TDK-Lambda DRJ15, DRJ15/E, DRJ30/E, DRJ50, DRJ30 Instruction Manual

...
TDKLambda
DRJ15100 Series
INSTRUCTION MANUAL
DRJ15100 Series
Instruction Manual
BEFORE USING THE POWER SUPPLY UNIT
Be sure to read this instruction manual thoroughly before using this product. Pay attention to all cautions and warnings before using this product. Incorrect usage could lead to an electrical shock, damage to the unit or a fire hazard.
DANGER
WARNING
• When installing, ensure that work is done in accordance with the instruction manual.When installation is improper, there is risk of electric shock and fire.
• Installation shall be done by Service personnel with necessary and appropriate technical training and experience. There is a risk of electric shock and fire.
• Do not cover the product with cloth or paper etc. Do not place anything flammable around. This might cause damage, electric shock or fire.
• Do not touch this product or its internal components while circuit in operation, or shortly after shutdown. There may be high voltage or high temperature present and you may receive an electric shock or burn.
• While this product is operating, keep your hands and face away from it as you may be injured by an unexpected situation.
• Do not drop or insert anything into this product. It might cause a failure, fire and electric shock.
• Do not use this product under unusual condition such as emission of smoke or abnormal smell and sound etc. It might lead to fire and electric shock. In such cases, please contact us. Do not attempt repair by yourself, as it is dangerous for the user.
• Do not make unauthorized changes to this product nor remove the cover as you might get an electric shock or might damage the product. We will not be held responsible after the product has been modified, changed or disassembled.
• Do not operate and store these products in environments where condensation occurs due to moisture and humidity. It might lead fire and electric shock.
• Do not drop or apply shock to this product. It might cause failure. Do not operate these products mechanical stress is applied.
CAUTION
• Do not use this product in special environment with strong electromagnetic field, corrosive gas or conductive substances and direct sunlight, or places where product is exposed to water or rain.
• Mount this product properly in accordance with the instruction manual, mounting direction and shall be properly be ventilated.
• This power supply is designed and manufactured for use within an end product such that it is accessible to SERVICE ENGINEERS only.
• Confirm connections to input/output terminals are correct as indicated in the instruction manual before switching on.
• Input voltage, Output current, Output power, ambient temperature and ambient humidity should be kept within specifications, otherwise the product will be damaged.
• Do not use this product in environment with a strong electromagnetic field, corrosive gas or conductive substances.
• For applications, which require very high reliability (Nuclear related equipment, medical equipment, traffic control equipment, etc.), it is necessary to provide a failsafe mechanism in the end equipment.
• Never operate the product under over current or shortcircuit conditions, or outside its specified Input Voltage Range. Insulation failure, smoking, burning or other damage may occur.
• This product contains a printed circuit board utilizing surface mounted devices. PCB stress such as bending, twisting etc. could cause damage. Therefore, please handle with care.
• This power supply has possibility that hazardous voltage may occur in output terminal depending on failure mode. The output of these products must be protected in the end use equipment to maintain SELV.
• The information in this document is subject to change without prior notice. Please refer to the latest version of the data sheet, etc., for the most upto date specifications of the product.
• No part of this document may be copied or reproduced in any form without prior written consent of TDKLambda.
Note : CE MARKING
CE Marking, when applied to a product covered by this handbook, indicates compliance with the low voltage directive.
<Page>
1/14 A2650401
1. Model name identification method
DRJ 15 241 /
Option (*1) (*1)Blank : Block terminal type
Single phase AC input /C2 : Block terminal type
Rated Output Voltage /C2E : European terminal type
Output Power type (*2) Option of DRJ100
Series Name
2. Terminal Explanation
TDKLambda
DRJ15100 Series
INSTRUCTION MANUAL
/E : European terminal type
compliant with UL609501 Class 2 output (*2)
compliant with UL609501 Class 2 output (*2)
DRJ15, DRJ30 DRJ15/E, DRJ30/E
+V
+VN-V
24VDC/1.25A
V.ADJ
DRJ30-24-1
100-240VAC
DC OK
L
-V -V
24VDC/1.25A
V.ADJ
DC OK
DRJ30-24-1/E
100-240VAC
N
1
+V : +Output terminal
2
-V : -Output terminal
3
Output voltage adjustment trimmer (DRJ100/C2 and /C2E do not have.)
4
L : Input terminal Live line (Fuse in line)
5
N : Input terminal Neutral line
6
: PE (Protective earthing) terminal
7
L
Output monitoring indicator (Green LED)
*All terminal screw are M3.5
DRJ50 DRJ50/E DRJ100, DRJ100/C2 DRJ100/E, DRJ100/C2E
+V
24VDC/2.1A
V.ADJ
DRJ50-24-1
100-240VAC
-V
-V
DC OK
L
N
+V
24VDC/2.1A
V.ADJ
DRJ50-24-1/E
100-240VAC
N
DC OK
-V+V -V
L
<Page>
2/14
+V -V-V
24VDC/4.2A
V.ADJ
DRJ100-24-1
100-240VAC
DC OK
L
N
+V -V+V -V
24VDC/4.2A
V.ADJ
DRJ100-24-1/E
100-240VAC
DC OK
L
N
TDKLambda
DRJ15100 Series
INSTRUCTION MANUAL
3. Connecting method
Pay attention to the input wiring. If it is connected to wrong terminal, the power supply will be damaged.
Input must be off when making connections.
Connect terminal to earth (frame ground of the equipment etc.) by thick wire for safety and improvement
of noise sensitivity.
