TCI MSD0023A300, MSD0030A300, MSD0035A300, MSD0045A300 Dimensional Sheet

SHEET 1 OF 1
SCALE
DATE
DWG. No.
APRVD.
DRN. BY
TOLERANCES
DECIMAL
.XX +/- .25 .XXX +/- .1
FRACTIONAL
+/- 1/16
ANGULAR
+/- 1
NO REVISION
DATE BY
DSW
12/17/14
1/4
1
1
2
2
3
3
4
4
A A
B B
C C
D D
105795DG
CUSTOMER IS RESPONSIBLE FOR INSTALLATION TO MEET ALL NATIONAL AND LOCAL ELECTRICAL CODES.
0.44 DIA HOLES 4 PLACES.
KTRMG
CAPACITORS
MSD PART NUMBER HP VOLTAGE CURRENT WEIGHT
MSD0023A300 15 480V 23 AMPS 75LBS MSD0030A300 20 480V 30 AMPS 75LBS MSD0035A300 25 480V 35 AMPS 75LBS MSD0045A300 30 480V 45 AMPS 90LBS
MSD 23 AMPS TO 45 AMPS
MotorShield Sinewave Filter
480/3/60, Type 1/ 3R.
FROM INVERTER
U
V
W
THERMAL SWITCH CONNECTIONS
KTRMG
CAP.
TS1
TS2
KTRMG
REACTOR
T1 T2
T3
TO
LOAD
CAPACITORS (TYP.)
THERMAL SWITCH (ON CAPACITOR)
RESISTOR BLEEDERS
THERMAL SWITCH
(KTRMG REACTOR)
W
V
U
A1
B1 C1
C2
B2
A2
T1
T2
T3
NOTE: FOR WIRE RANGE AND
TORQUE INFORMATION SEE IOM MANUAL.
GROUND LUG
MSD SCHEMATIC
GRD
CUSTOMER CONNECTIONS
TERMINAL BLOCK GROUND LUG WIRE RANGE: 1-22AWG WIRE RANGE: 1/0 -14AWG WIRE RANGE: 1-22AWG WIRE RANGE: 1/0 -14AWG WIRE RANGE: 1-22AWG WIRE RANGE: 1/0 -14AWG WIRE RANGE: 1-22AWG WIRE RANGE: 1/0 -14AWG
CUSTOMER CONNECTIONS
USE COPPER WIRE.
90 C MIN
C
3302 CAPS MOVED TO FRONT
5/6/2015
DSW
C
3302 Bleeder wiring chg on Schematic
D
3308 ADD CUSTOMER ENTRANCE
5/19/15
DSW
E
3364, 75°C TO 90°C MIN
6/30/2015DSW
DSW9/4/2015
F
3345 ENCLOSURE UPDATED
19.50
15.50
19.13
13.65
10.00
0.75 13.65
15.15
2.57 10.00
15.15
3696 ADD DISCHARGE LABEL
G
7/29/16 DSW
W132 N10611 Grant Drive Germantown, WI 53022
®
Loading...