SHEET 1 OF 1
SCALE
DATE
DWG. No.
APRVD.
DRN. BY
TOLERANCES
(EXCEPT AS NOTED)
DECIMAL
.XX +/- .25
.XXX +/- .1
FRACTIONAL
+/- 1/16
ANGULAR
+/- 1
NO REVISION
DATE BY
DSW
12/17/14
1/4
1
1
2
2
3
3
4
4
A A
B B
C C
D D
105795DG
CUSTOMER IS RESPONSIBLE FOR INSTALLATION
TO MEET ALL NATIONAL AND LOCAL ELECTRICAL CODES.
0.44 DIA HOLES
4 PLACES.
KTRMG
CAPACITORS
MSD PART NUMBER HP VOLTAGE CURRENT WEIGHT
MSD0023A300 15 480V 23 AMPS 75LBS
MSD0030A300 20 480V 30 AMPS 75LBS
MSD0035A300 25 480V 35 AMPS 75LBS
MSD0045A300 30 480V 45 AMPS 90LBS
MSD 23 AMPS TO 45 AMPS
MotorShield Sinewave Filter
480/3/60, Type 1/ 3R.
FROM
INVERTER
U
V
W
THERMAL SWITCH
CONNECTIONS
KTRMG
CAP.
TS1
TS2
KTRMG
REACTOR
T1
T2
T3
TO
LOAD
CAPACITORS
(TYP.)
THERMAL SWITCH
(ON CAPACITOR)
RESISTOR
BLEEDERS
THERMAL SWITCH
(KTRMG REACTOR)
W
V
U
A1
B1
C1
C2
B2
A2
T1
T2
T3
NOTE: FOR WIRE RANGE AND
TORQUE INFORMATION
SEE IOM MANUAL.
GROUND LUG
MSD
SCHEMATIC
GRD
CUSTOMER
CONNECTIONS
TERMINAL BLOCK GROUND LUG
WIRE RANGE: 1-22AWG WIRE RANGE: 1/0 -14AWG
WIRE RANGE: 1-22AWG WIRE RANGE: 1/0 -14AWG
WIRE RANGE: 1-22AWG WIRE RANGE: 1/0 -14AWG
WIRE RANGE: 1-22AWG WIRE RANGE: 1/0 -14AWG
CUSTOMER
CONNECTIONS
USE COPPER WIRE.
90 C MIN
C
3302 CAPS MOVED TO FRONT
5/6/2015
DSW
C
3302 Bleeder wiring chg on Schematic
D
3308 ADD CUSTOMER ENTRANCE
5/19/15
DSW
E
3364, 75°C TO 90°C MIN
6/30/2015DSW
DSW9/4/2015
F
3345 ENCLOSURE UPDATED
19.50
15.50
19.13
13.65
10.00
0.75 13.65
15.15
2.57 10.00
15.15
3696 ADD DISCHARGE LABEL
G
7/29/16 DSW
W132 N10611 Grant Drive
Germantown, WI 53022
®