TCL iQool9, iQool12, iQool18, iQool24 User And Installation Manual

Page 1
Smart WIFI Controlled Wall Mounted
Inverter Split Air Conditioner with Heat Pump
iQool9 9,000 BTU
iQool12 12,000 BTU iQool18 18,000 BTU iQool24 24,000 BTU
Thank you for choosing a TCL Air Conditioner
Please read this user manual before using this innovative
Air Conditioner and keep it safe for future reference.
Page 2
2
CONTENTS
SAFETY INSTRUCTIONS 3
OPERATION 4
REMOTE CONTROL & FUNCTIONS 5
WIFI CONTROL 11
FILTERS 21
END OF SEASON 21
START OF SEASON 22
REPLACING THE BATTERIES 22
INSTALLATION GUIDE 22
INSTALLATION OF THE OUTDOOR UNIT 29
STANDARD PIPELINES CONNECTION & AIR PURGING 30
ELECTRICAL WIRING DIAGRAMS 33
TROUBLESHOOTING AND SELF DIAGNOSIS 36
TECHNICAL SPECIFICATION 39
APPENDIX 41
Page 3
3
SAFETY INSTRUCTIONS
Important!
Carefully read the instructions before operating the unit This appliance comprises of an indoor and an outdoor unit. The indoor slim evaporator
is designed exclusively for indoor installations while the external condenser can be installed outside while still away from flood water or snow line.
Rating: This unit must be only connected to a 220-240 V / 50 Hz earthed power source. Installation must be in accordance with the regulations of the country where the unit is
used.
These air conditioners are supplied with pre flared refrigeration pipes and electrical
cables, which enables the installer to reduce the installation time.
European Union regulations requires for an F-Gas trained engineer to handle any
operation where non-qualified intervention could cause fluorinated gas to escape. A commissioning certificate must be issued with any installation.
If you are in any doubt about the suitability of your electrical supply have it checked and,
if necessary, modified by a qualified electrician.
This air conditioner has been tested and is safe to use. However, as with any electrical
appliance - use it with care.
Disconnect the power before dismantling, assembling or cleaning. Avoid touching any moving parts within the appliance. Never insert fingers, pencils or any other objects through the guard This appliance is not intended for use by persons (including children) with reduced
physical, sensory or mental capabilities. It is also not intended for use by those with a lack of experience and knowledge, unless they have been given supervision or instruction concerning the use of the appliance by a person responsible for their safety. Do not leave children unsupervised with this appliance.
Do not clean the unit by spraying it or immersing it in water. Never connect the unit to an electrical outlet using an extension cord. Both the indoor
unit and outdoor must be hardwired by a qualified electrician.
Never operate this appliance if the cord is damaged. Ensure the power cord is not
stretched or exposed to sharp objects or edges.
A damaged supply cord should be replaced by the manufacturer or a qualified
electrician in order to avoid a hazard.
Any service other than regular cleaning or filter replacement should be performed by an
authorized service representative or a qualified air conditioning engineer. Failure to comply could result in a voided warranty.
Do not use the appliance for any purpose other than its intended use. The outdoor part of the air conditioner unit must always be stored and transported
upright, otherwise irreparable damage may be caused to the compressor; if in doubt we suggest waiting at least 24 hours before starting the unit.
Avoid restarting the air conditioning unit unless 3 minutes have passed since being
turned off. This prevents damage to the compressor.
Never use the mains as a switch to start and turn off the air conditioning unit. Use the
provided ON/OFF button located on the remote control.
Always place the unit on a dry and stable surface. Install the outdoor unit on a wall with
wall-mounted brackets or fix to a floor slab with special floor mounting slab bolts or brackets away from flood or snow lines.
The indoor unit should not be installed in laundry or wet rooms.
Page 4
4
Energy Saving and Unit Safety Protection Tips
Do not cover or restrict the airflow from the outlet or inlet grills. For maximum performance the minimum distance from a wall or objects should be 50cm. Keep the filters clean. Under normal conditions, filters should only need cleaning once
every four weeks (approximately). Since the filters remove airborne particles, more frequent cleaning maybe necessary, depending on the air quality.
For the initial startup set the fan speed to maximum and the thermostat to 4-5 degrees
lower than the current temperature. After, set the fan switch to low and set the thermostat to your desired setting.
To protect the unit we recommend not using the cooling mode when the ambient indoor
temperature is higher than 35.
To protect the unit we recommend not using the heating mode when the indoor ambient
temperature is lower than 7. Performance will be reduced at lower temperatures.
Note the manufacturer operating temperature ranges at the end of this user manual.
OPERATION COOLING MODE
The compressor (6) in the external unit compresses the refrigerant into a high-temperature, high-pressure gas. When this gas flows along the cooling fins of the condenser (7), heat is exuded and the gas condenses into a liquid, which is then led to the evaporator (1) in the indoor unit. The liquid expands into a gas at a low temperature and low pressure. This gas absorbs the warmth of the air in the room, and a fan (3) draws the air through the filter and over the evaporator (1), blowing the cooled air back into the room. The heat is moved to the compressor along with the gas. A fan (8) draws air over the condenser and blows the warm air away.
1. Evaporator
2. Filter
3. Evaporator Fan
4. Gas Line
5. Liquid line
6. Compressor
7. Condenser
8. Condenser Fan
HEAT PUMP MODE
The system operates in reverse: the condenser works as an evaporator, the evaporator as a condenser: warm air is blown into the room. It is ideal as a maintenance heating when outside temperature is not too low and when the indoor temperature is more than 7°C.
