All spec i fi ca tions sub ject to change with out no tice. HART® is a reg is tered trade mark of the HART Com mu ni ca tions Foun da tion. All other trade marks ac knowl edged.
OPERATION MANUAL
This man ual is de signed to op ti mize the per for mance of the MST2000 Se ries Loop Powered
Multivariable SMARTFLOW® Trans mit ter. The end user should read and re view it care fully be fore in stall ing, us ing or main tain ing the trans mit ter. The in for ma tion con tained in this man ual cor re sponds
to the re vi sion level of the soft ware shipped with your MST2000. You can down load a copy of the lat est ver sion of this man ual along with other in for ma tion from our web site.
IMPORTANT: This man ual cov ers both the ENGLISH and METRIC Unit Ver sions of the MST2000 op er at ing soft ware. The ENGLISH or METRIC con fig u ra tion must be se lected at the time of or der and con fig ured at the fac tory. ENGLISH or METRIC UNIT CONFIGURATION IS NOT FIELD SELECTABLE.
It is the de sire of Thermo Brandt In stru ments that the MST2000 be setup and used as ef fec tively and ef fi ciently as pos si ble. If you have any ques tions or con cerns please con tact your
Thermo Brandt rep re sen ta tive or Thermo Brandt In stru ments at the fol low ing:
Tele phone:(919) 552-9011. Cus tomer Ser vice: Ex ten sion 28
Fac sim ile:(919) 552-9716
Web Ad dress:www.thermobrandt.com
E-mail:techsupp@brandtinstruments.com
TABLE OF CONTENTSPage
Model Num ber............................................2
Spec i fi ca tions ............................................3
MST2100 Di men sional Draw ing...................................4
MST2400 Di men sional Draw ing...................................4
Sec tion 1, Mount ing and Pro cess Con nec tions ...........................5
Sec tion 2, Con tin u ous Purge Op tion ................................5
Sec tion 3, In te gral “High Pres sure” Blowdown Sys tem Op tion ...................6
Sec tion 4, Elec tri cal Con nec tions ..................................7
Sec tion 5, LCD Dis play and In te gral Key Pad............................7
Sec tion 6, MST2000 Op er a tional Modes and Startup........................8
Sec tion 7, Pro gramming.......................................9
Sec tion 8, Pro gram Pa ram e ters...................................10
Sec tion 9, Alarm Pro gramming In for ma tion .............................16
Sec tion 10, For mulas & Con ver sion Factors ............................19
Sec tion 11, Test Jack ........................................20
Sec tion 12, Op tional Mod ule In stal la tion ..............................20
Sec tion 13, MST2000 HART® Com mu ni ca tions In for ma tion ....................23
Sec tion 14, Wiring Di a grams ....................................26
Sec tion 15, CSA Haz ard ous Area Ap provals ............................28
Sec tion 16, Cal i bra tion of the MST2000 ..............................30
PRODUCT OVERVIEW
Thermo Brandt In stru ments’ MST2000 Se ries Loop Powered Multivariable SMARTFLOW® Trans -
mit ter pro vides the nec es sary ver sa til ity re quired to sat isfy to day’s de mand ing in dus trial pro cess ap -
pli ca tions. With pro gram ma ble con stants, in put/out put op tions and com mu ni ca tion fea tures the
MST2000 will con cur rently mea sure and/or ap ply the nu mer ous pro cess vari ables for a true mass flow
mea sure ment.
The MST2000’s con fig u ra tion is user friendly and is ac com plished through the in te gral key p ad (no ex ter nal soft ware or hard ware is re quired). The MST2000 is ca pa ble of pro duc ing and dis play ing sig nals
for Dif fer en tial Pres sure or for Flow . Op tional in put, dig i tal I/O and com mu ni ca tion mod ules can be in stalled at the fac tory or in the field as re quired.
Page 4MST2000 Multivariable SMARTFLOW® TransmitterBrandt Instruments, Inc.
MST21 = MST2100, NEMA 1 Panel Mount En clo sure, Dif fer en tial Pres sure Con fig u ra tion & Non-isolated 4 Wire RTD In put Stan dard. u
MST24 = MST2400, NEMA 4X, Fi ber glass En clo sure, Dif fer en tial Pres sure Con fig u ra tion & Non-iso lated 4 Wire RTD In put Stan dard. u
ISOLATED INPUT MODULE: Ab so lute Pres sure Trans mit ter
0 = None
1 = Iso lated In put Mod ule: Ac cepts 4-20mA in put sig nal from an Ex ter nal Ab so lute Pres sure Trans mit ter. u
2 = Isolated Input Module with Integral Absolute Pressure Transmitter, 0-25 PSI (0-1.7 bar) range standard. Consult factory for
other ranges. MST2400 only. Requires Integral 24V Power Supply. See Output option 2 below.
ISOLATE
D INPUT
MODULE: Tem per a ture Trans mit ter
0 = None
CERTIFICATION
0 = None
1 = CSA Ap proved In trin sically Safe
COMMUNICATIONS
MODULE
DIGITAL I/O
MODULE
PRESSURE RANGES
1S = Stan dard Range 1Max. Span: 0-0.10” ( 0 to 2.54mm) W.C. Turn down to 0.010” (0.254mm)W.C. (10:1).
2S = Stan dard Range 2 Max. Span: 0-0.25” ( 0-6.35mm) W.C. Turn down to 0.025“ (0.635mm) W.C. (10:1).
3S = Stan dard Range 3 Max. Span: 0-1.00“ (0-25.4mm) W.C. Turn down to 0.10“ (2.54mm) W.C. (10:1).
4S = Stan dard Range 4 Max. Span: 0-4.00” (0-101.6mm) W.C. Turn down to 0.40” (10.16mm) W.C. (10:1).
5S = Stan dard Range 5 Max. Span: 0-16.0” (0-406.4mm) W.C. Turn down to 1.60” (40.64mm) W.C. (10:1).
6S = Stan dard Range 6 Max. Span: 0-50.0” (0-1270.0mm) W.C. Turn down to 5.00” 127.0mm) W.C. (10:1).
CR = Com pound RangeCon sult fac tory. Sup ply de sired Com pound Range.
All max i mum pres sure ranges have a turn down of 10:1.
Spec ify Pres sure Range # in model num ber (ex am ple 1S or CR).
Stan dard Ranges: MST2000 will be cal i brated at Max i mum Span. If an Ini tial Range Set ting is de sired, sup ply with
or der and unit will be shipped with this Ini tial Range pre set. (Ex am ple: 3S set to 0 to 0.5” W.C.).
Com pound Ranges: MST2000 will be cal i brated at de sired Com pound Range. Sup ply com pound range with or der
(ex am ple: -0.25 to +0.25” W.C.).
All spans will be cal i brated in Inches of W.C. Other Units of mea sure will be con verted to Inches of W. C.
OUTPUT & VERSION. See Note Be low.
1 = 4-20mA Out put. Eng lish Units Ver sion. u
2 = 4-20mA Out put with In te gral 120VAC to 24VDC Power Sup ply. 120VAC
3 = 4-20mA Out put. Met ric Units Ver sion.u
4 = 4-20mA out put with In te gral 120VAC to 24VDC Power Sup ply. 120VAC Source
2 = CSA Ap proved Di vi sion 2.
Review Sec tion 15 of this man ual for ap proval in for ma tion.
0 = None
H = HART® Com mu ni ca tions Mod ule.u
0 = None
D = Dig i tal I/O Mod ule with 1 In put, 1 Out puts. v
Source Re quired. MST2400 only. Eng lish Units Ver sion.
Re quired. MST2400 only. Met ric Units Ver sion.
OPTIONS
0 = None
B = In te gral High Pres sure Blowdown Sys tem. MST2400 Only. Re quires
Dig i tal I/O Mod ule. 120VAC source re quired. Reg u lated air sup plied to
100 PSIG. En clo sure size will change. Con sult Fac tory for spec i fi ca tions
and avail abil ity.
