TCF TCPE, WPB, WPD Installation, Operation & Maintenance Manual

Page 1
Propeller Wall Fans
IM-4800
INSTALLATION, OPERATION & MAINTENANCE MANUAL
WARNING Used when serious injury or death MAY result from misuse or failure to follow specific instructions.
CAUTION Used when minor or moderate injury or product / equipment damage MAY result from misuse or failure to follow specific instructions.
NOTICE
Indicates information considered important, but not hazard-related.
SAFETY INSTRUCTIONS
Indicates specific safety-related instructions or procedures.
It is the responsibility of all personnel involved in installation, operation and maintenance to fully understand the Warning and Caution procedures by which hazards are to be avoided.
July 2015
Models
TCPE, WPB, WPD
Twin City Fan & Blower Catalogs 4800 and 4820 provide additional information on this equipment. These catalogs can be found at www.tcf.com or by contacting your local Twin City Fan & Blower sales representative.
TCPE WPB WPD
©2009 – 2018 Twin City Fan Companies, Ltd.
Page 2
Receiving, Unpacking & Inspection
When the equipment is received all items should be carefully checked against the bill of lading to be sure all crates and cartons have been received. Before accepting delivery, carefully inspect each carton or crate for visible shipping damage. If any damage is noticed, the carrier should make the proper notation on the delivery receipt acknowledging the damage. Make notations of all damage on all copies of the bill of lading and have all copies countersigned by the delivering carrier. The carrier should also fill out a Carrier Inspection Report. The factory Traffic Department should then be contacted. File claim for damage with the carrier. Physical damage to the unit after acceptance is not the responsibility of Twin City Fan Companies, Ltd.
Unpack each carton or crate and verify that all required parts and proper quantities of each item have been received. Refer to drawings for part descriptions. Report shortages or missing items to your local representative to arrange for replacement parts.
Due to availability of carriers and truck space, it is not possible to guarantee that all items will be shipped together. Verification of shipments must be limited to only those items on the bill of lading.
Storage
NOTICE
The unit nameplate must be checked to make sure the voltage agrees with the power supply available.
CAUTION
Sheet metal parts, screws, clips and similar items inherently have sharp edges, and it is necessary that the installer and service personnel excercise caution.
The installation of this equipment shall be in accordance with the regulations of authorities having jurisdiction and all applicable codes. This equipment is to be installed by an experienced installation company and fully trained personnel. The mechanical installation of the exhaust ventilator consists of making final connections between the unit and building services, duct connections.
If fans are stored for any length of time, they should be stored in a clean, dry location to prevent rust and corrosion. Outdoor storage is not recommended. When outdoor storage is necessary, fans should be protected from the elements as completely as possible. Cover the fan inlet and outlet and keep motors dry and clean.
For extended storage (more than 3 months) motor shafts and bearings should be rotated monthly. If stored longer
Limitation of Warranties and Claims
Seller warrants to the original purchaser that the goods sold hereunder shall be free from defects in workmanship and material under normal use and service (except in those cases where the materials are supplied by the buyer) for a period of one year from the date of original installation or eighteen (18) months from the date of shipment, whichever occurs first. The liability of seller under this warranty is limited to replacing, repairing, or issuing credit (at cost, F.O.B. factory and at seller’s discretion) for any part or parts which are returned by buyer during such period provided that:
a. Seller is notified in writing within ten (10) days
following discovery of such defects by buyer, or within ten (10) days after such defects should reasonably have been discovered, whichever is less;
b. The defective unit is returned to seller, transportation
charges prepaid by buyer;
c. Payment in full has been received by seller or said
products;
d. Seller’s examination of such unit shall disclose to its
satisfaction that such defects have not been caused by misuse, neglect, improper installation, repair, alteration, act of God, or accident.
than 6 months, bearing grease in motor and fan should be purged and replaced with compatible grease. Belts should be rechecked for proper tension. Storage records should be kept to assure proper maintenance. The factory can advise warranty centers to provide motor and bearing service if needed.
No warranty made hereunder shall extend to any seller product whose serial number is altered, effaced or removed. Seller makes no warranty, express or implied, with respect to motors, switches, controls, or other components of seller’s product, where such components are warranted separately by their respective manufacturers. THIS WARRANTY IS EXPRESSLY IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, WHETHER STATUTORY OR OTHERWISE, INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. In no event shall seller be liable to buyer for indirect, incidental collateral, or consequential damages of any kind. (BUYER’S FAILURE TO PAY THE FULL AMOUNT DUE WITHIN SIXTY (60) DAYS OF DATE OF INVOICE SHALL OPERATE TO RELEASE SELLER FROM ANY AND ALL LIABILITY OR OBLIGATION ARISING PURSUANT TO ANY WARRANTY, EXPRESS OR IMPLIED, WHETHER STATUTORY OR OTHERWISE, INCLUDING ANY IMPLIED WARRANTY OR MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, MADE IN CONNECTION WITH ANY CONTRACT FORMED HEREUNDER. BUYER AGREES THAT SUCH FAILURE TO PAY SHALL CONSTITUTE A VOLUNTARY WAIVER OF ANY AND ALL SUCH WARRANTIES ARISING PURSUANT TO SUCH CONTACT.)