Dehumidifying
As with cooling, the moisture in the air condenses on the cold evaporator at room temperature acting as a powerful dehumidifier.
31 2 4568
7
Page 5
5
REMOTE CONTROL
The remote control has a range of up to 8m. Point the remote control at the receiver in the interior unit. A beep confirms that the remote control signal has been received.
REMOTE OPERATION
Turn the appliance on using the ON/OFF button. This activates the most recently used setting. The ON/OFF button also turns the air conditioner off.
*Horizontal swing not available on most models and the horizontal direction must be adjusted manually.
No.
Button
Function
1
Up
Press to increase temperature
2
Down
Press to decrease temperature
3
ON/OFF
Press to turn on/off the unit
4
Fan
Press to select the fan speed LOW / MED / HIGH
5
Timer
Press to set the timer
6
Sleep
Press to activate the “SLEEP” function
7
Eco
In cooling mode, press to increase the set temperature by 2oC. In heating mode, press to decrease the set temperature by 2oC
8
Mode
Press to select the desired operating mode
9
Turbo
Press to activate turbo mode. This will make the unit work its hardest to quickly cool or heat the room for a period of 15 minutes. The fan will be set to max, the temperature will be set to either 16oC in cooling mode or 31oC in heating mode.
10
Swing
Select the vertical direction of airflow ( Horizontal direction not adjustable on these models)
11
Mute
Press to turn off the beep when functions are selected
12
Display
Press to turn on/off the LED display
13
I Feel
Press to activate the follow me function
14
Health
Press to activate the antibacterial ioniser function
*
Page 6
6
oC/o
F
Temperature units can be changed on the remote by altering the switch under the battery cover. Remove the batteries, move the switch to the desired units then replace the batteries.
TEMPERATURE
The desired temperature is set with the up and/or down button, within the limits of the thermostat: 16°C – 32°C. Use the FAN SPEED button to set the fan speed at low, medium and high; or automatic (the symbol on the display will flash). The fan speed in the automatic setting is determined by the difference between the set temperature and the room temperature.
INDOOR UNIT
No.
Description
1
Front panel
2
Air filter
3
Optional filter
4
LED Display
5
Signal receiver
6
Terminal block cover
7
Ionizer generator (not applicable on all models)
8
Deflectors
9
Emergency button
10
Indoor unit rating label
11
Airflow direction louver
Page 7
7
DISPLAY PANEL Iqool 9/12/18 Iqool24
No.
Display
Function
1
POWER
Illuminated when power is on
2
SLEEP
Illuminated in sleep mode
3
Temp. / Error code
Shows the temperature / error code
4
TIMER
Illuminated when timer is activated
5
RUN
Illuminated when unit is turned on
OUTDOOR UNIT
No.
Description
12
Air outlet grille
13
Outdoor unit rating label
14
Terminal block cover
15
Gas valve
16
Liquid valve
Page 8
8
FUNCTIONS COOL
1. Press the MODE button until the COOL indicator appears.
2. Set the desired temperature.
3.
Use the FAN button
to set the fan speed.
HEAT
1. Press the MODE button until the HEAT indicator appears
2. Set the desired temperature.
3. Use the FAN button to set the fan speed.
FAN MODE
1. Press MODE button until the FAN indicator appears.
2. The temperature settings are disabled in fan mode.
3. Use the FAN button to set the fan speed, cycling through LOW / MED / HIGH / AUTO.
DEHUMIDIFY
1. Press the MODE button until the dehumidify indicator appears.
2. The fan speed will always be low in this mode and the FAN button is disabled. In addition the temperature cannot be adjusted in dehumidifying mode
AUTO MODE
1. Press the MODE button until the AUTO indicator appears.
2. The difference between the set temperature and room temperature determines how the air conditioner operates: cool, heat, fan or dry. It is not possible to change the temperature in this mode the unit will operate to achieve best performance. The operation logic is as below.
Ambient Temperature
Operation Mode
Auto Temperature
˂20°C
Heating
23°C
20°C - 26°C
Dry
18°C
˃26°C
Cool
23°C
3. Use the FAN button to set the fan speed.
TIMER OFF FUNCTION (WHILE THE AIR CONDITIONER IS ON)
1. Press the MODE button until the symbol appears for the operation you want.
2. Set the desired temperature.
3. Use the FAN button to set the fan speed.
4. Press the TIMER button to set the running time required. Use the up and down buttons to set the running time in 30 minute intervals (max 24 hours). Once the running time has elapsed, the appliance will switch itself off. To cancel the timer function before the set time has elapsed, press the TIMER button again.
TIMER ON FUNCTION (WHILE THE AIR CONDITIONER IS IN STANDBY)
1. The appliance is switched off in standby mode
2. Press the TIMER button to set the number of hours until switch on is required. Use the up and down button set the number of hours in 30 min intervals (max 24 hours). Set the desired operation, temperature, fan speed. Once the set time has elapsed, the appliance will switch itself on. To turn off the timer function before the set time has elapsed, press the TIMER button again.
Page 9
9
SLEEP MODE
1. Press the SLEEP button
2. Set the desired temperature.
3. Press the SLEEP button; The SLEEP indicator will appear on the display. Cancel the sleep mode by pressing the button again.
4. The fan will operate at low speed..
5. The temperature is automatically altered by 1oC every hour for 2 hours. In cooling mode the temperature will rise, in heating it will fall.
