TCF 14HA1B, 12HA2B, 12HA3B, 12HA1B, 14HA2B Installation, Operation & Maintenance Manual

...
Page 1
HA/HAB Fiberglass
Wall Mount Ventilators
INSTALLATION, OPERATION & MAINTENANCE MANUAL
Throughout this manual, there are a number of HAZARD WARNINGS that must be read and adhered to in order to prevent possible personal injury and/or damage to equipment. Two signal words "WARNING" and "CAUTION" are used to indicate the severity of a hazard and are preceded by the safety alert symbol.
WARNING Used when serious injury or death MAY result from misuse or failure to follow specific instructions.
CAUTION Used when minor or moderate injury or product / equipment damage MAY result from misuse or failure to follow specific instructions.
It is the responsibility of all personnel involved in installation, operation and maintenance to fully understand the Warning and Caution procedures by which hazards are to be avoided.
IM-3100
August 2015
Receiving
The HA/HAB ventilator is shipped in two parts:
1. Fan housing assembly complete with fiberglass inlet venturi to the wheel and complete motor and drive assembly.
2. Flanged extruded aluminum louver assembly.
Duct adapter and companion angles are shipped loose if unit is for inline application.
Handle the units carefully while delivering to installation location. Use ordinary care in unpacking the units. If the units, when unpacked, appear to be damaged in a way that could not be determined at the time of delivery, notify the carrier that concealed damage has been discovered and insist on inspection by the carrier. Obtain a copy of carrier’s inspection report showing the concealed damages so that a claim can be filed through your usual channels.
Study the attached installation prints carefully. Inspect the units carefully for identification marks, fan rotation symbols, etc.
Installation
Wall Application
1. Remove wood shipping supports from fan assembly (see Figure 1).
1
2. Locate and provide hole in the wall the fan housing (see Figure 2). This will provide an opening for the electrical wiring into the unit.
3. Anchor the box in the wall, keeping a minimum of 23⁄8" between the outside wall and any part of the box or the power assembly.
4. Fasten the flanged extruded louver to the exterior wall.
Inline Application
1. Remove wood shipping supports from fan assembly (see Figure 1).
2. Attach duct adapter and companion angles to unit per Figure 3 with fasteners supplied.
3. Before anchoring the unit to the ductwork, check line voltage and current characteristics outlined in previous section.
4. Fasten the flanged extruded louver to the exterior wall wherever the outlet of the ductwork ends.
For easy maintenance of the ventilator inline, provide a drop-out section between ductwork and duct adapter (see Figure 3).
2" larger than
©1997 – 2018 Twin City Fan Companies, Ltd.
Page 2
Check, Test & Start Procedure
WARNING
Electric shock hazard. Could cause severe injury or death. Failure to bond the frame of this equipment to the building electrical ground by use of the grounding terminal provided or other acceptable means may result in electrical shock. Disconnect electric power before servicing equipment. Service to be performed only by qualified personnel.
1. Check to verify that the wheel is free to rotate.
2. Verify that supply voltage on the line side of disconnect agrees with voltage on unit identification plate and is within the utilization voltage range as indicated in Table
1.
3. On three-phase units check and calculate phase unbalance as follows:
% Voltage Unbalance = 100 x max. voltage deviation from avg. voltage ÷ avg. voltage
Given example: With voltage of 220, 216 and 213
How To Use The Formula: a. Avg. Voltage = 220 + 216 + 213 = 649 ÷ 3 =
216
b. Max. Voltage Deviation From Avg. Voltage =
220 – 216 = 4 c. % Voltage Unbalance = 100 x (4 ÷ 216) = 1.8% Voltage unbalance should not exceed 2%.
5. Electrical Input Check: Perform check of fan ampere draw and verify that motor nameplate amps are not exceeded. Take account of the service factory range if motor is nameplated above a 1.0 service factor.
6. Fan RPM Check: Fan RPM should be checked and verified with a tachometer. Refer to Table 2 for maximum fan RPM values.
WARNING
Running fan at an RPM greater than the maximum RPM value in Table 2 will overload the fan motor and lead to premature motor failure.