2 Twin City IM-4800
Page 3
Electrical Connection
1. Connect supply wiring to a disconnect switch. Check the wiring diagrams on the motor for connections.
2. The motor is factory set at the voltage marked on the fan nameplate. Check the line voltage with the nameplate voltage and wiring diagrams.
3. The main power wiring should be sized for the ampacity shown on the dataplate. Size wires in accordance with the ampacity tables in Article 310 of the National Electrical Code. If long wires are required, it may be necessary to increase wire size to prevent excessive voltage drop. Wires should be sized for a maximum of 3% voltage drop.
CAUTION
Use copper conductors only.
Protect wiring from sharp edges. Leave some slack in the line to prevent damage.
4. (Optional) Disconnect switches are not fused. The power leads must be protected at the point of distribution in accordance with the fan dataplate.
5. On fans without a thermal protector integral to the motor (refer to unit or motor dataplate to determine if protector is present) a separate overload device is required. Refer to Sections 430-32 of the N.E.C. for sizing.
6. All units must be electrically grounded in accordance with local codes or, in the absence of local codes, with the latest edition of the National Electrical Code (ANSI/NFPA 70). A ground lug is provided as standard in the unit terminal box. Size grounding conductor in accordance with Table 250-95 of the National Electrical Code. DO NOT use the ground lug for connecting a neutral conductor.
7. Supply voltage to the power ventilator should not vary by more than 10% of the value indicated on the unit dataplate. Phase unbalance must not exceed 2%.
WARNING
Failure of motor due to operation on improper line voltage or with excessive phase unbalance constitutes product abuse and may cause severe damage to the unit’s electrical components.
Check, Test & Start Procedure
WARNING
Electric shock hazard. Could cause severe injury or death. Failure to bond the frame of this equipment to the building electrical ground by use of the grounding terminal provided or other acceptable means may result in electrical shock. Disconnect electric power before servicing equipment. Service to be performed only by qualified personnel.
SAFETY INSTRUCTIONS
BEFORE START-UP: Disconnect power to this unit before servicing the unit.
1. Check to verify that the propeller is free to rotate.
2. Verify that supply voltage on the line side of disconnect agrees with voltage on fan data plate and is within the 10% utilization voltage.
3. Apply power to unit and check rotation of propeller with the directional arrow on the unit.
WARNING
Especially check three-phase units for rotation. For three-phase, rotation can be changed by interchanging any two of the three line leads. If unit is checked on temporary wiring, it should be rechecked when permanently installed. Motor burn-out or tripped overload protection devices are usually the result of wrong rotation.
4. Electrical Input Check: Perform check of fan ampere draw and verify that motor nameplate amps are not exceeded. Take into account the service factor range if motor is nameplated above a 1.0 service factor.
5. Fan RPM should be checked and verified with a tachometer.
6. Units with Speed Control (TCPE): Verify that speed controller gives desired operating range of RPM. If minimum speed value is not desired, it may be adjusted. See page 4.
NOTICE
WARNING
Rotation is critical. If allowed to operate in the wrong direction, the motor will overload and burn out.
Twin City IM-4800 3
The fan was balanced at the factory to be within stringent vibration levels before shipment. However, there are several things that may cause vibration, such as rough handling in shipment and installation, weak foundations and alignments.
Page 4
Speed Control Installation
(Model TCPE - optional)
The controller is designed to start the motor at high speed and will then slow down. This gives the motor good starting characteristics.
Speed control is available using 115/60/1 open type PSC or shaded pole motors.
Installation
Connect control in series with motor and line voltage (115V only). Never connect across line. See Figure 1.
WARNING
Certain failure modes of solid-state controls such as half-waving can cause high levels of DC, motor overheating and motor burn-out. Therefore, a thermal overload protection (integral with motor) is required to limit the maximum motor temperature under such a failure.
Minimum Speed Setpoint
All controls are factory set to 65V±3V output as standard with an input voltage of 120V. If different minimum speed is desired, the control may be adjusted by turning minimum speed pot clockwise to decrease minimum speed and counterclockwise to increase minimum speed. Refer to Figure 2.
WARNING
If minimum speed is readjusted, verify unit ampere draw does not exceed motor nameplate amps. Do not operate unit in range where amp draw exceeds motor nameplate.
CAUTION
These motors operate more efficiently in the ranges set from the factory. Operating motor outside these ranges (see Table 2) may cause motor to run hotter and substantially shorten motor life.
NOTICE
Lowering the minimum speed setpoint may adversely affect motor start-up characteristics.
Table 1. Speed Controller Size
MOTOR
HP RPM VOLTAGE
1650/1500/
1/8
1350
1/8 860 115V X 1/6 860 115V X 1/4 860 115V X 1/2 860 115V X 1/6 1140 115V X 1/4 1140 115V X 1/2 1140 115V X
1 1140 115V X 1/3 1725 115V X 1/2 1725 115V X 3/4 1725 115V X
115V X
SPEED CONTROLLER
DESIGNATION / FLA
KBWC-15K
5 AMP
KBWC-110
10 AMP
KBWC-115
15 AMP
NOTICE
Do not allow any sleeve bearing motor to operate below 500 RPM. Operation below 500 RPM will substantially shorten bearing life.