6. After 10 hours in Sleep mode the unit will power off automatically.
TURBO
1. Press the TURBO button until the Turbo symbol appears.
2. Set the desired temperature.
3. Use the FAN button to set the fan speed
4. Press the TURBO button. The fan and compressor will run at maximum speed for 15 minutes, before returning to their previously set levels.
SWING
1. Press the SWING buttons to control the fan direction.
2. The controls the horizontal air movement (up/down)
3. The button is not activated on this model, and the horizontal direction of the airflow can be adjusted manually.
ECO
1. Press the ECO button to turn on the energy saving mode
2. In cooling mode, the desired temperature will increase by 2oC.
3. In heating mode, the desired temperature will decrease by 2oC.
IFEEL
1. Press the IFEEL button to activate the follow me mode.
2. In this mode the temperature of the unit will be set based on the temperature where the remote is situated.
3. The remote will act as a mobile thermostat which controls the unit.
HEALTH
1. Press the Health button to activate the antibacterial ioniser function.
2. The ionizer helps to eliminate pollutants in the air.
IMPORTANT AUTO RESTART.
The air conditioner will automatically restart when electricity is restored after a power cut. If in doubt, check the settings.
Page 10
10
RANGE OF INTERNAL THERMOSTAT
The internal thermostat can be set at a desired temperature between 16 and 32°C. Note that whether the desired value is achieved depends on the room size, temperature and insulation of the room.
RANGE OF HEAT PUMP FUNCTION
The heat function can be used when the external ambient temperature is above -15°C. The performance of the heat pump will degrade with lowering external temperatures. Please note the performance will reduce when the outdoor temperature drops below 5°C.
CAPACITY
The required cooling or heating capacity depends greatly on the location and/or use of the room where the air conditioner is installed. Strong sunlight and the presence of people, lights or equipment create an additional heat load. Normal living spaces require about 100 W per square metre of floor surface. In strong sunlight or if other sources of heat are present, this may be as much as 350 W/sqm.
Tip: On warm days, let the air conditioner cool the room as much as possible during the night and set the temperature constant from night to daytime.
EMERGENCY START
In the event of a problem, the air conditioner can be operated using the emergency button under the panel in the interior unit. Open the front panel and press the button, the air conditioner will:
-heat if the room temperature is 20 °C or less, cool if the room temperature is 25 °C or more and for values in between: dehumidify in a model without a heat pump and in a model with a heat pump in fan mode.
Page 11
11
BEFORE YOU START
Ensure your router provides a standard 2.4ghz connection.
If your router is dual band ensure that both networks have different network names (SSID).
The provider of your router / ISP will be able to provide advice specific to your router.
Once the app has been installed on your phone, turn off the data connection, and ensure your phone is connected to your router via wifi.
DOWNLOAD THE APP TO YOUR PHONE
Please note that your air conditioner requires a good signal during the setup process. Your air conditioner is designed to be connected to a 2.4ghz network, and the connection is set up using
the TCL “SMART LIFE” app. We would advise on using the QR codes below to ensure the
correct app is downloaded.
Android IOS
The unit can also be controlled using the “Smart Life” app by TUYA which is also available in the app stores. We would advise on using the version above which is optimised for use with your air conditioner as we cannot guarantee the correct functionality of all features with the TUYA app. If you would prefer to use the TUYA app, please use the QR codes below
Android IOS
Page 12
12
ACTIVATING THE APP
The first time the app is used, it will need activating. To do this, either press the scan button, and scan the QR code below, or
press “Enter Activation Code” and enter the
activation code: TCL
REGISTER THE APP
Upon the first use, an account will need to be registered. Click on the “Register” button to enter the registration screen. The account can be created by using either the default option of an email address, or alternatively by SMS message using the
“Register with mobile number” option.
EMAIL REGISTRATION
Enter your email address, and Press next. In the password box create a new password for your account, before pressing confirm. This should be at least 6 characters and include letters and numbers.
Page 13
13
SMS REGISTRATION
Press on the option at the bottom of the screen to choose the option for registering with a mobile number. You will receive an activation code via SMS. Enter the activation code into the verification code box, before entering your new password in the box below. Please note the password should be at least 6 characters and include letters and numbers. Then press the confirm button to log in.
FORGOTTEN PASSWORD
Should the password for your account be forgotten, it is possible to use the “Forgot Password”
option which will allow you to enter the email address or telephone number used to register the account, and a verification code will be sent to you via the method chosen.
Page 14
14
CONNECTION METHODS AVAILABLE FOR SETUP
The air conditioner has two different setup modes, CF (Quick Connection) and AP (Access Point). The CF mode is a quick and simple way to set the unit up. The AP connection uses a direct local wifi connection between your phone and the air conditioner to upload the network details.
Before starting the setup, please ensure that your air conditioner is in the correct standby mode for the connection type you are attempting, the display on the air conditioner will confirm the current connection mode during setup.
CHANGING BETWEEN CONNECTION TYPES
To change the unit between the two connection types, quickly press the display button on the remote 6 times, and wait approx. 10 seconds until the new connection mode is displayed on the panel of the air conditioner.
ADDING A DEVICE
1. Press the “Add device” button, which will bring up a screen to choose the device type.
2. Select “Split Air Conditioner” from the Device Type List.
3. The app will default to quick connection mode, and this can be changed by pressing the button labelled AP Mode in the top right of the screen.
