Tatsuta Electric Wire & Cable Co., Ltd. System Electronics Division
<<<Important Safety Instructions>>>
Warning
Erroneous operation of this water leakage detector not complying with the warning labels or the following
warnings may not only lead to possible fatality or serious injury, but also fire, electric shock or failure.
Warnings!
Strictly prohibited!
□ Never modify or disassemble the detector.□ The unqualified persons are forbidden to carry out the installation and the internal inspection and spot check. □ Do not touch any internal component of the detector with wet hands. □When performing maintenance on the product, avoid using organic solvent. Use soft cotton wastes such as the gauze
to wipe gently.
□ After the detector is installed, do not leave the cover open, except for the periodic inspection and maintenance.
-{}- Checkpoits!
□ Check detector supply voltage and rated voltage before installing.
□ When installing and making electrical connections to this detector, follow the instructions in the operation manual.□When inspecting and carrying out maintenance on this detector, follow the instructions in the operation manual.□When using control output contacts, check the contact rated load in the operation manual.
Do not install the detector in the following locations!
□ Locations easily accessible to the general public. □ Locations close to sources of vibration, corrosive gas or strong electromagnetic induction.□ Locations subject to excessive waste and dust.□ Locations where there is a possibility of exposure to water, or high temperature and humidity
Warranty
Before shipping, this product is subjected to strict quality control and inspection. In the event of spontaneous
failure resulting from defective manufacturing, we will repair or replace it according to the following provisions.
Warranty Provisions
1. Warranty period (one year after the delivery date of the product) Should the product fail during the warranty period under normal usage according to the operation manual, we will repair
or replace it free of charge. Please contact us using the contact information given below.
2. Cases not covered by the warranty
① After the period of warranty ① Failures due to incorrect usage, and unauthorized repairs and modifications ① Failures or damages due to moving, dropping etc. after purchase ① Failures or damages due to fire and natural disasters ① Failures not attributable to this product ① Fees for on-site service (visiting fee and technical fee)
Consultation
Shanghai Representative Office: Room B28/F, Huadu Mansion, No.838 Zhang Yang Road, Pudong New Area, Shanghai, China, ZIP 200122
8-1. Ratings
8-2 Performances
8-3 Control Output Contact Specifications
◇Attached Drawing 1 Outside Dimensions of Water Leakage Detector (AD-AS-10DRM)
◇Attached Drawing 2 Parts Layout of Water Leakage Detector (AD-AS-10DRM)
◇Attached Drawing 3 Parts Layout of CPU Unit (AD-AS-CPU)
◇Attached Drawing 4 Parts Layout of 5-circuit expansion unit
◇Attached Drawing 5 Instructions to the Resistance/ Detection Precision Operation
◇Attached Drawing 6 Instructions to Operation Switchover DIP Switch (AD-AS-10DRM)
Page 4
Termianal block for main control output contatct
(
Main water leakage and abnormality
)
(
Water leakage and break
) No.1~5
Terminal block for power source
Terminal block for individual control output contatct
(
water leakag
e and break
) No.6~10
Upper segment: CPU unit
Lower segment: 5
-
circuit expansion u
nit
First of all, thank you very much for purchasing the Water Leakage Detector AD-AS-10DRM.
Before using, read this operation manual carefully to ensure correct operation. Keep this manual in a convenient place for
quick reference.
1.Installation and Handling Precautions
1-1. Installation
1)Remove CPU unit and 5-circuit expansion unit from the body case. (Use M3 screw)
In winter, pay special attention to static electricity and install by holding board edge.
2) Drill installation hole and connecting hole on the body case, do not leave cutting power, etc.
3) After the body case is installed in the setting place, install various units removed in 1).
4) Install the terminal block wires and connectors on the CPU unit and 5-circuit expansion unit.
1-2 Handling Precautions
1) Use the detector in an environment with a temperature range between -10˚C and 50˚C, and a humidity range
between 35%. and 85%.
