TCi HarmonicGuard HGP, HarmonicGuard Series Installation, Operation And Maintenance Manual

Page 1
Harmoni
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
cGuard
®
Series Drive-Applied Harmonic Filter

Installation, Operation, and Maintenance Manual

Page 2
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
No pa by any means, mechanical, electr onic, photocopying, recording, or o therwise, without the prior written permissio n of TCI, LLC. The infor mation in this manual is sub ject to change without notice. Every precautio n has been taken in the preparation of this manual. TCI, LLC assumes no responsibility for errors or omissions. Neither is any liab ility assumed for damages resulting from the use of the information contained in this publication.
Page 3

T able of Contents

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Introduction .............................................................................................................................. 5
Receiving Inspection and Storage ............................................................................................ 7
Pre-installation Planning .......................................................................................................... 8
Installation Guidelines ............................................................................................................. 9
HGP Filter Operation ............................................................................................................. 10
Installation ............................................................................................................................. 11
Maintenance and Service ....................................................................................................... 12
Product Description ............................................................................................................... 14
Standard Option (S) ............................................................................................................... 17
Contactor Option (C) ............................................................................................................. 18
Fuse Monitor with Contactor Option (F).............................................................................. 19
Fuse Monitor without Contactor Option (G) ....................................................................... 20
CP Kit Enclosure (8) with Option (0) .................................................................................... 21
Line Reactor Installation ........................................................................................................ 22
Typical Voltage Distortion Option (0) .................................................................................. 23
High Voltage Distortion Option (1) ....................................................................................... 24
Page 4
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Page 5

Introduction

an electrostatic discharge can damage equipment. The text next
!
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com

Safety Instruc tions Over vie w

This section provides the safety instructions which must b e followed when installing, oper ating, and servicing t he HarmonicGuard Passive (HGP) filter. If negle cted, physical injur y or death may follo w, or damage may occur to the filter or equipment connected to the HGP filter. The material in this chapter must be read and understood before attempting any work on, or with, the product.
The HGP filter is intended to be connected to the input terminals o f one or more VFDs. Thr ee-phase power is connected to the input terminals of the HGP and power is supplied to the VFD or VFDs through the HGP. T he instr uctio ns, and particu larly t he saf ety inst ructio ns, for t he VFDs, motors, and any other related equipment must be read, understood, and followed when working on any of the equipment.

Warnings and Cautions

This manual provides two types of safety instructions. Warnings are used to call attention to instructions that describe step s that must be taken to avoid conditions that can lead to a serious fault condition, physical injury, or death.
Cautions are used to call attention to instructions that describe steps that must be taken to avoid conditions that can lead to a malfunction and possible equipment damage.

Warnings

Readers are informed of situations that can result in serious physical injury and/or serious damage to equipment with warning statements highlighted by the following s ymbo ls:
Warning
Warning
Warning
Dangerous Voltage Warning: warns of situatio ns where high voltage can cause physical injur y and/or damage equipment. The text next to this symbol describes ways to avoid the danger.
General Warning: warns of situations that can cause physical injury and/ or damage equipment by means other than electrical. The text next to this symbol describes ways to avoid the danger.
Electrostatic Discharge Warning: warns of situations in which
to this symbol describes ways to avoid the danger.

Cautions

Readers are informed of situations that can lead to a malfunction and possible equipment damage with caution statements:
Caution
General Caution: identifies situatio ns that can lead to a malfunction and possible equipment damage. The text describes ways to avoid the situation.
Page 6

General S afety Ins truct ions

!
!
!
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
These safety instructions are intended for all work on the HGP. Additional safety instructions are provided at appropriate points on other sections of this manual.
Warning
Warning
Warning
Warning
Warning
Warning
Be sure to read, understand, and follow all safety instructions.
Only qualified electricians should carry out all electrical installation and maintenance work on the HGP filter.
All wiring must be in accordance with the National Electrical Code (NEC) and/or any other codes that apply to the installation site.
Disconnect all power before working on the equipment. Do not attempt any work on a powered HGP filter.
The HGP filter, drive, motor, a nd other connected equipment must be properly grounded.
After switching off the power, always allow 5 minutes for the capacitors in the HGP filter and in the drive to discharge before working on the HGP, the drive, the motor, or the connecting wiring. It is a good idea to check with a voltmeter to make sure that all sources of power have been disconnected and that all capacitors have discharged before beginning work.
Page 7