4. After ensuring that the air conditioner is also in the correct connection mode, follow the relevant connection guide on the following pages.
Page 15
15
CONNECTING USING CF MODE (QUICK CONNECTION)
1. Ensure that the display on the air conditioner is displaying CF before pressing “Next Step” (otherwise to change the connection mode: Quickly press the display button on the remote 6 times and wait 10 seconds until CF is displayed)
2. Select your Wifi router from the drop down list and enter the password (Please note the password is case sensitive) before pressing next.
The app will automatically upload the connection information to the air conditioner, once the connection is completed, a message will be displayed to confirm. On this page there is the option to rename the air conditioner to something more relevant.
If the connection fails, please retry the connection, failing this try connecting using the AP mode connection.
Page 16
16
CONNECTING USING AP MODE (ALTERNATIVE METHOD)
1. Ensure that the screen on the air conditioner is displaying AP (otherwise to change the connection mode: Quickly press the display button on the remote 6 times and wait 10 seconds until AP is displayed)
2. Press on the AP Mode button in the top right of the screen to change the app to AP mode connection.
3. Select your Wifi router from the drop down list and enter the password (Please note the password is case sensitive) before pressing next.
4. Connect your phone to the wifi network by leaving the app, and connecting to the Wifi network created by the air conditioner “Smartlife-XXX”
5. Reopen the app and click on the “Connect now” button,
Page 17
17
The app will automatically upload the connection information to the air conditioner, once the connection is completed, a message will be displayed to confirm. On this page there is the option to rename the air conditioner to something more relevant.
If the connection fails, please retry the connection, failing this try connecting using the CF mode connection.
Page 18
18
CONTROLLING YOUR DEVICE THROUGH THE APP Now that your air conditioner is linked up to your network, you can control it from your phone.
Select your device in the device list to gain access to the controls for the device.
Use the + and – buttons to increase and decrease the desired temperature. The tabs on the
bottom of the screen should be used to change other settings.
Mode: Allows the operating mode to be changed between Feel, Heat, Dry, Cool and Fan. Speed: Allows the fan speed to be changed between Auto, Low, Medium and High. Function: Allows the Sleep, Turbo and Eco functions to be activated (See main manual for
description of the operation) and for vertical and horizontal swing on the louvres to be turned on / off (Not supported on all units)
Page 19
19
USING THE TIMER FUNCTION
The timer can be used to either set a time for the air
conditioner to turn on (and specify the settings it will run with), or a time for the unit to turn off. Multiple timers can be used together to build a schedule with on and off times.
1. Press the Timer button at the bottom right of the screen.
2. To set a new timer, press the “Add Timer” button at the bottom of the screen. If there is a timer already programmed that you would like to amend, press and hold the timer which requires amendment.
OFF TIMER:
1. Select Timer Off
2. Set the time the air conditioner should turn off 3.
Select which days the timer should operate
4. Press Save in the top right corner.
ON TIMER:
1. Select Timer On
2. Set the time the air conditioner should turn on
3. Select which days the unit should run on the auto timer.
4. Set the Mode, fan speed, desired temperature and function that the air conditioner
should run with.
5. Press Save in the top right corner.
Page 20
20
MORE SETTINGS
When on the main screen the three dots in the top right hand corner give you access to the settings options for the app. This a number of extra options for modifying the name of the air conditioner, and removing a device from the app.
Page 21
21
FILTERS
Ensure the power is turned off to the unit before attempting to service the filters.
B
C
B A
A. B.
Opening the front panel: at the A recesses, pull the front part up with both hands. The front panel will stay horizontal (at around 90°).
Closing the front panel: press the front part down at the sides at B and in the middle at. Make sure it is properly clicks into place.
1. Hold the front panel open (or put it in horizontal position) and remove the filter(s).
2. Use a vacuum cleaner to remove dirt. If the dust filter is very dirty, it may be washed in lukewarm water with a very small amount of neutral detergent. Rinse well and allow to dry completely (not in direct sunlight or near a source of heat).
3. Keep the front panel open and reinstall the filter(s). Press the panel shut; a click indicates it is closed properly.
4. Restore the power from the consumer unit and turn the air conditioner on.
Indoor Unit: While the unit is disconnected from power dust regularly with a dry cloth or slightly damp paper towel. Never use chemicals or solvents. Never spray a liquid in or over the appliance. Exterior unit: While the unit is disconnected from power. Remove dirt and keep the air intake and exhaust openings free of debris, etc. Cleaning with chemicals may cause damage.
END OF SEASON
If the air conditioner is not going to be used for an extended period:
Set in fan mode on a slightly warm day so that the inside of the appliance dries out.
Switch off the power from fuse box and remove the batteries from the remote control.
Clean filters as well
Page 22
22
START OF SEASON
If the air conditioner is to be used again after an extended period:
Check that the air intake and exhaust openings of the interior and exterior units are
not blocked. Remove all dirt and debris.
Check that filter is installed and is clean.
Check that the condensation outlet drains properly and there is no dirt or organic blockage
(otherwise leakage may occur)
Install 2 AAA batteries in the remote control.
Turn the appliance on, set the time and desired setting.
REPLACING THE BATTERIES
Remove the remote cover.
Replace the AAA batteries, ensuring the correct polarity.
Install the cover.
Press the on/off button; if no symbols appear on the display, the
batteries require replacing or have been incorrectly installed.