P = Con tin u ous Purge to Flowmeter. MST2400 Only. Spans of 0.25” W.C.
(6.35mmWC) or greater. A fil tered air sup ply source of 20 to 100 PSI
(1.4 to 6.9 bar) is re quired. u
ACCESSORIES
0 = None
P = Pipe Mount. MST2400 Only.
u De notes op tions & fea tures avail able with CSA In trin sically Safe
and Di vi sion 2 haz ard ous area ap prov als.
v De notes op tions & fea tures avail able with CSA Di vi sion 2 Ap -
provals Only.
Re view Sec tion 15, for CSA ap proval in for ma tion.
MST24111HD2S10P
MST2000’s with Eng lish or Met ric Unit Ver sions are avail able but must be se lected at time of or der and con fig ured at
the fac tory. IT IS NOT A FIELD SELECTABLE OPTION.
Ser vice:Clean, dry, non-corrosive Air or Gas. Other me dia may be pos si ble with the use of the Con -
Pres sure Ranges:Stan dard Pres sure Ranges:
Out put Sig nals: An a log: 4-20 mA sig nal (Max. Loop re sis tance = 615 Ohms @ 24 VDC) is user pro gram ma -
Com mu ni ca tions:Op tional: dig i tal HART® Com mu ni ca tions mod ule. See Sec tion 13, page 23 for HART® com -
Alarms:Pro gram ma ble hard ware alarms, underrange and overrange.
Dis play:High Con trast, 2 line, al pha nu meric LCD with -20 to 150o F (-28 to 66oC) op er at ing tem per -
Power Sup ply Re quired:24 to 40 VDC loop power, min i mum 11 volts re quired at in puts.
Re verse Po lar ity Pro tec tion: Yes
Turn On Time:4 sec onds (max i mum).
Tem per a ture Limits:Op er ating: -40 to 150oF (-40 to 66oC) Stor age: -40 to 180o F (-40 to 82oC)
Overpressure Limits:Proof Pres sure: 10 PSID (0.7 Bar) Burst Pres sure: 50 PSID (3.45 Bar)
Damping:Stan dard Time Con stant: 500 mSec. Ad di tional damp ing ad just able via in te gral key pad
Hu mid ity Limits:100% Non-condensing, (MST2400 Only).
In puts:Stan dard: Non-isolated, 4 wire RTD in put con nec tion.
PERFORMANCE SPECIFICATIONS
Ac cu racy:For spans from 40% to 100% of max i mum range with TD of 1:1 to 2.5:1 then ac cu racy =
Sta bil ity:0.1% of Max i mum Range / 12 Months
Am bi ent Tem per a ture:Zero: No Ef fect Span: Less than 0.001% of Re-ranged Span per Deg F. Cor rected by in -
Mount ing Po si tion Ef fect:Mi nor ef fect on Zero. Cor rected by setup pa ram e ters.
Vi bra tion Ef fect:Less than 0.2% of Max i mum Range / g, 10-130 Hz.
PHYSICAL SPECIFICATIONS:
En clo sure Types: MST2100: NEMA 1, An od ized Alu mi num.MST2400: NEMA 4X, Fi ber glass.
Pro cess Con nec tions:MST2100: 1/8” NPTF MST2400: 1/4” NPTF Stain less Steel
Elec tri cal Con nec tions:MST2100 & MST2400: Cage Clamp style ter mi nal block. 12-24 AWG wire size.
Weight:MST2100: 2.5 . (1.14 kg)MST2400: 8.0 lbs. (3.63 kg)
tin u ous Purge op tion. Con sult fac tory .
Range 1: 0 to 0.10” (0 TO 2.54mm) W.C. Range 4: 0 to 4.0” (0 to 101.6mm) W.C.
Range 2: 0 to 0.25” (0 to 6.35mm) W.C. Range 5: 0 to 16.0” (0 to 406.4mm) W.C.
Range 3: 0 to 1.0” (0 to 25.4mm) W.C.Range 6: 0 to 50.0” (0 to 1270.0mm) W.C.
ble to Dif fer en tial Pres sure or Flow Parameters. Ex ter nal in puts or pro grammed con stants
for tem per a ture and ab so lute pres sure along with con stants for Ef fec tive Area and Stan dard
Den sity, are nec es sary for a true flow mea sure ment.
Op tional Dig i tal: One (1) op tional dig i tal (open col lec tor) out put avail able. Ac ti va tion pro gram ma ble by end user.
mu ni ca tion in for ma tion.
a ture.
Max Line Pres sure: 50 PSIG (3.45 Bar).
from 0.5 to 5 Sec onds in 0.5 sec ond in cre ments.
Op tional 4-20mA Iso lated In puts: In put ranges are soft ware rangeable.
& Ex ter nal Tem per a ture: 4-20mA In put
& Ex ter nal Ab so lute Pres sure: 4-20 mA In put
Op tional Dig i tal In put: One op tional dig i tal (TTL level) in put is avail able.
0.15% of Re-ranged Span.
For spans from 20% to 39% of max i mum range with TD of 2.5:1 to 5:1 then ac cu racy =
(0.15 + 0.005 X TD)% of Re-ranged Span.
For spans from 10% to 19% of max i mum range with TD of 5:1 to 10:1 then ac cu racy =
(0.15 + 0.010 X TD)% of Re-ranged Span.
& TD = Max i mum Range / Re-ranged Span
ter nal tem per a ture sen sor.
MST2400: ½” Liq uid-Tight flex i ble con duit con nec tions.
Page 6MST2000 Multivariable SMARTFLOW® TransmitterBrandt Instruments, Inc.
The MST2000 can be mounted in any di rec tion. There may be a mi nor ef fect on Zero
that can be cor rected by the setup pa ram e ters.
1.1 MST2100: NEMA 1 En clo sure
A. Re view the di men sional draw ing on page 5.
B. Pro cess con nec tions are via 1/8" NPT fe male ports lo cated on the bot tom of the hous ing. The high
pres sure port is la beled “HIGH”, the Low pres sure port is la beled “LOW” on the mount ing plate.
1.2 MST2400: NEMA 4X En clo sure
A. Re view the di men sional draw ing on page 5.
B. With out a con tin u ous purge op tion, pro cess air should be non-corrosive and dry. If a con tin u ous
purge op tion is in stalled please re view sec tion 2 on the con tin u ous purge. The con tin u ous purge
must be bal anced.
C. Pro cess con nec tions are via 1/4" NPT fe male ports lo cated on the bot tom of the en clo sure. The high
pres sure port is la beled “HIGH”, the Low pres sure port is la beled “LOW”.
1.3 Three Valve Man i fold
A. It is rec om mended that a three valve man i fold be in stalled in the pro cess, un less a con tin u ous
purge is in stalled . A three valve man i fold is avail able from the fac tory. It is in stalled in the pro cess
lines to iso late the pro cess sig nal dur ing in stal la tion and/or re moval of the MST2000 thus pre vent ing
pos si ble trans ducer over-pressurization and to zero trans mit ter.
þ Notes:
& Be fore con nec tions are made blow out pro cess lines throughly.
& It is rec om mended that pipe thread tapes not be used on pneu matic pip ing.
& Soap test all joints and fit tings for leaks.
& Pro cess lines should be the same di am e ter and ap prox i mately the same length.
þ Note: MST2000 DP sen -
sor max i mum op er at ing
static pres sure is 25
PSID.
2.CONTINUOUS PURGE OPTION
The MST2400 can be or dered with a Con tin u ous
Purge Op tion. This op tion sup plies a con tin u ous
pneu matic purge to a Thermo Brandt pitot flow
sen sor to keep the sens ing ports free from plug ging dur ing op er a tion. There are Purge Bal ance
ad just ments lo cated on the front panel which
pro vide for the ze ro ing of pro cess air re sis tance.
