Tantalus TC-1200 Series Installation Instructions Manual

Tantalus Utility Network™
r
)
The TC-1200 series module is a two-way 900 MHz LAN device which is integrated into a single phase electro­mechanical meter. The TC-1200 series module counts meter disk rotations using an optical sensor and delivers meter readings on request or on a programmed schedule for Time-of-Use and interval data applications. The TC­1200 series module also reports power outages and monitors power quality including voltage (plus sag/swell alarms) and momentary outages (blinks).
The TC-1200 series module is retrofitted into a single phase electro-mechanical meter either in the utility company meter shop or a contract meter shop.
Installation Instructions
TC-1200 Series
WARNING
Energized meters, meter sockets and distribution lines present the risk of electrical shock. Work on this equipment should be performed only by qualified metering specialists or industrial electricians following all utility company established operational and safety procedures.
Installation Instructions
1. Remove the existing meter from the meter socket and record the final reading per utility standard practice.
2. Inspect the meter socket jaws to ensure that they are in good condition.
3. Perform voltage checks, line-to-line and line-to-neutral, to ensure the voltage is at proper levels.
4. Visually inspect the meter. Ensure that the optical interface is secured in place on the meter base.
5. Install the meter and observe the Network Status LED to verify that a valid association candidate is found per the table on the reverse page.
6. Install the meter ring and seal.
7. Record the new meter number and initial reading per utility standard practice.
Optical interface
P/N 900-0004 Rev 1.0 Proprietary and Confidential 2005-08-04
Network Status LED (Red)
Message Status LED (Green)
Transceiver LED (Ambe
TC-1200 SERIES MODULE Installation Instructions
TC-1200 series module Network Status LED (Red) (Amber on earlier versions)
Start-up/Power-up
Unassociated/Re-associating Solid ON
Valid association candidate found Flashing
Full network association confirmed OFF
TC-1200 series module Message Status LED (Green)
Start-up/Power-up OFF
Message queued for transmission Long flash
Valid message received (addressed to this device) Short flash
TC-1200 series module Transceiver (XVR) LED (Amber) (Green on earlier versions)
Start-up/Power-up OFF
RF packet transmitted Long flash
RF packet received (LAN activity) Short flash
Frequency Range: 902-928 MHz frequency hopping, license exempt
Solid ON (Fast flashing indicates module is not programmed)
Specifications
Operating Temperature: -22 to 140°F (-30 to +60°C)
Modulation: FSK Operating Humidity: 5 to 95% non-condensing
Antenna: under the glass Standards:
Power supply: 240VAC FCC CFR Title 47 Part 15b (unintentional radiators)
Power consumption: Quiescent 1.9 watts typical
ANSI C12.1:1995 Sections:
4.7.3.1 Insulation, 4.7.3.11 EFT/Burst
Data interface: optical to attached TUNet 3205
4.7.3.3.1 Surge Immunity, 4.7.3.3.2 Ring Wave Immunity
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Changes or modifications to this device not expressly approved by Tantalus Systems Corp. could void the user's authority to operate the equipment.
Contact Tantalus
Address all comments to:
Technical Support Tantalus Systems Corp. 100 – 2955 Virtual Way Vancouver, B.C. V5M 4X6
Telephone: 604-299-0458 Fax: 604-451-4111
Web http://www.tantalus.com
Email: techsupport@tantalus.com
Copyright 2005 © Tantalus Systems Corp. All rights reserved. No part of this publication, or associated software, may be reproduced, stored in a retrieval system, or transmitted in any form or by any means including photocopying, electronic, mechanical, recording or otherwise without the prior written consent of Tantalus Systems Corp. This document contains proprietary information of Tantalus Systems Corp. The contents are confidential and disclosure without the prior written consent of Tantalus Systems Corp. is strictly prohibited.
TUNet™ and Tantalus Utility Network™ are Trademarks of Tantalus Systems Corp.
Tantalus assumes no responsibility for errors or omissions in this document or their consequences. The information is subject to change without notice. Please report any errors to Tantalus at the address above.
P/N 900-0004 Rev 1.0 Proprietary and Confidential Page
2
Loading...