Tartarini Final Element SIL Verification - K Series, Tartarini-EN Manuals & Guides

Final Element SIL Verification
Project:
SIL Verification for BM9/BM5/BM5A (Contained Controller) SSV and COAX K
Customer:
Emerson Process Management Regulator Technologies, Inc.
China
Contract Number: Q21/04-020
Report No.: ERD 21/04-020 R001
Version V1, Revision R1, April 9, 2021
Jack Gao
The document was prepared using best effort. The authors make no warranty of any kind and shall not be liable in any
event for incidental or consequential damages in connection with the application of the document.
© All rights reserved.
Management Summary
Target
Achievable SIL Limits
SIL
RRF
PFDavg
AC
SC
This report documents the results of the Final Element SIL Verification for the SSV Remote Control with Solenoid Valve project. The Final Element SIL Verification was performed by exida on behalf of Emerson Process Management Regulator Technologies, Inc.
Industry standards for SIS require that for each Safety Instrumented Function (SIF), a Safety Integrity Level (SIL) target is selected and achievement of that target is confirmed by quantitative analysis. The SIL represents the amount of risk reduction that is required to ensure a tolerable risk is achieved for each specific hazard that is safeguarded by a SIF. For each SIF, this is a function of the risk the process poses without considering the benefit of the SIS. In order to determine the amount of risk reduction that is achieved, the conceptual design of the SIF must be evaluated in a SIL verification. The SIL verification considers probability of failure, minimum redundancy, and SIL capability requirements that result from the target SIL for each SIF.
In some cases suppliers of final elements are asked to provide confirmation that the final element meets specific performance requirements. In these cases verification is performed on just a portion of the equipment in the SIF.
exida supported the Final Element SIL Verification process by performing the following tasks:
Safety Integrity Level Verification on the final element
This analysis covers only the final element. To determine the performance of the SIF these results must be combined with the results for the sensor and logic elements.
exida in cooperation with Emerson Process Management Regulator Technologies, Inc. performed the SIL Verification to support the SSV Remote Control with Solenoid Valve. The SIL Verification calculation was performed to document the SIL level achieved by the final element(s).
Table 1 shows a summary of the SIL verification results. Details of the SIL verification process are presented in the exSILentia report in Appendix D.
Table 1 Final Element SIL Verification Summary
SIF Tag
SIF Name
RRF
Remarks
BM5/BM5A SSV (contained OS/8*X
SIF-01
Series Controller) +
174.6
COAX K Series Solenoid Valve
2 100 2 2 3
Comply
BM9 SSV (contained
SIF-02
OS9/8*X Series Controller) + COAX K Series Solenoid Valve
155.1
Note: COAX K Series Solenoid Valve detail model refer to [D2]
T-127 V1,R1 Page 2 of 27
© exida ERD 21_04-020 R001 V1R1 SIL Verification Report Final Element
Table of Contents
1 Purpose and Scope ........................................................................................................ 5
1.1 Background ......................................................................................................................... 5
1.2 Objectives and Scope ......................................................................................................... 5
2 Project Management ...................................................................................................... 6
2.1 exida ................................................................................................................................... 6
2.2 Project phases .................................................................................................................... 6
2.3 Roles of the parties involved ............................................................................................... 6
2.4 Standards and literature used ............................................................................................. 6
2.5 Reference documents ......................................................................................................... 7
2.5.1 Documentation provided by Emerson Process Management Regulator Technologies,
Inc. .............................................................................................................................. 7
2.5.2 Documentation generated by exida ............................................................................ 7
3 Final Element SIL Verification ........................................................................................ 8
3.1 Assumptions ........................................................................................................................ 8
3.2 Analysis Results .................................................................................................................. 9
3.2.1 Architectural Constraints ............................................................................................. 9
3.2.2 SIL Capability ............................................................................................................ 10
3.2.3 Probability of Failure on Demand .............................................................................. 10
4 Conclusions and Recommendations ............................................................................ 12
5 Terms and Definitions ................................................................................................... 13
6 Status of the Document ................................................................................................ 15
6.1 Liability .............................................................................................................................. 15
6.2 Version History .................................................................................................................. 15
6.3 Future enhancements ....................................................................................................... 15
6.4 Release signatures ........................................................................................................... 15
Appendix A SIL Verification Methodology .................................................................... 16
A.1 Overview ........................................................................................................................... 16
A.2 Modeling Assumptions ...................................................................................................... 17
A.3 Data and Statistics ............................................................................................................ 17
Appendix B Proof Tests ............................................................................................... 19
B.1 Base SIF Modeled Proof Test ........................................................................................... 19
B.2 SIF with PVST Modeled Proof Test .................................................................................. 19
B.3 Proof Test Coverage ......................................................................................................... 19
Appendix C Final Element Schematic .......................................................................... 20
Appendix D Detailed IEC 61511 Compliance Report ................................................... 21
D.1 SIF-01 BM5/BM5A SSV (contained OS/8*X Series Controller) + COAX K Series Solenoid
Valve ................................................................................................................................. 21
© exida ERD 21_04-020 R001 V1R1 SIL Verification Report Final Element
T-127 V1,R1 Page 3 of 27
D.1.1 General SIF Information .................................................................................................. 21
D.1.2 Safety Integrity Levels ..................................................................................................... 21
D.1.3 SIL Verification Parameters and Results ......................................................................... 21
D.1.4 Final Element Part Configuration ..................................................................................... 22
D.1.4.1 Final Element Group 1: BM5/BM5A SSV (contained OS/8*X Series Controller) +
COAX K Series Solenoid Valve ........................................................................................ 23
D.1.4.2 Final Element Leg 1-1: Final Element Leg ................................................................ 23
D.2 SIF-02 BM9 SSV (contained OS9/8*X Series Controller) + COAX K Series Solenoid Valve
24
D.2.1 General SIF Information .................................................................................................. 24
D.2.2 Safety Integrity Levels ..................................................................................................... 24
D.2.3 SIL Verification Parameters and Results ......................................................................... 24
D.2.4 Final Element Part Configuration ..................................................................................... 25
D.2.4.1 Final Element Group 1: BM9 SSV (contained OS9/8*X Series Controller) + COAX K
Series Solenoid Valve ....................................................................................................... 26
D.2.4.2 Final Element Leg 1-1: Final Element Leg ................................................................ 26
© exida ERD 21_04-020 R001 V1R1 SIL Verification Report Final Element
T-127 V1,R1 Page 4 of 27
1 Purpose and Scope
This report documents the results of the Final Element SIL Verification for the SSV Remote Control with Solenoid Valve project. The Final Element SIL Verification was performed by exida on behalf of Emerson Process Management Regulator Technologies, Inc.