If the Con tin u ous Purge Op tion has been or dered, please read the fol low ing setup in struc tions. The Con tin u ous Purge Op tion must be
bal anced once the pro cess is con nected to
the MST2400.
A 1/4" NPT fe male air sup ply port is pro vided on
the bot tom of the en clo sure for the Purge.
An in ter nal fil ter is sup plied with the unit, but air
sup ply should also be fil tered and reg u lated.
þ PROCESS LINE LENGTH & SIZE
& When a con tin u ous purge op tion is used, the pro cess
lines (Hi and Low lines) must be the same di am e ter
(pref er a bly 3/8" or larger) and the length of each line
should be the same within +/- 5%.
þ IMPORTANT:
& The Con tin u ous purge op tion air sup ply should be only clean, in stru ment qual ity air and should be greater than 20
psi (1.4 bar) and not ex ceed 100 psi (6.9 bar). A pre-filter should be in stalled in the sup ply line if the air qual ity is
sus pect. A 5 mi cron fil ter and a 0.3 mi cron co ales cent fil ter are rec om mended. Fail ure to pro vide clean, in stru ment
qual ity air through the Con tin u ous Purge can cause the MST2000 to give er ratic read ings. Fail ures at trib uted to a
con tam i nated air sup ply are not cov ered un der the war ranty.
Page 8MST2000 Multivariable SMARTFLOW® TransmitterBrandt Instruments, Inc.
OPERATION MANUALIn te gral “High Pres sure” Blowdown Sys tem
2.1 Bal ancing the Purge if the Pro cess is in Op er a tion
A. Re view the draw ing on page 5.
B. Pro cess must be in a steady state.
C. Dis con nect the HIGH and LOW lines from the trans mit ter. Mea sure the DP from the pro cess with a
pres sure cal i bra tor or other DP mea sur ing de vice..
D. Re cord the DP read ing. ______________________________
E. Re con nect the HIGH and LOW lines back to the trans mit ter. Make sure the Purge is op er at ing.
F.Ad just the “HIGH” and “LOW” Purge Bal ance ad just ments on the mount ing plate un til the dis play
read ing equals the read ing re corded in Step D. See the draw ing on page 5.
2.2 Bal ancing the Purge if the Pro cess is not in Op er a tion
A. Re view the draw ing on page 5.
B. En sure that there is no flow in the pro cess. If the flow can not be stopped com pletely fol low the in -
struc tions in Sec tion 2.1.
C. At tach the HIGH and LOW lines to flow me ter.
D. Ad just the “HIGH” and “LOW” Purge Bal ance ad just ments on the front panel till the dis play read ing
equals 0.0000 Inch W.C. See draw ing on page 5.
þ IMPORTANT: It is rec om mended that a Three Valve Man i fold not be used with an MST2400 which con -
tains the Con tin u ous Purge Op tion. Con sult fac tory.
2.3 In te gral 5 Mi cron Co ales cent Fil ter
A. The MST2400 with con tin u ous purge co mes with an in te gral 5 mi cron Co ales cent Fil ter. See the
Draw ing on page 5.
B. The fil ter is in tended as a sec ond ary de vice. The sup ply air should be reg u lated and fil tered be fore
en ter ing the en clo sure.
C. The in te gral fil ter will turn “RED” as it cleans the air. Re place the fil ter be fore the “RED” reaches the
right side, or out let end.
3.In te gral “High Pres sure” Blowdown Sys tem
The MST2400 can be or dered with an In te gral “High Pres sure” Blowdown Sys tem. This op tion is de signed to clean out Pitot Av er aging Flow sen sors us ing a blast of “High Pres sure” Air (up to 100 PSIG or
6.9 bar) while hold ing the last out put sig nal from the MST2400.
The MST2400 is ca pa ble of be ing pro grammed to per form a blowdown se quence any where from ev e ry
2 min utes up to once ev ery 24 hours (1440 min utes). The blowdown se quence can also be ac ti vated by
a re mote pulse from a DCS or other con trol ler.
A. Spec i fi ca tions:
a. Air Sup ply: Max i mum of 100 PSIG (6.9 bar) . If air sup ply is over 100 PSIG then a reg u la tor must be
in stalled.
b. Volt age: 120 VAC. Op tion con tains in te gral 24VDC power sup ply.
c. Se quence Du ra tion: Approximately 30 sec onds from time sig nal is held till sig nal is re stored.
d. Tem per a ture: Max i mum 150oF.
e. Pro gram ma ble intervals: 2 min utes to 1440 min utes (24 hours).
f. Pulse Sig nal from ex ter nal controller: Con tact clo sure for ½ sec ond (500 mil li sec onds).
B. Se quence of Op er a tion
a. The MST2400 be gins the Blowdown se quence by hold ing the last out put sig nal. “-HOLD-” will ap -
pear on the LCD. The Blowdown Status In di ca tor will also be lit. See the sec tion on the LCD Dis play.
b. Valves are ac ti vated to iso late and vent the trans mit ter from the pro cess to pre vent dam a ge.
c. The Hi & Low pro cess lines are al ter nately blown down for ap prox i mately 11 sec onds each.
d. Valves are au to mat i cally ac ti vated to re store sig nal from pro cess back to MST2400.
C. Ex ter nal Ac ti va tion Sig nal
The MST2400 In te gral Blowdown can be ac ti vated by a ½ sec ond ex ter nal contact closure pulse sig nal. The Blowdown can be con trolled by this sig nal only or in com bi na tion with the in te gral con trol of the
MST2400. The MST2000 must be pro grammed to ac cept this sig nal. Re fer to Pro gramming Pa ram e ters, Sec tion 8. See Wiring Di a grams in Sec tion 14.
þ Note: A 110VAC power source is re quired for the In te gral Blowdown Sys tem. An internal 24VDC
power sup ply is fur nished with the Blowdown. DO NOT USE THIS POWER SUPPLY TO POWER THE
LOOP SIGNAL.
draw ings.
B. Re fer to the MST2000 Ter mi nal Block Draw ing.
C. MST2000 In stru ment Elec tri cal Con nec tions are
cage clamp style for 12-24 AWG. Wire should be
stripped back a min i mum of 3/16" inches (5mm).
D. The MST2000 Multivariable dif fer en tial pres sure
trans mit ter is a HART® com pat i ble loop-powered
4-20 milliamp trans mit ter. Power con nec tion is
made at the two left ter mi nal po si tions marked
LOOP+ and LOOP-. Nom i nal power sup ply volt age
is 24 volts DC which al lows up to 600 ohms se ries
re sis tance in the loop cir cuit.
þ For HART® ap pli ca tions, min i mum loop re sis tance is
250 ohms.
4.2 MST2400: NEMA 4X En clo sure
A. A ½" Liq uid Tite con duit con nec tion is lo cated on
the bot tom of the En clo sure.
B. Con duit should be in stalled to pre vent con den sa tion
from col lect ing in the in stru ment.
4.3 In te gral Power Sup ply Op tion.
A. The In te gral Power Sup ply Op tion re quires an ex ter nal 120 Volt Power Sup ply.
B. A six (6) po si tion screw type ter mi nal block and ½" Liq uid Tite Con duit con nec tion are sup plied with
the In te gral Power Sup ply Op tion.
4.4 Ca na dian Stan dards As so ci a tion Hazardous Area Ap provals
The MST2100 and MST2400 have been ap proved by CSA for haz ard ous area in stal la tions.
See Sec tion 15 for de tails or con tact the fac tory.
5.LCD DISPLAY and INTEGRAL KEY PAD
All con trols and in di ca tors are Lo cated on the front panel of the MST2000. Re fer to the LCD & Key Pad
Draw ing.
5.1 Key Pad
All pro gram ming and con trol op er a tions are per formed us ing four (4) pushbuttons on the key pad.
Fol low ing are sum ma ries of each key.
MODE: ! Tog gles the MST2000 be tween
RUN Mode and PROGRAM
Mode.
! Also used to change the edit cur -
sor when en ter ing a numeric
value.