2)Do not use the detector in any location close to sources of vibration and harmful gas, and strong electromagnetic
inductive power sources, which may lead to malfunction and failure.
3) Avoid using the socket lead as the power source as far as possible, and use fixed wire to connect power source.
4) After installation, be sure to conduct tests in conformance with the operation check items described in Chapter 3.
2. External Connection
To form CPU unit AD-AS-CPU and 5-circuit expansion unit AD-AS-UNIT, set the terminal block as shown in Drawing 1.
Individual terminal block
for individual control output contactc
Terminal block
for connection sensor No.1~5
Terminal block
for connection sensor No.6~10
Drawing 1 Layout Drawing for Terminal Block
2-1 Power Connection Before connection, check that the power supply voltage is within the range of use, then connect it securely to the
terminal block.
*Inputting a power voltage outside the range of use may cause malfunctions and failure of the detector, so care should
be taken.
AC100V~AC200V
Drawing 2. Terminal Block for Power Supply
-1-
Page 5
S1 S2 S3
S4 S5
S6 S7
S8
S9 S10
CPU Unit
Connection Sensor
1~5
Connection Sensor
6~10 5-Circuit Expansion Unit
2-2 Water Leakage Sensor Connection (Refer to Attached Drawing 3 and Attached Drawing 4)
Connect the water leakage sensor to the “S1”-“S10” of the sensor connection terminal block. The sensor has no polarity.
Example: For S1, connect the water leakage sensor to A-6 and B6.
*Be sure to install break detection terminal on water leakage sensor.
If it is the point sensor, use break detection terminal built-in product (AD-PA-R).
(Precautions)
◇ When sensor is not connected, set the DIP switch at the position “ON”. When not set “ON”, break alarm will be
output. (Note) DIP switch dispatched by the factory has been set at the position “1”.
◇ When conducting wire change, etc., conduct it under the condition that the detector power source has been cut off.
◇ A-1 and B-1.are not used Do not connect water leakage sensor.
ON
1
ON
1
ON
1
ON
1
ON
1
ON
1
ON
1
ON
1
ON
1
ON
1
Drawing 3 Terminal Block for Sensor
2-3 Connection of Main Control Output Contact (Refer to Attached Drawing 3)
Due to main output contact of water leakage and abnormalities (contact c), connect when external control is required.
Setting SW2 on CPU unit, the operation can be changed as activated only when the break and
recovery occur.
For details, refer to Attached Drawing 6.
Water leakage
COM NC NO COM NC NO
Abnormality
Drawing 4 Main Control Output Contact
Water leakage contacts COM-NO: Closed when single-circuit water leakage is detected
COM-NC: Open when single-circuit water leakage is detected
Abnormality COM-NO: Closed when single-circuit water leakage or break is detected
COM-NC: Open when single-circuit water leakage or break is detected
*Contact operation
Setting SW2 on CPU unit can enable the alarm hold and the fail-safe function to be effective.
* If the fail-safe function is effective, the contact will be operated reversely.
For details, refer to Attached Drawing 6 and the Operation Chart of Chapter 4.
*Abnormal contact
-2-
Page 6
Power Indicator
LED
Power Switch
Thermistor
2-4 Connection of Individual Control Output Contact (Refer to Attached Drawing 3 and Attached Drawing 4)
Due to individual output of water leakage and break (contact c), connect when external control is required.
CPU Unit 5-Circuit Expansion Unit
Drawing 5 Individual Control Output Contacts
Water leakage (Rn) COM-NO: Closed when water leakage is detected under n circuit
COM-NC: Open when water leakage is detected under n circuit
Break (Dn) COM-NO: Closed when break is detected under n circuit
COM-NC: Open when break is detected under n circuit
*Contact operation
Setting SW2 on the CPU unit, the function of alarm hold and fail-safe can be effective.
* If the fail-safe function is effective, the contact will be operated reversely.
For details, refer to Attached Drawing 6 and the Operation Chart of Chapter 4.
3. Operation Check
3-1 Power-On (Refer to Attached Drawing 3) When the power source switch is at -, it is ON, when at o, it is OFF.