Figure 1. Connection Diagram, Speed Control
SPEED CONTROLLER
AC
LINE
(115V)
Table 2. Speed Controller RPM Range
HP RPM MAX. RPM MIN. RPM
1/8
1/8 1/6 1/4 1/2 1/6 1/4 1/2
1/3 1/2 3/4
NOTES:
1. Speed control available only with 115/60/1 open motors (thermally
2. Three-speed motor (multiple tap winding).
3. Speed control should not be connected to low speed tap on motor
4. Speed control connected to high speed tap on motor.
5. Speed control connected to medium speed tap on motor.
1650/1500/1350
1
protected).
because of starting characteristics.
Figure 2. Low End Setpoint Adjustment
NOTE: 5 amp model shown. On 10 and 15 amp models, adjustment is made through clearance hole in heat sink.
SWITCH TRI-AC
MOTOR
4
2,3
860 860 500
1140 1140 900
1725 1725 1200
SETPOINT ADJUSTMENT SCREW
1650 1500
5
1300
950
4
5
NOTE: For TCPE fans using Electronically Commutated (EC) Motors, refer to IM-4055.
4 Twin City IM-4800
Page 5
PANEL
MOUNTING
FRAMING
BOLTS TO
REMOVE FAN
WIRING HOLE ‘A’
ROTATION
AIRFLOW
Panel Installation (without collar) — TCPE
1. The TCPE panel fan is an axial exhauster that can be mounted either vertically or horizontally. Figure 3 depicts a typical wall installation.
2. A typical frame is usually roughed in so that the inside square dimension is approximately 1⁄2" to 3⁄4" more than what the fan panel measures. If using the optional wall collar the frame should be
3
4" to 1"
more than what the fan panel measures.
3. Place the unit into the frame with the wiring hole A in the position that is most suitable for wire to enter the unit. Fasten the unit to the frame through the holes provided using lag bolts. If the electrical wire will be coming from within the wall that the TCPE is being mounted to, run the wire through hole A by entering it from the orifice side of the panel. This should be done before the panel is fastened to the frame to reduce the need of disassembly. If the wiring is not done during the installation the motor and guard can be removed from the panel fan without having to actually remove the panel itself. See Figure 3. Make sure a strain relief is attached to the wires after the wire is pulled into position.
CAUTION
Use copper conductors only.
Protect all wires from sharp edges. Do not route wire through wiring hole without a strain relief to protect it.
4. Connect the electrical wire to a disconnect switch and then connect the wire to the motor (an optional speed control may be installed in series with a 115V ODP motor and disconnect switch). See Figure 1 on Page 4. The wiring diagram for the motor is on a label attached to the motor. Main power wiring should be sized for the amperage shown on the data plate attached to the fan panel.
5. Disconnect switches (Optional) are not fused; there­fore, the power leads must be protected at the point of distribution in accordance with the unit data plate.
6. All TCPE motors are thermally protected. All units must be electrically grounded in accordance with local codes or in accordance with the NEC. A grounding point is provided with all motors and will be described on the wiring diagram that is attached to the motor.
7. Supply voltage to the motor should not vary by more than 10% of the value indicated on the unit data plate. Phase unbalance must not exceed 2%.
Figure 3. Typical Installation
TCPE
SIZE
8 13.25 13.75 10 x 10
12 18.25 18.75 15 x 15 14 21.25 21.75 18 x 18
18 25.25 25.75 22 x 22 20 27.25 27.75 24 x 24 24 30.25 30.75 27 x 27
PANEL
SQ.
WALL
OPENING
DAMPER
SIZE
'M' (MIN.)
14.010 15.25 15.75 12 x 12
14.016 23.25 23.75 20 x 20
14.0
Wall Opening Requirements
Wall opening size and the distance between propeller and damper are two important dimensions for fan installation. Fans mounted in or to the wall require a different wall opening size than those mounted in collars. Propeller-to-damper distance (M) is important to reduce turbulence at the damper, which may lead to premature damper failure, and to prevent the propeller blades from hitting the actuator on motorized damper units.
Figure 4. Fan Assembly Without a TCPE Wall Collar
M" (Min).
BACK OF
FAN TO
FAN
DAMPER
DAMPER
(EXTENDED FLANGE)
WEATHERHOOD
WARNING
Failure of the unit due to improper line voltage or
excessive phase unbalance constitutes product abuse. Severe damage to the unit’s electrical components may occur.
8. Make sure unit is properly sealed around the frame edges so that the outside elements cannot enter the building.
Twin City IM-4800 5
FIELD
FABRICATED
WALL COLLAR
Page 6
Panel Installation (without accessories) — WPB & WPD
Wall Opening Requirements
Wall opening size and the distance between propeller and damper are two important dimensions for fan installation. Fans mounted to the wall require a different wall opening size than those mounted in collars or wall boxes. Propeller­to-damper distance (M) is important to reduce turbulence at the damper which may lead to premature failure, and to prevent the propeller blades from hitting the actuator on motorized damper units. Use general installation procedure from page 5.
