Tanda TX7210 Installation And Operation Manual

TX7210
Addressable Single Input/Output Module
Installation and Operation Manual
TANDA UK Technology Copyright ©2015, All right reserved.
Installation & Operation Manual
4050100267-Rev1.6-0916
TANDA UK
Specifications are subject to change without prior notice
2
Product Safety
To prevent severe injury and loss of life or property, read the instruction carefully before installing the module to ensure proper and safe operation of the system.
European Union directive
2012/19/EU (WEEE directive): Products marked with this symbol cannot be disposed
of as unsorted municipal waste in the European Union. For proper recycling, return this product to your local supplier upon the purchase of equivalent new equipment, or dispose of it at designated collection points.
For more information please visit the website at www.recyclethis.info
EN54 Part 18 Compliance
TX7210 Addressable Single Input/output Module complies with the requirements of EN 54-18:2005.
EN54 Standard Conformity Information
0832
17 TANDA(UK) LIMTIED FOURTH FLOOR 30-31 FURNIVAL STREET LONDON EC4A 1JQ(Type 1, Option 2 Crosslisting)
TX7210 0832-CPR-F1830
EN 54-18:2005
Installation & Operation Manual
4050100267-Rev1.6-0916
TANDA UK
Specifications are subject to change without prior notice
3
Table of Content
1 Introduction ............................................................................................................................................................ 4
1.1 Overview ......................................................................................................................................................... 4
1.2 Feature and Benefits ..................................................................................................................................... 4
1.3 Technical Specification ................................................................................................................................ 4
2 Installation .............................................................................................................................................................. 5
2.1 Installation Preparation ................................................................................................................................. 5
2.2 Installation and Wiring .................................................................................................................................. 5
3 Interface Module Configuration ........................................................................................................................ 7
3.1 Preparation ..................................................................................................................................................... 7
3.2 Write: Addressing ........................................................................................................................................... 7
3.3 Feedback Mode ............................................................................................................................................ 8
3.4 Input Check Mode ........................................................................................................................................ 9
3.5 Output Check Mode .................................................................................................................................... 9
3.6 Read Configuration .................................................................................................................................... 10
4 General Maintenance ....................................................................................................................................... 10
5 Troubleshooting Guide ...................................................................................................................................... 11
Appendix 1 .............................................................................................................................................................. 11
Limitation of Interface Module ........................................................................................................................ 11
Installation & Operation Manual
4050100267-Rev1.6-0916
TANDA UK
Specifications are subject to change without prior notice
4
1 Introduction
1.1 Overview
The TX7210 Addressable Single Input/output Module is characterized as one input or output volt free relay and control module. The unit is normally used for overriding equipment such as lift return, door holder, smoke extract fans, air handling unit, auto dialler to fire brigade, BMS and etc. The unit has built-in feedback signal feature, according to the pre-configured interface module command fire scenario, the alarm controller send out start command to the equipment required to start. After receiving the command, output module enables its relay to change state. Once the module is under control and operated a confirmation signal will be sending back to the alarm controller. In addition, the unit incorporates an intelligent processor that provides automatic monitoring for both open and short circuit of the input signal line.
The unit manufactured base on the requirement of EN 54 part 18, European Standard. The unit is aesthetically pleasing with unobtrusive design that will complement modern building designs and its plug-in type assembles make installation and maintenance more convenient to the installer. The unit is compatible to the TX7004 Analogue Intelligent Fire Alarm Control Panel, produced by single manufacture T&A, to avoid addressable communication compatibility problem.
1.2 Feature and Benefits
EN54-18 Compliance Built-in MCU processor and digital addressing 24VDC/2A Output relay contact and Control module Input Fire or Supervisory signal configuration LED status indicator Onsite Adjustable Parameter Loop or external power input Aesthetically pleasing design Surface mounting with fix base for simple installation
1.3 Technical Specification
Listed LPCB Certification Compliance EN 54-18:2005 Input Voltage Loop Power:24VDC [16V to 28V]
External PSU: 20 to 28VDC
Current Consumption Loop: Standby 0.6mA, Alarm: 1.6mA
External PSU: Standby 0.6mA, Alarm: 45mA
Control output voltage 24VDC / 2A rating Input Relay Normally Open dry contact Input Resistance 5.1Kohms/ ¼ W Protocol/Addressing T&A, Value range from 1 to 254 Indicator Status Normal: Single blink/Active: Steady/Fault: Double Blink Material / Colour ABS / White Glossy finishing Dimension / LWH 108 mm x 86 mm x38 mm Weight 170g (with Base), 92g (without Base) Operating Temperature -10°C to +50°C Ingress Protection Rating IP30 Humidity 0 to 95% Relative Humidity, Non condensing