TCS Basys Controls SZ1017N Product Manual

Description
The SZ1017N is a thermostat with a 7-day time clock designed for applications with modulating heating or cooling.
Features
! Stand-alone or network operation ! 7-day time clock ! Discharge air sensor input with high and low limits and
reset
heating or cooling output
! Adjustable delay on powerup for soft starts ! P+I control option ! Smart Recovery ! No backup battery required ! Built-in HVAC equipment protection ! 32 character LCD display ! Six LEDs for status monitoring ! Remote room sensing capability ! User setpoint adjustment limits ! Local and remote override capability ! System and fan switching with access lockouts ! Fan interlock safety option ! Filter service input and indication ! Equipment monitoring inputs and indication ! External time clock input ! Energy management input for setpoint shift ! Access to programming or schedule may be locked out or
limited with the use of an access code
! Fahrenheit or Celsius temperature display
Product Manual
Contents
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
N2 Bus Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Setting Clock & Schedule . . . . . . . . . . . . . . . . . . . . . . . . .7
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Checkout & Troubleshooting . . . . . . . . . . . . . . . . . . . . . . .9
LED Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Limiting Occupant Access . . . . . . . . . . . . . . . . . . . . . . . . .12
User’s Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
N2 Point Mapping Table . . . . . . . . . . . . . . . . . . . . . . . . . .13
Mounting
The SZ1017N is designed for wall mounting using two #6 sheet metal screws, either over a horizontally installed 2" x 4" junction box, or directly to block or drywall.
For best results, the SZ1017N should be mounted on an interi­or wall which reflects normal room environment, at a height of approximately five feet from the floor. Avoid areas exposed to direct sunlight, unusual heat sources, open doors and win­dows, or unventilated locations.
If using a remote room sensor, it should be mounted in the manner described above. The thermostat may be mounted in an area which is accessible for adjusting its settings.
R
SZ1017N
Modulating Thermostat with 7-day Time Clock
Communicating Thermostats
R
2800 LAURA LANE IMIDDLETON, WI 53562 I(800) 288-9383 IFAX (608) 836-9044 Iwww.tcs-basys.com
1
W
iring
The SZ1017N uses standard terminal designations for wiring. See diagram below.
REMOTE SENSOR WIRING
Use 18 AWG shielded twisted-pair grounded at the sensor mounting location. Sensor wiring runs of up to 250 feet are attainable if properly shielded wire is used and the installation environment is free of electrical noise. Sensor wire should be kept at least five feet away from line voltage wiring.
The SZ1017N accept two remote sensors. Consult the TS Series Temperature Sensor Submittal Data sheet for a com­plete listing of packaging and application styles. When using TCS/Basys Controls three-wire sensors, use the black and red leads and either clip or twist off the white lead. Make sure that the dip switches are set for the sensors you are using.
POWERING THE SZ1017N
The SZ1017N is powered from 24 VAC +/- 20 %.
If wiring for communications, dedicated power must be used to power the SZ1017N. Several S-series thermostats may be powered from the same transformer, provided that the trans­former has sufficient power, although the polarity must be kept the same throughout because these are half-wave recti­fied devices. (SZ1017N thermostats require 8 VA @ 24 VAC).
When the SZ1017N is used as a stand-alone thermostat with­out communications, the unit transformer may be used to power it. However, using separate power will eliminate possi­ble ground loops which may damage the thermostat.
Packaged Unit/Modulating Terminations
1
3
4 44
5 5
Zone/Return
Air Temp
Discharge
Air Temp
N2 Bus
R
G
Y1 or
W1
Y2
or
W2
Time Clock
Output
+
-
5
Outdoor
Air Temp
7 6
HWV or CWV
2
CAUTION
When multiple TCS devices are using a single transformer, the polarity of the power wiring must be maintained because all TCS devices are half-wave rectified and have common return paths.
!
!
1
2
For communication wiring, use twisted, shielded 18 AWG. Must be run separately.
Dry momentary contact. Must not be powered.
3
4
24 VAC transformer. See powering instructions.
Dry contact. Must not be powered.
5
6
Sensor input wiring 18 AWG, twisted, shielded pair.
4 to 20 mA output. 600 ohm max. Do not power actu­ator with power from the thermostat. The thermostats are half-wave rectified, whereby the power ground is common with the signal ground.
Up to nominal 28 VAC from equipment transformer.
R
2800 LAURA LANE IMIDDLETON, WI 53562 I(800) 288-9383 IFAX (608) 836-9044 Iwww.tcs-basys.com
2
7
KEYPAD ACCESS
The dipswitches in the cover (shown above connected with ribbon cable) must be set in order to lock the user out of programming and/or to set the clock and schedule. Use the guide below to set these dipswitches for your application. Otherwise, user access may be limited with an access code set in programming. (The fan and system switches are enabled or disabled in programming only, and require no dipswitch placement.)
Keypad access to both programming and clock setup. (This is the default setting.)
No keypad access to programming or clock setup.
Keypad access to programming only.
Keypad access to clock setup only.
Once the dipswitches have been set and you have confirmed that the sensors are reading correctly (and program and clock setup are finished, if locking out access with dip­switches), secure the cover to the base with the two set screws located at the top right and the left side to prevent tampering.
Setup
Note: If using remote sensor(s), the calibration may need to be adjusted. See “Checkout and Troubleshooting” section.
SENSOR SELECTION
The dipswitches in the cover (shown above connected with ribbon cable) as well as the programming must be set when using remote room, discharge, and/or outdoor sensors. Use the following guide to determine the dipswitch settings for your application.
Using built-in room sensor only. (This is the default setting.)
Using built-in room sensor with discharge air sensor only.
Using built-in room sensor with outdoor air sensor only.
Using built-in room sensor with both discharge and outdoor air sensors.
Using remote room sensor only.
Using remote room sensor with discharge air sensor only.
Using remote room sensor with outdoor air sensor only.
Using remote room sensor with both discharge and outdoor air sensors.