To achieve the minimum 'M' dimension, this installation requires a spacer (by others)
SPACER
(BY OTHERS)
between the fan and the wall.
If the wall is equal to or greater than the minimum 'M' dimension, the fan can be mounted directly to the wall.
PROP
SIZE
14 -- 17.00 -- 14.50 -- 17.50 -- 14 x 14
18 -- 22.00 -- 19.50 -- 22.50 -- 19 x 19 21 25.00 25.00 22.50 22.50 25.50 25.50 22 x 22 22 x 22
30 36.00 36.00 33.50 33.50 36.50 36.50 33 x 33 33 x 33 36 42.00 42.00 39.50 39.50 42.50 42.50 39 x 39 39 x 39
48 54.00 54.00 51.50 51.50 54.50 54.50 51 x 51 51 x 51 54 60.00 -- 57.50 -- 60.50 -- 57 x 57 -­60 66.00 -- 63.50 -- 66.50 -- 63 x 63 --
PANEL SQ.
WPB WPD WPB WPD WPB WPD WPB WPD
SURFACE MOUNT RECESS (IN WALL)
WALL OPENING (MIN.)
AIR
FLOW
FAN
MIN
DAMPER SIZE
BACKDRAFT DAMPER
'M'
(MIN.)
16.0016 -- 20.00 -- 17.50 -- 20.50 -- 17 x 17
16.0024 28.00 28.00 25.50 25.50 28.50 28.50 25 x 25 25 x 25
16.0042 48.00 48.00 45.50 45.50 48.50 48.50 45 x 45 45 x 45
19.00
6 Twin City IM-4800
Page 7
WALL COLLAR WITH ACCESSORIES — TCPE
O
F
F
O
N
Removable Screen
Panel Fan
OSHA Motor Side Guard
Backdraft Damper
Weatherhood
Damper Guard
Bird Screen
Wall Collar
Disconnect Switch
O
F
F
O
N
Removable Screen
Panel Fan
Wall Box
Backdraft Damper
Weatherhood
Bird Screen
Damper Guard
Disconnect Switch
Disconnect Switch (Optional)
N O
F F O
Variable Speed Control (Optional)
Mounting Screw
WALL COLLAR WITH ACCESSORIES — WPB, WPD
Fan
Wall Collar
Backdraft Damper
Weatherhood
or
Damper Guard
WALL BOX WITH ACCESSORIES — WPB, WPD
Twin City IM-4800 7
Page 8
Mounting Arrangements — With Wall Collar or Wall Box
O
O
O
GUARD SCREEN
O
O
GUARD SCREEN
WEATHERHOOD WITH SCREEN
BACKDRAFT DAMPER
M
O
UNTING FLANGE
REMOVABLE
GUARD SCREEN
AIR
FLOW
SUPPORTS
(BY OTHERS)
FAN
Flush with Outside Wall
UNTING FLANGE
M
REMOVABLE
GUARD SCREEN
BACKDRAFT DAMPER
WEATHERHOOD WITH SCREEN
REMOVABLE
GUARD SCREEN
M
UNTING FLANGE
BACKDRAFT DAMPER
WEATHERHOOD WITH SCREEN
AIR
FLOW
INSIDE
Exhaust
REMOVABLE
AIR
FLOW
FAN
INSIDE
SUPPORTS
(BY OTHERS)
FAN
SUPPORTS
(BY OTHERS)
M
UNTING FLANGE
BACKDRAFT DAMPER
OUTSIDE
Middle of Wall
WEATHERHOOD WITH SCREEN
OUTSIDE
INSIDE
REMOVABLE
INSIDE
AIR
FLOW
FAN
SUPPORTS
(BY OTHERS)
AIR
FLOW
FAN
SUPPORTS
(BY OTHERS)
UNTING FLANGE
M
BACKDRAFT DAMPER
OUTSIDE
Supply
WEATHERHOOD WITH SCREEN
OUTSIDE
Exhaust
Flush with Interior Wall
M
UNTING FLANGE
BACKDRAFT DAMPER
REMOVABLE
GUARD SCREEN
AIR
INSIDE
OUTSIDE
INSIDE
Exhaust
8 Twin City IM-4800
FLOW
FAN
SUPPORTS
(BY OTHERS)
Supply
WEATHERHOOD WITH SCREEN
OUTSIDE
Supply
Page 9
Wall Collar, Wall Box Housings
The wall collar and wall box are intended to give the panel fan an easy way to adapt other accessories for a completed unit. They are set up to accept a panel fan, damper, and weatherhood or a damper guard screen. All holes are pre drilled for the fan and accessories to help make the installation easy.
Wall Collar Installation
1. If the collar is ordered as a field assembly, assemble it first by following the directions provided with the kit.
1
2. When roughing in the frame make the inside dimension This will give the collar enough clearance so that it will install easily.
3. Predrill holes into the collar wherever it is decided that it can be fastened to the roughed-in frame. The wall collar can be fastened to a roughed-in frame with lag screws through holes that need to be drilled into the collar. It is recommended that two lag screws per collar side be used to fasten it to the frame and that the bent edge of the collar is flush with the outside wall.
