Introduction
This Installation Guide provides instructions and safety
information on pressure equipment so as to avoid any
foreseeable risk during the use.
For further information refer to Types A/100 and A/110
Instruction Manual, n° 0095 and Bulletin, n° 0068.
To receive a copy of the Bulletin, contact your local O.M.T.
Tartarini Sales Office or O.M.T Tartarini Sales
Representative.
A/100
Per Article 3 section 3, these “SEP” products must not
bear the CE marking.
Specifications
Body Sizes and End Connection Styles
DN 2” BSP inlet and outlet
DN 2” PN 16 UNI/DIN - Sliding flanges (available on request)
DN 2” ANSI 150 - Sliding flanges (available on request)
General Remark
The standard gas pressure devices (regulators and safety
shut-off devices) are those used in the assemblies dealt
with into EN 12186 and EN 12279 and their use has to be
under the provisions into ENs 12186 & 12279.
Fail-to-open stand-alone regulators cannot be used as a
safety accessory according PED 97/23/EC to protect
downstream pressure equipment.
In the pressure regulators (with or without built-in safety
shut-off devices) manufactured by OMT Tartarini shall be
used additionary pressure accessories (e.g. pilots or
filters) manufactured and labeled by OMT Tartarini.
OMT Tartarini will be not responsible for any possible
inefficiency due to installation of not own production
additionary pressure accessories (e.g. pilots or filters).
When pressure containing parts of possible built-in safety
shut-off device (SSD) valve and pilot have different
maximum allowable pressures, the SSD is differential
strength type.
P.E.D. Categories and Fluid Group
According to EN 14382, only in integral strength type and
Class A configuration (when both over and under pressure
protections are set up), the possible built-in safety shut-off
device can be classified like a safety accessory according
to PED.
The minimum PS between SSD valve and pilot shall be
the PS of the safety accessory to comply the provisions of
EN 14382 about integral strength type.
Downstream equipments, protected by possible built-in
safety shut-off device (in its Class A and integral strength
configuration) of this product, shall have technical features
such as to be category per table below according Directive
97/23/EC “PED”.
Product Size Category Fluid Group
DN 2“ I 1
Possible built-in pressure accessories (e.g. pilots OS66/)
conform to Pressure Equipment Directive (PED) 97/23/EC
Article 3 section 3 and were designed and manufactured
in accordance with sound engineering practice (SEP).
! WARNING !
Maximum Operating Inlet Pressure (1)
A/102 • A/109: 8 bar
A/102-AP • A/109-AP: 8 bar
Operating Outlet Set Pressure Ranges
A/102 • A/109: 10 ÷ 60 mbar
A/102-AP • A/109-AP: 60 ÷ 300 mbar
Minimum/Maximum Allowable Temperature (TS) (1)
See nameplate
(1) : The pressure/temperature limits in this Safe Use
Guide and any applicable standard or code limitation
should not be exceeded.
Marking
Note 1: See “Specifications” paragraph
Note 2: See page header
Note 3: Class 1: -10/+60 °C
Note 4: PN 16 PS = 16 bar
ANSI 150 PS = 19.3 bar
Threaded 2” = 20 bar
http://www.tartarini.it

Safe Use Guide
A/100
Year of Manufacture 2008
SG0095GB Rev.06
Overpressure Protection
The recommended maximum allowable pressures are
stamped on the regulator nameplate.
If actual version hasn’t a built-in safety shut-off device,
some type of overpressure protection is needed if the
actual outlet pressure exceeds the actual maximum
operating outlet pressure rating.
Overpressure protection should also be provided if the
regulator inlet pressure is greater than the maximum
operating inlet pressure.
Downstream side pressure after possible built-in SSD’s
intervention shall stay within the actual maximum
operating set-up range to avoid anomalous back
pressures that can damage the SSD’s pilot.
Downstream overpressure protection shall be also
provided if the SSD outlet pressure can be greater than
the PS of the SSD pilot (differential strength type).
Regulator operation below the maximum pressure
limitations does not preclude the possibility of damage
from external sources or debris in the line.
The regulator should be inspected for damage after any
overpressure condition.
Transport and Handling
Established transport and handling procedures shall be
followed to avoid any damage on the press ure containing
parts by shocks or anomalous stresses.
Built-up sensing lines and pressure accessories shall to
be protected by shocks or anomalous stresses.
Installation
! WARNING !
Installation shall be in accordance with national
standard for material use limitations in gas
pressure reducing stations.
Only qualified personnel should install or service
a regulator. Regulators should be installed,
operated, and maintained in accordance with
international and applicable codes and
regulations, and O.M.T. Tartarini instructions.
If the regulator vents fluid or a leak develops in
the system, it indicates that service is required.
Failure to take the regulator out of service
immediately may create a hazardous condition.
Personal injury, equipment damage, or leakage
due to escaping fluid or bursting of pressurecontaining parts may result if this regulator is
over pressured or is installed where service
conditions could exceed the limits given in the
Specifications section, or where conditions
exceed any ratings of the adjacent piping or
piping connections.
To avoid such injury or damage, provide
pressure-relieving or pressure-limiting devices
(as required by the appropriate code, regulation,
or standard) to prevent service conditions from
exceeding limits.
Additionally, physical damage to the regulator
could result in personal injury and property
damage due to escaping fluid.
To avoid such injury and damage, install the
regulator in a safe location.
Before installation, check shall be done if service
conditions are consistent with use limitations and
if pilot set-up of possible built-in safety shut-off
device are in accordance with service conditio ns
of protected equipment.
All means for venting have to be provided in the
assemblies where the pressure equipment are
installed (ENs 12186 & 12279).
All means for draining have to be provided in the
equipment installed before regulators & shut-off
devices (ENs 12186 & 12279).
Further the ENs 12186 & 12279, where this product is
used:
− provide the cathodic protection and electrical
isolation to avoid any corrosion and
− in accordance with clause 7.3/7.2 of aforesaid
standards, the gas shall be cleaned by proper
filters/separators/scrubbers to avoid any technical
& reasonable hazard of erosion or abrasion for
pressure containing parts.
Pressure equipment in subject shall be installed in nonseismic area and hasn’t to undergo fire and thunderbolt
action.
Clean out all pipelines before installation of the regulator
and check to be sure the regulator has not been damaged
or has collected foreign material during shipping.
Apply pipe compound to the male pipe threads.
Install the regulator in any position desired, unless
otherwise specified, but be sure flow through the body is
in the direction indicated by the arrow on the body.
Installation must be done avoiding anomalous stresses o n
the body and using suitable joint means according
equipment dimensions and service conditions.
For a correct and safe use of the connections check also
Instruction Manual and Bulletin before installation.
User has to check and carry out any protection suitable for
assembly’s specific environment.
Note: It is important that the regulator be installed so
that the vent hole in the spring case is unobstructed at
all times. For outdoor installations, the regulator should
be located away from vehicular traffic and positioned
so that water, ice, and other foreign materials cannot
enter the spring case through the vent. Avoid placing
the regulator beneath eaves or downspouts, and be
sure it is above the probable snow level.