1 2 3 4 5
1 2
1
2
3
4
5
1 2
R
2800 LAURA LANE IMIDDLETON, WI 53562 I(800) 288-9383 IFAX (608) 836-9044 Iwww.tcs-basys.com
3
Programming
The SZ1017N may be programmed through the display and keypad, or with a PC.
If programming with a PC, the following must be set through the keypad prior to programming:
! Address (step #3) ! Temperature scale (step #4)
For more information on programming through the PC, con­sult your software manuals.
PROGRAMMING THROUGH THE KEYPAD
To access the programming screens, press the program setup button. To make changes, use the warmer and cooler keys. Access may be locked out with dipswitches, or an access code may be required.
fan
Occup ied
Heating
Cooling
Fan
Service
Program/
COOLER
WARMER
Data
switch
system switch
program
setup
clock setup
override
service
status
program
setup
program
setup
SET ADDRESS:
000
2.
ENTER ACCESS
000
1.
CODE
MON
72F
12:00 AM
program
setup
3.
program
setup
program
setup
program
setup
program
setup
program
setup
program
setup
program
setup
11.
UNOCCUPIED HEAT
SETPOINT: 60F
OCCUPIED HEAT
10.
SETPOINT: 68F
SET UNOCCUPIED
FAN MODE: AUTO
9.
8.
SET OCCUPIED FAN
MODE: ON
USER ACCESS TO
FAN MODE? YES
7.
SET SYSTEM
6.
MODE: AUTO
USER ACCESS TO
5.
SYSTEM MODE? YES
TEMPS SHOWN IN:
4.
FAHRENHEIT
program
setup
Main Monitoring Screen. Press the pro-
gram setup button to access the following screens.
Access Code Entry Screen. Will appear if access code is required for programming. Use 248 as the default. If the wrong code is entered, it will revert to the previous screen.
Controller Address Screen. If using a PC to access the SZ1017N, set a unique address from 1 to 255.
Display Type Screen. Choose between FAHRENHEIT and CELSIUS for tempera­ture indication.
System Access Screen. Choose whether or not to enable user’s access to the sys­tem switch to set the system mode.
System Mode Screen. Choose from AUTO, HEAT, COOL, or OFF for system mode. In the OFF mode, all outputs are off.
Fan Access Screen. Choose whether or not to enable the user’s access to the fan switch to set the occupied fan mode.
Occupied Fan Mode Screen. Choose between ON (continuous), COOL (gas heat or no heat), or AUTO for your fan run times during the occupied modes.
Unoccupied Fan Mode Screen. Choose from AUTO or COOL for fan run times in the unoccupied mode.
Occupied Heat Setpoint Screen. Set the occupied heat setpoint.
Unoccupied Heat Setpoint Screen. Set the unoccupied heat setpoint.
R
2800 LAURA LANE IMIDDLETON, WI 53562 I(800) 288-9383 IFAX (608) 836-9044 Iwww.tcs-basys.com
4
program
setup
program
setup
program
setup
program
setup
program
setup
program
setup
program
setup
program
setup
30.
DISCHARGE AIR
LOW LIMIT: 45F
29.
28.
ENABLE DISCHARGE
AIR SENSOR? YES
SETPOINT
OFFSET: 00F
27.
UNOCCUPIED ACTION
25.
MODULATING
MODULATING OUT
RANGE: 4-20 MA
24.
OUTPUT ACTION:
.
DIRECT
22.
MODULATING OUT
IS: COOL
21.
SET CONTROL
MODE: P+I
23.
program
setup
PROPORTIONAL
BAND: 5F
26.
program
setup
TIME CLOCK OUTPUT
OCCUPIED=CLOSED
program
setup
program
setup
program
setup
program
setup
program
setup
program
setup
program
setup
program
setup
STAGE 2
DIFF: 2F
20.
STAGE 2
OFFSET: 2F
19.
18.
STAGE 1
DIFF: 2F
STAGE 1
OFFSET: 0F
17.
STAGE OUTPUT 1&2
16.
AS: HEAT
SET OVERRIDE
TIME: 180 MINUTES
15.
LIMIT SETPOINT
14.
ADJUST +/-: 5F
13.
UNOCCUPIED COOL
SETPOINT: 80F
12.
OCCUPIED COOL
SETPOINT: 72F
program
setup
Occupied Cool Setpoint Screen. Set
the occupied cool setpoint.
Unoccupied Cool Setpoint Screen.
Set the unoccupied cool setpoint.
User Setpoint Limit Screen. Enter the number of degrees you want the user to be allowed to change the pre­set occupied setpoints up or down.
Override Time Screen. Enter the number of minutes (0 to 255) that the SZ1017N will maintain occupied set­points when overridden.
Stage Mode Screen. Choose whether stages 1 and 2 perform heating or cooling functions, or whether both stages are to be disabled.
Stage 1 Offset Screen. Enter an off­set value for stage 1. First stage is nor­mally 0 offset. This screen does not appear if stage outputs 1 and 2 are disabled.
Stage 1 Differential Screen. Enter a differential value for stage 1. This screen does not appear if stage out­puts 1 and 2 are disabled.
Stage 2 Offset Screen. Enter an off­set value for stage 2. This screen does not appear if stage outputs 1 and 2 are disabled.
Stage 2 Differential Screen. Enter a differential value for stage 2. This screen does not appear if stage out­puts 1 and 2 are disabled.
Control Mode Screen. Enter whether you want to control by temperature only (P) or add a time factor (P+I). This applies to both the stage outputs.
Time Clock Output Screen. Choose whether the auxiliary output will be OPEN during occupied periods (and closed during unoccupied periods) or CLOSED during occupied periods (and open during unoccu­pied periods).
Modulating Output Define Screen.
Choose whether the modulating output will be used for COOL, HEAT or AQUASTAT. With DI2 set to AQUASTAT, the analog out­put will be used for cooling with DI2 open and heating with DI2 closed.
Modulating Output Action Screen. Choose whether the output will be direct or reverse acting. (When DI2 is set to AQUAS­TAT, the output will automatically reverse action when DI2 is closed.)
Modulating Output Range Screen.
Choose whether the modulating output range will be 0-20 mA or 4-20 mA.
