Tantalus TUNet TC-1120, TUNet TC-1120-RD, TUNet TC-1220, TUNet TC-1220-RD, TUNet TC-11/1210 Quick Reference

...
Tantalus Utility Network™
TUNet® TC-1120/1120-RD
And
TC-1220/1220-RD
Quick Reference
The TC-1120/1120-RD and TC-1220/1220-RD is a family of two-way 900 MHz LAN smart meter communication modules that are integrated into the Itron CENTRON® C2s family of electrical watthour meters. The CENTRON C2s metrology unit sends a blurt message that conforms to the ANSI C12.19 PSEM protocol to the communication module. The Tantalus LAN communication module delivers meter readings on request or on a programmed schedule for Time-of-Use and interval data applications. The LAN communication module also reports power outages and monitors power quality including voltage (plus sag/swell alarms) and momentary outages (blinks).
Energized meters, meter sockets and distribution lines present the risk of electrical shock. All work on this equipment should be performed by qualified
Warning
metering specialists or industrial electricians.
Personnel working with this equipment should follow all utility company established operation and safety procedures.
Installation Instructions
1. Remove the existing meter from the meter socket and record the final reading per utility standard practice.
2. Inspect the meter socket jaws to ensure that they are in good condition.
3. Perform voltage checks, line-to-line and line-to-neutral, to ensure the voltage is at proper levels.
4. Visually inspect the meter. Ensure that the optical interface is secured in place on the meter base.
5. Install the meter and observe the Network Status LED to verify that a valid association candidate is found per
the table on the reverse page.
6. Install the meter ring and seal.
7. Record the new meter number and initial reading per utility standard practice.
Network Status LED (Red)
Message Status LED (Green)
Transceiver LED (Amber)
KT-24534 Proprietary and Confidential 05/29/2012
TUNet® TC-1220 Quick Reference
TUNet® LAN Module Network Status LED (Red)
Start-up/Power-up Solid ON (Fast flashing indicates module is not programmed)
Unassociated/Re-associating Solid ON
Valid association candidate found Flashing
Full network association confirmed OFF
TUNet® LAN Module Message Status LED (Green)
Start-up/Power-up OFF
Message queued for transmission Long flash
Valid message received (addressed to this device) Short flash
TUNet® LAN Module Transceiver (XVR) LED (Amber)
Start-up/Power-up OFF
RF packet transmitted Long flash
RF packet received (LAN activity) Short flash
Specifications
Frequency Range: 902-928 MHz frequency hopping, license exempt
Operating Temperature: -22 to 140°F (-30 to +60°C)
Modulation: FSK Operating Humidity: 5 to 95% non-condensing
Antenna: under the glass Standards:
Power supply: 120V/240VAC FCC CFR Title 47 Part 15b (unintentional radiators)
Power consumption: Quiescent 0.75 watts typical
ANSI C12.1:2001 Sections:
4.7.3.1 Insulation, 4.7.3.11 EFT/Burst
4.7.3.3.1 Surge Immunity, 4.7.3.3.2 Ring Wave Immunity
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Changes or modifications to this device not expressly approved by Tantalus Systems Corp. could void the user's authority to operate the equipment.
Contact Tantalus
Address all comments to:
Technical Support Tantalus Systems Corp. 301 – 3480 Gilmore Way Burnaby, B.C. V5G 4Y1
Telephone: 604-299-0458 Fax: 604-451-4111
Web http://www.tantalus.com
Email: techsupport@tantalus.com
Copyright © 2012 Tantalus Systems Corp. All rights reserved. No part of this document or associated
software may be reproduced, adapted, stored or transmitted in any form or by any means except with prior permission of Tantalus Systems Corp. or as explicitly allowed by copyright laws applicable to your situation. This document contains proprietary information of Tantalus Systems Corp. that may be your permitted workers and users of TUNet ® products and services who need to know.
disclosed only to
Tantalus, TUNet, Tantalus Utility Network, the stylized T logo, and the names of the products and services offered therewith, are trademarks of Tantalus Systems Corp. All other product and brand names referenced herein may be trademarks of their respective owners.
Tantalus assumes no responsibility for errors or omissions in this document or their consequences. The information is subject to change without notice. Please report any errors to Tantalus at the address above.
KT-24534 Proprietary and Confidential Page 2