules. When ordering a FRU, please refer to its Lambda-EMI number and
the model number of the power supply. The table below provides a list of the modules and
their EMI part numbers.
Caution: Proper ESDS (Electrostatic Discharge Sensitivity) procedures should be adhered to
whenever replacing a module or troubleshooting the power supply.
Prior to removing the top cover of the power supply, Refer to Safety Precautions, section 1.2
of page 1. Simply loosen the screws that attach the cover to the chassis and remove the
cover.
6.5INVERTER A200
There are four inverter board assemblies in the power supply. Inverter failures are indicated
on the front panel by their LEDs. To remove a module, loosen the five captive screws on the
plate between inverters 1 and 2 (or inverters 3 and 4), then remove the plate. Unplug the
multi-pin cable near the top and remove the screws holding the red and black wires. Lift out
the module and unplug the red two pin connector. Install the new module in the reverse
order. All four inverter modules are removed and installed in the same manner.
6.5.1 INVERTER A200 TEST
After the module has been replaced, the following test procedure should be done:
A) With no load connected to the output terminals of the power supply, adjust the front
panel's Voltage and Current controls fully counter clockwise.
B) Apply power. Turn on the front panel CB (supply starts after a ten second delay).
Turn up the Current and Voltage controls until the output is about 15% of Max.
voltage, then adjust the load for about 20% of Max. current.
6.6 A100 CONTROL BOARD
All of the plugs (12 total) on the A100 board should be disconnected before removing the
board. Unscrew and remove the six screws which hold the board to the chassis. Remove J1
83-481-004
Page 57 of 59 Rev. Z
Page 65
which is located on the rear panel. The board should now be free of any connections and
can be simply removed. Replace in the reverse order and be sure the connectors are
correctly plugged back into the PCB. If unsure, mark the connectors before unplugging.
A) Rotate the front panel controls fully counter clockwise.
B) Apply AC power. Turn on the front panel CB and slowly advance the current control 1/4
turn. Slowly advance the voltage control. The output should gradually increase as the
Voltage control is rotated.
6.7 FAN ASSEMBLY
The procedure for removing the fans is as follows. Unscrew the captive screws (two for
each) that attach each fan to the chassis. After the base screws are loose, remove the two
screws near the top which screw into the flat chassis plate where the A100 PCB is mounted.
After unsoldering the wires to the AC terminal, the fan assembly can be removed. To install,
follow the reverse order.
6.8 MAIN RECTIFIER ASSEMBLY
To remove the rectifier assembly, face the front panel. The chassis left side cover has to be
removed. This side cover is fastened with seven screws to the chassis. After this side is
removed the rectifier assembly can be accessed. The two bottom flat head screws, hold the
bracket to the chassis.
After the flat head screws are removed, the five large wires and eleven small wires must be
removed before the assembly is ready for removal. Because of the large number of wires,
mark each wire as it is being removed so that it can be replaced correctly. The reassembling
is the reverse sequence of that used to remove the module.
A) Adjust the front panel controls fully counter clockwise.
B) Apply AC power and turn the front panel CB on.
C) Advance the current control fully counter clockwise and slowly adjust the voltage control
until system output voltage is achieved.
D) Apply full load current and the output voltage deviation should be less than 0.1% of
maximum output. The unit can now be returned to service.
6.9 A900 OVP BOARD
A) After the board has been replaced, the operation of the board should be checked.
B) Apply AC power and turn on the CB.
C) Adjust front panel OVP control fully clockwise, as the voltage of the set increases to the
front panel setting of the voltage pot on front panel, turn the OVP control pot counter
clockwise until the OVP activates. After the OVP has been activated, turn CB off and
return OVP setting to the desired point. Turn CB back to verify that set is functioning
properly.
6.10 CALIBRATION
Calibration of the A100 Board is necessary whenever replacing the A100 Board, the voltage
control, or the current control. The following is the calibration procedure for the A100 Board.
Refer to schematic #01-000-716.
83-481-004
Page 58 of 59 Rev. Z
Page 66
1. Remove cover.
2. Rotate voltage and ammeter potentiometers counter clockwise.
3. Turn power supply on.
4. Partially rotate voltage potentiometer clockwise.
5. Connect negative lead of DVM to pin 2 of U24.
6. Connect positive lead of DVM to cathode of CR31.
7. Digital meter should display 6 Vdc.
8. Rotate voltage potentiometer counter clockwise.
9. Adjust R15 until DVM displays -0.6 volts.
10. Partially rotate current potentiometer clockwise.
11. Connect positive pin of DVM to cathode of CR41 (keep negative lead of DVM at pin 2 of
U24).
12. DVM should display 6 volts.
13. Rotate current potentiometer fully counter clockwise.
14. Adjust R21 until DVM displays -0.6 volts.
15. Connect positive pin of DVM to collector of Q1 (keep negative lead of DVM at pin 2 of
U24).
16. Connect another DVM across output of power supply (no load is connected to output).
17. Rotate voltage potentiometer fully clockwise.
18. Voltage of collector Q1 should be 5 0.01 Vdc, if not adjust R6.
19. Adjust R148 until output of power supply is equal to V
20. Disconnect DVMs. Turn off circuit breaker. Connect R
out max.
0.1 Vdc.
(maximum output voltage
load
maximum output current) to output terminals of power supply.
21. Connect a DVM to pins 1 & 2 of J2 (shunt R12). Refer to the A100 board schematic (use
R25 and R26 for convenience).
22. Connect positive lead of another DVM to collector of Q2. Connect negative lead to pin 2
of U24.
23. Turn on circuit breaker. Rotate current potentiometer fully clockwise. Verify that the
supply is in the current mode; the current LED should glow.
24. Voltage of collector Q2 should be 5 0.01 Vdc, if not adjust R8.
25. Adjust R34 until voltage across shunt (pins 1 & 2 of internal J2) is 100 .01%.
6.1SCHEMATICS AND COMPONENTS
The following pages contain component charts and schematics to be used as references for
any troubleshooting, replacement or calibration.
83-481-004
Page 59 of 59 Rev. Z
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.