Unoccupied Action Screen. Choose whether the unoccupied action will be mod­ulating, 0 or 4 mA, or 20 mA.
Modulating Output Proportional Band Screen. Enter the number of degrees away
from the setpoint that the valve or damper will be fully open.
Analog Output Setpoint Offset Screen.
Enter a setpoint offset. This is a value below the heating setpoint or above the cooling setpoint where the analog output begins to modulate.
Discharge Air Sensor Screen. Choose whether or not you are using the discharge air sensor function. To monitor only, select no.See setup instructions for dipswitch settings which must also be set.
Discharge Air Low Limit Screen. Enter a discharge air low limit value. This screen will not appear if the discharge air sensor function is disabled.
R
2800 LAURA LANE IMIDDLETON, WI 53562 I(800) 288-9383 IFAX (608) 836-9044 Iwww.tcs-basys.com
5
program
setup
program
setup
program
setup
program
setup
program
setup
program
setup
program
setup
program
setup
39.
DI2 USED FOR:
SERVICE
38.
37.
DI1 USED FOR
FAN PROVING
HEATING LOCKOUT
TEMP: 70F
36.
COOLING LOCKOUT
35.
TEMP: 80F
ENABLE OUTDOOR
AIR SENSOR? YES
34.
RESET RATIO
33.
FACTOR: 2F
32.
DISCHARGE AIR
SETPOINT: 90F
31.
CONTROL BASED
ON: SPACE
DISCHARGE AIR
HIGH LIMIT: 120F
program
setup
program
setup
program
setup
program
setup
program
setup
program
setup
program
setup
MON
12:00 AM 72F
45.
SET ACCESS
CODE: 000
44.
REQUIRE CODE FOR
CLOCK / SCHED? YES
43.
ENABLE SMART
YES
RECOVERY?
REQUIRE CODE FOR
PROGRAMMING? YES
42.
DELAY ON POWERUP
60 SECONDS
ENABLE SMART
RECOVERY? YES
DI3 USED FOR:
FILTER SERVICE
41.
DELAY ON POWERUP
60 SECONDS
DI3 USED FOR:
FILTER SERVICE
40.
DI3 USED FOR:
FILTER SERVICE
program
setup
DI3 USED FOR:
FILTER SERVICE
SET DI2 SETPOINT
SHIFT: 02F
46.
Discharge Air High Limit Screen. Enter a discharge air high limit value. This screen will not appear if the discharge air sensor function is disabled.
Discharge Air Reset Screen. Choose whether to control based on DIS­CHARGE air reset or SPACE tempera­ture. This screen will not appear if the discharge air sensor function is disabled.
Discharge Air Setpoint Screen. Enter a value at which the discharge air setpoint is to be controlled. This screen will not appear if the control is based on space temperature.
Reset Ratio Factor Screen. Enter a reset ratio factor. This is the number of degrees that the discharge air setpoint is raised when the space temperature falls by 1 degree for heating, or the number of degrees that the discharge air setpoint is lowered when the space temperature rises by 1 degree for cooling.
Outdoor Air Sensor Screen. Choose whether or not you are using an outdoor air sensor function To monitor only, select no. See setup instructions for dip­switch settings which must also be set.
Cooling Lockout Screen. Enter an out­door air cooling lockout temperature. This screen will not appear if the outdoor air sensor function is disabled.
Heating Lockout Screen. Enter an out­door air heating lockout temperature. This screen will not appear if the outdoor air sensor function is disabled.
DI1 Choice Screen. Choose DI1 as FAN PROVING or a MONITOR point. Select MONITOR if unused.
DI2 Choice Screen. Choose DI2 as SERVICE, AQUASTAT, or MONITOR. Select MONITOR if unused.
DI2 Shift Screen. Enter the setpoint shift value. This screen will only appear if DI2 is set to MONITOR.
DI3 Choice Screen. Choose FILTER SER­VICE, EXTernal OVERRIDE, or EXTernal TIME CLOCK. Select FILTER SERVICE if unused.
Delay On Powerup Screen. Enter a value in seconds, such that when the unit is powered up, no control starts for this amount of time.
Smart Recovery Screen. Choose whether or not smart recovery will be used. Note: Smart Recovery is not avail-
able when DI3 is used as EXTernal TIME CLOCK.
Programming Access Screen. Choose whether or not a code will be required to enter programming setup. A dipswitch option to lock out access altogether is also available.
Clock and Schedule Access Screen.
Choose whether or not a code will be required to enter clock and schedule setup. A dipswitch option to lock out access altogether is also available.
Access Code Screen. Enter an access (0 to 255) code that will be used to enter the programming and/or clock and schedule setups if access code has been required in the last two steps. The default is 248.
Main Monitoring Screen.
R
2800 LAURA LANE IMIDDLETON, WI 53562 I(800) 288-9383 IFAX (608) 836-9044 Iwww.tcs-basys.com
6
Setting Clock & Schedule
The SZ1017N clock and schedule may be set through the keypad on the face, or with a PC. For more information on programming through the PC, consult your software manual.
SETTING CLOCK & SCHEDULE THROUGH THE KEYPAD
To access the clock and schedule screens, press the clock setup button. To make changes, use the warmer and cooler keys. For screens that have more than one field to set, use the override key to move to the next field. Access may be locked out with dipswitches, or an access code may be required.
clock setup
Main Monitoring Screen. Press the service button to access the following screens.
Access Code Entry Screen. May appear if access code is required for setting clock and schedules. Use 248 as the default. If the wrong code is entered, it will revert to the previous screen.
Time and Day Screen. Set the hour, minutes, AM or PM, and day of the week.
Schedule Announcement Screen.
Announces the next screen.
Occupied Times Screen. Set hours and minutes of start and end times for up to two occupied periods.
Schedule Announcement Screen.
Announces the next screen.
Copy Schedule Screen. Choose to use the same schedule that was used for the previous day. If so, the next screen does not appear.
Occupied Times Screen. Set hours or minutes of start and end times for up to two occupied periods.
Main Monitoring Screen.
MON
72F
12:00 AM
3.