Table 2. Maximum Fan RPM (Belt Driven Units)
MODEL
HAB
12HA1B, 2B, 3B 14HA1B, 2B, 3B 14HA4B 14HA5B 18HA1B, 2B 18HA3B 18HA4B 18HA5B 24HA1B 24HA2B 24HA3B 24HA4B 24HA5B 30HA1B 30HA2B 30HA3B 30HA4B 30HA5B 30HA5B
MOTOR
HP
1/4 1738 1/4 1468 1/3 1615 1/2 1849 1/4 945 1/3 1040 1/2 1191 3/4 1363 1/4 575 1/3 633 1/2 725 3/4 830
1 913 1/3 436 1/2 500 3/4 572
1 630
1
/2 721
1
2 793
MAXIMUM
FAN RPM
Table 1. Utilization Voltages
SYSTEM VOLTAGE/
UNIT NAMEPLATE
115/60/1 208-230/60/1 or 208- 230/60/3 187 253 230/60/1 or 230/60/3 207 253 277/60/1 249 305 200/60/3 180 220 380/60/3 342 418 460/60/3 414 506 575/60/3 517 633 110/50/1 99 121 220/50/1 198 242 380-415/50/3 342 456 440/50/3
UTILIZATION VOLTAGE
MIN. MAX.
104 127
396 484
4. Apply power to unit and check rotation of wheel with the directional arrow on the unit.
WARNING
Especially check three-phase units for rotation. For three-phase, rotation can be changed by interchanging any two of the three line leads. If the unit is checked on temporary wiring, it should be rechecked when permanently installed. Motor burn-out or tripped overload protection devices are usually the result of wrong rotation.
Maintenance
General
Fan shaft bearings on belt drive units are factory lubricated and require no lubrication for the first 3-6 months of operation. Lubricate at intervals shown in Table 3 thereafter. With fan running and with a low pressure grease gun, add grease slowly until a slight bead forms between the seals. Use Sinclair Litholene, Shell Gadus S2 V100 2, Socony Vacuum Armvac 781, Sinclair Oil Stranolith 57 or equal.
Table 3. Bearing Lubrication Interval (Belt Drive Model HAB Only)
OPERATING CONDITION GREASING INTERVAL
FAIRLY CLEAN
MODERATE TO
EXTREMELY DIRTY
1. Frequency or regreasing will vary, depending on the hours of operation, temperature and surrounding conditions.
2. Bearings have been prelubricated from factory with NLGI Grade No. 2 lithium-12 hydroxysterate base grease.
Belts on belt-drive units should be readjusted after 24 hours of operation. Loosen motor base bolts and apply 15 lbs. pull per belt for proper belt tensions. Tighten motor base bolts.
Check contact surfaces of belt for excessive wear. If belts have a slick, glazed look or are cracked, belts are slipping. Replace belts as required.
6 to 12 Months
1 Month
2
Twin City Installation and Maintenance Manual IM-3100
Page 3
Motors require no lubrication for 10 years of normal operation.
The inlet venturi is molded shock-resistant, bonded, reinforced fiberglass and will require no maintenance.
Wall Application
1. Servicing or inspecting the unit can be accomplished from the exterior by removing the flanged extruded louver and from the interior of the building by removing the fiberglass inlet (see Figure 2).
2. To remove the motor assembly for servicing, unplug the motor from the provided outlet and unfasten the four vibro-isolator bolts. The entire motor assembly, including the wheel and bearing (belt drive units), will slide out of the housing.
Figure 1. Removal of Wood Shipping Supports
Housing
Inline Application
For easy maintenance of the inlet unit, provide a dropout section between the ductwork and duct adapter (see Figure 3).
Servicing or inspection can then be accomplished by removing the dropout section, then removing the fiberglass inlet. The motor assembly can then be removed by disconnecting the motor from the provided outlet and unfastening the four vibro-isolator bolts. Periodic inspection and cleaning of the fan will insure smooth operation.
Figure 2. Wall Application
Electrical Wiring By Others
Instructions: Remove wood shipping supports frame before installing unit
Hole Provided for Electrical Entrance Into Unit
Electrical Junction Box With Outlet
Belt Drive Motor Assembly
.