1.1 Background
The functional safety standards describing the implementation of SIS are based on the safety lifecycle. The safety lifecycle is a management system that will yield a functionally safe system if all steps are implemented properly. The IEC 61511 standard introduces the concept of Safety Integrity Level (SIL). SIL is a measure of the amount of risk reduction that a Safety Instrumented Function (SIF) is capable of providing, as defined by its average Probability of Failure on Demand (PFD
IEC 61511 requires that for each Safety Instrumented Function (SIF), a SIL target is selected and achievement of that target is confirmed by quantitative analysis. The required amount of risk reduction is a function of the unmitigated risk of the process, or the risk the process poses without considering the SIF. In order to determine the amount of risk reduction that is required, the process risk must be compared against guidelines for tolerable risk. The difference between the process risk and the tolerable risk is the required risk reduction capability for the SIF. In order to determine the amount of risk reduction that is achieved, the conceptual design of the SIF is evaluated during SIL verification where probability of failure, minimum redundancy, and SIL capability requirements are analyzed.
) or Probability of Failure per Hour (PFH).
AVG
In some cases, suppliers of final elements are asked to provide confirmation that the final element meets specific performance requirements. In these cases, verification is performed on just a portion of the equipment in the SIF.
1.2 Objectives and Scope
The objective of this study is to verify, through quantitative analysis, the achieved SIL for the final element(s) identified in the SSV Remote Control with Solenoid Valve project. The SIL verification process yields estimates for average probability of failure on demand (PFD without architectural constraints), achieved SIL Capability, and mean time to fail spuriously (MTTFS).
This report covers the quantitative aspects of the SIL verification only. Qualitative requirements as for software development are not addressed by the assessment described in this report.
), SIL (with and
AVG
© exida ERD 21_04-020 R001 V1R1 SIL Verification Report Final Element
T-127 V1,R1 Page 5 of 27
2 Project Management
2.1 exida
exida is one of the world’s leading accredited Certification Bodies and knowledge companies,
specializing in automation system safety and availability with over 400 years of cumulative experience in functional safety. Founded by several of the world’s top reliability and safety experts
from assessment organizations and manufacturers, the world.
lifecycle engineering tools, detailed product assurance, cyber-security and functional safety certification, and a collection of on-line safety and reliability resources.
comprehensive failure rate and failure mode database on process equipment based on 250 billion hours of field failure data.
exida offers training, coaching, project-oriented system consulting services, safety
2.2 Project phases
This report, the Final Element SIL Verification for the SSV Remote Control with Solenoid Valve project, documents the results of the analysis performed by exida on behalf of Emerson Process Management Regulator Technologies, Inc.
exida performed the following tasks as part of this project:
exida is a global company with offices around
exida maintains a
Safety Integrity Level Verification on the final element
2.3 Roles of the parties involved
Emerson Process Management Regulator Technologies, Inc. - Manufacturer of the BM9/BM5/BM5A SSV and the integrator of the SSV and COAX K Series Solenoid Valve assembly
exida - Project leader for the Final Element SIL Verification
2.4 Standards and literature used
The services delivered by exida were performed based on the following standards / literature.