1.
clock setup
ENTER ACCESS
SET TIME & DAY:
MON12:00 AM
2.
000
CODE
override
clock setup
clock setup
SET OCCUPIED
A:08:00 TO 12:00
4.
5.
TIMES MONDAY:
B:13:00 TO 17:00
SET OCCUPIED
6.
TIMES TUESDAY:
The following screens are repeated for Wednesday, Thursday, Friday, Saturday and Sunday.
COPY MON FOR
TUE? YES
7.
MON
72F
12:00 AM
A:08:00 TO 12:00
B:13:00 TO 17:00
clock setup
override
clock setup
clock setup
clock setup
override
Operation
UNOCCUPIED SETBACK
The SZ1017N operates in either an occupied or unoccupied mode. During the occupied mode, the occupied heating and cooling setpoints will be maintained, and the fan will oper­ate according to its occupied setting. During the unoccupied mode, the unoccupied heating and cooling setpoints will be maintained, and the fan will operate according to its unoc­cupied setting. The occupied LED will be lit when the unit is operating in the occupied mode.
The occupied schedule may be set utilizing the internal time clock or DI3 may be used with an external time clock, whereas when DI3 is closed, the unit is in the occupied mode. The Smart Recovery function is disabled when DI3 is used for external time clock.
OVERRIDE
A timed override is available on the keypad or through momentary N.O. contacts. The amount of time the unit will be overridden is set from 0 to 255 minutes in the program­ming. This override only activates when the thermostat is operating in the unoccupied mode. Both the software and the service button allows you to view the time remaining in the override mode. If the occupant desires to return the ther­mostat to unoccupied operation before that time interval is up, they may press the button on the keypad or the momen­tary contact again.
Continuous override is available using DI3. If DI3 is set to external override, the unit will be in the occupied mode whenever the DI3 contact is closed. When using this option, the timed override may still be activated.
The software allows you to override the thermostat by putting the override parameter into the remote mode, and thus disabling the timed override.
SETBACK AND OVERRIDE APPLICATIONS
In most applications, it is desired to maintain a regular schedule, and allow timed override with the button on the face or with a remote momentary contact.
To allow a regular schedule, and also automatically override with the use of occupancy or light sensor, set DI3 to over­ride and set it up so that the contact is closed when you want the override.
For applications where a room might not be used on a regu­lar schedule, such as conference rooms, set DI3 to time clock and close the contact when you want the room occu­pied, such as with a switch or wind-up timer. If each occu­pancy period is about the same, (theaters, meetings) another option is to set the DI3 to time clock, and use the timed override button to put the unit in occupied mode.
To make the unit always occupied, set DI3 to time clock and short the DI3 terminal to ground.
R
2800 LAURA LANE IMIDDLETON, WI 53562 I(800) 288-9383 IFAX (608) 836-9044 Iwww.tcs-basys.com
7
air temperature rises 2° above the lockout temperature. If the outdoor temperature rises above the HEATING LOCK­OUT TEMP, all heating stages will be locked out and will remain locked out until the outdoor air temperature falls 2° below the lockout temperature.
The outdoor air span is -40 to 160 °F (-40.0 to 71.1 °C).
FAN PROVING
The SZ1017N allows DI1 to be set for fan proving to pro­tect equipment on fan failure. To utilize this, a pressure or current switch is required, which indicates when the fan is running. If the thermostat turns on the FAN, and DI1 is not closed after thirty seconds, the system will go to OFF, dis­abling all outputs, the fan LED will turn off, and the service LED will be lit until the system is manually reset by switching the system to a mode other than OFF.
DI2 SETPOINT SHIFT
The SZ1017N allows DI2 to be set for setpoint shift for energy demand setback. This is enabled by setting DI2 to the MONITOR mode. A digital contact that closes when setback is needed should be wired into DI2. You may speci­fy a number of degrees such that, when the thermostat is operating in the occupied mode, and DI2 is closed, the heating setpoint will be lowered this number of degrees, and the cooling setpoint will be raised this number of degrees. The fan will continue to operate according to its occupied setting. If you are using DI2 as monitor for anoth­er purpose, make sure to set the setpoint and shift value to zero.
STAGE OUTPUT PARAMETERS
The SZ1017N will control up to two stages of either heat­ing or cooling.
For each stage, you may specify an offset and a differential value. The offset value is the amount away from the set­point a stage will turn off. By assigning a stage a value other than zero, you “anticipate” that the residual heat or cooling in the duct or the other stages will bring the tem­perature back to setpoint. In most cases, the first stage is set to zero. The differential value is the difference between the on and off points.
DISCHARGE AIR TEMPERATURE SENSING
The SZ1017N accepts a remote 1000 discharge air sensor (TS1009 or TS1002) for monitoring purposes. (See setup instructions for dipswitch placement for this option.)
Choose YES in programming screen #28 only if you are using a discharge air sensor and you want to enable the dis­charge air temperature high and low limit functions or dis­charge air reset function. See Discharge Air Reset section for further programming options. If NO is chosen, the dis­charge air is still monitored.
When the function is enabled, a LOW LIMIT and HIGH LIMIT are entered in steps #29 and #30. If the HIGH LIMIT is reached, the fan and heating stages will be turned off and will remain off until the discharge air temperature falls 3° below that limit. If the LOW LIMIT is reached, the fan and cooling stages will be turned off and will remain off until the discharge air rises 3° above that limit. When either limit is reached, the service LED will be on until normal operation resumes.
The discharge air span is 0 to 150 °F (-17.8 to 65.6 °C).
ANALOG OUTPUT / DISCHARGE AIR RESET
The analog output on the SZ1017N is used to control the heating or cooling in a space. To use the discharge air reset function, a discharge air sensor must be installed. In pro­gramming step #28, the discharge air sensor must be enabled. In programming step #31, the control must be based on DISCHARGE air.
In programming screen #32, you are asked to enter a dis­charge air setpoint. The discharge air temperature will be controlled to this setting by modulating the heating or cool­ing device.