EDIT: ! Se lects the pa ram e ter to edit
when in Pro gramming Mode.
! Also saves the ed ited pa ram e ter
data to memory.
INCREMENT: ! In cre ments (steps for ward) through pa ram e ters and/or nu meric val ues.
DECREMENT: ! Dec re ments (steps back wards) through pa ram e ters and/or nu meric val ues.
RESET: ! Re sets the CPU. Re starts pro gram and loads in pro grammed vari ables stored in
the E-Prom
Page 10MST2000 Multivariable SMARTFLOW® TransmitterBrandt Instruments, Inc.
OPERATION MANUALMST2000 OPERATIONAL MODES and START UP
5.2 LCD Dis play
The MST2000 High Con trast LCD dis play will
dis play two (2) lines si mul ta neously. The dis play
is used to setup and cal i brate the MST2000 and
dis play and mon i tor in put and out put sig nals and
other vari ables.
The lines of dis play are:
Nu meric: ! Where the val ues for DP or
Flow are dis played.
! The vari ables for pa ram e ters
are ed ited and dis played.
Al pha nu meric: ! Where units of mea sure and
pa ram e ter names are dis played.
Sta tus
In di ca tors:
! Used to dis play the op er a tional sta tus of the MST2000. The Sta tus in di ca tor will
in di cate when the MST2000 is in “RUN Mode”, if there is an Alarm and whether
an AutoZero or Blowdown se quence is in pro cess.
6.MST2000 OPERATIONAL MODES and START UP
The MST2000 has two ba sic op er a tional Modes. They are:
RUN MODE ! In this mode the MST2000 is op er at ing and dis play ing the mea sure ments.
PROGRAM
MODE
! In this mode the MST2000 is ready for pro gram ming. Note: The PROGRAM Mode
can be pass word pro tected.
Startup
When power is first ap plied, the MST2000 Liq uid Crys tal Dis play (LCD) will first dis play RESET fol lowed
by READEE and then dis play the se lected runtime pa ram e ter. The avail able runtime pa ram e ters are
listed be low.
ENGLISH UNITS VERSIONMETRIC UNITS VERSION
INWC
SCFM
ACFM
LBHR
TEMP
ABS_PR
ALARMS
DP in Inches of Wa ter Col umn
Gas Flow in Stan dard Cu bic Feet per Min ute
Gas Flow in Ac tual Cu bic Feet per Min ute
Mass Flow in Pounds per Hour
Process Tem per a ture in De grees Fahr en heit
Process Ab so lute Pres sure in PSI
MST2000 Alarm Sta tus
MMWC
NM3-HR
M3-HR
KG-HR
TEMP
ABS_PR
ALARMS
DP in mil li me ters of Wa ter Col umn
Gas Flow in Nor mal Cu bic Me ters per Hour
Gas Flow in Cu bic Me ters per Hour
Mass Flow in Ki lo grams per Hour
Process Tem per a ture in De grees Cel sius
Process Ab so lute Pres sure in Bar
MST2000 Alarm Sta tus
• The de fault dis play mode is ini tially set at the fac tory for inches of wa ter col umn (INWC) or mil li me ters of wa ter col umn (MMWC). The user may se lect other runtime flow vari ables by press ing
the INC (in cre ment) or the DEC (dec re ment) keys. Note: Eng lish or Met ric Unit Con fig u ra -
tions are not field selectable. They must be set at the fac tory.
• The MODE key is used to tog gle be tween RUN mode andPRO GRAM mode.
• The EDIT key is used to clear ‘latched’ alarms in runtime (RUN) mode.
The MST2000 PROGRAM mode is ac cessed by press ing the MODE key. When the MODE key is
pressed one of the fol low ing will oc cur.
þ NOTE:
& The MST2000 can be Pass word pro tected to pre vent un au tho rized ac cess to pro gram ming pa ram e ters. The
MST2000 is shipped from the fac tory with the Pass word dis abled.
7.1 If the Pass word Pa ram e ter is En abled (else go to Sec tion 7.2)
A. The MST2000 will then dis play ENT_PWprompt ing the user to en ter the re quired pass word.
þ NOTE:
& The user must press the EDIT key within 4 sec onds to be gin en ter ing the cur rent pass word or the MST2000 will re -
turn to RUN mode. The pass word is a unique num ber be tween 1 and 9999 and is en tered as de scribed in Sec tion
7.5.
& Dur ing pass word en try, if no keys are pressed for more than 4 sec onds, the MST2000 will re turn to RUN mode.
7.2 If the Pass word Pa ram e ter is Dis abled or af ter the Pass word is suc cess fully en tered.
Af ter the pass word has been prop erly en tered, Brandt and verXXX will be mo men tarily dis played
and then fol lowed by the first avail able PROGRAM pa ram e ter.
þ NOTE: ver XXX indicates the installed soft ware re vi sion level.
7.3 Se lect the Pa ram e ter to Edit
A. Once the Pa ram e ters are dis played use the INC and DEC keys to scroll up and down through the
avail able pa ram e ters. See pa ram e ters, Sec tion 8.0.
B. To edit a se lected pa ram e ter, press the EDIT key and the ed it ing menus will be come ac tive.
C. Pa ram e ters are ei ther a nu meric value (ex am ple: Ef fec tive Area) or con trol a hard ware/op er at ing
mode.
7.4 Editing of a Hard ware/Op er ating Mode Pa ram e ter.
A. If a pa ram e ter con trols a hard ware or op er at ing mode fea ture, use the INC and DEC keys to scroll
through the avail able set tings.
B. Af ter the de sired set ting is se lected, press the EDIT key again to save the se lected set ting to mem -
ory.
C. The LCD will dis play SAVED for ap prox i mately 1 sec ond and then redisplay the new set ting.
7.5 Editing a Nu meric Value Pa ram e ter.
A. If the se lected pa ram e ter to edit is a nu meric value,
the ed it ing menus will dis play the cur rent value and
the cur rent cur sor po si tion for the dec i mal po si tion.
B. Use the INC and DEC keys to in cre ment or dec re -
ment the nu meric value at the cur rent cur sor po si -
tion.
C. To change the cur sor po si tion press the MODE
key. The LCD will dis play ‘x 1’ if the ones col umn is
to be changed, ‘x 10’ for the tens col umn, ‘x D1’ for
the tenths col umn, ‘x D01’ for the hun dredths col -
umn, etc. The num ber will not in cre ment or dec re -
ment if the pa ram e ter limit is reached. See the
Chart Be low and the ex am ples to the right.
Page 12MST2000 Multivariable SMARTFLOW® TransmitterBrandt Instruments, Inc.
OPERATION MANUALPROGRAM PARAMETERS
LEFT OF
DECIMAL
X1XX D1X
X10XX D01X
X100XX D001X
X1KXX D0001X
X10KX
X100KX
X1MX
1000000.100000.10000.1000.100.10.1.
RIGHT OF
DECIMAL
.1.01.001.0001
D. Af ter the num ber is changed to the de sired value, press the EDIT key again to save the new value to
mem ory.
E. The LCD will dis play savedfor ap prox i mately 1 sec ond and then redisplay the new set ting.
8.PROGRAM PARAMETERS
The Avail able PROGRAM pa ram e ters are shown be low along with a de scrip tion of how each pa ram e ter is ap plied. They are listed in the or der they ap pear in the PROGRAM menus.
Pa ram e terDe scrip tionFac tory De fault
LCDCONLCD Con trast ad just ment. Avail able range is from 0 to 10. Use lower
set tings for best con trast in colder en vi ron ments and higher set tings for
best con trast in hot ter en vi ron ments.
5
420OUT4-20 milliamp Out put as sign ment. Avail able as sign ments are: 0 = INWC or MMWC
Eng lish Units Ver sion: 0 = INWC (pri mary vari able), 1 = SCFM,
2 = ACFM, 3 = LBHR.
