TCI KLCUL User Manual

Warnings and Cautions
Field Wiring
Warning
Warning
!
Dangerous Voltage Warning: warns of situations in which a high voltage can cause injury and/or equipment damage. e text next to this symbol describes ways to avoid danger.
General Warning: warns of situations that can cause physical injury and/ or equipment damage by means other than electrical. e text next to this symbol describes ways to avoid the danger.
General Safety Instructions
Warning
Be sure to read, understand, and follow all safety instructions.
!
Warning
Only qualied electricians should carry out all electrical installation and
!
Warning
!
maintenance work on output lter.
All wiring must be in accordance with the National Electrical Code (NEC) and/or any other codes that apply to the installation site.
KLCUL Field Wiring Connection Terminals Compression type terminals are provided for all line wiring connections. e wire size capacity ranges and tightening torque for the power terminals are listed in the table.
KLCUL Model
Numbers
KLCUL2A to KLCUL12A
KLCUL16A to KLCUL55A
KLCUL80A 1 - 22 35
KLCUL110A to KLCUL130A
KLCUL160A to KLCUL200A
KLCUL250A to KLCUL300A
KLCUL360A Two: 350 MCM - 4 275
KLCUL420A to KLCUL600A
KLCUL750A
Input and Output Motor Power
Wire Size
12 - 18 10
4 - 18 20
2/0 - 6 120
250 MCM - 6 275
600 MCM - 4
Two: 250 MCM - 1/0
Two: 600 MCM - 2 500
Two: 800 MCM - 300
MCM
Torq u e
(in. - lb.)
500
500
KLC/KLCUL
Installation
Guide
Warning
Warning
Warning
Disconnect all power before working on the equipment. Do not attempt any work on a powered output lter.
e KLC, VFD, motor, and other connected equipment must be properly grounded.
e VFD terminals and connected cables are at a dangerously high voltage when power is applied to the VFD, regardless of motor operation.
See www.transcoil.com for dimension tables
Please contact TCI Technical Support or your TCI distributor for application information regarding the use of KLC output lters on the output side of the VFD.
TCI, LLC
W132 N10611 Grant Drive
Germantown, WI 53022
Ph: 800-TCI-8282
www.transcoil.com
TCI, LLC
W132 N10611 Grant Drive
Germantown, WI 53022
Ph: 800-TCI-8282
www.transcoil.com
KLC/KLCUL Output Filter
Installation Instruction
Installation Checklist
• Make sure that the installation location will not be exposed
to direct sunlight, rain or dripping liquids, corrosive liquids
or gases, explosive or combustible gases or dust, excessive
airborne dirt and dust, or excessive vibration.
• Select a mounting area that will allow adequate cooling air
and maintenance access.
• Make sure that all wiring conforms to the requirements of
the National Electric Code (NEC) and/or other applicable
electrical codes.
• Ground the KLC Output Filter to a dedicated system
ground to ensure safety and lter performance. Use a
properly sized grounding conductor.
• Wire the output power terminals of the VFD, T1(U), T2(V),
& T3(W) to the input terminals of the KLC lters L1, L2,
and L3.
• Wire the output power terminals, of the KLC, T1, T2, & T3
to the motor power connections.
• Make sure the VFD is set for operating modes and ranges
that are compatible with the KLC Output Filter.
• Check the entire system thoroughly before energizing and
operating any equipment.
When you receive the unit, you should immediately inspect
the shipping container and report any damage to the
shipping carrier who delivered the unit.
Verify the Application
Make sure the KLC output lter is correct for the application.
e current ratings of the KLC should be sized to handle
the FLA rating of the motor but not to exceed 110% of the
drive output current rating. is output lter is best applied
matched closely to the load. e KLC output lter is not
selected by the drive input current rating.
Vari a bl e Frequency Drive Settings
Make sure that the variable frequency drive will be set for
operation modes and ranges that are compatible with the
KLC output lter:
• Maximum output frequency: 60 Hz
• PWM switching frequency best between 2kHz and 4kHz
• Mode of operation: Do not use with DC braking unless
the drive application has been conrmed by TCI
Technical Support.
• Do not use on overhauling loads without bus voltage control.
Mounting an open style unit
If you are mounting an open style unit in your own
enclosure, you must provide an enclosure that is adequately
sized and ventilated suciently to prevent overheating. e
lter is designed with a maximum ambient temperature of
40°C (104°F). If the ambient temperature exceeds this value
it is the responsibility of the customer to provide auxiliary
cooling to reduce the ambient operating temperature
around the KLC lter. TCI strongly recommends using
auxiliary cooling devices such as cooling fans, heat
exchangers, or possibly air conditioning units when
required to maintain the proper operating temperature.
Position the KLC lter to be as close as possible (No greater
than 20 .) from the drive output terminals. e KLC must
be mounted so that the included line reactor is positioned
vertically. Mounting it vertically is important for natural
convection cooling.
Power Wiring
e conduit and wiring from the output of the variable
frequency drive to the motor must be routed to the KLC
and then to the motor. TCI recommends a separate
dedicated conduit run for each drive/lter/motor run
unless properly shielded and segregated wiring procedures
are practiced. Parasitic and induced capacitance can greatly
reduce the eectiveness of the lter performance. Under
no circumstances should you wire both control and power
wire in the same conduit unless the wire way is specically
designed for this practice. e unit temperature is
sensitive to lead wire oversizing. Avoid lead wires more
than ve times oversized by copper cross sectional area
and operating current, regardless of the material used. Use
75°C copper conductors only or the equivalent, unless
the wire connector is marked for Al/Cu, then the use of
aluminum wire is permitted. Use copper conductor only
on units rated above 80 amps.
Wiring Cable Entry Locations
TCI has not provided knock-outs due to the wide variety of application requirements. TCI allows installing electricians the option of locating the cable openings at a point of their choosing.
Grounding
e KLC lter must be connected to the ground of the premises wiring system. is can be conducted by identifying a known premises ground near by the lter or running a special ground dedicated for this application. e ground connection must be made using a wire conductor. Metallic conduit is not a suitable grounding conductor. e integrity of all ground connections should be periodically checked.
Wiring Diagram
L
A1
B1
C1
R
L
R
L
R
C CC
RRR
A2
B2
C2
Product Specications
Current Rating: 2 - 750 Amps UL and cUL Listed
Open, UL Type 1 and UL Type 3R
Enclosures
Eciency > 98%
Insulation Rating: 600V Class Insulation Class: Class H (180°C or better) Altitude (Maximum): 1000m Lead Length: 3000 . (specic applications,
consult TCI Tech Support over 1000 .)
Operating Temp: 40°C Ambient
Loading...