[N1] IEC 61508-2: 2010 Functional Safety of Electrical/Electronic/Programmable
Electronic Safety-Related Systems
[N2] IEC 61511: 2016 Functional Safety: Safety Instrumented Systems for the
Process Industry Sector
[N3] Safety Equipment Reliability
Handbook, 4
[N4] Goble, W.M. 2010 Control Systems Safety Evaluation and Reliability, 3rd
[N5] O’Brien, C. & Bredemeyer,
L., 2009
th
Edition, 2015
exida LLC, Safety Equipment Reliability Handbook, Third
Edition, 2015, ISBN-13: 9781-934977-15-6
edition, ISA, ISBN 97B-1-934394-80-9. Reference on FMEDA methods
exida LLC., Final Elements & the IEC 61508 and IEC
Functional Safety Standards, 2009, ISBN 978-1-9934977­01-9
© exida ERD 21_04-020 R001 V1R1 SIL Verification Report Final Element
T-127 V1,R1 Page 6 of 27
2.5 Reference documents
January 8, 2020
2.5.1 Documentation provided by Emerson Process Management Regulator Technologies, Inc.
[D1] Coax-K series SIL3, No.
968/V 1202.00/20, 2020­11-23
[D2] en_k15ex-datasheet,
E3.23-05/2018
[D3] General Operating Munual
for Valves-en, Version 07/2017
[D4] Operating Instructions for
k15, revision 07/2006
[D5] 130527en-certificate-
k15ex-防爆证书
IEC 61508 Certificate
Datasheet
General Operating Manual
Operating Instructions
EC-TYPE-EXAMINATION CERTIFICATE
2.5.2 Documentation generated by exida
[R1] Q21 04-020 Emerson SIL
Verification.exi
[R2] ERD 10-12-069 R002
V4R1 BM5 FMEDA report, February 4, 2021
[R3] ERD 16-08-037 R001
V1R3 BM9 FMEDA report,
exSILentia File
BM5/BM5A FMEDA report
BM9 FMEDA report
[R4] ERD 21_04-020 R001
V1R1 SIL Verification Report Final Element, April 9, 2021
© exida ERD 21_04-020 R001 V1R1 SIL Verification Report Final Element
T-127 V1,R1 Page 7 of 27
Final Element SIL Verification report for the Emerson Process Management Regulator Technologies, Inc. SSV Remote Control with Solenoid Valve project.
3 Final Element SIL Verification
Safety Integrity Level (SIL) is an order of magnitude classification of the effectiveness of a Safety Instrumented Function (SIF), as defined by a range of average Probability of Failure on Demand (PFD for the low demand mode of operation.
Table 2 Safety Integrity Levels and Associated Parameters (Low Demand Mode)
). Table 2 shows the relationship between SIL, PFD
avg
, and Risk Reduction Factor (RRF),
AVG
Safety Integrity Level Average Probability of Failure on Demand
avg
)
(PFD
3 10-3 to 10-4 1,000 to 10,000
2 10-2 to 10-2 100 to 1,000
1 10-1 to 10-2 10 to 100
Risk Reduction Factor
(RRF)
A SIL is assigned to each individual SIF and reflects the amount of risk reduction that is required to move the process risk from its existing level to a level that is considered tolerable. The objective of the SIL verification process is to verify that the equipment that has been selected for the SIF as part of the conceptual design, meets the requirements of the selected SIL, both in terms of PFD
AVG
and architectural constraints.
3.1 Assumptions
Assumptions can be divided into general modeling assumptions and project specific assumptions. An overview of the general modeling assumptions is provided in Appendix A. Project specific assumptions are listed in this section.
Based on the SIL selection, it is concluded that each SIFs demand interval is at least twice as long as the longest proof test interval, therefore it is determined that all Safety Instrumented Functions operate in low demand mode.
The mission time is 10 years; therefore, all equipment will be replaced or refurbished every 10 years.
The Startup time, the time it will take between a nuisance trip and restart of the unit, is 24 hours
The Mean Time To Restoration (MTTR) is 24 hours on all equipment.
It is assumed that all devices are implemented in accordance with their safety manuals.
The proof test coverage (PTC) value is assumed based on standard proof test procedures
for COAX K Series Solenoid Valve, and its corresponding coverage, when available. Otherwise, generally acceptable values are used. The PTC has a significant impact on the PFDavg calculation. It is recommended that proper proof test procedures be in place to justify the proof test coverage values used in this study, especially for final elements, since their performance most often limits the overall design performance.
© exida ERD 21_04-020 R001 V1R1 SIL Verification Report Final Element
T-127 V1,R1 Page 8 of 27
Maintenance will be performed to a good standard (Site Safety Index SSI = 2). During
Target
Achievable SIL Limits
SIL
RRF
PFDavg
AC
SC
maintenance, 90% of detectable faults will be detected and corrected, and equipment will be reassembled correctly at least 90% of the time (this is a reasonable estimate based on typical industry data). This is indicated as “SSI (Site Safety Index) = 2” in the detailed analysis report.
It is assumed that the only diagnostic capabilities implemented are application level diagnostics.
The SILver SIL verification software tool used in this work (part of the exSILentia package) is designed to verify Safety Instrumented Systems (SIS) that are based on the de-energize­to-trip principle. De-energize-to-trip implies that on loss of power the SIS will go to a safe state
3.2 Analysis Results
The results of the Final Element SIL Verification study is shown in Table 3.
Table 3 Final Element SIL Verification Summary
SIF Tag
SIF Name
BM5/BM5A SSV
(contained OS/8*X
SIF-01
Series Controller) +
COAX K Series Solenoid
Valve
2 100 2 2 3
BM9 SSV (contained
SIF-02
OS9/8*X Series
Controller) + COAX K
Series Solenoid Valve
Note: COAX K Series Solenoid Valve detail model refer to [D2]
3.2.1 Architectural Constraints
The architecture meets the requirements for SIL 2 based on IEC 615113.