INSTALLATION GUIDE
SAFETY
Only qualified personnel should install this appliance. This installation manual is intended for
use by individuals possessing adequate backgrounds and qualifications in electrical, electronic, refrigerant and mechanical field. Any attempt to install or repair the appliance may result in personal injury and property damage.
The manufacturer or seller cannot be responsible for the interpretation of this information, nor
can it assume any liability in connection with its use.
The units are designed for permanent installation. The equipment is designed for domestic or office use and we are not making any
endorsements for use in industrial or maritime environment.
Do not place near sources of heat, vapors, industrial machine oil or other flammable gases.  High-frequency waves generated by radio equipment, welders and medical equipment will
interfere with the normal operation of the unit.
Install this device only when it complies with local/national legislation, ordinances and
standards.
Check the mains voltage and frequency. This unit is only suitable for an earthed electrical
supply, connection voltage 230 V~ / 50 Hz. The information, specifications and parameter are subject to change due to technical modifications or improvement without any prior notice. The accurate specifications are presented on the nameplate label.
Please read this installation manual completely before installing the product. When the power cord is damaged, replacement work shall be performed by authorized
personnel only.
Installation work must be performed in accordance with all European, national and / or local
directives and standards and must be done by authorized personnel only.
Always make sure to wear the correct personal safety protections such as protective
eyewear, gloves, ear protection etc.
Page 23
23
This air conditioner contains a refrigerant and can be classified as pressurized equipment.
Therefore always contact an authorized air conditioning engineer for installation and maintenance of the air conditioner.
The air conditioner must be inspected and serviced on an annual basis by an authorized air
conditioning engineer.
INDOOR UNIT POSITION
The air inlet and outlet vent should be away from any obstruction, ensuring that there is a good airflow through the whole air-conditioned space. Select a position where the condensing water can be easily drained out, and the indoor unit can be easily connected to outdoor unit. The wall
where the unit is fixed should be strong enough to withstand the full weight and vibration of the
unit. The unit should be accessible for service maintenance. The height of the installed unit should be ideally more than 200cm from the floor. The air conditioner must not be installed in a wet environment such as a bathroom, shower or swimming pool etc.
OUTDOOR UNIT POSITION A convenient position, dry and well ventilated, outside of direct sunlight or strong winds, which is
not on flood line and where noise and airflow does not cause interference or inconvenience. Select a location where there are no obstructions to the inlet and outlet vents. The location should be able to withstand the full weight and vibration of the outdoor unit and permit safe installation. Make sure that the outdoor unit is installed in compliance with the installation dimension diagram with easy maintenance access. Select a place where it is out of reach of children. Do not block utilities access or fire escapes.
The external unit must be lifted and put in place by two people.
NOTES:
1. Only use a power supply with the correct ratings, making sure the correct sized power cables
are used
2. The appliance shall be installed in accordance with standard wiring regulations by qualified
personnel
3. Only replace fuses according to their printed rating or corresponding pcb boards.
Page 24
24
RECOMMENDED INSTALLATION SPACING DIAGRAM
Page 25
25
TOOLS RECOMMENDED FOR INSTALLATION
Electric drill
Screwdrivers
Core hole
Cutter
Number 14 (7mm)
Masonry drill
1.5
inch number
10 screws
roundhead slotted
7
mm wallplugs
Pipe & cable detector
Hammer
Tape measure
Spirit Level
Pencil and chalk
Small stepladder
Protective glasses and mask 4
inch plastic ties
Page 26
26
Also the following
2
inch Pipe clips
Circuit breaker
Garden gloves when lifting the outdoor unit
Dustsheets
Foam Filler
Silicone sealant and gun
Page 27
27
. Check the area for any
1
hidden wires or pipes.
2
. Mark the right hand
backplate screw
position.
3
. Remove the backplate
and drill a 7mm hole.
4
. Tap home a 7mm
wallplug.
. Screw the backplate
5
to the wall using 1.5
inch number 10
screws.
6
. Check level, mark the
other holes and swing
the backplate away.
7
. Drill the rest of the
holes and tap in
wallplugs
8
. Fix the backplate to
the wall.
9
. Mark the hole centre
make sure the
cutter will clear the
backplate.
10
. Drill the hole at a slight
downward angle. When
you feel the pilot drill exit
the outside wall stop
11
. Finish the hole from
the outside to keep it
clean
12
. Feed the cord and
drain hose carefully
through the wall
Page 28
28
65
65
Page 29
29
The piping can be lead out on the right, left or directly behind the indoor unit as seen in fig. 1. Please cut off the pipe hole guards if you are changing the pipe position. The unit also features alternative guards for more pipe positioning.
Make sure that the drain pipe is underneath the pipelines. (Fig.3) (When the drain pipe passes the room interior, some condensed water might occur to its surfaces if the humidity is very high).
Tidy up the copper pipes, electrical cables and water drains and pass them through the wall hole drilled earlier (fig.2).
Hang the mounting slots of the indoor unit on the wall mounting bracket making sure is tight in place (fig.3) so that the hooks at the bottom of the indoor unit match the hooks of the wall mounting bracket (fig.4)
Notes:
1. The height of the installed unit is recommended to > 200 cm.
2.
Either the indoor unit or the outdoor unit can be higher, but the height difference must comply with a max. 5 metres level difference.
3. Try to avoid bending the pipes as much as possible so as to avoid possible negative impacts upon the performances of the unit.