Set the CPU unit power source switch “ON” and check that the power source indication LED on the CPU unit is
lighting up.
In the case that the LED does not light up, the detector may be out of order. Power off the detector promptly and
contact the manufacturer.
Drawing 6 Power Switch
-3-
Page 7
3-2 Check for Break Detection Function (Refer to Attached Drawing 3, Attached Drawing 4 and Drawing 3)
1) Check that the DIP switch for the circuit required to be checked has been set at “I”.
2) After powering off the detector, remove the water leakage sensor from the trunk terminal block and
then power on the detector.
3) The buzzer sounds, the break Indicator LED flashes, and individual contacts (break) function.
4) After the operation check, power off the detector, and then connect the sensor and the DIP switch again.
*When water leakage sensor circuit is not connected, set the DIP switch at “ON”.
*When water leakage sensor circuit is connected, set the DIP switch at “1”.
3-3 Check for Water Leakage Detection Function (Refer to Attached Drawing 3, Attached Drawing 4 and Drawing 3)
1) Check that the DIP switch for the circuit required to be checked has been set at “I”.
2) Drop tap water on the sensor.
3) The buzzer sounds, the water leakage Indicator LED flashes, and individual contacts (water leakage) function.
4) Wipe the tap water dropped on the sensor with dry rags, etc. and check that the water leakage status returns
to normal.
-4-
Page 8
Power
Power Indicator
LED
Indicator LED Test Switch
Water leakage detection function
Water leakage indicator
LED
Break detection function
Break indicator
LED
Buzzer Alarm Stop Switch
B
uzzer stop indicator
LED
Buzzer sounding
Total control output contact
Total control output contact
(
water leakage:
COM-NO)
(
Abnormal:
COM-NO)
(
Water leakage:
COM-NO)
(
Break:
COM-NO)
Individual control output contact
Individual control output contact
OFF OFF
OFF
OFF
OFF OFF
OFF
OFF
OFF
OFF OFF OFF OFF OFF
ON
ON
ON
ON ON
ON ON ON
Lighting out
Lighting out
Lighting out
Lighting out
Lighting out
Lighting out
Lighting out
Lighting out
Lighting out
Lighting out
Lighting out
Lightin
g up Lighting up
Lighting up
Lighting up
Lighting up
Lighting up
Lighting up
Lighting up
Open Open
Open Open Open
Open Open
Open Open
Closed
Closed
Closed
Closed
Closed
4. Operation Chart
4-1 Standard Operation Chart
(* No setting of failure safety and alarm hold)
For Operation Chart, refer to Drawing 7
Fail-safe function
Drawing 7 Operation Chart 1
Buzzer Operation
Press the buzzer stop switch and the buzzer stops.
However, if the same circuit or other circuits give the alarms again, the buzzer will re-sound. To make the buzzer not
alarm, set SW2 and Bit 8 of the CPU unit ON.
If the failure safety function is effective, the output contact will be operated reversely.
-5-
Page 9
Power
Power Indicator
LED
Indication LE
D test switch
Water Leakage Indicator
LED
Break detect
ion function
Break Indicator
LED
Buzzer alarm stop switch
Buzzer Stop Indicator
LED
Buzzer sounding
Main control output contact
Main control output contact
(water leakage:
COM-NO)
(
Abnormal:
COM-NO)
(
water leakage:
COM-NO)
(
break:
COM-NO)
Individual control output co
ntact
Individual control output contact
OFF OFF
OFF
OFF
OFF OFF
OFF
OFF
OFF
OFF OFF
OFF OFF OFF
ON
ON
ON
ON ON ON ON Lighting out
Lighting out
Lighting out
Lighting out
Lighting
Lighting out
Lighting out
Lighting up
Lighting up
Lighting up
Lighting up
Lighting up
Open Open
Open
Open
Open
Open Open
Open
Closed
Closed
Closed
Closed
(alarm cancel switch)
Flashing twice
Flashing twice
Flashing twice
ON
Lighting
Lighting
ON
4-2 Operation Chart When Alarm Hold Setting is Activated
(Water leakage, break indication, main control output contact and individual control output contacts are set to be
alarm hold) For Operation Chart, refer to Drawing 8
Water leakage detection function
out
out
out
When alarm holding is activated, the alarm status is held until the indicator LED test switch (alarm cancel switch) is
pressed. Electric power failure or power off, alarm holding is canceled. * When alarm hold is not set for switch 1, 2
and 3, refer to Drawing 7 and Operation chart 1.