Met ric Units Ver sion: 0 = MMWC (pri mary vari able), 1 = NM3-HR,
2 = M3-HR, 3 = KG-HR
420_ZE4 Milliamp Zero set ting. The 4 milliamp zero set ting ad justs the
milliamp lower range of the pri mary vari able (INWC or MMWC). The
avail able range is the nat u ral span of the dif fer en tial pres sure sen sor.
420_SP20 Milliamp Span set ting. The 20 milliamp span set ting ad justs the
milliamp span value of the pri mary vari able (INWC or MMWC). The
avail able range is the nat u ral span of the dif fer en tial pres sure sen sor.
þ NOTE: The 420_SP value (span) must al ways be greater than the 420_ZE
value (zero) for proper op er a tion.
F_SPANFlow Span set ting. The flow span set ting con trols the up per 4-20
milliamp value as sign ment (turn down) when the 4-20 out put is as signed to the runtime cal cu lated flow vari ables (SCFM, ACFM, LBHR
or NM3-HR, M3-HR, KG-HR). The lower 4-20 milliamp value as sign ment is al ways ref er enced to zero (0). The avail able range is:
Eng lish Unit Ver sion: 0 to 10,000,000 (no units).
Met ric Unit Ver sion: 0 to 50,000,000 (no units).
E_AREAEf fec tive Area of flow me ter de vice. The ef fec tive area is re quired for
flow cal cu la tions and is en tered to be the same as shown on the Thermo
Brandt flow me ter la bel. The avail able range is:
Eng lish Unit Ver sion: 0.0000 to 500.0000 square feet.
Met ric Unit Ver sion: 0.0000 to 100.0000 square meters.
þ NOTE: Some flow me ter de vices use ‘K fac tors’ in stead of ef fec tive ar eas to
de fine mass flow re la tion ships. Ef fec tive ar eas can be cal cu lated from given
K fac tors. See For mulas, Sec tion 10.
þ NOTE: Thermo Brandt flow me ter de vices are spec i fied in square feet. To
con vert to square me ters, mul ti ply the square feet value by 0.0929.
STDDENStandard Density. The standard density is required for mass flow
calculations and is entered for the specific gas being measured. The
standard density is entered at the standard reference temperature of 68
degrees F or 20 de grees C. The avail able range is:
Eng lish Unit Ver sion: 0.0000 to 2.0000 pounds per cu bic foot.
Met ric Unit Ver sion: 0.0000 to 40.0000 Ki lo grams per cu bic me ter.
TMPSRCTemperature source. Available assignments are 0 = CONstant,
1 = EXTernal and 2 = RTD.
TMPCONTemperature Constant. The temperature con stant can be used for
mass flow calculations when no external temperature inputs are
available and is entered as the average gas temperature. The avail able
range is:
Eng lish Unit Ver sion: -50.0000 to 900.0000 de grees F.
Met ric Unit Ver sion: -50.0000 to 900.0000 de grees C.
1.0000 for English.
0.0929 for Metric.
0.07517 for English.
1.20367 for Metric.
0 = CONstant
68.0000 for English.
20.0000 for Metric
RTDCALRTD Calibration offset. The RTD calibration offset constant allows the
user to offset the actual measured value from the direct RTD input. The
value may be positive or negative and is entered in degrees F. The
available range is :
Eng lish Unit Ver sion: -10.0000 to 10.0000 de grees F.
Met ric Unit Ver sion: -10.0000 to 10.0000 de grees C.
EX_TPZExternal Temperature Zero. The External Temperature Zero is the
lower range (4 milliamp zero) setting for the external 4-20 milliamp
‘temperature’ input channel. The available range is:
Eng lish Unit Ver sion: -50.0000 to 100.0000 de grees F.
Met ric Unit Ver sion: -50.0000 to 100.0000 de grees C.
TPZCALTemperature Zero Calibration. The Temperature Zero Calibration
value is the 4 milliamp (zero) count value from the external 4-20 milliamp
‘temperature’ input channel. This parameter is used to calibrate the zero
point of the incoming 4-20 signal from the external 4-20 temperature
device. To calibrate the zero point of the incoming 4-20 signal, press the
EDIT key. The screen will display IN4MA. Set the incoming signal for 4
milliamps (or connect an external 4-20 calibrator set for 4 milliamps) and
press the EDIT key. The MST2000 will measure the external temperature
input channel and save the new 4 milliamp reference to memory.
0.0000
0.0000
4175
If an external
temperature option
is pre-installed and
calibrated at the
factory this will be
custom set for that
unit.
Page 14MST2000 Multivariable SMARTFLOW® TransmitterBrandt Instruments, Inc.
OPERATION MANUALPROGRAM PARAMETERS
Pa ram e terDe scrip tionFac tory De fault
EX_TPSExternal Temperature Span. The External Temperature Span is the
upper range setting for the external 4-20 milliamp ‘temperature’ input
channel. The avail able range is:
Eng lish Unit Ver sion: 0.000 to 990.0000 de grees F.
Met ric Unit Ver sion: 0.000 to 990.0000 de grees C.
TPSCALTemperature Span Calibration. The Temperature Span Calibration
Value is the 20 milliamp (span) count value from the external 4-20
milliamp ‘temperature’ input channel. This parameter is used to
calibrate the span point of the incoming 4-20 signal from the external
temperature device. To calibrate the span of the incoming 4-20 signal,
press the EDIT key. The screen will display IN20MA. Set the incoming
signal for 20 milliamps (or connect an external 4-20 calibrator set for 20
milliamps) and press the EDIT key. The MST2000 will measure the
external temperature input channel and save the new 20 milliamp
reference to memory.
APRSRCAbsolute Pressure Source. Available assignments are 0 = CONstant
and 1 = EXTernal.
þ Note: MST2000 DP sen sor max i mum op er at ing static pres sure is 25 PSID.
APRCONAbsolute Pressure Constant. The absolute pressure constant can
be used for mass flow calculations when no external absolute pressure
input is available and is entered as the average absolute pressure
inside the duct. The avail able range is:
Eng lish Unit Ver sion: 0.000 to 100.0000 PSIA.
Met ric Unit Ver sion: 0.000 to 100.0000 Bar.
200.0000
21000
If an external
temperature op tion
is pre-installed and
calibrated at the
factory this will be
custom set for that
unit.
0 = CONstant
14.6960 for English.
1.01325 for Metric.
EX_APZExternal Absolute Pressure Zero. The External Absolute Pressure
Zero is the lower range (4 milliamp zero) setting for the external 4-20
milliamp ‘absolute pressure’ input channel. The avail able range is:
Eng lish Unit Ver sion: 0.000 to 100.0000 PSIA.
Met ric Unit Ver sion: 0.000 to 100.0000 Bar.
þ Note: MST2000 DP sen sor max i mum
op er at ing static pres sure is 25 PSID.
APZCALAbsolute Pressure Zero Calibration The Absolute Pressure Zero
Calibration value is the 4 milliamp (zero) count value from the external
4-20 milliamp ‘absolute pressure’ input channel. This parameter is
used to calibrate the zero point of the incoming 4-20 signal from the
external 4-20 absolute pressure device. To calibrate the zero point of
the incoming 4-20 signal, press the EDIT key. The screen will display
IN4MA. Set the incoming signal for 4 milliamps (or connect an external
4-20 calibrator set for 4 milliamps) and press the EDIT key. The
MST2000 will measure the external absolute pressure channel and
save the new 4 milliamp reference to memory.
EX_APSExternal Absolute Pressure Span. The External Absolute Pressure
Span is the upper range setting for the external 4-20 milliamp ‘absolute
pressure’ input channel. The available range is:
Eng lish Unit Ver sion: 0.000 to 100.0000 PSIA.
Met ric Unit Ver sion: 0.000 to 100.0000 Bar.
þ Note: MST2000 DP sen sor max i mum
op er at ing static pres sure is 25 PSID.
0.000
4175
If an external
absolute pressure
option is
pre-installed and
calibrated at the
factory this will be
custom set for that
unit.