RRF
174.6
155.1
Remarks
Comply
3
Hardware Fault Tolerance; for details see 11.4.5 of IEC 61511-1.
T-127 V1,R1 Page 9 of 27
© exida ERD 21_04-020 R001 V1R1 SIL Verification Report Final Element
Table 4 IEC 61511 Architectural Constraints
Safety Integrity Level
1 (any mode) 0
2 (low demand mode) 0
2 (continuous mode) 1
3 (high demand mode or continuous mode) 1
4 (any mode) 2
Minimum Required Hardware
Fault Tolerance
3.2.2 SIL Capability
All devices used in the system are assessed to a minimum of SIL 3.
3.2.3 Probability of Failure on Demand
The hardware configuration for the SSV Remote Control with Solenoid Valve was listed in Table 5.
Table 5 Hardware Variations
SIF Tag SIF Name
SIF-01
BM5/BM5A SSV (contained OS/8*X Series
Controller) + COAX K Series Solenoid Valve
Diagnostic Proof Test
None
Timed full valve stroke test
and leak test
SIF-02
BM9 SSV (contained OS9/8*X Series
Controller) + COAX K Series Solenoid Valve
Note: COAX K Series Solenoid Valve detail model refer to [D2]
The PFD
was calculated for each SIF considering proof test intervals 12 months. The results are
avg
show in Figure 1 and Figure 2.
None
Timed full valve stroke test
and leak test
© exida ERD 21_04-020 R001 V1R1 SIL Verification Report Final Element
T-127 V1,R1 Page 10 of 27
Figure 1 SIF-01 PFD
Figure 2 SIF-02 PFD
Proof Test Intervals 12 months
avg
Proof Test Intervals 12 months
avg
© exida ERD 21_04-020 R001 V1R1 SIL Verification Report Final Element
T-127 V1,R1 Page 11 of 27
4 Conclusions and Recommendations
The results of the analysis show that the SSV Remote Control with Solenoid Valve meets the SIL
2. To achieve this proof testing and diagnostic need to be implemented as modeled in the SIL Verification calculations.
This analysis covers only the final element. To determine the performance of the SIF these results must be combined with the results for the sensor and logic elements.
© exida ERD 21_04-020 R001 V1R1 SIL Verification Report Final Element
T-127 V1,R1 Page 12 of 27
5 Terms and Definitions
ALARP As Low As Reasonably Practicable
Architectural Constraints Limitations that are imposed on the hardware selected to implement
a safety-instrumented function, regardless of the performance calculated for a subsystem. Architectural constraints are specified (in IEC 61508-2-Tables 2 and 3, and IEC 61511-Tables 5 and 6) according to the required SIL of the subsystem, type of components used, and SFF of the subsystem’s components. Type A components are simple devices not incorporating microprocessors, and Type B devices are complex devices such as those incorporating microprocessors.
Availability The probability that a device is operating successfully at a given
moment in time. This is a measure of the “uptime” and is defined in units of percent.
BPCS Basic Process Control System
Diagnostic Coverage A measure of a system’s ability to detect failures. This is a ratio
between the failure rates for detected failures to the failure rate for all failures in the system.
FIT Failure unIT, 1 FIT = 1.00E-9 Failures / Hour
FMEDA Failure Modes Effects and Diagnostic Analysis
A systematic procedure during which each failure mode of each
component is examined to determine the effect of that failure on the system and whether that failure is detected by any automatic diagnostic function
HFT Hardware Fault Tolerance
The number of dangerous random failures tolerated by a system
while still maintaining the ability to successfully perform the safety function
IEC International Electrotechnical Commission
MTTFS Mean Time To Fail Spurious
PFDavg average Probability of Failure on Demand
PFH Probability of Dangerous Failure per Hour
PLC Programmable Logic Controller
PTC Proof Test Coverage, the percentage failures that are detected
during the servicing of equipment.
PTI Proof Test Interval, the time interval between servicing of the
equipment.
RRF Risk Reduction Factor, the inverse of PFD
avg
SERH Safety Equipment Reliability Handbook
© exida ERD 21_04-020 R001 V1R1 SIL Verification Report Final Element
T-127 V1,R1 Page 13 of 27
SFF Safe Failure Fraction
A measure of safety integrity defined by IEC 61508-2 consisting of
the ratio of safe random failures plus dangerous detected random failures divided by all total random failures. It is used to determine minimum levels of hardware fault tolerance (redundancy for safety).
SIF Safety Instrumented Function
SIL Safety Integrity Level
Discrete level (one out of a possible four) for specifying the safety
integrity requirements of the safety functions to be allocated to the electronic / programmable electronic safety-related systems, where safety integrity level 4 has the highest level of safety integrity and safety integrity level 1 has the lowest [IEC 61508-4]
Note – there is an analogy between the SIL of IEC 61508 and the
Class / Category of IEC 61513 / IEC 62128 based on a comparison of requirements.
SIS Safety Instrumented System – Implementation of one or more Safety
Instrumented Functions. A SIS is composed of any combination of sensor(s), logic solver(s), and final element(s).