In programming screen #33, you are asked to enter a reset ratio factor. This is the number of degrees that the dis­charge air setpoint is raised when the room temperature falls below the heating setpoint by 1 degree if the analog output is set for heating, or the number of degrees that the dis­charge air setpoint is lowered when the room temperature rises above the cooling setpoint by 1 degree if the analog output is set for cooling.
OUTDOOR AIR TEMPERATURE SENSING
The SZ1017N accepts a remote 1000 outdoor tempera­ture sensor (TS1003) for monitoring purposes. (See setup instructions for dipswitch placement for this option.)
Choose YES in programming screen #34 only if you are using an outdoor air sensor and you want to enable the out­door air heating and cooling lockout functions. If NO is chosen, the outdoor air is still monitored.
When the function is enabled, a COOLING LOCKOUT TEMP and HEATING LOCKOUT TEMP are entered in steps #35 and #36. If the outdoor temperature falls below the COOLING LOCKOUT TEMP, all cooling stages will be locked out and will remain locked out until the outdoor
Heat Setpoint
Cool Setpoint
ON
ON
ON
ON
OFF
OFF
OFF
OFF
Differential
Differential
Offset
Offset
Differential
Differential
R
2800 LAURA LANE IMIDDLETON, WI 53562 I(800) 288-9383 IFAX (608) 836-9044 Iwww.tcs-basys.com
8
ANALOG OUTPUT PARAMETERS
Use programming steps #22 through #26 to program the operating parameters for the analog output. Select whether the analog output is set for heating, cooling or aquastat. Select direct or reverse action. Select whether you want the analog output to modulate from 4 to 20mA or 0 to 20mA. Select the unoccupied action ("20mA or 0 / 4mA" will hold the analog output device open or closed during unoccupied times. "Modulating" will modulate the analog output device to maintain the unoccupied heating or cooling setpoint.). Enter a proportional band (throttling range) in degrees.
P+I OPTION
The SZ1017N also has a P+I option. Without enabling this option, stages turn on and off based on temperature vs. set­point alone, as described above. By enabling this option, you add a time factor to anticipate heating and cooling.
DI2 AQUASTAT
DI2 may be set as an aquastat function. When DI2 is select­ed to have an aquastat function, and the analog output is selected to have an aquastat function, operation is as fol­lows.
With DI2 "Open", the analog output operates in cooling mode, and uses selected direct or reverse action. When DI2 is "Closed", the analog output operates in heating mode, and uses the opposite of the selected direct or reverse action.
SMART RECOVERY
“Smart Recovery” may be enabled. It ramps the setpoint 4°F/hr. when going from the unoccupied mode to the occu­pied mode. At the beginning of the occupied mode, the occupied setpoint will be reached, many times without the need for the second stage to come on. This feature is auto­matically disabled when DI3 is set to external time clock.
BUILT-IN DELAYS
The SZ1017N has delays built into the programming sequences to protect equipment. The fan has a minimum on and off time of 30 seconds. When the fan is in AUTO or COOL mode, it will come on 30 seconds before the heating or cooling stages are allowed to sequence on, and remain on for 30 seconds after the heating or cooling stages sequence off. Each stage has a minimum on and off time of two min­utes. There is a minimum of two minutes between when one stage turns on until the next stage is allowed to turn on, as well as when one stage turns off until the next stage is allowed to turn off.
DELAY ON POWERUP
The SZ1017N has an adjustable delay on powerup. When several thermostats are used at one location, and the power goes out, most thermostats turn all of the units back on at the same time on regain of power, creating a peak. The ther­mostat allows you to set a value, in seconds, where no out­puts are allowed to turn on for that length of time on powerup. Setting each unit to a different delay allows you to soft start your system, and thus prevent this peak.
Checkout & Troubleshooting
CHECKOUT
Note: The fan has a minimum on and off time of 30 sec­onds. The heating and cooling stages have a minimum on and off time of 2 minutes.
You may verify the status of heating and cooling stages and fan in monitoring screens 5, 6, and 7, which are accessed by pressing the SERVICE STATUS button.
1.Verify all wiring prior to powering the thermostat.
2. Turn power on. The thermostat will display a momentary screen with the model number , and then the main moni­toring screen with the time, day and current temperature.
4 20
4 20
4 20
4 20
4 20
4 20
P
Z o n e
T e
m
p
Output (mA)
P
Output (mA)
DIRECT ACTING
REVERSE ACTING
P
P
Output (mA)
Output (mA)
Z o n e
T e
m
p
P
P
Output (mA)
Output (mA)
P
P
Z o n e
T e
m
p
CSP
CSP
HSP HSP
CSP
CSP
HSP HSP
" SZ1017N "
R
2800 LAURA LANE IMIDDLETON, WI 53562 I(800) 288-9383 IFAX (608) 836-9044 Iwww.tcs-basys.com
9
3. Press the PROGRAM SETUP button until you reach the screen # 14 which allows you to set the occupant set­point adjustment limits. Change this to +/-20 °F (11.1 °C). Press the PROGRAM SETUP button once more to store the change. Then press the SERVICE STATUS but­ton once to exit the programming.
4. Press the FAN SWITCH button to access the fan mode and change the mode to AUTO. Press the FAN SWITCH button once more to store the change. Press the SYS­TEM SWITCH button to access the system mode and change the mode to AUTO. Press the SYSTEM SWITCH button once more to store the change.
5. Verify that the thermostat is operating in the occupied mode by making sure that the top LED is lit. If not, press the OVERRIDE button. The LED should light up.
6. Take note of the current temperature reading. Press the WARMER (up) button. The setpoint adjustment screen should now be showing. Press the WARMER button until the heating setpoint is greater than the current tem­perature by at least five degrees. The fan will come on. The heating stage(s) will sequence on after 30 seconds.
7. Press the cooler (down) button until the heating setpoint is one degree less than the current temperature. The heat­ing stage(s) will sequence off. The fan will turn off 30 seconds after the last heating stage.
8. Press the cooler button until the cooling setpoint is less than the current temperature by at least five degrees. The fan will come on. The cooling stage(s) will sequence on after 30 seconds.