4. If power is coming into the unit from within the wall a wire to enter the collar. Be sure the metal edges of the hole are protected so the wire will not get cut.
5. If a damper, weatherhood or damper guard screen are being used, they can be fastened to the collar before the collar is fastened to the frame.
6. Make sure the edges around the collar and frame are sealed after it is installed.
The wall box is installed in the same way.
2" to 3⁄4" larger than the outside dimension of the collar.
3
4" to 1" hole may also have to be drilled for the power
TCPE
SIZE
8 13.50 14.25 10 15.50 16.25 12 18.50 19.25 14 21.50 22.25 16 23.50 24.25 18 25.50 26.25 20 27.50 28.25 24 30.50 31.25
COLLAR
SQ.
WALL
OPENING
WPB/WPD
SIZE
14 -- 17.25 -- 18.00 16 -- 20.25 -- 21.00 18 -- 22.25 -- 23.00 21 25.25 25.25 26.00 26.00 24 28.25 28.25 29.00 29.00 30 36.25 36.25 37.00 37.00 36 42.25 42.25 43.00 43.00 42 48.25 48.25 49.00 49.00 48 54.25 54.25 55.00 55.00 54 60.25 -- 61.00 -­60 66.25 -- 67.00 --
COLLAR/WALL
BOX SQ.
WPB WPD WPB WPD
WALL
OPENING
Weatherhood and Damper Guard Screen
The weatherhood and damper guard screen are both items designed to help protect the damper from damage and keep birds and other things from entering the building. The weatherhood will help deflect the outside elements from entering into the building through the fan. It also helps protect the damper from being inappropriately operated by the wind.
Weatherhood/Damper Guard Screen Installation
1. If mounting the damper guard screen or weatherhood onto a wall collar place it over the damper and use the self-tapping screws provided with the collar to fasten it through the pre drilled holes in the collar’s bent edge.
2. Make sure any undesired gaps are sealed to keep the elements from leaking into the building.
Twin City IM-4800 9
Page 10
Maintenance
Installation and maintenance are to be performed only by qualified personnel who are familiar with local codes and regulations and experienced with this type of equipment.
CAUTION
Sharp edges and screws are a potential injury hazard. Avoid them.
WARNING
Hazardous moving parts. Unit may contain protected
fan motor which may start automatically and cause injury. Allow time for reset. Disconnect power before
servicing.
Preventive maintenance is the best way to avoid unnecessary expense and inconvenience. Start-up and routine maintenance should cover the following items:
a. Tighten all setscrews, bolts and wire connections.
b. Check belt tension and sheaves for wear.
c. Lubricate fan bearings (see Tables 3 and 4).
d. Cleaning of unit, propeller and damper (if present).
All motors containing ball bearings are permanently lubricated from the factory. No additional maintenance is required.
1. Before performing any maintenance on the fan, be sure power is turned off and locked in the OFF position at the service entrance.
2. Ventilators should be carefully checked at least once a year. For critical or rugged applications, a routine check every two or three months is suggested.
3. All motors supplied with Twin City Fan & Blower ventilators carry a one-year limited warranty from date of shipment. For repairs within the warranty period, the motor must be taken to the motor manufacturer’s authorized service dealer. Contact your representative for additional warranty details.
4. A periodic motor check should consist of spinning the motor shaft with the power off to be sure the motor turns freely and the bearings run smoothly. The belt on belt driven units should be removed from the motor sheave.
5. When removing or installing a belt, do not force the belt over the sheave. Loosen the motor mount so that the belt can be easily slipped over the sheave.
6. The belt on belt driven units should be removed and carefully checked for glazing, cracks, ply separation or irregular wear. A small irregularity in the contact surface of the belt will result in noisy operation. If any of these defects are apparent, the belt should be replaced. Check the sheaves also for chipping, dents or rough surfaces which could damage the belt.
7. The correct belt tension is important. Too tight of a belt will result in excess bearing pressure on the motor bearings and shaft pillow blocks and may also overload the motor. Too loose of a belt will result in slippage which will quickly “burn” out belts. A belt should feel “live” when thumped, approximately belt deflection (3 to 5 lb.) when subject to finger pressure at midpoint between sheaves.
8. The belt alignment should also be checked to be sure the belt is running perpendicularly to the rotating shafts. Fan and motor shafts must be parallel. Improper alignment will result in excessive belt wear.
9. Check sheave setscrews to ensure tightness. Proper keys must be in keyways.
10. For blade angle adjustments on Type 'E' Propellers (Level 3) refer to Engineering Supplement ES-404.
11. If unit is to be left idle for an extended period, it is recommended that belts be removed and stored in a cool, dry place to avoid premature belt failure.
12. The standard pillow block bearings on belt driven ventilators are factory lubricated and are provided with external grease fittings. Annual lubrication is recommended, or more frequently if needed (see Table 3).
It is recommended to add fresh grease at start-up,
but do not over-grease. Use only 1 or 2 shots of a recommended lubricant with a hand gun in most cases (see Table 4). Maximum hand gun rating 40 P.S.I. Rotate bearings during lubrication where good safety practice permits.