INSTALLATION OF THE OUTDOOR UNIT
Try to move the product to the installation location in its original packaging As the gravity center of the unit is not at the installation center, special caution should be taken when using hoisting cables to lift it up During transport, the outdoor unit must not be tilted to over 45 degrees (also do not store the unit horizontally. Use expansion bolts to fix the mounting supports on the wall; Use bolts and nuts to fix the outdoor unit firmly on the supports and keep on the same level; If the unit is installed on the wall or at the rooftop, the supports have to be firmly fixed so as to resist earthquakes or strong wind. Dimensions for parallel units installations
300mm(1')min
Page 30
30
STANDARD PIPELINES CONNECTION & AIR PURGING
No dust or any other particles, air or moisture should be allowed to enter the air conditioning system. Careful attention should be paid when pipeline connection for outdoor unit is made. Try to avoid repeated curves as much as possible; otherwise damage to the copper pipes may occur. Suitable wrenches should be used when the pipeline connection is done so as to ensure appropriate torque (refer to following torque table). Excessive torque action might damage the joints while too little torque might lead to leakage.
Torque based upon the wrench to be used
AIR PURGING WITH VACUUM PUMP
1. Check that pipelines connection have been properly connected, remove the charging port cap, and connect the manifold gauge and the vacuum pump to the
charging valve by service hoses
as shown
2. Open the valve of the low-pressure side of manifold gauge, then run the vacuum pump. Vacuum the indoor unit and the connecting pipes until the pressure in them lowers to below 1.5mmHG (The operation time for vacuuming is about 10 minutes). When the desired vacuum is reached, close the valve of the low pressure of the manifold and stop the vacuum pump.
3. Disconnect the service hoses and fit the cap to the charging valve.
4. Remove the blank caps, and fully opens the spindles of the 2-way and 3-ways valves with a service valve wrench.
5. Tighten the blanking caps of the 2-way and 3-ways valves, applying the above torque Table
Copper pipe
diam.
Tightening torque
Strengthened tightening
torque
6.35(1/4")
160kgf.cm(63kgf.inch)
200kgf.cm(79kgf.inch)
9.52(3/8")
300kgf.cm(118kgf.inch)
350kgf.cm(138kgf.inch)
12.7(1/2")
500kgf.cm(197kgf.inch)
550kgf.cm(216kgf.inch)
750kgf.cm(295kgf.inch)
800kgf.cm(315kgf.inch)
Page 31
31
ADDING REFRIGERANT
Refrigerant must be added if the pipe length is more than 5 metres (16'5"). This operation can only be performed by a professional F-Gas engineer, for the additional gas amount, see the below
Liquid pipe diameter
Additional Refrigerant
Additional Refrigerant
Φ6.3 or Φ6 (1/4)
20g per each meter added
Total length of pipe run – 5 meters) x 20 g
Φ9.52 or Φ9 (3/8)
30g per each meter added
Total length of pipe run – 5 meters) x 30 g
GAS LEAKAGE INSPECTION
After the pipeline connection is done, use a leakage inspection device to carefully check if there is any leakage at the joints. This is an important step to ensure the quality of installation. Once a leak is detected, proper action should be taken immediately.
1. For good drainage, the drain hose should be angled downwards.
2. Do not pull on or bend the drain hose or flood its end with water.
3. When the long drainage hose passes through indoor areas, it should be wrapped in insulation.
Page 32
32
NOTES: The copper pipe used in the refrigeration lines are very soft, high pressure copper and prone to get damaged if not handled correctly. Try to avoid bending or stretching the pipework. Always use the pipe’s foam protectors and the plastic ring before putting the pipes through the wall. Those will help prevent damage to the pipes.
To keep the allowed bending radius please make the packed soft pipes vertical before extending
Please do not extend only one side of the packed soft pipes.
Please make use of semicircle pulley to keep the allowed bending angle
Extreme bending could damage the pipes
Please use a twisting wheel to avoid improper bending.
Over bent soft pipes will lead to irregular bending
Please use rigid elbow to keep the bending angle while soft pipes operating.
Undersize bending will damage the soft pipe.
Please kee p the minimum bending angle while installing
Do not use short sharp angle bends.
Page 33
33
ELECTRICAL WIRING DIAGRAMS
INDOOR UNIT
Iqool9/12/18:
Iqool24:
Page 34
34
OUTDOOR UNIT
Iqool9/12
Iqool18
Page 35
35
Iqool24
Page 36
36
TROUBLESHOOTING AND SELF DIAGNOSIS
MALFUNCTION
POSSIBLE CAUSE
The appliance does not operate
Power failure
Damaged indoor/outdoor unit fan motor
Faulty compressor thermomagnetic circuit breaker
Faulty protective device or fuses
Loose connections
Self protection in adverse conditions
Voltage higher / lower than the voltage range
Active TIMER-ON function
Damaged electronic control board
Strange odour
Air filter dirty
Noise of running water
Back flow of liquid in the refrigerant circulation
A fine mist comes from the air outlet
This occurs when the air in the room becomes very cold, for example in the COOLING or DEHUMIDIFYING modes.
A strange noise can be heard
This noise is made by the expansion or contraction of the front panel due to variations in temperature and does not indicate a problem.
Insufficient airflow, either hot or cold
Inappropriate temperature setting.
Air inlet or outlet of indoor or outdoor unit has been blocked.
Air filter is blocked.
Fan speed set at minimum.
Other sources of heat in the room.
No refrigerant.
The appliance does not respond to commands
Remote control is not near enough to indoor unit.