9. Press the warmer button until the cooling setpoint is greater than the current temperature by one degree. The cooling stage(s) will sequence off. The fan will turn off 30 seconds after the last cooling stage.
10. Take note of the room (and discharge) air temperatures. If the analog output is set for Cooling, press the Cooler button until the cooling setpoint is less than the current room temperature by at least 5°. The cooling device should start operating. If the analog output is set for Heating, press the Warmer button until the heating set­point is greater than the current room temperature by at least 5°. The heating device should start operating.
11. Go back to programming step #14 and set the setpoint adjust limit back to the desired value. Make any other changes in programming, clock, and schedule. Set the fan and system modes to their desired settings.
12. If using remote sensors, verify that the reading is cor­rect. If not, see Wrong Temperature Display in “Troubleshooting” section.
TROUBLESHOOTING
No Display
Check for 24 VAC on terminals “+24” and “-24”. Check the cable connecting the cover to the base for a good connec­tion.
Fan Does Not Come On
The fan is on whenever the fan LED is on. If the fan should be on, but the fan LED is off, check the fan and system switch modes, and the unoccupied fan mode in programming. If the fan is off but the fan LED is on, check wiring. Short terminals “R” to “G” and see if the fan comes on. This is a check for a mechanical relay failure.
Heating or Cooling Does Not Come On
At least one stage of heating is on whenever the heating LED is on, and at least one stage of cooling is on whenever the cooling LED is on. If heating or cooling should be on but the heating or cooling LED is off, check the fan and system switch modes. Also, check the heating and cooling setpoints, offsets and differentials, and the room temperature to be sure heating or cooling should be on. If using outdoor air heating and cooling lockouts, or discharge air high and low limits, check their values to be sure heating or cooling is allowed. If heating or cooling is off, but the corresponding LED is on, check the wiring. Short terminals “R” to “Y/W1” or “Y/W2” and see if the heating or cooling comes on. This is a check for a mechanical relay failure.
Wrong Temperature Display
If any of the temperatures is reading slightly high or low, there are three adjustment pots located in the cover to adjust them. “T1” is for the room temperature, “T2” is for the discharge air temperature, and “T3” is for the outdoor air temperature. If the temperature is at a minimum or maximum reading, check the sensor dipswitch positions. (See setup instructions.) Check for wiring problems (opens or shorts). A remote 1000 sensor should read 1080 to 1090 at room temperature. The built-in sensor should read 108 to 109 at room temperature.
Service LED is On
If the service LED is on, it may be for monitoring purposes or it may indicate a critical problem. The first monitoring screen accessed by pressing the service status button will display why the light is on.
Outputs Will Not Shut Off
First check the room temperature and the setpoints and deter­mine whether the output should be on. There are delays and minimum on and off times for the fan and heating and cooling stages. Also, check the service status menus to verify that the outputs are on. Turning the system to “off” will instantly turn all outputs off. The thermostat can be reset by pressing the system switch button and the service status button simultane­ously.
R
2800 LAURA LANE IMIDDLETON, WI 53562 I(800) 288-9383 IFAX (608) 836-9044 Iwww.tcs-basys.com
10
Analog Output Not Working Properly
Check wiring. A separate transformer should be used for the SZ1017N and a separate transformer should be used for the damper motor(s). Check to make sure that the analog output is programmed correctly.
Check the Service Menu. The Mod Out Screen will tell you what the SZ1017N is trying to put out for an output. Compare this with the actual position of the heating or cool­ing device.
SERVICE SCREENS
Continually pressing the service status button allows more extensive monitoring. The screens are shown at right.
LED Description
Six LEDs on the face allow the occupant to view the current operating status of the thermostat.
OCCUPIED
This LED will be lit whenever the unit is operating in the occupied mode.
HEATING
This LED will be lit when any heat output is on.
COOLING
This LED will be lit when any cooling output is on.
FAN
This LED will be lit when the fan output is on.
SERVICE
This LED will be lit when the high or low discharge air limit has been reached, when the fan interlock has indicated failure, or when the filter service or service input are closed.
PROGRAM/DATA
This LED will be lit when the thermostat is within the pro­gramming or clock setup menus. It will blink when the unit is being accessed by a PC.
Additional monitoring is available by continually pressing the service key.
MON
72F
12:00 AM
DISCHARGE AIR
55F
OUTDOOR AIR
OVERRIDE ON
178 MINUTES
75F
HEAT STAGE 1 OFF
MOD OUT 100%
SERVICE STATUS
OK
TEMP
1.
2.
3.
4.
5.
6.
7.
TEMP
HEAT STAGE 2 OFF
DI1 OPEN
DI2 SERVICE OFF
FILTER OK
MON
72F
12:00 AM
fan
Occupied
Heating
Cooling
Fan
Service
Program/
COOLER
WARMER
Data
switch
system
switch
program
setup
clock setup
OVERRIDE
service
status
service
status
service
status
service
status
service
status
service
status
service
status
service
status
service
status
Main Monitoring Screen. Press the service
button to access the following screens.
Service Screen. This message may be fol­lowed by any or all of the following: CHECK FILTER, CHECK FAN, DISCHARGE HIGH, DISCHARGE LOW, or CHECK DI2.
Discharge Air Temperature Screen.
Shows discharge air temperature if sensor is used.
Outdoor Air Temperature Screen. Shows outdoor air temperature if sensor is used.
Override Status Screen. Shows whether the override is active and if so, how many minutes remaining.
Heat or Cool Stages Status Screen.
Shows the status of the first and second stages of heating or cooling.
Mod Out and DI1 Screen. Shows the per­centage of modulating output and the status of the fan interlock, or DI1.
DI2 and DI3 Status Screen. Shows DI2 status and filter status or DI3 status.
Main Monitoring Screen.
R
2800 LAURA LANE IMIDDLETON, WI 53562 I(800) 288-9383 IFAX (608) 836-9044 Iwww.tcs-basys.com
11
User’s Guide
Inside the hinged door of the thermostat is the SuperstatTMUser’s Guide. This guide is designed to assist the installer in explaining to the end user how to operate their new thermostat, as well as serve as a handy future reference for the end user.