Louver Assembly
Fan
Housing
Assembly
Twin City Installation and Maintenance Manual IM-3100
Direct Drive Motor
Assembly
By Removing 4 Fasteners (Interior Side)
Trim Angle Assembly
Access To Power Pack of Ventilator
or Louvers (Exterior Side)
Fiberglass Inlet Venturi
3
Page 4
Figure 3. Inline Application
Louver Assembly
on Exterior Wall
Wiring By Others
Ductwork By Others
Duct Adaptor (Shipped Loose With Fasteners)
Ductwork By Others
Companion Angles (Shipped Loose)
With Fasteners)
Access to Power Pack of Inline
Unit By Removing 4 Fasteners
Dropout Section of Duct For
Easy Maintenance (By Others)
4
Twin City Installation and Maintenance Manual IM-3100
Page 5
Location
Serviced by
Job Name: _______________________ Organization: _____________________ Address: _________________________ Address: _________________________ City / State / Zip: __________________ City / State / Zip: __________________ Telephone: ( ) _________________ Telephone: ( ) _________________ Contact: _________________________ Contact: _________________________
Fan
Nameplate Information
Motor
Nameplate Information
Model: _____________________
HP ____ Rpm _____
Volts _________
Serial #: ____________________
Phase ___ Hz ____
Amps _________ (FLA)
Tag/Mark: __________________
Mfr: ____________
Model: ___________ Location: ___________________ Frame _______ Enclosure _________ Date Installed: _______________ Thermal Protection: Yes ___ No ___
Air Volume: Design CFM __________ Power Supply ________ Volts _______
Fan Rpm: _______
Actual CFM __________ (actual)
Drives: Motor Sheave ______________ Bushing __________ Turns Open _____
Fan Sheave ______________ Bushing __________ Belt __________ Qty ___
Date Done By
MAINTENANCE
MAINTENANCE RECORD
Notes
Refer to page 2 for recommended maintenance.
Seller warrants to the original purchaser that the goods sold hereunder shall be free from defects in workmanship and material under normal use and service (except in those cases where the materials are supplied by the buyer) for a period of one year from the date of original installation or eighteen (18) months from the date of shipment, whichever occurs first. The liability of seller under this warranty is limited to replacing, repairing, or issuing credit (at cost, F.O.B. factory and at seller’s discretion) for any part or parts which are returned by buyer during such period provided that:
a. seller is notified in writing within ten (10) days
following discovery of such defects by buyer, or within ten (10) days after such defects should reasonably have been discovered, whichever is less;
b. the defective unit is returned to seller, transportation
charges prepaid by buyer.
c. payment in full has been received by seller or said
products; and
d. seller’s examination of such unit shall disclose to its
satisfaction that such defects have not been caused by misuse, neglect, improper installation, repair, alteration, act of God, or accident.
Limited Warranty
No warranty made hereunder shall extend to any seller product whose serial number is altered, effaced or removed. Seller makes no warranty, express or implied, with respect to motors, switches, controls, or other components of seller’s product, where such components are warranted separately by their respective manufacturers. THIS WARRANTY IS EXPRESSLY IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, WHETHER STATUTORY OR OTHERWISE, INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. In no event shall seller be liable to buyer for indirect, incidental collateral, or consequential damages of any kind. (BUYER’S FAILURE TO PAY THE FULL AMOUNT DUE WITHIN SIXTY (60) DAYS OF DATE OF INVOICE SHALL OPERATE TO RELEASE SELLER FROM ANY AND ALL LIABILITY OR OBLIGATION ARISING PURSUANT TO ANY WARRANTY, EXPRESS OR IMPLIED, WHETHER STATUTORY OR OTHERWISE, INCLUDING ANY IMPLIED WARRANTY OR MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, MADE IN CONNECTION WITH ANY CONTRACT FORMED HEREUNDER. BUYER AGREES THAT SUCH FAILURE TO PAY SHALL CONSTITUTE A VOLUNTARY WAIVER OF ANY AND ALL SUCH WARRANTIES ARISING PURSUANT TO SUCH CONTACT.)
Twin City Installation and Maintenance Manual IM-3100
5
Page 6
TWIN CITY FAN & BLOWER | WWW.TCF.COM
5959 Trenton Lane N | Minneapolis, MN 55442 | Phone: 763-551-7600 | Fax: 763-551-7601