APSCALAbsolute Pressure Span Calibration. The Absolute Pressure Span
Calibration value is the 20 milliamp (span) count value from the external
4-20 milliamp ‘absolute pressure’ input channel. This parameter is used
to calibrate the span point of the incoming 4-20 signal from the external
absolute pressure device. To calibrate the span point of the incoming
4-20 signal, press the EDIT key. The screen will display IN20MA. Set the
incoming signal for 20 milliamps (or connect an external 4-20 calibrator
set for 20 milliamps) and press the EDIT key. The MST2000 will measure
the external absolute pressure channel and save the new 20 milliamp
reference to memory.
INPUTOInput Offset. The Input Offset parameter allows the user to adjust
(calibrate) the actual pressure (zero) value to the MST2000 displayed
value. The input offset parameter is displayed and stored in memory as
counts. After the EDIT key is pressed, the edit menu displays the real
time pressure input. The user then uses the INC and DEC keys to adjust
the desired offset. The pressure input must be connected to a pressure
source and be at minimum range value (zero reference) during this
adjustment. Use the MODE key to adjust the cursor position (i.e.. x D1, x
D10, x D100, etc.) to change the offset count by different increments. The
available range is –50,000 to 50,000 counts (approximately +/- 20%
adjustment of full scale). The factory default is as set by the factory during
initial system calibration.
INPUTGInput Gain. The Input Gain parameter allows the user to adjust the gain
of the actual pressure (full scale) value to the MST2000 displayed value.
The input gain parameter is displayed and stored in memory as a gain
multiplier. After the EDIT key is pressed, the edit menu displays the real
time pressure input. The user then uses the INC and DEC keys to adjust
the desired gain. The pressure input must be connected to a pressure
source and at maximum range value during this adjustment. Use the
MODE key to adjust the cursor position (i.e.., x D1, x D01, x D001 etc.) to
change the gain multiplier by different increments. The available range is
0.8000 to 1.2000 (approximately +/- 20 % adjustment of full scale). The
factory default is as set by the factory during initial system calibration.
21000
If an external
absolute pressure
option is
pre-installed and
calibrated at the
factory this will be
custom set for that
unit.
This is a factory
default setting
determined during
calibration. It should
be recorded by the
user in the event it
will be necessary to
restore the InputOffset to the original
value. This setting
is also recorded on a
label located under
the cover of the
MST2000.
This is a factory
default setting
determined during
calibration. It should
be recorded by the
user in the event it
will be necessary to
restore the InputGain to the original
value. This setting
is also recorded on a
label located under
the cover of the
MST2000.
OUTPTOOutput Offset. The Output Offset parameter allows the user to adjust the
actual 4 milliamp (zero) output value as referenced to the MST2000
displayed zero value. The output offset parameter is displayed and
stored in memory as counts. After the EDIT key is pressed, the edit menu
displays the actual count offset and the microprocessor sets the output to
the 4.000 milliamp value. The user then presses the INC and DEC keys
to adjust the desired milliamp offset. Use the MODE key to adjust the
cursor position (i.e. x D1, x D10, x D100, etc.) to change the offset count
by different increments. The available range is –1,000 to 10,000 counts
(approximately 3.9 to 6.5 milliamp adjustment range). The factory default
is as set by the factory during initial system calibration.
Page 16MST2000 Multivariable SMARTFLOW® TransmitterBrandt Instruments, Inc.
This is a factory
default setting
determined during
calibration. It should
be recorded by the
user in the event it
will be necessary to
restore the OutputOffset to the original
value. This setting is
also recorded on a
label located under
the cover of the
MST2000.
OPERATION MANUALPROGRAM PARAMETERS
Pa ram e terDe scrip tionFac tory De fault
OUTPTGOutput Gain. The Output Gain parameter allows the user to adjust the
actual 20 milliamp (span) output value as referenced to the MST2000
displayed full scale value. The output gain parameter is displayed and
stored in memory as a gain multiplier. After the EDIT key is pressed, the
edit menu displays the actual multiplier value and the microprocessor
sets the output to the 20.000 milliamp value. The user then uses the
INC and DEC keys to adjust the desired full scale milliamps. Use the
MODE key to adjust the cursor position (i.e., x D1, x D01, x D001 etc.)
to change the gain multiplier in different increments. The available
range is 0.8000 to 1.1000. (Approximately 16.5 to 20.5 milliamp
adjustment range). The factory default is as set by the factory during
initial system calibration.
þ NOTE: The minimum and maximum output current range is 3.9 milliamps
and 20.5 milliamps (3.8 milliamps is reserved for fault ‘low’ current and
21.0 milliamps is reserved for fault ‘high’ current).
þ Note: If HART
ited to 4.0 milliamps.
®
com mu ni ca tions are en abled, the min i mum cur rent is lim -
AVGFACAveraging Factor. The Averaging Factor controls the digital filtering
level (damping) of the displayed pressure value (and the 4-20 milliamp
output). The average factor parameter controls the size (depth) of the
digital FILO (first in – last out) filter algorithm. Available range is 1 to 10.
The average factor does not affect the inherent update rate of the LCD
or 4-20 milliamp output (approximately two times per second) except
during power up initialization when the FILO registers are first being
loaded.
This is a factory
default setting
determined during
calibration. It should
be recorded by the
user in the event it
will be necessary to
restore the OutputGain to the original
value. This setting
is also recorded on a
label located under
the cover of the
MST2000.
1= No Filtering
DEFDSPDefault Display. The Default Display parameter assignment selects
the LCD display mode after power up and initialization. Available
assignments are:
Eng lish Unit Ver sion: 0 = INWC (pri mary vari able), 1 = SCFM, 2 = ACFM,
3 = LBHR or 4 = SCAN. Se lecting SCAN will cause the dis play to se quence
through the cal cu lated vari ables at 4 sec ond in ter vals.
Met ric Unit Ver sion: 0 = MMWC (pri mary vari able), 1 = NM3-HR, 2 =
M3-HR, 3 = KG-HR or 4 = SCAN. Se lecting SCAN will cause the dis play to
se quence through the cal cu lated vari ables at 4 sec ond in ter vals.
DSPRESDisplay Resolution. The Display Resolution parameter assignment
controls the number of digits that are displayed to the right of the
decimal. The display resolution can be set as fol lows:
Eng lish Unit Ver sion: From 1 to 4 Digits to the right of the dec i mal. Met ric
Unit Ver sion: From 1 to 3 Digits to the right of the dec i mal.
aLARMS The MST2000 has multiple alarm features. Alarms are available for
4-20 milliamp limit checks (under-range and over-range), RTD faults,
external 4-20 milliamp PCB communication failures and internal
hardware circuit faults. Alarms are enabled and disabled by setting the
individual binary bits in the ALARM WORD register to a ‘1’ or ‘0’
respectively. Since the individual binary bits cannot be displayed on the
LCD, the user must input the decimal word equivalent representing the
enabled and disabled bits. The individual alarm bit assignments and
the associated binary values are shown in Sec tion 9.
P_WORDPassword. The password is used to prevent unauthorized access to the
programming parameters. The password may be any value between 0
and 9999. A password value of 0 disables the password feature.
BD_ENBBlow Down Enable. The Blow Down Enable parameter allows the user
to enable or disable the integrated blow down sys tem.
• A value of ‘0’ dis ables the Blowdown Sequence.
• A value of ‘1’ en ables the blowdown func tion with ex ter nal trig ger
only. An external trig ger must be ap plied to the ‘IN1’ ter mi nal to
ini ti ate the Blowdown se quence.
• A value be tween 2 and 1440 en ables the MST2000 to con trol the
Blowdown se quence on timed in ter vals (in min utes). The time in ter val be gins as soon as the MST2000 is put back in ‘RUN’
mode. For val ues be tween 2 and 1440 min utes, an ex ter nal trig ger may also be ap plied to com mand ad di tional blowdown se quences. The ex ter nal trig ger event does not re set the MST2000
blowdown in ter nal timer.