Drawing 8 Operation Chart 2
-6-
Page 10
Circuit No. Indicator
LED Indicator
LED for resistance/ detection sensitivity
Circuit selection switch
(1~5 : 1~5 circuit)
5. Adjustment of Water Leakage Detection Precision
5-1 Adjustment Method (Refer to Attached Drawing 3, Attached Drawing 4, Attached Drawing 5 and Attached Drawing 6)
1) Rotate circuit selection switch to select the circuit required to be adjusted.
2) Set the 1 of SW2 on the CPU unit ON to indicate detection sensitivity.
(Drawing 9 shows that the target detection precision of Circuit 1 has been set 5.0kΩ.)
3)Rotate the precision adjustment VR of the required circuit, observe the precision indication while adjusting the value
required to be set.
Clockwise rotation indicates that the precision is higher, and counterclockwise rotation indicates that the precision is
lower.
The detection precision can be adjusted within the scope 2.0kΩ~9.0kΩ±10% by the interval 0.5kΩ.
4) If the precision adjustment is completed, set the 1 of SW2 at CPU unit to be OFF.
The detector of the company has been adjusted to be the standard precision (about 5kΩ) according to the
characteristic of the water leakage sensor (manufactured by our company) when dispatched from the factory.
When the detection precision is required to be changed, contact with our company for confirmation.
6. Buzzer Setting
6-1 Buzzer Volume Setting
Perform volume adjustment through the volume adjustment VR of the indicator unit.
When rotating clockwise, the volume is increased and when rotating counterclockwise, the volume is decreased. When dispatched from the factory, the volume has been set as the maximum.
6-2 Buzzer Stop Setting
1) Applicable to the occasion when alarming, buzzer sounding is required not to be activated temporarily
When alarming is given put, press the buzzer stop switch, the buzzer stops, indicator LED lights up and the buzzer
stops temporarily.
However, if the same circuit or other circuits alarms again, the buzzer stops, the indicator LED lights out and the
buzzer sounds again.
When the alarms from all the circuits recover, the indicator LED for buzzer stops lights out.
(Refer to Operation Chart in Chapter 4)
2) When the buzzer sounding is required not to be activated often
Set 8 of SW2 of the CPU to be ON.(Refer to Attached Drawing 5)
When the indicator LED for buzzer stop lights up, the buzzer sounding is set to be not activated..
-7-
Page 11
7. Maintenance and Periodic Inspection
◇ When inspecting the facilities, conduct inspections in conformance with the operation check items described in
Chapter 3.
(Note)During inspection of the detector, the control output contacts are functioning, so if the control output
contacts are used, adopt the measures such as underlay wiring in order not to affect other devices.
◇ Be careful to prevent oil-based substances, such as wax, from adhering to the sensor; this may repel water and
interfere with correct detector operation.
◇ If the sensor is tainted with water absorbing substances, electrically conductive dirty water, etc., replace it with a
new one.
-8-
Page 12
Maximum sound pressure: 70dB / 30 cm (Catalogue value by
Contact
configuratio
8. Specifications
8-1. Ratings
For ratings, see Table 1.
Item Specification
Rated voltage AC100-200V (common to 50/60Hz)
Range of fluctuation for supply
voltage
Power consumption 20VA or less
Control output contacts *Check Section 8-3, control output contact specifications
Applied voltage of sensor AC5.5V (maximum value)
Working ambient temperature
Working ambient humidity
8-2 Performances For performances, refer to Table 2.