SRS Safety Requirements Specification
TI Test Interval, used in risk analysis equations to represent the proof
test interval described above
© exida ERD 21_04-020 R001 V1R1 SIL Verification Report Final Element
T-127 V1,R1 Page 14 of 27
6 Status of the Document
Contract
Number
Report Number
Revision Notes
Q21/04-020
ERD 21/04-020 R001 V1, R1
Initial
Jack Gao, Senior Safety Engineer
Desmond Lee, CFSE, Senior Safety Engineer
6.1 Liability
exida provides services and analyses based on methods advocated in international and national standards. Input information for the Final Element SIL Verification is obtained from the customer / owner / operator, i.e. Emerson Process Management Regulator Technologies, Inc. exida accepts no liability whatsoever for the correct and safe functioning of a plant or installation developed based on this Final Element SIL Verification analysis or for the correctness of the standards on which the general methods are based.
6.2 Version History
Reviewer: Desmond Lee, exida, April 9, 2021 Status: Released, April 9, 2021
6.3 Future enhancements
None are foreseen
6.4 Release signatures
© exida ERD 21_04-020 R001 V1R1 SIL Verification Report Final Element
T-127 V1,R1 Page 15 of 27
Appendix A SIL Verification Methodology
This appendix will provide an overview of the SIL verification methodology that was applied during the Final Element SIL Verification study.
A.1 Overview
National and International standards that describe the implementation of automated systems for safety related purposes, including IEC 61508, and IEC 61511 present the safety lifecycle model, which is a management system for implementing Safety Instrumented Systems (SIS). These standards define either three or four Safety Integrity Levels (SIL) that represents the effectiveness of each Safety Instrumented Function (SIF). SIL are categories of the average Probability of Failure on Demand (PFD that are related to those categories, including PFD the inverse of PFD
Table 6 Safety Integrity Levels and Associated Parameters (Low Demand Mode)
, for the low demand mode of operation.
AVG
). Table 6 shows categories of SIL and the performance parameters
AVG
and Risk Reduction Factor (RRF), which is
AVG
Safety Integrity Level
3 10-3 to 10-4 1,000 to 10,000
2 10-2 to 10-2 100 to 1,000
1 10-1 to 10-2 10 to 100
Average Probability of Failure on Demand
avg
)
(PFD
Risk Reduction Factor
(RRF)
The requirements that are defined for a SIS specify both design features (hardware, software, redundancy, etc.) and operational philosophy (inspection maintenance policy, frequency and quality of testing, etc.). These attributes of a SIS, as described above, will determine how that system will function. An important part of the safety lifecycle includes quantitatively describing the effectiveness of each SIF. SIF performance is usually described by the metrics of PFD Mean Time To Fail Spurious (MTTFS).
SIF performance metrics can be estimated using the historical system performance data of the individual components that comprise a SIF. A number of techniques that estimate the performance metrics based on the performance of the components that comprise a system and a description of how they are logically related have been employed for the task of SIS analysis. Collectively, these techniques are called “fault propagation models”. Some of the most commonly used fault propagation models include fault tree analysis, event tree analysis, reliability block diagrams, and Markov models.
While PFDAVG is the key variable that SIS designers are concerned with, safe failures must also be considered. The safe failures are alternately referred to as nuisance trips, or spurious trips. Safe failures are typically described by the Mean Time To Fail Spurious (MTTFS) metric. Spurious trips can adversely impact the safety of a process in number of ways. Process start-up and shutdown are typically higher risk time periods than normal operation; thus, unnecessarily increasing the number of startups will often have a detrimental effect on safety. In some cases, the nuisance shutdown itself may cause hazards, such as hydraulic hammer of pipe work, that are as great as the hazard that the SIF is protecting against. As a result, reducing the number of spurious trips often increases the safety of the process. Spurious trips may also cause financial losses due to
AVG
and
© exida ERD 21_04-020 R001 V1R1 SIL Verification Report Final Element
T-127 V1,R1 Page 16 of 27
decreased productivity, lost batches, and decreased product quality. Increasing acceptable MTTFS requirements can often be justified because of the high cost associated with a spurious trip.
A.2 Modeling Assumptions
While performing Final Element SIL Verification study, the following assumptions about the SIS and SIFs under consideration were made when modeling its performance.
The SIF being evaluated is designed, installed, and maintained in accordance with all applicable national and international standards regarding SIF at a level of Site Safety Index (SSI)=2. Reference:
of-human-factors-on-functional-safety
The failure rate of components is assumed to be constant over the life of the system.
It is generally assumed that the failure of an individual component is statistically
independent of the failure of other components. All failure events are independent events.
The failed state and the operating state are mutually exclusive; a component must be either completely failed or completely operational at all points in time.
Once a component has failed, it remains in the failed state until repaired.
Unless specifically noted otherwise, all repairs will return a component to its original failure-
free state.
http://www.exida.com/Resources/Whitepapers/quantifying-the-impacts-
Testing frequencies are assumed to be much higher than failure rates.