þ Note: The min i mum ex ter nal trig ger pulse width is 500 mil li sec onds.
HT_ENBHART En able. The HART
or dis able the HART® Com mu ni ca tion op tion. Avail able as sign ments are
0 = Dis abled and 1 = En abled.
þ Note: IF the HART
milliamp ‘un der range’ cur rent val ues are not al lowed on the 4-20mA out put
ter mi nals dur ing RUN Mode.
®
En able pa ram e ter al lows the user to en able
®
op tion is en abled, 3.8 milliamp ‘fault cur rent’ and 3.9
0 = Password
Disabled
0 = Blowdown
Disabled.
0 = Default if no
HART® option
installed.
1 = Enabled if
HART® option
installed.
Page 18MST2000 Multivariable SMARTFLOW® TransmitterBrandt Instruments, Inc.
OPERATION MANUALALARM PROGRAMMING INFORMATION
9.ALARM PROGRAMMING INFORMATION
9.1 Alarm ‘ENABLE’ Word Def i ni tion
The ALARM ‘ENABLE’ WORD (16 bit word) is divided into two 8 bit bytes. The lower order byte (bits 1 –
8) is used to enable and disable the alarm functions. The higher order byte (bits 9 – 16) is used to control
how the alarm is displayed and/or output to the user interface. Some bits are currently undefined and
reserved for future use.
A. Under-range: En abling the un der-range alarm bit will cause the un der-range alarm to be come ac -
tive when the 4-20 milliamp out put cur rent reaches 3.9 milliamps.
B. Over-range: Enabling the over-range alarm bit will cause the over-range alarm to become active
when the 4-20 milliamp output current reaches 20.5 milliamps.
C. RTD Fault: Enabling the RTD fault alarm bit will cause the RTD fault alarm to become active if an
open circuit or short circuit is sensed in the 4-wire RTD loop connection. See Sec tion 9.3 G
D. ISO Comm er ror: En abling the ISO Comm er ror alarm bit will cause the ISO Comm er ror alarm(s)
to be come ac tive if any com mu ni ca tion er rors or hard ware faults are de tected from any of the ex ter nal 4-20 milliamp in put boards. (ISO = Iso lated Out put Mod ule). See Sec tion 9.3 G.
E. Hardware Fault: Enabling the Hardware Fault error alarm bit will cause the Hardware Fault error
alarm to become active if any internal hardware circuit faults (including microprocessor watchdog
timer faults) are detected from the MST2000 internal circuitry.
1
þ Note: For each alarm fault bit above, in di vid ual alarm sta tus bit(s) are pro vided in the ALARM STATUS word to
iden tify which alarm is ac tive. Each alarm sta tus bit and the as so ci ated bi nary val ues are de scribed later in this
sec tion.
9.3 High Byte ‘BIT’ Def i ni tions
A. Fail-low: Enabling the Fail-low bit will cause the 4-20 milliamp output to change to the fault current
value of 3.8 milliamps if any alarm is active.
B. Fail-high: Enabling the Fail-high bit will cause the 4-20 milliamp output to change to the fault current
value of 21.0 milliamps if any alarm is active.
C. Last-val: Enabling the Last-val bit will cause the 4-20 milliamp output to hold at the last value if any
alarm is active.
þ Note:
& The user must insure that only one of the 3 fault current control bits is set for proper operation.
& When entering PROGRAM mode, the 4-20 milliamp output current will change to the fault current as set by the fault
current control bits.
D. LCD Icon: Enabling the LCD Icon bit will cause the LCD ‘Alarm’ icon to be turned on if any alarm is
E. Latched Output: Enabling the Latched Output bit will cause any active alarm to become latched
and held active even if the alarm condition clears. Any ‘latched’ alarms can be cleared during RUN
mode by pressing the EDIT key (if the active alarm(s) are no longer active). After pressing the EDIT
key, any latched alarms that are no longer active will be cleared and any alarms that are still active
will remain latched.
F.Digital Out1: Enabling the Digital Out1 bit will cause the digital output channel (OUT1) to change to
the LOW state if any alarm is active.
þ Note: The OUT1 (and OUT2) channels are ‘open collector’ style outputs. The user must externally
connect an active pull-up voltage to the output pins for proper operation. The maximum external pull-up
voltage that can be applied to the output pins is 24 volts DC.
G. Ex ter nal Con stants: En abling the Ex ter nal Con stants bit will cause the pro grammed con stants for
tem per a ture or pres sure to be used in the mass flow cal cu la tions if ei ther the ex ter nal tem per a ture
or pres sure in puts are se lected and in fault con di tions.
9.4 Alarm ‘STATUS’ Word Def i ni tion
The ALARM STATUS word indicates which alarms are active during RUN mode. Since the
individual binary bits cannot be displayed on the LCD, the decimal word equivalent representing the
active alarm status bits is displayed. The individual alarm status bit assignments and the associated
binary values are shown below.
þ Note: If alarms are ac tive, the alarm ICON on the LCD will be lit and the ALARM sta tus value will be dis -
played ev ery 10 sec onds. The user may also use the INC/DEC keys to ac cess the alarm sta tus value on
the LCD.
A. Under-range: Indicates Under-range alarm is active.
• Bi nary value = 1.
B. Over-range: Indicates Over-range alarm is active.
• Bi nary value = 2.
C. RTD Fault: Indicates RTD fault (open circuit or short circuit) alarm is active.
• Bi nary value = 4.
D. ISO Comm1 error: Indicates communication or hardware fault error alarm from external 4-20 PCB
channel 1 is active.
• Bi nary value = 8.
E. ISO Comm2 error: Indicates communication or hardware fault error alarm from external 4-20 PCB
channel 2 is active.
• Bi nary value = 16.
F.ISO Comm3 error: Indicates communication or hardware fault error alarm from external 4-20 PCB
channel 3 is active.
• Bi nary value = 32.
1
Page 20MST2000 Multivariable SMARTFLOW® TransmitterThermo Brandt In stru ments
OPERATION MANUALALARM PROGRAMMING INFORMATION
G. Hardware Fault: Indicates hardware fault error from MST2000 internal circuitry is active.
• Bi nary value = 64.
H. Watchdog Timer Fault: Indicates watchdog timer fault error from internal microprocessor is active.
• Bi nary value = 128.
9.6 Alarm ‘ENABLE’ Word Dec i mal Cal cu la tion Ex am ples
To calculate the decimal word equivalent for the ALARM ‘ENABLE’ WORD the user must determine
which alarms and alarm control bits are to be enabled and then sum the binary values of each enabled
bit. The decimal word equivalent is then programmed into the ALARM ‘ENABLE’ WORD using the
programming menus.
A. EXAMPLE 1
The user desires to enable the following alarm/alarm control enable bits:
LCD Icon, Fail-low, RTD Fault and Under-range.
a. LCD Icon bi nary value = 2048
b. Fail-low bi nary value = 256
c. RTD Fault bi nary value = 4
d. Un der-range bi nary value = 1
• Dec i mal equiv a lent sum = 2309 (dec i mal value to pro gram into ALARM ‘EN ABLE’ WORD).
B. EXAMPLE 2
The user desires to enable the following alarm/alarm control enable bits:
Digital Out1, Latched Output, Fail-high, ISO Comm error, Over-range and Under-range.
a. Dig i tal Out1 bi nary value = 8192
b. Latched Out put bi nary value = 4096
c. Fail-high bi nary value = 512
d. ISO Comm er ror bi nary value = 8
e. Over-range bi nary value = 2
f. Un der-range bi nary value = 1
• Dec i mal equiv a lent sum = 12811 (dec i mal value to pro gram into ALARM ‘EN ABLE’ WORD).
9.7 Alarm ‘STATUS’ Word Dec i mal De code Ex am ples
To determine which individual alarm status bits are active, the user must take the decimal equivalent
value from the ALARM ‘STATUS’ WORD register and decode it into the associated binary bit values.
