TCL TAC-24CF/E, TAC-24CHF/E Service Manual

TCL
SERVICE MANUAL
No.TE040610
FLOOR-STANDING AIR CONDITIONERS
TAC-24CF/E TAC-24CHF/E
CONTENTS
1. IMPORTANT NOTICE ···································2
2. TECHNICAL SPECIFICATION ·····················3
3. OPERATION DETAILS ···································4
4. WIRING DIAGRAM ············· 5
5. EXPLOSION VIEW ···························· 12
6. PARTS LIST ·············18
IMPORTANT NOTICE
This service manual is intended for use by individuals possessing adequate backgrounds of electrical, electronic and mechanical experience. Any attempt to repair the appliance may result in personal injury and property damage. The manufacturer or seller cannot be responsible for the interpretation of this information, nor can it assume any liability in connection with its use.
The information, specifications and parameter are subject to change due to technical modification or improvement without any prior notice. The accurate specifications are presented on the nameplate label.
How to order spare parts
To have your order filled promptly and correctly, please furnish the following information:
1. Model No. with Indoor or Outdoor
2. No. in the Explosion View
3. Part Name
4. The quantity you ordered
TCL Air Conditioner Service ManualTCL Air Conditioner Service ManualTCL Air Conditioner Service Manual
TCL Air Conditioner Service Manual
2
TCL Air Conditioner Service Manual
3
Technical Specifications
Model No. TAC-24CS/F TAC-24CHS/F
Type Cooling Only Heating Pump Control type Remote Remote Rated cooling capacity Btu/h 24000 24000 Rated heating capacity Btu/h N/A 25000 EER for cooling Btu/h.w 9.6 10.3 COP for heating W/W N/A 3.2 Moisture removal Liters/h 2.2 2.2
High dB(A) 48 48 Med. dB(A) 46 46
Indoor noise level at cooling
Low dB(A) 40 40
Outdoor noise level dB(A) 58 58
Electrical Data
Power supply 220-240V~/50Hz Voltage Range V
Cooling A 11.5 12.0
Rated current
Heating A N/A 10.0 Cooling W 2400 2300
Rated input
Heating W N/A 2100
Refrigerating System
Refrigerant/Charge Gram R22/1450g R22/2350g
Type Rotary Rotary Model ------------------ ----------------- LRA A ------ -------
Compressor
MFG ----------------- ----------------- Evaporator Louver fin and Grooved tube type (φ7) Condenser Corrugated fin and Grooved tube type (φ9.53) Expansion device Capillary tube Defrosting system Microcomputer controlled reverse system
Fan System
Indoor air circulation m3/h 1200 1200 Indoor fan type Cross flow Cross flow
Cooling rpm 480/430/380 480/430/380
Heating rpm N/A 480/430/380
Dry rpm 380 380
Indoor fan speed H/M/L
Sleep rpm 380 380 Indoor fan motor output W 76 76 76 Outdoor air circulation m3/h --- --- Outdoor fan type Propeller fan Propeller fan Outdoor fan speed rpm 850 850 Outdoor fan motor output W 76 76
Connections
Refrigerant coupling Flare type
Gas Inches 3/8 3/8 Connecting Pipe
Liquid Inches 5/8 5/8 Connecting Wiring
Size × Core
number Drainage Pipe O.D 16mm
Others
Suitable area m2 35~48 35~48
Indoor mm 480×1730×330 710×250×179 Net dimensions (W x H x D)
Outdoor mm 860×640×310 600×500×232
Indoor kg 36 7.5 Net weight
Outdoor kg 56 25
Indoor mm 588×1825×425 805×325×270 Packing dimensions (W x H x D)
Outdoor mm 990×720×420 745×352×542
Indoor kg 45 10 Gross weight
Outdoor kg 66 29 Loading Capacity 40’/40’HC 32/75/84 32/75/84
4
Note: Each mode and relevant function will be further specified in following pages.