A.3 Data and Statistics
The analysis presented in this report depends, to a substantial degree, on the reliability and failure data that was used to calculate the various SIF performance parameters. The data needed for a component is usually presented in terms of four variables: failure rate (λ), percentage safe failures, diagnostic coverage of safe failures (Cs), and diagnostic coverage of dangerous failures (Cd), or in terms of failure rates for each mode. Using these component performance parameters and information about system maintenance and testing, the PFD
Collection, analysis and presentation of this data are important parts of the analysis process. Quantification of equipment failure rates depends on historical information regarding how events that cause or propagate an accident have occurred in the past. The best source of failure rate data is records of failures and maintenance of equipment that exist in the process plant that is being studied. This information is best because the failure rate describes the actual conditions under which the process equipment is being used. Unfortunately, historical reliability data is often unavailable.
In cases where company specific data is unavailable or incomplete, industry average data has been used. exida has compiled a proprietary equipment failure database. The database is a compilation of failure data collected from a variety of public and confidential sources. exida has selected the most appropriate data from the various sources and combined them on a consistent basis for many types of process equipment and services. Basic event frequencies used in this study are included at the end of the appendices that contain detailed calculation information.
and MTTFS are calculated.
AVG
© exida ERD 21_04-020 R001 V1R1 SIL Verification Report Final Element
T-127 V1,R1 Page 17 of 27
exida recognizes that some data provides a more accurate representation of failure rates than others. The following priority is given to the various data sources that might be available for an equipment item.
1. Results of FMEDA analysis that is integral in the certification report presented by an accredited independent third-party organization when results are within statistical confidence limits of process industry field failure data.
2. Results of FMEDA analysis performed by generally accepted practices, using generally accepted and comparable databases of component reliability. Prior to use of this type of data exida would review and approve of the analysis process and data. NOTE: exida typically does not use MTTF data published by equipment vendors that was determined on the basis of field returns, as that data is often misleading. In the case of this analysis some of the failure rate data was provided by the equipment manufacturer.
3. Compilation of published and proprietary failure rates for instruments used in the process industries.
The exida reliability database is published in the “Safety Equipment Reliability Handbook”. 4
th
Edition (ISBN-13: 9781-934977-15-6).
© exida ERD 21_04-020 R001 V1R1 SIL Verification Report Final Element
T-127 V1,R1 Page 18 of 27
Appendix B Proof Tests
energize the solenoid valve, measure and record the time required for the valve
onfirm that the Safe State was
SIF-02
92%
According to section 7.4.5.2 f) of IEC 61508-2 proof tests shall be undertaken to reveal dangerous faults which are undetected by automatic diagnostic tests. This means that it is necessary to specify how dangerous undetected faults which have been noted during the Failure Modes, Effects, and Diagnostic Analysis can be detected during proof testing.
B.1 Base SIF Modeled Proof Test
The SIL Verification analysis modeled a timed full valve stroke test and leak test as the proof test. The proof test at the final element level is outlined in Table 7. Refer to the table in B.3 for the Proof Test Coverages.
Table 7 Base SIF Modeled Proof Test
Step Action
1. Bypass the safety function and take appropriate action to avoid a false trip.
2. De­assembly to move to the fully closed position. C achieved and within the correct time.
3. Perform a leak test across the valve. Confirm that the leak test was successful.
4.
5. Remove the bypass and otherwise restore normal operation.
Re-energize the solenoid. Inspect the valve assembly for any leaks, visible damage or contamination and confirm that the normal operating state was achieved.
B.2 SIF with PVST Modeled Proof Test
The SIL Verification analysis modeled a timed full valve stroke test and leak test as the proof test. The proof test at the final element level is outlined in Table 7. In addition to the proof test the SIL Verification modeled a PVST as an application diagnostic. Refer to the table in B.3 for the Proof Test Coverages. The PVST should be implemented in the safety system logic solver and should momentary de-energize the solenoid and confirm that the valve assembly begins to move and closes the required amount (typically 5% to 10% of travel) within that required time. If the test fails the failure must automatically be annunciated.
B.3 Proof Test Coverage
The Proof Test Coverage for the SIFs is given in Table 8.
Table 8 Proof Test Results – SSV Remote Control with Solenoid Valve
Safety Function
SIF-01 91%
Proof Test
Coverage
© exida ERD 21_04-020 R001 V1R1 SIL Verification Report Final Element
T-127 V1,R1 Page 19 of 27
Appendix C Final Element Schematic
Figure 3 shows the schematic of the SSV Remote Control with Solenoid Valve.
Figure 3 SSV Remote Control with Solenoid Valve Schematic
© exida ERD 21_04-020 R001 V1R1 SIL Verification Report Final Element
T-127 V1,R1 Page 20 of 27
Appendix D Detailed IEC 61511 Compliance Report
SIF Name:
BM5/BM5A SSV (contained OS/8*X Series Controller) + COAX K Series Solenoid Valve
SIF Tag
SIF-01
SIF Description:
When solenoid valve de-energized, SSV shut off immediately
SIL 2 with RRF ≥ 100
SIL 2 with RRF = 174.6
Analysis Date:
8 April 2021
Mission Time:
10 years
Startup Time:
24 hours
Demand Mode:
Low
Architectural Constraints:
IEC 61511
Consider Systematic Capability:
Yes Consider MTTFS:
Yes
Site Safety Index:
SSI 2
Include SSI in Failure Rate
Yes
The subsequent pages in this appendix provide a detailed overview of the SIL verification results for the SSV Remote Control with Solenoid Valve project. The SIL verification was performed using the exida exSILentia® SILver tool.