Battery in Remote controller may have been exhausted..
Obstacles between remote control and signal receiver in indoor unit.
The display is off
Active LED function
Power failure
Switch off the air conditioner immediately and cut off the power supply in the event of:
Strange noises during operation.
Faulty electronic control board
Faulty fuses or switches.
Spraying water or objects inside the appliance.
Overheated cables.
Very strong smells coming from the appliance.
Page 37
37
ERROR SIGNALS ON THE DISPLAY
In case of error, the display on the indoor unit shown the following error codes:
Error Code
Light flash code
Failure type
E0
Run & Timer – both blinking
Indoor and outdoor communication failure
EC
Run & Timer – both blinking
Outdoor communication failure
E1
Run – 1 flash every 8 seconds
Indoor room temperature sensor
E2
Run – 2 flashes every 8 seconds
Indoor coil temperature sensor
E3
Run – 3 flashes every 8 seconds
Outdoor coil temperature sensor
E4
Run – 4 flashes every 8 seconds
System abnormity
E5
Run – 5 flashes every 8 seconds
Model configuration wrong
E6
Run – 6 flashes every 8 seconds
Indoor fan motor fault
E7
Run – 7 flashes every 8 seconds
Outdoor temperature sensor
E8
Run – 8 flashes every 8 seconds
Exhaust temp. sensor
E9
Run – 9 flashes every 8 seconds
IPM drive and module fault
EF
Run – 10 flashes every 8 seconds
Outdoor fan motor fault (DC motor)
EA
Run – 11 flashes every 8 seconds
Current sensor fault
EE
Run – 12 flashes every 8 seconds
EEPROM fault
EP
Run – 13 flashes every 8 seconds
Temp. switch fault ( on top of the compressor)
EU
Run – 14 flashes every 8 seconds
Voltage sensor fault
Protection Display Code List
P1
Run and Timer – 1 flash every 8 seconds
Overvoltage /lower voltage protection
P2
Run and Timer – 2 flashes every 8 seconds
Overcurrent protection
P4
Run and Timer – 4 flashes every 8 seconds
Exhaust over temperature protection
P5
Run and Timer – 5 flashes every 8 seconds
Too cool protection in cooling mode
P6
Run and Timer – 6 flashes every 8 seconds
Overheat protection in cooling mode
P7
Run and Timer – 7 flashes every 8 seconds
Overheat protection in heating mode
P8
Run and Timer – 8 flashes every 8 seconds
Outdoor over temperature / lower temperature protection
P9
Run and Timer – 9 flashes every 8 seconds
Drive protection (software control )
P0
Run and Timer – 10 flashes every 8 seconds
Module protection (hardware control)
Page 38
38
OUTDOOR UNIT FAULT CODES
The outdoor unit has an LED on the power board. This LED will be illuminated when the compressor is running and blink 1s on and 1s off when the compressor is in standby. If there is a fault on the outdoor unit, it will blink on and off for half a second at a time, followed by a 3s gap. The number of consecutive blinks will show the fault as per the table below:
No. of blinks
Fault
1
IPM protection
2
Over voltage /lower voltage
3
Overcurrent
4
Exhaust over temperature protection
5
Outdoor coil over temperature protection
6
Drive fault and protection (V1VP1)
7
Communication fault with indoor unit
8
Compressor overheat fault (compressor top switch)
9
Short-circuit / open-circuit fault of outdoor temperature sensor
10
Short circuit / open-circuit fault of outdoor heat exchanger temperature sensor
11
Short-circuit / open-circuit fault of exhaust temperature sensor
12
Voltage sensor fault
13
Current sensor fault
14
IPM fault
15
Communication fault between power source board and IPM
16
No feedback from DC fan motor(outdoor unit)
17
Defrost state
Page 39
39
WIFI CONTROL TROUBLESHOOTING
Description
Possible Cause
Air conditioner
can’t be configured
successfully
1. Check the mobile device is connected to WIFI
2. Check the AC is connected
3. Check that any firewall or other restrictions are causing problems
4. Check the router is functioning normally
5. Check that the router isn’t blocking the App
Mobile device can’t
control the air conditioner
The app displays “Identification failed”. This indicates that the AC has
been reset and the mobile device has lost contact with the AC. Reconnect the device following the above instructions. If this fails, delete the AC from your devices list and start the install process from the beginning.