Receivi ng Inspection and Storage

Product Family
Warranty Period
KLR, KDR
For the life of the drive with which they are installed.
One (1) year of useful service,
HGP, HG7, KH, 3H, KRF
Three (3) years from the d ate of shipment.
KCAP, KTR, KMP
Five (5) years from the date of shipment.
One (1) year of useful service,
not to exceed 18 months from the date of shipment.
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Thank you fo r select ing the H armonicGuard Passive (HGP) filter. TCI has produced this filter for use in many variable frequency drive (VFD) app lications that require input power line harmonic current reduction. This manual describes how to install, operate and maintain the HGP filter.

Receiving Inspection

The HGP filter has been thoroughly inspected and functionally tested at the factory and carefully packaged for shipment. When you receive the unit, you should immediately inspect the shipping container and report any damage to the carrier that delivered the unit. Verify that the part number of the unit you received is the same as the part number listed on your purchase order.

TCI Limited Warranty Policy

TCI, LLC (“TCI”) warrants to the original purch aser only that its produ cts will be free from defects i n materials and workmanship under normal use and service for a period originating on the date of shipment from TCI and expiring at the end of the period described below:
KLC, KLCUL, KMG,
V1k
All Other Products
The foregoing limited warranty is TCI’s sole warranty with respect to its products and TCI makes no other warranty, representation, or promise as to the quality or performance of TCI’s products. THIS EXPRESS LIMITED WARRANTY IS GIVEN IN LIEU OF AND EXC LUDES ANY AND ALL EXPRESS OR IMP LIED WARRANTIES INCLUDING, WITHOUT LIMITATION, ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.
This warranty shall not apply if the product was: a) altered or repaired b y anyone other than TCI;
b) applied or used for situations other than those originally specified; or c) subjected to negligence, accident, or damage by circumstances beyond TCI’s control, including but not
limited to, improper storage, installation, operation, or maintenance.
If, within the warranty period, any product shall be found in TCI’s reasonable judgment to be defective, TCI’s liability and the Buyer’s exclusive remedy under this warranty is expressly limited, at TCI’s option, to (i) repair or replacement of that product, or (ii) return of the product and refund of the purchase price. Such remedy shall be Buyer’s sole and exclusive remedy. TCI SHALL NOT, IN ANY EVENT, BE LIABLE FOR INCIDENTAL DAMAGES OR FOR CONSEQUENTIAL DAMAGES INCLUDING, BUT NOT LIMITED TO, LOSS OF INCOME, LOSS OF TIME, LOST SALES, INJURY TO PERSONAL PROPERTY, LIABILITY BUYER INCURS WITH RESPECT TO ANY OTHER PERSON, LOSS OF USE OF THE PRODUCT OR FOR ANY OTHER TYPE OR FORM OF CONSEQUENTIAL DAMAGE OR ECONOMI C LOSS .
The foregoing warranties do not cover reimbursement for removal, transportation, reinstallation, or any other expenses that may be incurred in connection with the repair or replacement of the TCI product.
The employees and sales agents of TCI are not authorized to make additional warranties about TCI’s products. TCI’s employees and sal es agents oral statement s do not constitute warrant ies, these shall not be relied upon by the Buyer, and are no t part of any contract for sale. All warranties of TCI embodied in this writing and no other warranties are given beyond those set forth herein.
TCI will not accept the return of any product without its prior written approval. Please consult TCI Customer Service for instructions on the Retur n Aut h or i z a ti o n Pr oc e dur e .
not to exceed 18 months from the date of shipment.