D.1 SIF-01 BM5/BM5A SSV (contained OS/8*X Series Controller) + COAX K Series Solenoid Valve
This chapter details the SIL Verification results, selections, and assumptions for the SIF-01 BM5/BM5A SSV (contained OS/8*X Series Controller) + COAX K Series Solenoid Valve Safety Instrumented Function.
D.1.1 General SIF Information
The following characterizes the Safety Instrumented Function.
D.1.2 Safety Integrity Levels
The target Safety Integrity Level determined for this Safety Instrumented Function is:
The calculated achieved Safety Integrity Level for this Safety Instrumented Function is:
D.1.3 SIL Verification Parameters and Results
This section provides a detailed overview of the Safety Integrity Level verification performed for the SIF-01 BM5/BM5A SSV (contained OS/8*X Series Controller) + COAX K Series Solenoid Valve Safety Instrumented Function. In order to perform the reliability calculations part of the Safety Integrity Level verification, the following assumptions have been made.
© exida ERD 21_04-020 R001 V1R1 SIL Verification Report Final Element
T-127 V1,R1 Page 21 of 27
ACHIEVED SIL
A
IEC 61511
5.73E-03
174.6 2 2 3 170.4
SIL LIMITS
A
IEC 61511
5.73E-03
2 3 170.4 0 2
Number of Final Element group(s):
1 Voting between groups:
1oo1
Given the reliability data and SIL verification selections and assumptions described in the subsequent subsections in this report the SIF-01 BM5/BM5A SSV (contained OS/8*X Series Controller) + COAX K Series Solenoid Valve Safety Instrumented Function achieves the functional safety performance as displayed in the following table.
Table 9 SIL Verification Results
PFDAVG RRF
PFDAVG
RCH.
CONSTRAINTS
SYSTEMATIC
CAPABILITY
MTTFS
(YEARS)
D.1.4 Final Element Part Configuration
The functional safety and spurious trip behavior of the final element part of the SIF-01 BM5/BM5A SSV (contained OS/8*X Series Controller) + COAX K Series Solenoid Valve Instrumented Function is quantified as follows.
Table 10 Final Element Part SIL Verification Results
PFDAVG
RCH.
CONSTRAINTS
SYSTEMATIC
CAPABILITY
MTTFS
(YEARS)
HFT SSI
T-127 V1,R1 Page 22 of 27
© exida ERD 21_04-020 R001 V1R1 SIL Verification Report Final Element
β-factor [%]:
N/A
Group Name:
BM5/BM5A SSV (contained OS/8*X Series Controller) + COAX K Series Solenoid Valve
Final Element Legs:
Final Element Leg
Voting within group:
1oo1
Voting type:
Identical
HFT:
0
β-factor [%]:
N/A
MRT [Hours]:
24
Proof Test Interval [Months]:
12
Proof Test Coverage [%]:
91 Proof Test Execution:
Leak Test; Offline
SERH
VERSION
AC
TYPE
SIL
CAP
COAX K Series Solenoid Valve, 2-way
 - A 3
Diaphragm Controllers - UPSO
 - A 3
BM5/5A SSV
 - A 3
Valve Open On Trip:
No
Tight Shutoff Required:
No
Severe Service:
No
FAILURE RATES [1/HR]
SD
SU
DD
DU
AD
AU
NE
COAX K Series Solenoid Valve, 2-way
- - -
1.28E-07
- - -
Diaphragm Controllers
- UPSO
-
1.56E-07
-
1.15E-07
- - -
BM5/5A SSV
-
2.00E-08
-
4.30E-07
- - -
D.1.4.1 Final Element Group 1: BM5/BM5A SSV (contained OS/8*X Series Controller) + COAX K Series Solenoid Valve
The information and reliability data underneath describe the BM5/BM5A SSV (contained OS/8*X Series Controller) + COAX K Series Solenoid Valve final element group as it has been analyzed in this Safety Integrity Level verification.
D.1.4.2 Final Element Leg 1-1: Final Element Leg
The following table shows the equipment that defines final element leg 1-1 Final Element Leg.
Table 11 Final Element Leg 1-1: Final Element Leg Details
FINAL ELEMENT LEG 1-1
2H PIU
The Reliability Data table shows the reliability data used during the SIL verification of final element leg 1-1 Final Element Leg.