1
4"
CAUTION
Greases of different soap bases (lithium, sodium, etc.) may not be compatible when mixed. Prevent such intermixing by completely purging the bearing of old greases.
The most frequent causes of bearing failure are not
greasing often enough, using an excessive quantity of grease or using incompatible greases. Excessive vibration, especially if the bearing is not rotating, will also cause bearings to fail. Bearings must also be protected from water and moisture to avoid internal corrosion.
13. During the first few months of operation it is recommended that the bearing setscrews be checked periodically to ensure that they are tight.
14. The rotating propeller requires particular attention since materials in the air being handled can build up on the blades to cause destructive vibration or weaken the structure of the propeller by corroding and/or eroding the blade metal. Regular inspection and corrective action at intervals determined by the severity of each application are essential to good service life and safety.
10 Twin City IM-4800
Page 11
Table 3. Suggested Fan Bearing Greasing Intervals Table 4. Grease Manufacturers
INTERVAL (MONTHS)
12 to 18
6 to 12
3 to 6
1 to 3
TYPE OF SERVICE
Infrequent operation or light duty in clean atmosphere
8 to 16 hrs./day in clean, relatively dry atmosphere
12 to 24 hrs./day, heavy duty, or if moisture is present
Heavy duty in dirty, dusty locations; high ambient temperatures; moisture laden atmosphere; vibration
MANUFACTURER GREASE (NLGI #2)
Shell Gadus S2 V100 2
Exxon/Mobil Ronex MP
Bearing Replacement
Fan bearings on belt driven fans should not need to be replaced for many years if the previous recommendations are strictly adhered to. However, use the following procedure when bearing replacement is necessary.
1. Gain access to the fan bearings. Remove the bearing cover, if any.
2. Loosen the belts by shifting the motor.
3. Remove the propeller and disconnect the remote lubrication tubes (if applicable).
4. Measure the location of the bearing to the propeller end of the shaft and the bearing spacing.
5. Remove the shaft and bearing assembly. Note the position of the bearings’ shims (if applicable).
6. Loosen all bearing/shaft setscrews or other locking devices.
7. Remove bearings (may need to be pressed off the shaft).
8. Polish the shaft with fine emery paper (240 grit or finer) and file the setscrew dimples left on the shaft flat.
Motors
9. Install new bearings on the shaft, making sure that the collars are together (i.e. facing each other on the shaft). Lightly seat one setscrew or eccentric locking collar on each bearing to hold in the approximate marked position.
10. Mount the shaft/bearing assembly in the fan with bolts. Do not tighten yet. Just snug up. Loosen the setscrew.
11. Center the shaft in the housing (both ends) as closely as possible. (The fan propeller may need to be temporarily installed to get its clearances equal.)
12. Tighten the bearing mounting bolts.
13. Reinstall the lube tubes (if applicable).
14. Install propeller and belts and adjust the motor to get proper belt tension. Also, make sure that the sheaves are properly aligned.
15. If a new shaft is supplied, ignore items 6 thru 8.
Twin City Fan & Blower recommends periodic checks of voltage, frequency and current of a motor while in operation. Such checks assure the correctness of frequency and voltage applied to the motor, and yield an indication of the fan load. Comparison of this data with previous data will give an indication of the fan performance. Any serious deviations could indicate a potential motor failure.
All motors have pre lubricated sealed bearings and are lubricated for the life of the motor.
1. All motors carry a one-year limited warranty from date of shipment. For repairs within the warranty period, the motor must be taken to the motor manufacturer’s authorized service dealer. Contact your representative for additional warranty details.
Twin City IM-4800 11
2. A periodic motor check should consist of spinning the motor shaft with the power off to be sure the motor turns freely and the bearings run smoothly. The belt on belt driven units should be removed from the motor pulley.
Repair or replacement of motors is normally performed by a repair station authorized by the manufacturer. Contact your representative or the factory for locations nearest you. DO NOT ship motor to the factory without specific authorization forms.
Page 12
V-Belts
V-belts on these belt driven fans are oil, heat, and static resistant type and oversized for continuous duty. With proper installation and maintenance, years of operating efficiency can be added to the lifespan of the V-belt drive.
The condition of V-belts and the amount of belt tension should be checked prior to start-up (see Figure 5). When it becomes necessary to adjust belt tension, do not over-tension as bearing damage will occur. Recommended belt tension should permit per inch of span of the belt at the center of the belt span. To find this point, measure halfway between the pulley centerlines as shown in Figure 6. Extreme care must be exercised when adjusting V-belts as not to mis­align the pulleys. Any misalignment will cause a sharp reduction in belt life and will also produce squeaky, annoying noises (see Figure 7). On units equipped with 2 groove pulleys, adjustments must be made so that there is equal tension on all belts (see Figure 9).
Figure 5. Eliminate Slack Figure 6. Belt Deflection
1
64" deflection
1. Where tensioning rods are not available, adjustment is more easily obtained by loosening and adjusting one side of the motor bracket at a time.