Storage Instructions

If the HGP filter is to be stored before use, be sure that it is stored in a location that conforms to published storage humidity a nd temperature specifications stated in Table 2 (HarmonicGuard Passive Filter Technical Specifications). Store the unit in its original packaging.
Page 8

Pre-installation Planning

!
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com

Verify th e A pplicat ion

HGP Ratings
Make sure that the HGP filter is correct for the application. The volta ge ratings of the filter must matc h the input voltage rating of the connected drive. The horsepower and current ratings of the filter must be appropriate for the connected load.

Select a Suitable Location

Environment
Locating the HGP in a suitable environment will help ensure proper performance and a normal operating life. Refer to the environmental specifications listed in Table 2, marked on the unit's nameplate, and/or noted on the drawings furnished with the unit.
Warning
The unit must be installed in an area where it will not be exposed to:
Direct sunlightRain or dripping liquids (unless filter is in a Type 3R enclosure) Corrosive liquids or gassesExplosive or combustible gases or dust Excessive airborne dirt and dustExcessive vibration
Unless specifically labeled as approved for such use, this equipment is not suitable for use in an explosive atmosphere or in a "Hazardous (Classified) Location" as defined in article 500 of the National Electrical code.
Working Space
Provide sufficient access and working space around the unit to permit ready and safe installation, operation and maintenance. Make sure that the installation conforms to all working space and clearance requirements of the National Electrical Code (NEC) and/or any other applicable codes. Provide sufficient unobstructed space to allow cooling air to flow through the unit.

Mounting an Open Panel Unit

If you are moun ting an open p anel unit in your own enclosure , you must provide an enclosure that is adequately sized and ventilated sufficiently to pre vent overheating. The ratin g and dimension tables for open panel units list the watts of heat loss dissipated by the HGP filter. The maximum temperature of the air around the HGP filter capacitors, line reactor, and tuning reactor should not exceed 50°C (122°F).

Power Wiring

When selecting a mounting location for the HGP f ilte r, plan for the routing of the po wer wiring. Route the conduit and wiring from the power source to the filter and the n to the VFD. The HGP is provided wit h i nternal fuses.
Page 9

Installa tion Guidelines

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com

Mounting

The HGP must be mounted vertically on a smooth, solid surface, free from heat, dampness, and condensation.

Wiring

Cable Entry Locations
The enclosed HGP filters are not provided with enclosure wir ing kno c ko ut s. A lo ca tio n c a n b e se le ct ed at the time of installation. Typical or recommended cable entry locations are shown in the drawings section of t his manual.
Field Wiring Connection Terminals
Compression type terminals are provided for all field wiring connections. The wire size capacity ranges and tightening torques for all field wiring connections are listed in the drawings and other information shipped with the unit.
Grounding
The HGP pane l equipme nt-groundi ng lug mu st be conne cted to the ground of the wir ing s ystem. The equipment-grounding connection must conform to the requirements of the National Electric Code (NEC) and/or any other codes that apply to the installation site. The ground connection must be made using a wire conductor . Metallic conduit is not a suit able grounding cond uctor. The integrity of all ground connections should be periodically checked.
Power Wiring
Caution
Connect three-phase power of the appropriate voltage and current capacity to the circuit protective device to the HGP input power terminals.
Note: in large units, the input power conductors are connected directly to the input terminals on the line reactors.
Connect the output terminals of the HGP to the input power terminals of the VFD.
Use copper wire that is appropriate for the voltage and current rating of the equipment. The wire selection must conform to the requirements of the National Electrical Code and/or other applicable electrical codes.
For units rated less than 100 amps, use wire with an insulation temperature rating of 60°C or higher.
For units rated 100 amps or more, use wire with an insulation temperature rating of 75°C or higher.
Note: in large units, the output po wer conductors are co nnected dir ectly to the output ter minals on the line reactors. Refer to the VFD installation instructions for additional information.
Page 10

HGP Filt er Operation

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Caution
Thoroughly check the installation before ap plying power and oper ating the equipment for the first time.