We recommend that the installer fill out pages 1, 5, 7 and 8 (where applicable) and explain to the user how the thermo­stat operates, what settings may be changed, and how the time clock schedules are used.
Limiting Occupant Access
SETPOINT ADJUSTMENT
The occupant may temporarily change the occupied heating and cooling setpoints +/- 5°F by factory default. This set­point change will remain until the end of the current occu­pied period, at which time the program reverts to the set­points defined in programming. To change the range of adjustment allowed, see programming step # 14.
OVERRIDE
The occupant has the ability to put the unit into occupied mode by pressing the override button on the front. By facto­ry default, the unit will remain in the occupied mode for 180 minutes. This value may be changed from 0 to 255 minutes in programming step # 15.
FAN SWITCHING
The option to allow the occupant to change the occupied fan mode is allowed by factory default. To lock out access to fan switching, see programming step #7.
SYSTEM SWITCHING
The option to allow the occupant to change the system mode is allowed by factory default. To lock out access to system switching, see programming step #5.
SETTING CLOCK & SCHEDULE
The ability to set the clock and schedule is allowed by fac­tory default. An access code may be required as set in pro­gramming step # 44, or access may be denied altogether using dipswitches described in the setup section.
PROGRAMMING
The ability to program control parameters is allowed by fac­tory default. An access code may be required as set in pro­gramming step # 43, or access may be denied altogether using dipswitches described in the setup section.
SUPERSTAT
TM
POINT MAPPING TABLES
SZ1017N............................Pages 13 - 15
TCS/Basys Controls Technical Support
800-288-9383
R
2800 LAURA LANE IMIDDLETON, WI 53562 I(800) 288-9383 IFAX (608) 836-9044 Iwww.tcs-basys.com
12
Pointmap Table for SZ1017N
NPT
NPA UNITS
POINT DESCRIPTION RANGE/VALUE ADDITIONAL NOTES
ADI 1 # DI2 control mode 0=Aquastat, See programming step #39.
1=monitor, 2=service
ADI 2 # Unocc Analog output action 0=0or4 mA, 1=20 mA See programming step #26.
2=Modulating
ADI 3 # Analog output mode 0=heat, 1= cool, See programming step #23.
2=Aquastat
ADI 4 # DI3 control mode 0=filter service, See programming step #41.
1=external override,
2= external timeclock ADI 5 # Occupied Fan mode 0=on, 1=cool, 2=auto "Fan Switch" button on keypad. ADI 6 # System mode 0=off,1=auto,2=heat "System Switch" button on keypad.
3=cool ADI 7 Day Internal time clock "day" 0-6, mon to sunday Day of Week. ADI 8 Hours Internal time clock "hours" 0-23 0-12 (AM), 13-23 (PM). ADI 9 DegF Setpoint adjust limit from keypad 0-50 Limits keypad adjustment of occupied
heating and cooling setpoints. ADI 10 DegF Differential for stage 1 0-50 ADI 11 DegF Offset for stage 1 0-50 ADI 12 DegF Differential for stage 2 0-50 ADI 13 DegF Offset for stage 2 0-50 ADI 14 DegF Setpoint shift value 0-50 When DI2 is selected "Monitor", this is
number of degrees that the occupied
cooling setpoint is shifted up and the
heating setpoint is shifted down. ADI 15 DegF (space) Setpoint offset 0-50 See programming step #28. ADI 16 DegF AO Proportional Band 0-50 See programming step #27. ADI 17 Seconds Internal time clock "second" 0-59 ADI 18 Minutes Internal time clock "minute" 0-59
ADI 19 DegF Occupied heating setpoint 40-90 Occupied heating setpoint must be less
than occupied cooling setpoint. ADI 20 DegF Unoccupied heating setpoint 40-90 Unoccupied heating setpoint must be less
than unoccupied cooling setpoint. ADI 21 DegF Occupied cooling setpoint 40-90 ADI 22 DegF Unoccupied cooling setpoint 40-90
ADI 23 DegF Room temperature 40-90 Read only. ADI 24 % Analog Output 0-100% Read only. ADI 25 DegF Discharge air setpoint 0-150 See programming step #33. ADI 26 # Reset ratio 0-150 See programming step #34 (Note 6). ADI 27 DegF Discharge air low limit 0-150 Discharge air high limit must be less
than discharge air low limit. ADI 28 DegF Discharge air high limit 0-150
ADI 29 DegF Discharge air temperature 0-150 Read only. ADI 30 DegF Outdoor heat lockout temp -40 to 160 See programming step #37. ADI 31 DegF Outdoor cool lockout -40 to 160 See programming step #36. ADI 32 DegF Outdoor air temperature -40 to 160 See Note 4 ADI 33 Minutes Override period 0-255 Unoccupied override time allowed. ADI 34 Seconds Power on delay time 0-255 Time before control begins on powerup. ADI 35 Minutes Remaining override time 0-255 Read Only. Time remaining before the
override period expires. ADI 36 DegF Current user setpoint adjust Min=-50, Max=50 Read Only. + or - amount the occupied
setpoint has been adjusted from actual
settings. ADI 37 Minutes Monday Occupied start time 0-1439 There are two occupied and two un-
for schedule A occupied time periods allowed per day.
ADI 38 Minutes Monday Occupied end time 0-1439 All times are measured in minutes from
for schedule A midnight.
R
2800 LAURA LANE IMIDDLETON, WI 53562 I(800) 288-9383 IFAX (608) 836-9044 Iwww.tcs-basys.com
13
Pointmap Table for SZ1017N (continued)
NPT NPA UNITS POINT DESCRIPTION RANGE/VALUE ADDITIONAL NOTES ADI 39 Minutes Monday Occupied start time 0-1439
for schedule B
ADI 40 Minutes Monday Occupied end time 0-1439
for schedule B ADI 41 Tuesday 0-1439 ADI 42 Tuesday 0-1439 ADI 43 Tuesday 0-1439 ADI 44 Tuesday 0-1439 ADI 45 Wednesday 0-1439 ADI 46 Wednesday 0-1439 ADI 47 Wednesday 0-1439 ADI 48 Wednesday 0-1439 ADI 49 Thursday 0-1439 ADI 50 Thursday 0-1439 ADI 51 Thursday 0-1439 ADI 52 Thursday 0-1439 ADI 53 Friday 0-1439 ADI 54 Friday 0-1439 ADI 55 Friday 0-1439 ADI 56 Friday 0-1439 ADI 57 Saturday 0-1439 ADI 58 Saturday 0-1439 ADI 59 Saturday 0-1439 ADI 60 Saturday 0-1439 ADI 61 Sunday 0-1439 ADI 62 Sunday 0-1439 ADI 63 Sunday 0-1439 ADI 64 Sunday 0-1439
BD 1 DI1 control mode 0=fan proving, See programming step #38.
