INSTALLATION AND SERVICE MUST BE PERFORMED BY A QUAUHED TECHNlaAN.
IMPORTANT: SAVE FOR THE LOCAL ELECTRICAL INSPECTOR'S USE.
READ AND SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE,
1,
Clearances and Dimensions
a. Provide adequate clearances between tile range and adjacent combustible surfaces.
b. Location--Check location where the range will be installed. Check for proper electrical supply and tile stability of
floor.
c. Dimensions that are shown must be used. Given dimensions provide minimum clearance. Contact surface
must be solid and level.
T
Minimum t Minimurn to
wall on either either side
Minimumto 1/16"-t_ _- j 18" cabinetson
side of range _ _ of range.
I_--- B ------_1
BACK
VIEW
SIDE
VIEW
Maximum depth
for cabinets
above range top.
I_- 13"€_ I
FRONT
VIEW
RANGE
24" 24" 24"
DIMENSIONS
A C
B
25"
A
48"
Maximum
- I ....
45"
bOOg Operl '/ \
36" ± 1/8")
C
\\
* 30" MINIMUM CLEARANCE BETWEENTHETOP OF THECOOKING SURFACEAND THE BOTTOM OFAN UNPROTECTED
WOOD OR METAL CABINET;OR 24" MINIMUM WHEN BOTTOM OFWOOD OR METAL CABINET IS PROTECTEDBY NOT
LESSTHAN I/4" FLAME RETARDANTMILLBOARD COVEREDWITH NOT LESSTHAN NO. 28 MSG SHEETSTEEL,0.015"
STAINLESSSTEEL,0.024" ALUMINUM OR 0.020" COPPER.0" CLEARANCE IS THE MINIMUM FORTHE REAROF THE
RANGE. FOLLOWALL DIMENSION REQUIREMENTSPROVIDEDABOVE TO PREVENTPROPERTYDAMAGE, POTENTIALFIRE
HAZARD, AND INCORRECTCOUNTERTOPAND CABINET CUTS.
TO ELIMINATE THE RISK OF BURNS OR FIRE BY REACHING OVER HEATED SURFACE UNITS, CABINET STORAGE
SPACE LOCATED ABOVE THE SURFACE UNITS SHOULD BE AVOIDED. IF CABINET STORAGE tSTO BE PROVIDED,
THE RISK CAN BE REDUCED BY INSTALLING A RANGE HOOD THAT PROJECTSHORIZONTALLY A MINIMUM OF 5"
BEYOND THE BOTTOM OF THE CABINETS.
Printed in United States P/N318154301 (0703) Rev.D
2. Install Anti-Tip Bracket(s). (Seeinstructions on
page 4.)
3_ Serial Plate Information
The serial plate is located on the frame and is visible
when the drawer is opened. See the serial plate for
the following information;
A.Model, lot and serial number of range.
B.Kilowatt rating (power requirements).
C.Voltage ratings.
Serial plate location
4. Electrical Connection Requirements
This appliance must be properly installed and grounded
by a qualified technician in accordance with the National
Electrical Code ANS!/NFPA No. 70-qatest edition--and
local electrical code requirements.
This appliance may be connected by means of
permanent "Hard Wiring" or "Power Supply Cord Kit."
When hard wiring, do not leave excess wire in range
compartment. Excess wire in the range compartment
may not allow the access cover to be replaced properly,
and could create a potential electrical hazard if wires
become pinched. Connect only as instructed under
"WIRING INSTRUCTIONS" in sections 6 and 7. When
using flexible conduit or range cable, use flex connector
or range cable strain relief.
NOTE: Only use copper wire in connection to terminal
block.
RISK OF FIRE OR ELECTRICAL SHOCK
MAY OCCUR IF AN INCORRECT SIZE RANGE CORD KIT
IS USED, THE INSTALLATION INSTRUCTIONS ARE NOT
FOLLOWED OR STRAIN RELIEFBRACKET IS DISCARDED.
This appliance may be connected by means of a power
supply cord. Only a power supply cord kit rated at 40
amperes, 125/250 volts minimum, and marked for use
with ranges shall be used. Cord must have three (3)
conductors. Terminals on end of wires must be either
closed loop or open-end spade lugs with upturned ends.
Cord must have strain relief clamp.
NOTE: MOBILE HOME INSTALLATION OR AREAS
WHERE LOCAL CODES DO NOT PERMIT GROUNDING
THROUGH NEUTRAL, A FOUR (4) CONDUCTOR
POWER CORD MUST BE USED.
A 1-3/8" knock-out hole is provided at the bottom of the
range terminal box for connecting the power supply cord
kit to the range terminal block (see Figures 2 and 3).
5. Permanent Hard Wiring (3 or 4 Wires)
Insert the residence 3-wire power supply (:able through
the I-1/8" hole at the bottom of the range terminal box
(see Figure 2). For mobile home application or where
connections with a 3-wire power supply cable is not
allowed, use a 4-wire power supply cable (for
connections, see Figure 3). Use a U.L. approved strain
relief clamp to secure tile cable to the terminal box.
6. Wiring Instructions - 3°Wire Supply Cable
ELECTRICAL GROUND IS REQUIRED ON
THIS APPLIANCE.
This appliance is manufactured with the neutral terminal
connected to the frame. If local codes permit connection
of the frame grounding conductor to the neutral wire of
the copper power supply cord:
4B. Models Requiring Power Supply Cord Kit
U.S. STYLE
Figure 1 - 3-Wire Cord Kit
(The 3-conductor cord or (:able must be replaced with a
4-conductor cord or (:able where grounding through the
neutral conductor is prohibited in new installations,
mobile homes, recreational vehicles or in other areas
where local codes do not permit neutral grounding.)