Before Applying Power for the Fir st Time

Inspect the installation to make sure that all equipment has been completely and correctly installed in accordance with the Installation Guidelines section of this manual.
Check to see that the cooling fan(s) a re operating in units so equipped .Check to make sure power connections are torqued to recommended torque value.

Operation

Since the HGP is a passive filter, it is always operating whenever the drive is operating.
Page 11

Installation

filter. Be sure to
Make sure that the installation lo c a tion will not be exposed to direct sunligh t, c orrosive or
Select a mounting area that will allow adequate cooling air and maintenance access.
Make sure that all wiring conforms to the requirements of the National Electric Code (NEC)
Connect the HGP equipment-grounding lug to the syst em ground o f the premises wiring system.
Connect three-phase power to the input terminals of the HGP, L1, L2 & L3.
Connect the output power terminals, of the HGP, T1, T2 & T3, to the input power terminals of
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com

Intended Audience

This manual is intended for use by all personnel responsible for the installation, operation and maintenance of the HGP filte rs. Such personnel are expected to have knowledge of electrical wiring practices, electronic components and electrical schematic symbols.

Additional Information

Caution
This manual pro vid es gene ra l in fo r mati o n desc ri b i ng your HGP carefully review the more specific information that is provided by the drawings shipped with the unit. Information provided by the drawings takes precedence over the information provided in this manual.
The ratings, dimensions and weigh ts given in this manual ar e appro xi mate and should not be used for any purpose requiring exact data. Contact the factory in situations where certified data is r e quired. All data is subject to change wit ho ut notice.

Installation Checklist

The following are the key points to be followed for a successful installation. These points are explained in detail in the following sections of this manual.
combustible airborne contaminants, excessive dirt or liquids.
and/or other applicable electrical codes.
Use a properly sized grounding conductor.
the VFD.
Page 12

Maintenance a nd Service

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com

HGP Filte r Re liabil ity and Servic e Life

The HGP has been designed to provide a service life that equals or exceeds the life of the VFD. It has been thoroughly tested at the factory to assure that it will perfor m reliably from the time it is put into service. It is recommended that the fo llowing maintena nce be done once a year to ensure t hat the HGP filter will always perform reliably and provide the expected service life.

Periodic Maintenance

Warning
Check to see that the installation environment remains free from exposure to excessive dirt and contamina nts. Refer to the Pre-installation P lanning section of this manual.
Check to make sure that the enclosure ventilation openings are clean and unobstructed. Clean the air filter in units that have filtered a ir inlets. Clean as often as necessary to prevent d irt build-
up from impeding air flow. Check the o peration of t he cooling fan. Inspect the interior of the enclosure for signs of overheated components. Clean the interior of the
enclosure whenever excess dirt has accumulated.
Only qualified electricians should carry out all electrical installatio n and maintenance work on the HGP filter.
Disconnect all sources of power to the drive and HGP before working on the equipment. Do not attempt any work on a powered HGP.
Torque all power wire connections, loose connections can overheat and damage the filter.

Troubleshooting

Warning
Note: when disconnecting wires from components and terminations, mark the wires to correspond to their component and terminal connection.
Only qualified electricians should carry out all electrical installatio n and maintenance work on the HGP filter.
Disconnect all sources of power to the drive and HGP before working on the equipment. Do not attempt any work on a powered HGP filter.
The harmonic filter contains high voltages and capacitors. Wait a t least five minutes after disconnecting p ower from the filter before you attempt to service the harmonic filter. Check for zero voltage between all terminals on the capacitors. Also, check for zero voltage between all phases of the line side of the fuses, Fu1(a)–Fu2(a)–Fu3(a), and all input terminals L1, L2 and L3 of the line reactor (KDR). All setup, maintenance, and troubleshooting must be done by a qualified electrician. Failure to follow standard safety procedures may result in death or serious injury.
Page 13

Replacement Parts

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
If replacement parts are needed, please contact your TCI representative. To ensure that the HGP filter continues to perform to its original specifications, replacement parts should conform to TCI specifications.