1=Monitor BD 2 Unocc fan mode 0=cool, 1= auto Not accessible with "Fan Switch" button. BD 3 Enable occupied fan switch 0 = No, 1=Yes Enables "Fan Switch" button. BD 4 Enable system switch 0 = No, 1=Yes Enables "System Switch" button. BD 5 Use of discharge air sensor 0 = No, 1=Yes Always monitored, enables discharge
air function. BD 6 Use of outdoor air sensor 0 = No, 1=Yes BD 7 Enable smart recovery routine 0 = No, 1=Yes 4° per hour setpoint ramp prior to oc-
cupancy forboth heating and cooling. BD 8 Require access code 0 = No, 1=Yes Programming access from keypad.
for programming?
BD 9 Require access code 0 = No, 1=Yes Clock/Schedule access from keypad.
for clock/schedule?
BD 10 Enable stage 1 & 2 0=disable, 1=enable See programming step #16. BD 11 Stage 1 & 2 action 0=cool, 1=heat See programming step #16. BD 12 Time clock relay output 0=Normally Open State of relay output during occupied
1=Normally Closed period.
BD 13 Control mode 0=Proportional Stages turned on and off using offsets
and differentials only.
1=Prop. + Integral Stages turned on and off using offsets
and differentials + a time factor. BD 14 Control is based on 0=Space See programming step #32.
1=Discharge
BD 15 Analog output range 0 = 0 - 20 ma, See programming step #25.
1 = 4 - 20 ma
BD 16 Analog output action 0 = Direct, See programming step #24.
1 = Reverse
R
2800 LAURA LANE IMIDDLETON, WI 53562 I(800) 288-9383 IFAX (608) 836-9044 Iwww.tcs-basys.com
14
Pointmap Table for SZ1017N (continued)
NPT NPA UNITS POINT DESCRIPTION RANGE/VALUE ADDITIONAL NOTES BD 17 DI1 source 0=local contact "Local" means read by or controlled by
Thermostat.
1=remote request "Remote" means the state of the input
or
output is controlled only by computer.
BD 18 DI2 source 0=local contact
1=remote request
BD 19 DI3 source 0=local contact
1=remote request
BD 20 Override function source 0=local keypad
1=remote request
BD 21 Fan relay source 0=local mode
1=remote requset
BD 22 Remote DI1 request 0=off, 1=on When selected to be "Remote", turns
input or output on and off. BD 23 Remote DI2 request 0=off, 1=on BD 24 Remote DI3 request 0=off, 1=on BD 25 Remote override request 0=off, 1=on This is a permanent override. BD 26 Remote Fan request 0=off, 1=on
BD 27 Stage 1 relay status 0=off, 1=on Read only. BD 28 Stage 2 relay status 0=off, 1=on Read Only BD 29 Fan relay status 0=off, 1=on Read only. BD 30 Timeclock relay status 0=off, 1=on Read only. BD 31 DI1 status 0=off, 1=on Read only. BD 32 DI2 status 0=off, 1=on Read only. BD 33 DI3 status 0=off, 1=on Read only. BD 34 Override status 0=off, 1=on Read only. Timed override. BD 35 Device's occupied status 0=Occupied Read only.
1=Unoccupied BD 36 Service status 0=OK, 1= fail Read only. See Note 1. BD 37 Fan interlock status 0= OK, Read only. DI1 Fan Proving.
1= Fan interlock fail BD 38 Filter service status 0=OK, 1=check Read only. DI3 Filter Status.
Filter BD 39 Discharge air high limit 0=OK, 1= Above Read only. Discharge air function.
high limit BD 40 Discharge air low limit 0=OK, 1= Below Read only. Discharge air function.
low limit BD 41 DI2 service status 0=OK, 1= Check DI2 Read only. DI2 Service.
NOTE 1: The Service status point represents general Check status, if this is point is 1, then by polling point 37 to 41 the user can find out actual failing condition. If this point is 0 then points 37 to 41 will be also 0.
NOTE 2: All of the ADI and BD points support the override function. The value overridden will be stored permanently, so the sta­tus attribute will never have any override active status. Because none of these points support the override release function, the controller will acknowledge the override release function but never release the value. The controller will respond with NAK error N10 if the value for the override command is outside the limits for that point. Points that are "Read Only" can not be overridden. The controller will acknowledge the override command, but the actual change will never happen.
NOTE 3: All of the points in this map can be adjusted through the keypad except: “Read Only” points, ADI 32, and BDpoints 17 through 26. In the case of loss of communications for 15 minutes (i.e., if the controller is not addressed for 15 minutes), the con­troller will revert BD points 17 to 26 to zero value (make them all local requests).
NOTE 4: ADI point 32, Outdoor Air Temp., can be overridden for a default of 10 minutes. After 10 minutes it reverts back to its original port value.
NOTE 5: Communications are disabled when programming mode or clock/schedule mode is entered via the keypad. Entering programming mode via the keypad can be disabled.
NOTE 6: 0-150 number represents 0.0 to 15.0°F.
R
2800 LAURA LANE IMIDDLETON, WI 53562 I(800) 288-9383 IFAX (608) 836-9044 Iwww.tcs-basys.com
15
Rev: 1000
R
2800 LAURA LANE IMIDDLETON, WI 53562 I(800) 288-9383 IFAX (608) 836-9044 Iwww.tcs-basys.com
16
Loading...