Mobile device can’t
find AC
The app displays “Air conditioner out of line”. Check the below:
1. The AC has been reconfigured
2. The AC is not receiving power
3. The router is not powered on
4. The AC can’t connect to router
5. The AC can’t connect to network through the router
6. The mobile device can’t connect to the router
7. The mobile device can’t connect to a network (when being used remotely)
TECHNICAL SPECIFICATION
Model
Iqool9 – v3
Iqool12 – v3
Iqool18 – v3
Iqool24 – v3
Rated voltage and frequency
(Ph-V-Hz)
1Ph/220-
240V~/50Hz
1Ph/220-
240V~/50Hz
1Ph/220-
240V~/50Hz
1Ph/220-
240V~/50Hz
Fuse Required
13A
13A
13A
16A
Mode
Cooling
Heating
Cooling
Heating
Cooling
Heating
Cooling
Heating
Rated capacity (W)
2520
(900
3200)
2570
(900
3200)
3230
(1000
3720)
3290
(1000
3830)
5120
(1310~
5730)
5230
(1330~
6540)
6810
(1500~
7310)
6850
(1500~
7530)
Power input (W)
740
(300
1265)
640
(230
1200)
1090
(320
1300)
1000
(320
1450)
1500
(500
2100)
1500
(500
2350)
1940
(350~
2800)
1988
(300~
3200)
Current input (A)
4.3(1.3~
5.5)
3.2(1.3~
6.4)
5.2(1.4 6.5)
4.6(1.4 5.9)
6.7(2.3~
9.6)
6.7(2.3~
10.8)
8.5(1.7~
13.5)
8.7(1.5 ~15.5)
SEER/SCOP(W/W)
6.1/A++
4.0/A+
6.1/A++
4.0/A+
6.3/A++
4.0/A+
6.3/A++
4.0/A+
Nominal load (kW)
2.52
2.57
3.23
3.29
5.12
5.23
6.81
6.85
Balance point temperature
heating (oC)
/
-7 / -7 / -7 / -7
Min. outdoor operating
temperature (oC)
/
-15 / -15 / -15 / -15
Thermostat-off mode (W)
35
35
51
42.5
Standby mode (W)
4 4 2
6.76
Off mode (W)
0 0 0
0
Page 40
40
Annual consumption (kW)
143
875
184
980
270
1785
378
2100
Copper Pipe Type length
5m
5m
5m
5m
Liquid side / Gas side
(mm/inch)
6.35 (1/4) + 9.52 (3/8)
6.35 (1/4) + 9.52 (3/8)
6.35 (1/4) + 12.7 (1/2)
6.35 (1/4) + 15.88 (5/8)
Max. refrigerant pipe length
25m
25m
25m
25m
Max. elevation
10m
10m
10m
10m
Interconnecting Cable
4×1.0mm²
4×1.0mm²
4×1.5mm²
4×1.5mm²
Fuse Rating
3.15A on indoor PCB
3.15A on indoor PCB
3.15A on indoor PCB
3.15A on indoor PCB
Moisture Removal (L/h)
0.8 1 1.2
2.4
Indoor
Air Flow (m3/h)
550
550
800/815
1000/1100
Dimensions (L*W*H)
(mm)
777×250×205
777×250×205
910×292×205
1010×315×220
Packaging (L*W*H
(mm)
848×318×277
848×318×277
977×370×275
1094×386×300
Net / Gross weight
(Kg)
8.5/10.5
8.5/10.5
10/13
13/16
Noise – Sound
pressure level
(dB/A)
19~40
19~40
27~43
30~44
Noise – Sound
power level (dB/A)
29~50
29~50
37~53
40~54
Outdoor
Dimension (L*W*H)
(mm)
700×552×256
700×552×256
780×605×290
902×650×307
Packaging (L*W*H)
(mm)
803×585×325
803×585×325
883×653×412
1015×720×425
Net / Gross Weight
(Kg)
24/27
25/28
37/41
50/56
Noise – Sound
pressure level
(dB/A)
50
50
55
58
Noise – Sound
power level (dB/A)
60
60
65
68
Refrigerant type/weight
R410A/650g
R410A/780g
R410A/1350g
R410A/2000g
Defrost mode
Automatic defrosting
Automatic defrosting
Automatic defrosting
Automatic defrosting
Applicable climate
types
Cooling (0oC –
53oC)
Heating(0oC –
30oC)
Cooling (0oC –
53oC)
Heating(0oC –
30oC)
Cooling (0oC –
53oC)
Heating(0oC –
30oC)
Cooling (0oC –
53oC)
Heating(0oC –
30oC)
Due to continuous product development process specification may change.
These units contain a gas governed by F-Gas regulations. The gas must be handled by
qualified F-Gas engineers.
Page 41
41
APPENDIX
Disposal: Do not dispose this product as unsorted municipal waste. Collection of such waste must be handled separately as special treatment is necessary. Recycling facilities are now available for all customers at which you can deposit your
old electrical products. Customers will be able to take any old electrical equipment to
participating sites run by their local councils. Please remember that this equipment will be further handled during the recycling process, so please be considerate when depositing your equipment. Please contact the local council for details of your local household waste recycling centres.
WARRANTY INFORMATION
TCL guarantee provides cover against material or manufacturing faults.
This means that if your air conditioner develops a fault during the guarantee period, we will arrange for it to be repaired or replaced.
Faults arising from a faulty installation are specifically excluded. The system must be serviced annually by qualified personnel. This unit must be operated under conditions as recommended in this user
manual, at voltages indicated on the unit. Any attempts made to service or modify the unit by unqualified person, will render this WARRANTY VOID. This warranty is in addition to, and does not affect, your statutory rights. Our warranty is RTB warranty and cover parts and labour only.
We recommend that you note the details of your purchase below and retain your original proof of purchase receipt with this manual. Keep these documents safe in the event of a warranty claim.
Purchase Date: _____________________________
Retailer name: _____________________________
Model number: _____________________________
Serial number: _____________________________
Installation Date: _____________________________ Installer name: _____________________________ Service Date: _____________________________ Engineer/ Company name: _____________________________
Page 42
42
TCL UK SUPPORT
Please, for your own convenience, check the troubleshooting guide before calling the service line.
If the unit still fails to operate call: 0871 620 1057 or complete the online form
Office hours: 9AM - 5PM Monday to Friday
TCL AIR CONDITIONING
Unit J6, Lowfields Business Park
Lowfields Way, Elland
West Yorkshire, HX5 9DA
Loading...