Factory Contacts and Tech Suppor t

For technical support, contact your local TCI distributor or sales representative. You can contact TCI directly at 800-TCI-8282. Select "Customer Service" or "Tech Support" a nd ha ve
your HGP filter nameplate informatio n available.
Page 14

Product Descript ion

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com

HGP Drive-Applied Filter

The HGP is a drive-applied harmonic filter designed and developed by TCI to reduce the harmonic currents drawn from the power source by VFDs. It is suitable for use with 3-phase diode bridge rectifier loads such as PWM AC drives. SCR or th yristor loads such as DC drives would require a different filter configuration outside the scope of this product offering. Please contact TCI Technical Support for additional information.
The HGP is a passive filter connected in series with the input terminals of a VFD or several VFDs that operate as a group. It is designed to provide a low impedance path for t he major harmonic currents demanded by the drive. The filter is a stand-alone device tha t can be f urnis hed in its own enclosure and mounted adjacent to the drive. It is also availabl e on an o pen pane l for mount ing wit hin an e nclosure with the dri ve or other e quipment.
The HGP filters consi st minimally of the following features and components :
A KDR tuned series reactor to prevent system interaction and improve filter performance An L-C-L filter circuit with:
A TCI 3-phase tuning reactor specifically designed for the HGP filter High-endurance, harmonic-rated capacitors
Bleeder resistors to ensure safe capacitor discharge upon filter shu tdown Cooling fans (on select models) to ensure adequate cooling and safe operating
temperatures
Compression terminals for ease and integrity of all power and control wiringFuses, sized to protect the capacitor wiring
Nameplate Data
The following informati on is marked on the nameplate:
Part number: encoding is explained on the following page
FLA: the rate d continuous operating current (RMS amps)
System Voltage: the rated 3-phase line voltage (RMS volts)
Hz: the rated frequency (60 Hz)
Phase: 3 – The HGP filter is designed for use only with 3-phase power.
Drawing #: outline and mounting dimension drawing number
Schematic #: schematic diagram drawing number
Manufacturing #: for TCI internal use
Enclosure Type: UL designation or "Open" panel construction
Page 15
F
G
Option:
0
- St andard
0
- St andard
Option:
0
- Typic al V ol tage Dist ort i on
Option:
1
- High Vol t age Di st ort i on
0
0
Option:
0
- St andard
Option:
- Fus e M oni t or with Cont act or
- Fus e M oni t or without Cont act or
W
- 60 Hz
Enclosure:
0
- Open
Frequency:
Horse P ower:
Vol t age Rat i ng:
A - 480 V
000
Series:
AW1SP150G
H
1
- Type 1
C
- Contac tor
S
- St andard
3
- Type 3R
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com

Part Number Encoding

Figure identifies the significance of each character in the HGP part number. The example part number, HGP0150AW1S0000 designates an HGP filter that is rated 150 HP, 480 volts, 6 0 Hz . I t incl ud e s a line reactor, tuni ng reac tor, and capacitors in a UL Type 1 enclosure. It is designed for use with a 150 HP drive.

Figure 1 – HGP Par t Number Enc oding

Page 16

Product Technical Specifications

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Table 1 lists the major technical sp0ecifications for the HGP Filter.

Table 1 – HGP Technical Specifications

Voltage ratings 480V, 3 phase, 60 Hz kVar ratings 1.3 to 270 kVar depending on voltage. Load types 3-phase diode bridge rectifier loads such as PWM AC drives Load power range 5 -900 HP Current ratings The included series reactors can tolerate 200% of rated current for at
least 3 minutes.
SCCR (short circuit current rating)
Maximum elevation 3,000 feet (1,000 meters) as standard. Maximum ambient operating
temperature
Maximum ambient storage temperature
Maximum humi d it y, operating or storage
Enclosure options UL Type 1 enclosure
Agency approvals or certifications
Standard rating is 100kA.
50°C (122°F) – Open Panel; 40°C (104°F) – Enclosed Panel. Product must be equipped with special cooling provisions for
operation above this temperature. 60°C (140°F)
95%, non-condensing.
UL Type 3R enclosure
UL and cUL Listed to UL508A
Insertion Impedance +/- 10% at full load current Fusing and protection: All units have internal fuse prote c tion for the harmonic filter circuit.
Page 17