SLEEP
FAN
TIMER
SWING
ON/OFF
MODE
MID
SWING
AUTO
DRY FAN HEAT
COOL
FEEL
SLEEP
TIMER ON
HIGH
LOW
TMIER OFF
The remote controller transmits signals to the system.
Remote controller
1
2
4
3
5
6
7
8
8
4
MODE button
FAN SPEED control button
UP button (TOO COOL button)
DOWN button (TOO WARM button)
ON/OFF button
SLEEP button
VANE control button
TIMER button
Used to select the type of operation mode: Feel, Cooling, Dry, Fan and Heating(Only for Heat Pump).
Used to select the indoor fan motor speed: Auto, High, Mid and Low.
Used to increase the set room temperature
and time.
Used to decrease the set room temperature and time.
Used to set or cancel sleep mode operation.
Used to start and stop operation when pressed.
Used to adjust airflow direction.
Used to select TIMER operation.
Remote controller
6
2
5
3
7
1
11
TCL Air Conditioner Service Manual
Operation Details
Remote Control
The remote controller is not presetted as Cooling Only Air Conditioner or Heat Pump by manufacturer. Each time after the remote controller replace batteries or is energized, the arrowhead will flashes on the front of
Heat or Cool on LCD of the remote controller. User can preset the remote controller type depending on the air conditioner type you have purchased as follows: Press any button when the arrowhead flashes on the front of Cool , Cooling Only is set. Press any button when the arrowhead flashes on the front of Heat , Heat Pump is set. If you don t press any button within 10 seconds, the remote controller is preset as Heat Pump automatically.
Note :
If the air conditioner you purchased is a Cooling Only one, but you preset the remote controller as Heat Pump, it doesn t bring any matter. But if the air conditioner you purchased is a Heat Pump one, and you preset the remote controller as Cooling Only, then you CAN NOT preset the Heating operation with the remote controller.
TCL Air Conditioner Service Manual
5
Elctronic Controller
1. Safety Control
(1) Time Delay Safety Control
3 minutes delay for compressor---The compressor is ceased for 3minutes to balance the pressure in the
refrigeration cycle in order to protect the compressor.
2 minutes delay for 4-way valve---The 4-way valve is ceased for 2 minutes to prevent the
refrigerant-gas abnormal noise when the HEATING operation is OFF or switch to the other operation
mode.
20 seconds delay for indoor fan--- When the assistant thermistor turns off, the indoor fan operates in
low speed for 20 seconds to release the heat of indoor unit.
(2) Indoor Pipe Temperature Sensor Frost Prevention Control
When the indoor pipe temperature sensor reads 0 or below for 5 minutes, the indoor pipe temperature
sensor frost prevention control starts. The compressor and outdoor fan stop and indoor fan operates at high speed for 3 minutes. After that, if the indoor pipe temperature sensor reads less than 5 this control prolonged until the indoor pipe temperature sensor reads 5 or more.
(3) High Temperature Protection Control
During HEATING operation, the outdoor fan motor and compressor are controlled by the indoor pipe
temperature to prevent the high temperature of compressor. Outdoor fan OFF: 52 Outdoor fan ON:48 Compressor OFF:62 Compressor ON:48
2. “I Feel” Mode Operation
(1) When the “I Feel” mode is selected, the operation mode and initial set temperature are determined by the
initial room temperature at start-up of the operation except to turn off the air conditioner and operates it
again.
(2) If the mode is change to “I Feel” mode from other mode, the “I Feel” mode doesn’t operate until compressor
stop for more than 3 minutes.
In the “I Feel” mode , when the controller receives the up or down single of temperature, the set
temperature can adjust by 1
upper or lower. The biggest you can adjust by 2℃ upper or lower.
3. “COOLING” Mode Operation
(1) When the COOLING mode is selected without setting temperature, the system will set the set temperature at
26
automatically with the AUTO FAN speed.