2. Always loosen tension adjustment enough to place belts on sheaves without running belts over the edge of either sheave. A new belt may be seriously damaged internally by careless handling (see Figure 8).
When removing or installing belts, never force belts over pulleys without loosening motor first to relieve belt tension.
3. Fan speed can be increased by closing the adjustable motor pulley, or decreased by opening it. Two and three groove adjustable pitch pulleys must be adjusted an equal number of turns. (See Figure 9). Always check load on motor when increasing fan speed.
WARNING
Belt Span
Slack belts wear excessively, cause slippage and deliver less power. For longest belt life, always provide proper tension
Figure 7. Alignment Figure 8. Belts
CORRECT
Do not force belt. Forcing the belt will break the cords and cause belt failure.
Figure 9. 2-Groove Sheaves
INCORRECT
Mount belts straight. Shafts must be parallel and sheaves in alignment to prevent unnec­essary belt wear.
Deflection
Deflection = 64
Belt Span
Two-groove variable pitch sheaves must be opened the same number of turns on both sides; otherwise, slip­page occurs, wearing belts rapidly,
12 Twin City IM-4800
Page 13
Fan Troubleshooting Chart
PROBLEM POSSIBLE CAUSES
FAN DOES NOT OPERATE 1. Wrong voltage.
2. Electricity turned off or not wired properly.
3. Tripped overload protector.
4. Blown fuses.
5. Loose pulleys.
6. Broken belts.
TOO LITTLE AIR 1. Propeller rotating in wrong direction.
2. Fan speed lower than design.
3. System is more restrictive (more static pressure) than expected.
4. Restricted fan inlet or outlet.
5. Inlet or outlet screens clogged.
6. Filters, if applicable, are dirty or clogged.
TOO MUCH AIR 1. Fan speed higher than design.
2. System is less restrictive (less static pressure) than expected.
3. Filters, if applicable, not in place.
EXCESSIVE HORSEPOWER 1. Propeller rotating in wrong direction.
2. Propeller rubbing on inlet venturi.
3. Fan speed higher than design.
4. Worn fan bearings.
EXCESSIVE NOISE 1. Propeller or sheaves loose.
2. Bearing or drive misalignment.
3. Accumulation of material on propeller.
4. Worn or corroded propeller.
5. Propeller out of balance.
6. Propeller hitting housing.
7. Bent shaft.
8. Bearings need lubrication.
9. Loose bearing bolts.
10. Loose or worn bearings.
11. Mismatched belts.
12. Belts too loose or too tight.
13. Belts oily or dirty.
14. Belts worn.
15. Loose fan mounting bolts.
16. Rattle of components in high velocity airstream.
17. Electrical noise.
18. Noise from high velocity air system.
19. Vibrating parts not isolated from building.
20. Vibrating ductwork.
EXCESSIVE VIBRATION 1. Propeller or sheaves loose on shaft.
2. Propeller out of balance.
3. Excessive buildup of dirt/dust on propeller.
4. Belts too loose or too tight.
5. Mismatched belts.
6. Bent shaft.
7. Bearing or drive misalignment.
8. Loose or worn bearings.
9. Fan mounting bolts loose.
10. Structures not cross-braced.
It is recommended that the users and installers of this shipment familiarize themselves with AMCA Publication #201, “Fans and Systems” and publication #202, “Troubleshooting” which are published by the Air Movement and Control Association (AMCA), 30 West University Drive, Arlington Heights, Illinois 60004. www.amca.org
Twin City IM-4800 13
Page 14
X Max
Model Nomenclature
TCP E - 14 - 2 A
Model TCPE, Direct Drive
E = Exhaust
Propeller Diameter
Model WPD = Wall Propeller Fan, Direct Drive
WPB = Wall Propeller Fan, Belt Driven
E = Exhaust, S = Supply
Fan Size
Propeller Type
L1 & L2 = Level 1 & Level 2, Fabricated Steel, Fixed Pitch (5-Bladed) B = Cast Aluminum, Adjustable Pitch (4, 5, and 6-Bladed) E = Cast Aluminum, Adjustable Pitch (4 and 8-Bladed) C = Cast Aluminum, Adjustable Pitch (4 and 6-Bladed) Z = Fabricated Steel, Fixed Pitch (5-Bladed)
Hub Designation (B Propellers Only)
No. of Blades
Propeller Blade Angle (B, C, E, and Z Propellers Only)
Design Vintage / Motor Type A = Design A AE = Design A with EC Motor
Speed 0 = 800 or 1350 RPM 1 = 1100 or 1500 RPM 2 = 1700 or 1650 RPM
WPB - E - 24 - B - 1 - 05 - 25
Dimensional Data
TCPE – Direct Drive
.
AIR
FLOW
A SQ.