Standard Option (S)

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
The Standard Option includes ve r y hi g h qua li t y harmonic-grade capacitors and line reactors. This filter will meet the major ity of ap plica tion req uire ments found to day. T his cos t e ffective p rod uct is a vailab le as an open panel version, in a UL Type 1 enclosure, or in an UL Type 3R enclosure. The open panel is perfect for inclusion in a MCC section or easy installation into industry standard enclosures. The UL Type 1 enclosed units maintain the same vertical profile as the open panel design. This design is perfect for applications where floor space is at a premium. The UL Type 3R enclosure protects the filter from harsh conditions.
Product Description

HGP S Option Filter

The HGP harmonic filter is a drive-applied harmonic filter designed and developed by TCI to reduce the harmonic curr ents dra wn fr om the po wer sour ce b y VFDs. T he HGP har monic filter is for 480 volt systems (60 Hz). It is suitable for use with 3-phase diode bridge rectifier loads such as PWM AC VFDs.
The HGP harmonic filter is a passive filter connecte d in series with the input ter minals of a VFD or several VFDs that operate as a group. It is designed to provide a low impedance path for the major harmonic currents demanded by the VFD. The filter is a stand-alone device that can be furnished in its own enclosure and mounted adjacent to the VFD. It is also available on an open panel for mounting within an enclosure with the VFD or other equipment.
The HGP Standard Option consists of the following standard features and components:
A KDR tuned series reactor. A TCI 3-phase tuning reactor specifically designed for the HGP filter. High-endurance, harmonic-rated capacitors. Bleeder resistors to ensure safe capacitor discharge upon filter shutdown, located on
capacitors.
Cooling fans (on select models) to ensure adequate cooling and safe operating
temperatures.
Control Power transformer on enclosed units requiring auxiliary cooling fans. Compression terminals for ease a nd integrity of all power and control wiring.Fuses
Page 18

Contactor Opti on (C)

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
The Contactor Option includes a contactor, control power transformer and connection terminals in the filter circuit which allows the VFD user to control the insertion of this circuit through the use of a r elay contact in the VFD. It is recommended that t he VFD contact be programmed to open the contactor below 33% motor power. For variable torque (fan) loads this will be approximately below 70% speed, so the at-speed contact may be used. This reduces the possibility of leading power factor interacting with other devices on the power system. Contacto r logic should also maintain the conta ctor closed in cases where the VFD is bypassed and the filter is not bypassed.
Product Description

HGP C Option Filter

The HGP harmonic filter is a drive-applied harmonic filter designed and developed by TCI to reduce the harmonic curr ents dra wn fr om the po wer sour ce b y VFDs. T he HGP har monic filter is for 480 volt systems (60 Hz). It is suitable for use with 3-phase diode bridge rectifier loads such as PWM AC VFDs.
The HGP harmonic filter is a passive filter connecte d in series with the input ter minals of a VFD or several VFDs that operate as a group. It is designed to provide a low impedance path for the major harmonic currents demanded by the VFD. The filter is a stand-alone device that can be furnished in its own enclosure and mounted adjacent to the VFD. It is also available on an open panel for mounting within an enclosure with the VFD or other equipment.
The HGP Contactor Option consists of the following standard features and components:
A KDR tuned series reactor. A TCI 3-phase tuning reactor specifically designed for the HGP filter. High-endurance, harmonic-rated capacitors. Bleeder resistors to ensure safe capacitor discharge upon filter shutdown, located on
capacitors.
Filter enable/disable contactor with protection and drive interlock provisions.Cooling fans (on select models) to ensure adequate cooling and safe operating
temperatures.
Control power transformer Compression terminals for ease a nd integrity of all power and control wiring.FusesContactor
Page 19

