TDE Instruments Digalox DPM72-MPP Instruction Manual

Digalox DPM72-MPP
Instruction manual (Rev-2019-04)
Graphical panel meter with RGB backlight
for analogue signal 0/2 - 10 V and 0/4 - 20 mA
Package contents: Panel meter Digalox DPM72-MPP, mounting bracket,
5 jumpers, 2 instruction manuals (EN + DE)
Read instruction manual carefully before operating the device! Keep for later reference.
Mounting and installation must be carried out by suitably qualified and competent persons only.
When working on the device hazardous voltages must not be connected to the device! The terminals J1-J12 are not isolated from the measuring circuit.
The device must not be used as the only protective device or protective shutdown.
The device is not intended to protect persons or facilities against harm. Specific devices must be used to guarantee safety (protection relays, cut-off switches, etc.).
When connecting switches to the terminals J1-J6, only switches must be used whose isolation voltage is at least twice the maximum occurring measurement voltage. For example, when measuring 30;V DC switches must be isolated for at least 60;V.
Do not open the housing!
Do not use the device in the presence of explosive or flammable substances!
All cables carrying hazardous voltages must be secured with external separators.

2. Meaning of symbols

General warning sign (Attention, observe the documentation!)
Warning of an electrical hazard
----- 1 / 8 -----

3. Intended use

Indoor use non condensing, non corrosive.
Panel mounting.
Failure to comply with these instructions will void all guarantee and warranty.
In operation, supply the device preferably via screw terminals with 12 to 24;V
AC/DC. If the device is supplied via USB in operation, USB supply voltage must be at least 5;V.

4. Description

The measurement modes analogue signal 0/2 to 10 V and 0/4 to 20 mA DC are supported. The multi display with RGB backlight is able to display up to four parameters simultaneously. Thresholds can be associated with individual warning colours. The unit can be switched between measurement modes via an external switch. Minimum and maximum values are recorded and can be displayed and reset via jumper or an external switch. Measured values are recorded over a timespan of three minutes up to 14 days. The timebase as well as the display of the measuring history can be activated by an external switch. The measured values remain stored as long as the device is supplied with voltage.
The following parameters can be adjusted using the USB configuration software “Digalox Manager”: scale endpoint, scale caption, display style (pointer, tachometer, bar graph, and more), splash image, backlight colour, thresholds for alarm output, threshold warning colour (light, blink), hysteresis, and more. Recorded measurement values can be read and a continuous transmission of the actual measuring value can be enabled. Using the software, values can be viewed and exported as CSV.
Visit www.digalox.com to download the software “Digalox Manager”.
----- 2 / 8 -----

5. Product overview

3
5
4
2
1
2
6
Front
1 Unit or free text
2 Threshold values
3 Upper scale caption
4 Graphical measurement display
5 Digital measurement value
6 Lower scale caption
Supply
12 - 24 V
~/
M o d e 1
M o d e 2
M o d e 3
A u t
o s c a l
e
M i
n /
M a
x
T i
m e
b a s e
+
Outputs max.
30 V
50 mA
Digalox DPM72-MPP
www.digalox.com Made in Germany
I
low
I
high
U
highUlow
100 mA max. 30 V max.
B u s 1
B u s 2
N C
G P I
O 1
G P I
O 2
N C
J1J2J3J4J5J6J7J8J9J
1 2
J 1 1
J 1 0
USB
3
2
1
4
5
Back
1 2 optocoupler switch outputs
2 Jumper pins J1–J12
for activating/switching of graphical historic data display, min/max display, auto-scaling, measurement mode
3 Supply voltage input
4 USB interface
5 Measurement inputs

6. Mounting

Carefully insert the device into the panel cut-out. Insert the mounting bracket from the back and push towards the panel until the device sits tight. Make sure the mounting bracket is snapped into the side of the housing. To ensure IP65 protection (dust and water jet) when mounting in a front panel, use optional gasket (separately available).