(INSIDE)
Exhaust Supply
TCPE
SIZE
080A, 081A, 082A, 082AE 13.25 8.38 1.25 4.00 10.25 12.25 8.00 10 x 10 13.75
120A, 121A, 122A, 122AE 18.25 12.38 2.00 6.50 11.50 13.50 12.00 15 x 15 18.75 140A, 141A, 142A, 142AE 21.25 14.50 2.75 8.00 19.00 21.00 14.00 18 x 18 21.75 160A, 161A, 162A, 162AE 23.25 16.50 3.00 9.00 19.00 21.00 16.00 20 x 20 23.75 180A, 181A, 182A, 182AE 25.25 18.50 3.00 10.00 19.00 21.00 18.00 22 x 22 25.75 200A, 201A, 202A, 202AE 27.25 20.63 3.00 11.00 20.50 22.50 20.00 24 x 24 27.75
240A, 241A, 242A 30.25 24.63 3.00 12.00 22.00 24.00 24.00 27 x 27 30.75
A
I.D.
B
I.D
C F
F
B
I.D.
F
C2"
X
MAX.YMAX.
A SQ.
(OUTSIDE)
PROP.
DIA.
B
I.D.
0.313 HOLES
DAMPER
SIZE
AIR
FLOW
R RAD.
(D QTY)
Y Max.
2.00
C
OPENING
WALL
SQ.
MIN.
F
F
1.00
MOTOR FRAME
48100A, 101A, 102A, 102AE 15.25 10.38 1.50 5.00 11.25 13.25 10.00 12 x 12 15.75
56C
14 Twin City IM-4800
Page 15
WPD – Direct Drive
XD
Dimensional Data
C SQ. OUTSIDE
AIR FLOW
D MA
B
A DIA.
2.00
A DIA.
Exhaust Airflow Supply Airflow
WPD SIZE
A B C SQ.
EXHAUST SUPPLY
DAMPER
SIZE
14 14.25 2.75 17 11.18 14.88 14 x 14 56 16 16.25 3.00 20 11.18 14.88 17 x 17 56 18 18.25 3.00 22 11.18 14.88 19 x 19 56
21 21.25 3.50 25 14.41 17.36 22 x 22 145T 24 24.25 3.50 28 14.55 17.36 25 x 25 184T 30 30.38 4.00 36 14.74 19.05 33 x 33 184T 36 36.38 5.00 42 15.67 19.93 39 x 39 215T 42 42.38 5.50 48 23.59 30.00 45 x 45 254T 48 48.38 6.00 54 23.59 30.00 51 x 51 254T
D MAX
MAX
MOTOR
FRAME
MAX
2.00
AIR FLOW
B
WPB – Belt Driven, Levels 1 & 2
D MAX
B
A DIA.
2.00
A DIA.
MAX MOTOR
DAMPER
SIZE
L1 L2
C SQ. OUTSIDE
AIR FLOW
D MAX D MAX
Exhaust Airflow Supply Airflow
WPB SIZE
A B C SQ.
21 21.25 3.50 25 15.88 15.88 18.44 18.44 22 x 22 56 145T 24 24.25 3.50 28 16.19 16.19 19.19 19.19 25 x 25 56 145T 30 30.38 4.00 36 17.81 19.31 20.50 22.00 33 x 33 145T 184T 36 36.38 5.00 42 17.50 19.13 21.50 23.13 39 x 39 145T 184T 42 42.38 5.50 48 17.88 19.38 22.19 23.75 45 x 45 145T 184T 48 48.38 6.00 54 18.75 20.13 23.06 24.63 51 x 51 145T 184T 54 54.38 6.50 60 18.88 20.50 23.69 25.19 57 x 57 145T 184T 60 60.38 7.25 66 19.50 24.75 24.44 29.94 63 x 63 145T 215T
EXHAUST SUPPLY
L1 L2 L1 L2
FRAME
2.00
AIR FLOW
B
Twin City IM-4800 15
Page 16
Dimensional Data
WPB – Belt Driven, Level 3, Sizes 21-36
AIR FLOW
D MAX D MAXC SQ. OUTSIDE
2.00
B
A DIA.
Exhaust Airflow Supply Airflow
WPB SIZE
A B C SQ.
EXHAUST SUPPLY
21 21.25 3.50 25 17.25 20.50 22 x 22 145T 24 24.25 3.50 38 17.25 20.50 25 x 25 145T 30 30.38 4.00 36 18.31 20.93 33 x 33 184T 36 36.38 5.00 42 18.31 21.93 39 x 39 184T
D MAX
DAMPER
SIZE
WPB – Belt Driven, Level 3, Sizes 42-60
A DIA.
MAX
MOTOR
FRAME
2.00
AIR FLOW
B
C SQ. OUTSIDE D MAX D MAX
AIR FLOW
2.00
B
A DIA. A DIA.
Exhaust Airflow Supply Airflow
WPB SIZE
A B C SQ.
EXHAUST SUPPLY
D MAX
DAMPER
SIZE
42 42.38 5.50 48 21.31 26.75 45 x 45 215T 48 48.38 6.00 54 21.31 26.75 51 x 51 215T 54 54.38 6.50 60 26.13 32.30 57 x 57 254T 60 60.38 7.25 66 26.13 32.30 63 x 63 256T
MAX
MOTOR
FRAME
2.00
AIR FLOW
B
TWIN CITY FAN & BLOWER | WWW.TCF.COM
5959 Trenton Lane N | Minneapolis, MN 55442 | Phone: 763-551-7600 | Fax: 763-551-7601