Fuse Monitor with Contactor Option (F)

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
The Fuse Monitor with Contactor Option includes a voltage monitor module and relay that can be connected to a VFD or other device. The fuse monitor will indicate a fuse failure and communicate this condition through the relay to a connected device.
This option includes a contactor, control power transformer, and connection terminals in the filter circuit which allows the VFD user to control the insertion of this circuit thr ough the use of a relay contact in the VFD. It is recommended that the drive contact be programmed to open the contactor below 33% motor power. For variable torque (fan) loads this will be approximately below 70% speed, so the at-speed contact may be used. This reduces the possibility of leading power factor interacting with other devices on the power system. Contactor logic should also maintain the conta ctor closed in cases where the VFD is bypassed and the filter is not bypassed.
Product Description

HGP F Option Filter

The HGP harmonic filter is a drive-applied harmonic filter designed and developed by TCI to reduce the harmonic currents drawn from the power source by VFDs. The HGP harmonic filter is for 480 volt systems (60 Hz). It is suitable for use with 3-phase diode bridge rectifier loads such as PWM AC drives.
The HGP harmonic filter is a passive filter connecte d in series with the input ter minals of a VFD or several VFDs that operate as a group. It is designed to provide a low impedance path for the major harmonic currents demanded by the VFD. The filter is a stand-alone device that can be furnished in its own enclos ure and mounted adjacent to the VFD. It is also available on an open panel for mounting within an enclosure with the VFD or other equipment.
The HGP F Option consists of the foll owing sta ndard features and components:
A KDR tuned series reactor. A TCI 3-phase tuning reactor specifically designed for the HGP filter. High-endurance, harmonic-rated capacitors. Bleeder resistors to ensure safe capacitor discharge upon filter shutdown, located on
capacitors.
Filter enable/disable contactor with protection and drive interlock provisions.Cooling fans (on select models) to ensure adequate cooling and safe operating
temperatures.
Control power transformer Compression terminals for ease a nd integrity of all power and control wiring.FusesContactorVoltage monitor module to report status of fuses to control
Page 20

Fuse Monitor wi thout Contactor Option ( G)

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
The Fuse Monitor witho ut Contactor Option includes a voltage monitor module and relay that can be connected to a VFD or other device. The fuse monitor will indicate a fuse failure and communicate this condition through the relay to a connected device.
Product Description

HGP G Option Filter

The HGP harmonic filter is a d rive-applied harmonic filter designed and developed by TCI to reduce the harmonic curr ents dra wn fr om the po wer sour ce b y VFDs. T he HGP har monic filter is for 480 volt systems (60 Hz). It is suitable for use with 3-phase diode bridge rectifier loads such as PWM AC VFDs.
The HGP harmonic filter is a passive filter connecte d in series with the input ter minals of a VFD or several VFDs that operate as a group. It is designed to provide a low impedance path for the major harmonic currents demanded by the VFD. The filter is a stand-alone device that can be furnished in its own enclosure and mounted adjacent to the VFD. It is also available on an open panel for mounting within an enclosure with the VFD or other equipment.
The HGP G Option consis t s of the following standard features and components:
A KDR tuned series reactor. A TCI 3-phase tuning reactor specifically designed for the HGP filter. High-endurance, harmonic-rated capacitors. Bleeder resistors to ensure safe capacitor discharge upon filter shutdown, located on
capacitors.
Cooling fans (on select models) to ensure adequate cooling and safe operating
temperatures.
Control Power transformer on enclosed units requiring auxiliary cooling fans. Compression terminals for ease and integrity of all power and control wiring.FusesVoltage monitor module to report status of fuses to control
Page 21

CP Kit Enclosure (8) with Option (0)