(2) When selecting the COOLING mode operation, the system will operate according to the setting by the
remote controller and the operation is as following:
Mode
Initial room temperature
COOLING
DRY
HEATING for Heat Pump Type
FAN for Cooling Only Type
26 or more
20 to 25
Less than 20
Initial set temperature
24
18
23
TCL Air Conditioner Service Manual
6
Room Temp.
Set TEMP. +1
Set TEMP. 1
Time
More than 2 min More than 2 min More than 2 min More than 2 min More than 2 min
Indoor Fan Set Speed Set Speed Set Speed Set Speed Set Speed
Compressor ON OFF ON OFF ON
Outdoor Fan ON OFF ON OFF ON
4. “DRY” Mode Operation
(1) The system for DRY operation used the same refrigerant circle as the cooling circle.
(2) When the system operates in DRY mode ,at first it operates in cooling mode at 18
for 3 minutes, and
then, the system operates in cooling mode with low speed that regards the temperature of the room
temperature sensor reads decrease 2 as the set temperature. During the course of this, the fan speed
setted operation is failing but the vane motor can be controlled.
5. “HEATING” Mode Operation (Only available for Heat Pump)
(1) When the HEATING mode is selected without setting temperature, the system will set the temperature at 23
automatically with the AUTO FAN speed.
(2) When selecting the HEATING mode operation, the system will operate according to the setting by the
remote controller and the operation is as following:
Set Temp. +1 Set Temp. -1
Room Temp.
Time
More than 2 min More than 2 min More than 2 min More than 2 min More than 2 min
Compressor ON OFF ON OFF ON
Outdoor fan ON OFF ON OFF ON
(3) In HEATING mode, the indoor fan motor is controlled by Cold Air Prevention Control.
(4) Cold Air Prevention Control
The function is intend to prevent cold air from being discharged when the heating operation starts or
when defrosting.
The indoor fan speed will be controlled as following: The vane angle is at the angle C(100°).
34
30
27
25
23
OFF UL Set Speed UL OFF UL
Indoor Pipe Temperature
TCL Air Conditioner Service Manual
7
(5) Defrost
Defrosting of the outdoor heat exchange is controlled by the microprocessor with detection by the defrost
sensor.
Defrost starting conditions
When the conditions of a) or b) is satisfy, the defrosting operation starts.
a) Under the heating operation, the compressor cumulative operation time exceeds 50 minutes and the temperature of the outdoor defrost sensor reads lower than -8
b) Under the heating operation, the compressor cumulative operation time exceeds 50 minutes, if the
indoor pipe temperature sensor reads lower than 40
continuously for 2minutes.
Note: If haven’t the outdoor pipe temperature sensor that use the condition b) to defrost, against
use the condition a).
Defrost terminating conditions
When the condition c) or d) is satisfy, the defrosting operation stops.
c) The outdoor defrost sensor reads 15
or more.
d) The defrosting time exceeds 10 minutes.
Defrosting time chart
Outdoor Fan ON OFF ON
Revering Valve ON OFF ON
Compressor Relay ON OFF ON OFF ON
39S 5S Defrost Count MAX 12min 19S 15S t
(6) Assistant Thermistor Function
Assistant thermistor is add the thermitor of the electricity to rise the heating capacity automatically not
effected by the signal of the remote controller about assistant thermistor ON/OFF buttons.
1) When the condition all of A~G are satisfy, the assistant thermistor opens.
A. Under the heating operation, the compressor operates over than 3 minutes.
B. The indoor fan operates in normal.
C. The system operates not in defrosting.
D. The assistant thermistor turn off over than 30 seconds.
E. The set temperature is 3
or more than the room temperature.
F. The room temperature sensor reads less than 22
.
G.
The indoor pipe temperature reads 43 or less.
2) When one of the conditions of A~E is satisfy, the assistant thermistor is off.
A. The compressor is turned off.
B. The room temperature sensor reads 24 or more.
C.
The indoor pipe temperature sensor reads 48 or more.
D.
The indoor fan is stopped.
6. “FAN” mode operation