Table 12 Reliability Data Final Element Leg 1-1 Final Element Leg
COMPONENT
© exida ERD 21_04-020 R001 V1R1 SIL Verification Report Final Element
T-127 V1,R1 Page 23 of 27
COMPONENT
FAILURE RATES [1/HR]
SD
SU
DD
DU
AD
AU
NE
SFF [%]
20.7
ROUTE 2
H
COMPLIANT
-
SIF Name:
BM9 SSV (contained OS9/8*X Series Controller) + COAX K Series Solenoid Valve
SIF Tag
SIF-02
SIF Description:
When solenoid valve de-energized, SSV shut off immediately
SIL 2 with RRF ≥ 100
SIL 2 with RRF = 155.1
Analyst:
Analysis Date:
8 April 2021
Mission Time:
10 years
Startup Time:
24 hours
Demand Mode:
Low
Architectural Constraints:
IEC 61511
Consider Systematic Capability:
Yes Consider MTTFS:
Yes
Site Safety Index:
SSI 2
Include SSI in Failure Rate
Yes
D.2 SIF-02 BM9 SSV (contained OS9/8*X Series Controller) + COAX K Series Solenoid Valve
This chapter details the SIL Verification results, selections, and assumptions for the SIF-02 BM9 SSV (contained OS9/8*X Series Controller) + COAX K Series Solenoid Valve Safety Instrumented Function.
D.2.1 General SIF Information
The following characterizes the Safety Instrumented Function.
D.2.2 Safety Integrity Levels
The target Safety Integrity Level determined for this Safety Instrumented Function is:
The calculated achieved Safety Integrity Level for this Safety Instrumented Function is:
D.2.3 SIL Verification Parameters and Results
This section provides a detailed overview of the Safety Integrity Level verification performed for the SIF-02 BM9 SSV (contained OS9/8*X Series Controller) + COAX K Series Solenoid Valve Safety Instrumented Function. In order to perform the reliability calculations part of the Safety Integrity Level verification, the following assumptions have been made.
© exida ERD 21_04-020 R001 V1R1 SIL Verification Report Final Element
T-127 V1,R1 Page 24 of 27
ACHIEVED SIL
A
IEC 61511
6.44E-03
155.1 2 2
3
159.62
SIL LIMITS
A
IEC 61511
6.44E-03
2
3
159.62
0
2
Number of Final Element group(s):
1
Given the reliability data and SIL verification selections and assumptions described in the subsequent subsections in this report the SIF-02 BM9 SSV (contained OS9/8*X Series Controller) + COAX K Series Solenoid Valve Safety Instrumented Function achieves the functional safety performance as displayed in the following table.
Table 13 SIL Verification Results
PFDAVG RRF
PFDAVG
RCH.
CONSTRAINTS
SYSTEMATIC
CAPABILITY
MTTFS
(YEARS)
D.2.4 Final Element Part Configuration
The functional safety and spurious trip behavior of the final element part of the SIF-02 BM9 SSV (contained OS9/8*X Series Controller) + COAX K Series Solenoid Valve Safety Instrumented Function is quantified as follows.
Table 14 Final Element Part SIL Verification Results
PFDAVG
RCH.
CONSTRAINTS
SYSTEMATIC
CAPABILITY
MTTFS
(YEARS)
HFT SSI
T-127 V1,R1 Page 25 of 27
© exida ERD 21_04-020 R001 V1R1 SIL Verification Report Final Element
Voting between groups:
1oo1
β-factor [%]:
N/A
Group Name:
BM9 SSV (contained OS9/8*X Series Controller) + COAX K Series Solenoid Valve
Final Element Legs:
Final Element Leg
Voting within group:
1oo1
Voting type:
Identical
HFT:
0
β-factor [%]:
N/A
MRT [Hours]:
24
Proof Test Interval [Months]:
12
Proof Test Coverage [%]:
92 Proof Test Execution:
Leak Test; Offline
SERH
VERSION
AC
TYPE
SIL
CAP
COAX K Series Solenoid Valve, 2-way
 - A 3
Diaphragm Controllers - UPSO
 - A 3
BM9 SSV
 - A 3
Valve Open On Trip:
No
Tight Shutoff Required:
No
Severe Service:
No
FAILURE RATES [1/HR]
SD
SU
DD
DU
AD
AU
NE
COAX K Series
- - -
1.28E-07
- - -
D.2.4.1 Final Element Group 1: BM9 SSV (contained OS9/8*X Series Controller) + COAX K Series Solenoid Valve
The information and reliability data underneath describe the BM9 SSV (contained OS9/8*X Series Controller) + COAX K Series Solenoid Valve final element group as it has been analyzed in this Safety Integrity Level verification.
D.2.4.2 Final Element Leg 1-1: Final Element Leg
The following table shows the equipment that defines final element leg 1-1 Final Element Leg.
Table 15 Final Element Leg 1-1: Final Element Leg Details
FINAL ELEMENT LEG 1-1
2H PIU
The Reliability Data table shows the reliability data used during the SIL verification of final element leg 1-1 Final Element Leg.
Table 16 Reliability Data Final Element Leg 1-1 Final Element Leg
COMPONENT
© exida ERD 21_04-020 R001 V1R1 SIL Verification Report Final Element
T-127 V1,R1 Page 26 of 27
COMPONENT
FAILURE RATES [1/HR]
SD
SU
DD
DU
AD
AU
NE
Solenoid Valve, 2-way
Diaphragm Controllers
- UPSO
-
1.56E-07
-
1.15E-07
- - -
BM9 SSV
-
6.60E-08
-
5.42E-07
- - -
SFF [%]
22.0
ROUTE 2
H
COMPLIANT
-
T-127 V1,R1 Page 27 of 27
© exida ERD 21_04-020 R001 V1R1 SIL Verification Report Final Element
Loading...