DRJ15, DRJ30 DRJ50 DRJ100, DRJ100/C2
+V
24VDC/0.63A
V.ADJ
DRJ15-24-1
100-240VAC
N
-V
DC OK
L
Load
+V
24VDC/2.1A
V.ADJ
DRJ50-24-1
100-240VAC
-V
-V
DC OK
L
N
Load
+V -V-V
24VDC/4.2A
V.ADJ
DRJ100-24-1
100-240VAC
DC OK
L
N
Recommended torque : DRJ15, DRJ30 Input, Output terminal 1.0N·m (10.2kgf·cm) ~ 1.4N·m (14.2kgf·cm)
DRJ15, DRJ30 terminal 1.0N·m (10.2kgf·cm) DRJ50, DRJ100 Input, Output terminal, terminal
1.0N·m (10.2kgf·cm) ~ 1.4N·m (14.2kgf·cm)
DRJ15/E, DRJ30/E DRJ50/E DRJ100/E, DRJ100/C2E
+V
-V -V
24VDC/0.63A
V.ADJ
DC OK
DRJ15-24-1/E
100-240VAC
N
L
Load
+V
24VDC/2.1A
V.ADJ
DRJ50-24-1/E
100-240VAC
N
-V+V -V
DC OK
L
Load
+V -V+V -V
24VDC/4.2A
V.ADJ
DRJ100-24-1/E
100-240VAC
DC OK
L
N
<Page>
3/14
TDKLambda
DRJ15100 Series
INSTRUCTION MANUAL
4. Explanation of Functions and Precautions
41. Input Voltage Range
Input voltage range is single phase 85264VAC (4763Hz) or 120370VDC. Input voltage, which is out of specification, might lead unit damage. For cases where conformance to various safeties required, described as 100240VAC (5060Hz). In case of using input voltage, which is less than specification, output voltage might repeat start and stop. Output derating is required for AC input voltage less than 90VAC (less than 100VAC for /C2 and /C2E). Regarding the output derating, please see at 53. Output Derating according to Input Voltage.
42. Output Voltage Range
Output voltage is set the rated value at shipment. Output voltage within +18%/10%5V : +20%/10%, 12V : +25%/10%can be adjusted by V.ADJ trimmer (except for /C2 and /C2E). Turning the trimmer clockwise, the output voltage will be increased. Take note when the output voltage is
increased excessively, over voltage protection (OVP) function may trigger and voltage will be shut down. Furthermore, when increasing the output voltage, reduce the output current as not to exceed the maximum output power. When the trimmer turns quickly at no load condition, the output voltage might not change quickly. In this case, flow the output current, or wait until the output voltage is stable, and then reinput. Please turn the trimmer slowly during the output voltage adjustment.
43. Inrush Current
This series equipped Power thermistor to limit the inrush current. The higher current will flow at higher ambient temperature or reinput condition. Please select input switch and fuse carefully with the high temperature and reinput the power condition. The inrush current value is under cold start at 25in the
specification. Regarding the external fuse, please see at 9. External Fuse Rating.
44. Over Voltage Protection (OVP)
The OVP function is inverter shut down method and manual reset type. OVP function operates within125145% (5V : 124146%, 12V : 133156%) of nominal output voltage. When OVP triggers, the output will be shut down. To reset OVP, remove the input of power supply for a few minutes, and then reinput. In addition, the setting value of OVP is fixed and not adjustable. Pay attention not to apply voltage externally to the output terminal to avoid unit failure. In case of inductive load, put protective diode in series to the output power line.
45. Over Current Protection (OCP)
This series is hiccup mode with automatic recovery. OCP function operates when the output current exceeds 105% of maximum DC output current of specification. The outputs will be automatically recovered when the overload condition is removed. Never operate the unit under over current or shorted conditions, which may lead unit damage. OCP setting is fixed and cannot be adjusted externally.
46. Output Ripple & Noise
The standard specification for maximum ripple value is measured according to measurement circuit specified by JEITA RC9131B. When load lines are longer, ripple will becomes larger. In this case, electrolytic capacitor, film capacitor, etc. might be necessary to use across the load terminal. The output ripple cannot be measure accurately if the probe ground lead of oscilloscope is too long.
Power
Supply
150mm
+
C1
C2
Load
Coaxial Cable
1.5m 50Ω
<Page>
4/14
C1 : 0.1uF Cap., Film C2 : 100uF Cap., Elect C3 : 4700pF Cap., Ceramic R1 : 50Ω
Oscilloscope
R1
C3 Bandwidth : 20MHz
47. Series Operation
For series operation, either method (A) or (B) is possible.
Method (A) Method (B)
TDKLambda
DRJ15100 Series
INSTRUCTION MANUAL
Power
Supply
Power
Supply
+V
+V
V
V
Load
Power Supply
Power
Supply
Note :In case of (A), please connect bypass diodes to prevent reverse voltage.
Please select a bypass diode with maximum forward current rating more than output load current. And maximum reverse voltage must withstand each power supply output voltage.
48. Parallel Operation
(A) Operation to increase the Output Current is not possible. (B) Operation as a Backup Power Supply is possible as follows.
1.Set the power supply output voltage higher by the amount of forward voltage drop (VF) of the diode.
2.Please adjust the output voltage of each power supply to be the same.
3.Please use within the specifications for output voltage and output power.
4.Please select a reverse current prevention diode with maximum forward current rating more than output load current. And maximum reverse voltage must withstand each power supply output voltage.
(A) (B)
+V
+V
V
Load
V
Load
Power
Supply
Power
Supply
+V
+V
V
V
Load
Power
Supply
Power
Supply
+V
+V
V
V
Load
49. Isolation Test
Isolation resistance between Output  terminal is more than 100MΩ at 500VDC. For safety operation, voltage setting of DC isolation tester must be done before the test. Ensure that the unit is fully discharged after the test.
■ Output  terminal : 500VDC More than 100M
AC (L)
V
AC (N)
V
Isolation
Tester
<Page>
5/14