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
The HGP CP Kit Option is a harmonic filter component package designed and developed by TCI to allow qualified customers to build harmonic filters to reduce the harmonic currents drawn from the power source by VFDs. The HGP CP Option is available f or 480 volt systems (60 Hz). When properly designed, assembled, and installed, the completed product is intended to be suitable for use with 3-phase diode bridge rectifier loads such as PWM AC VFDs. SCR or thyristor lo ad s suc h a s DC d rives would require a different filter configuration outside the scope of this product offering. Please contact TCI Technical Support for additional information.
Product Description

HGP CP Kit Option Filter

The HGP CP Kit O ption is a package of the primary passive filter components needed to build and install a harmonic filter on a VFD or VFD system. The filter components are tuned to p rovide a low impedance path for the major harmonic currents demanded by the VFD when follo wing the sche matic connectio ns used by TCI in the HGP filter.
The HGP CP Option filter component package consists of the following components:
A KDR tuned serie s reactor. A TCI 3-phase tuning reactor specifically designed for the HGP filter. High-endurance, harmonic-rated capacitors. Bleeder resistors to ensure safe capacitor discharge upon filter shutdown, located on
capacitors.
Faston terminals for wiring single -phase capacitors (select models).
Page 22

Line Rea ctor Installation

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Review all Pre-Installation and Installation instructions at the beginning of this manual. If you are assembling a CP unit i n your own enc losure, you must provide a n enclosure tha t is adequate ly
sized and ventilated sufficiently to prevent overheating. The maximum temperature of the air around the HGP filter capacitors should not exceed 50°C (122°F).

KDR Line Re actor In stalla tion Ins tructio n

Recommendations and Considerations: When installing the KDR Line Reactors on the INPUT side of the VFD, please use the following guidelines
when wiring the unit: The KDR Line Reactor is a 3-phase device and should be wired in series and positioned on the input side of
the VFD. All Terminal Block connectors will be marked. A1, B1, and C1 are the input terminals where the 3 phases of
incoming power are to be wired. The tap for the filter co nnection will be marked AT, BT, and CT. Output terminals will be marked A2, B2, and C2. Do not swap input and output terminals. Units with copper bus or ring lug terminals are not marked. Wiring from the output terminals sho ul d connect to the input of the VFD.
Refer to NEC wiring practices for appropriate wire sizes for your application. TCI recommends that these reactors be wired and located as close to the front end of the VFD as possible to
have the greatest success in both protecting the VFD as well as mitigating line harmonics. We reco mmend this be 10 feet of cable or less.
Reactors generate a lot of heat in normal operations, and their surfaces get very hot. In standard 40°C ambient or less installations, a clearance of 3 inches on all sides of the reactors and its enclosure is recommended for assisting in heat dissipation. This is a general guideline for typical applications. If the reactor is being installed ne xt to a heat sensitive instrument or control device, we recommend reviewing specific requirements or heat limitations. Line reactor heat loss information is available in the standard TCI product literature or on the web.
eactors are designed to be floor-mounted, or wall-mounted. Large open-style devices should be pane l
These r mounted by incorporating a bracket that would act as a shelf to support the reactor and/or enclosure. When installing an open style device in an existing contro l cabinet, drive cabinet, motor control center, or other large enclosure, the reactor should be mounted in the lower half of the cabinet to prevent hot spots or pockets of heat. Locating the reactor in the lower half of the cabinet typically allows better thermal dissipation and heat convection. Reactors with ducts should be mounted vertically for proper cooling.
Page 23

Typical Voltage Distortion Option (0 )

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
The Typical Voltage D istortion Option, intended for applications with levels of background voltage distortion less than 2%, i s a co nfiguratio n that e nable s the H GP filter to a chieve lower levels of current harmonic distortion in applications with lo w backgro und volta ge distor tion. T his per formance op tion is available in all of the package options.
Page 24

High V oltage Distortion Option (1)

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
The High Voltage Distortion Option, intended for applications with levels of background voltage distortion of 2% or higher, is a c onfiguration that enables the HGP filter to achieve lower le vels of current har monic disto rtio n in a pplic ations wit h high b ackgr ound volta ge di storti on. T his p erfor mance option is available in all of the pa c kage o ptions.