Tappan TEF242BW2, TEF242BW3, TEF242BW4, TEF242BW5, TEF242BU2 Installation Guide

...
INSTALLATION AND SERVICE MUST BE PERFORMED BY A QUAUHED TECHNlaAN.
IMPORTANT: SAVE FOR THE LOCAL ELECTRICAL INSPECTOR'S USE.
READ AND SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE,
1,
Clearances and Dimensions
a. Provide adequate clearances between tile range and adjacent combustible surfaces. b. Location--Check location where the range will be installed. Check for proper electrical supply and tile stability of
floor.
must be solid and level.
T
Minimum t Minimurn to
wall on either either side
Minimumto 1/16"-t_ _- j 18" cabinetson side of range _ _ of range.
I_--- B ------_1
BACK VIEW
SIDE VIEW
Maximum depth for cabinets
above range top.
I_- 13"€_ I
FRONT
VIEW
RANGE
24" 24" 24"
DIMENSIONS
A C
B
25"
A
48"
Maximum
- I ....
45"
bOOg Operl '/ \
36" ± 1/8")
C
\\
* 30" MINIMUM CLEARANCE BETWEENTHETOP OF THECOOKING SURFACEAND THE BOTTOM OFAN UNPROTECTED
WOOD OR METAL CABINET;OR 24" MINIMUM WHEN BOTTOM OFWOOD OR METAL CABINET IS PROTECTEDBY NOT LESSTHAN I/4" FLAME RETARDANTMILLBOARD COVEREDWITH NOT LESSTHAN NO. 28 MSG SHEETSTEEL,0.015" STAINLESSSTEEL,0.024" ALUMINUM OR 0.020" COPPER.0" CLEARANCE IS THE MINIMUM FORTHE REAROF THE RANGE. FOLLOWALL DIMENSION REQUIREMENTSPROVIDEDABOVE TO PREVENTPROPERTYDAMAGE, POTENTIALFIRE HAZARD, AND INCORRECTCOUNTERTOPAND CABINET CUTS.
TO ELIMINATE THE RISK OF BURNS OR FIRE BY REACHING OVER HEATED SURFACE UNITS, CABINET STORAGE SPACE LOCATED ABOVE THE SURFACE UNITS SHOULD BE AVOIDED. IF CABINET STORAGE tSTO BE PROVIDED,
THE RISK CAN BE REDUCED BY INSTALLING A RANGE HOOD THAT PROJECTSHORIZONTALLY A MINIMUM OF 5"
BEYOND THE BOTTOM OF THE CABINETS.
Printed in United States P/N318154301 (0703) Rev.D
2. Install Anti-Tip Bracket(s). (Seeinstructions on
page 4.)
3_ Serial Plate Information
The serial plate is located on the frame and is visible when the drawer is opened. See the serial plate for the following information; A.Model, lot and serial number of range.
B.Kilowatt rating (power requirements).
C.Voltage ratings.
Serial plate location
4. Electrical Connection Requirements
This appliance must be properly installed and grounded by a qualified technician in accordance with the National
Electrical Code ANS!/NFPA No. 70-qatest edition--and local electrical code requirements.
This appliance may be connected by means of permanent "Hard Wiring" or "Power Supply Cord Kit."
When hard wiring, do not leave excess wire in range compartment. Excess wire in the range compartment may not allow the access cover to be replaced properly, and could create a potential electrical hazard if wires become pinched. Connect only as instructed under
"WIRING INSTRUCTIONS" in sections 6 and 7. When
using flexible conduit or range cable, use flex connector or range cable strain relief.
NOTE: Only use copper wire in connection to terminal block.
RISK OF FIRE OR ELECTRICAL SHOCK
MAY OCCUR IF AN INCORRECT SIZE RANGE CORD KIT IS USED, THE INSTALLATION INSTRUCTIONS ARE NOT
FOLLOWED OR STRAIN RELIEFBRACKET IS DISCARDED.
This appliance may be connected by means of a power supply cord. Only a power supply cord kit rated at 40 amperes, 125/250 volts minimum, and marked for use with ranges shall be used. Cord must have three (3)
conductors. Terminals on end of wires must be either closed loop or open-end spade lugs with upturned ends.
Cord must have strain relief clamp.
NOTE: MOBILE HOME INSTALLATION OR AREAS WHERE LOCAL CODES DO NOT PERMIT GROUNDING
THROUGH NEUTRAL, A FOUR (4) CONDUCTOR POWER CORD MUST BE USED.
A 1-3/8" knock-out hole is provided at the bottom of the
range terminal box for connecting the power supply cord kit to the range terminal block (see Figures 2 and 3).
5. Permanent Hard Wiring (3 or 4 Wires)
Insert the residence 3-wire power supply (:able through
the I-1/8" hole at the bottom of the range terminal box (see Figure 2). For mobile home application or where
connections with a 3-wire power supply cable is not allowed, use a 4-wire power supply cable (for
connections, see Figure 3). Use a U.L. approved strain
relief clamp to secure tile cable to the terminal box.
6. Wiring Instructions - 3°Wire Supply Cable
ELECTRICAL GROUND IS REQUIRED ON
THIS APPLIANCE.
This appliance is manufactured with the neutral terminal connected to the frame. If local codes permit connection of the frame grounding conductor to the neutral wire of the copper power supply cord:
4B. Models Requiring Power Supply Cord Kit
U.S. STYLE
Figure 1 - 3-Wire Cord Kit
(The 3-conductor cord or (:able must be replaced with a 4-conductor cord or (:able where grounding through the
neutral conductor is prohibited in new installations, mobile homes, recreational vehicles or in other areas
where local codes do not permit neutral grounding.)
Loading...
+ 2 hidden pages