This is accomplished using binary division of the decimal word. The examples below show manual
division. The user may also use a decimal to binary calculator to simplify this procedure.
A. Example 1
• ALARM ‘STATUS’ WORD = 37
• Using bi nary di vi sion, di vide the dec i mal word by each bi nary bit value start ing with the most sig -
nif i cant bit value (bit 8 = 128) and then each suc ces sive lower bit.
a.
37 B 128 = 0 with a re main der of 37.......bit 8 (Watch dog timer fault) = 0
b.
37 B 64 = 0 with a re main der of 37........bit 7 (Hard ware fault) = 0
c.
37 B 32 = 1 with a re main der of 5.........bit 6 (ISO comm3 er ror) = 1
d.
5 B 16 = 0 with a re main der of 5 .........bit 5 (ISO comm2 er ror) = 0
e. 5 B 8 = 0 with a re main der of 5...........bit 4 (ISO comm1 er ror) = 0
f.
5 B 4 = 1 with a re main der of 1...........bit 3 (RTD fault) = 1
g. 1 B 2 = 0 with a re main der of 1 ..........bit 2 (Over-range) = 0
h.
1 B 1 = 1 with a re main der of 0...........bit 1 (Un der-range) = 1
• The dec i mal ALARM ‘STATUS’ WORD of 37 in di cates the fol low ing ac tive alarms:
ISO Comm3 error, RTD fault and Under-range.
• Using bi nary di vi sion, di vide the dec i mal word by each bi nary bit value start ing with the most sig -
nif i cant bit value (bit 8 = 128) and then each suc ces sive lower bit.
a.
206 B 128 = 1 with a re main der of 78 ......bit 8 (Watchdog timer fault) = 1
b.
78 B 64 = 1 with a re main der of 14........bit 7 (Hard ware fault) = 1
c. 14 B 32 = 0 with a re main der of 14 ........bit 6 (ISO comm3 er ror) = 0
d.
14 B 16 = 0 with a re main der of 14 ........bit 5 (ISO comm2 er ror) = 0
e. 14 B 8 = 1 with a re main der of 6 ..........bit 4 (ISO comm1 er ror) = 1
f.
6 B 4 = 1 with a re main der of 2 ...........bit 3 (RTD fault) = 1
g.
2 B 2 = 1 with a re main der of 0 ...........bit 2 (Over-range) = 1
h.
0 B 1 = 0 with a re main der of 0 ...........bit 1 (Un der-range) = 0
• The dec i mal ALARM ‘STATUS’ WORD of 206 in di cates the fol low ing ac tive alarms:
Watchdog timer fault, Hardware fault, ISO Comm1 error, RTD fault and Over-range.
10. FORMULAS & CONVERSION FACTORS
The following formulas are used in the MST2000 software calculations:
• Velocity =×÷1096845.DP Density
•
ACFM=×××÷Ae 667.657 DPT P
•
SCFM =×××÷AeDPP T23972 677..
• LB/ HR = SCFM Standard ××Density (@F)
()
()
o
6860
• Ae or Effective Area (sq.ft)=×Kfactor Nominal Area (sq.ft). Thermo Brandt supplies the
Effective Area (Ae) specification with each of its flowmeters.
• Where:
6 Ve loc ity is in Feet per Min ute
6 DP (Dif fer en tial Pres sure) is in Inches of Wa ter Col umn
6 T (Tem per a ture) is in de grees Ran kine (de grees Ran kine = de grees Fahr en heit + 459.67)
6 P (Ab so lute pres sure) is in pounds per square inch (PSI)
6 Den sity is in pounds per cu bic foot (Lb/FT3)
6 Ae (Ef fec tive Area) is in Square Feet.
Met ric Con ver sion Fac tors
• Me ters per sec ond x 196.850 = Feet per min ute
• Bar x 14.5038 = PSIA
• Square me ters x 10.7643 = Square feet
• Mil li me ters of wa ter col umn B 25.4 = Inches of Wa ter Col umn
• Ki lo grams per hour x 2.205 = Pounds per hour
• Ki lo grams per cu bic me ter B 16.0136 = Pounds per cu bic foot.
• Cu bic meters per hour x 0.5885 = Cu bic feet per min ute
• (De grees C + 273.15) x 1.8 = de grees Ran kine
• Ae or Ef fec tive area (in square feet) = Kfactor x Nom i nal Area (square me ters) x 0.0929.
Thermo Brandt sup plies the Ef fec tive Area (Ae) spec i fi ca tion with each of its flowmeters. The
user must con vert to square me ters be fore en ter ing the ef fec tive are pa ram e ter in the ‘E_AREA’
pro gram ming menu.
11.
Page 22MST2000 Multivariable SMARTFLOW® TransmitterBrandt Instruments, Inc.
OPERATION MANUALTEST JACK
TEST JACK
A Test Jack is stan dard on the Non I.S. Ap proved MST2000’ s. It al lows the user to mon i tor the mA out put of the unit with out dis con nect ing the loop. Re view di men sional draw ings on page 4. The Test Jack
is re moved for all I.S. and Di vi sion 2 ap proved MST2000’s.
To monitor the mA output of the MST2000 you will need a precision milliammeter. Push the positive lead
from the meter into the positive jack (RED) and the negative lead from the meter into the negative jack
(BLACK).
12. OPTIONAL MODULE INSTALLATION
The MST2000 Loop Powered Multivariable SMARTFLOW® Trans mit ter’s de sign is such that op tional in put, dig i tal I/O and HART® com mu ni ca tion mod ules can be in stalled in the field. This al lows the
user the ver sa til ity to change and adapt to dif fer ent ap pli ca tion needs. This sec tion con tains guide lines
for in stall ing the op tional mod ules and up dat ing the MST2000’s pro gram ming if nec es sary. Please re view this sec tion be fore at tempt ing to make any up grades. If there are any ques tions or prob lems
please call the fac tory for as sis tance.
þ NOTE:
& Any upgrades should be made in a clean and dust free environment.
& Anti-static discharge precautions should be adhered to.
12.1 Iso lated 4-20mA In put Mod ules (ISO Mod ule)
A. Thermo Brandt Part Number FP37-OPTN-ISO
a. The Iso lated 4-20mA In put Mod ule (ISO) al lows the MST2000 to ac cept an iso lated 4-20mA sig nal
from ei ther an Ab so lute Pres sure Trans mit ter or Ex ter nal Tem per a ture Trans mit ter. The 2nd D.P.
Trans mit ter Op tion is un avail able at the time this man ual was printed.
b. All iso lated 4-20mA In put Mod ules are iden ti cal, but they must be mounted in the cor rect lo c a tion on
the Main Board. See pho to graph and draw ings in this sec tion.
c. The Mod ule will be shipped in a sealed bag along with stand offs (2) and in struc tion sheet.
B. Installing the ISO Module Option.
a. Dis con nect all power from the MST2000.
b. De cide which slot the ISO Mod ule will fill. Re move the Op tion Cover La bel cov er ing that slot.
c. Take off the MST2000 Cover by re mov ing the 4 flat head screws. It is not nec es sary to re move the
Main Board from the hous ing.
d. Lo cate the slot, con nec tor and two mount ing holes for the ISO Mod ule on the Main Board.
e. Re move the ISO Mod ule and two (2) stand offs from the bag.
f. Snap the Stand offs into the two holes lo cated on the Main Board as shown in the draw ing. Note the
Align the ISO Mod ule such that the re set but ton and LED are to ward the LCD and fac ing up. The
con nec tor will be on the bot tom of the board. Snap the ISO Mod ule into the stand offs while mak ing
sure the con nec tor and header are prop erly aligned.
h. Re place the cover.
i. Hook up the MST2000 as per the ter mi nal block wir ing di a gram on page 7.
j. Ap ply Power to the MST2000.
C. Programming the MST2000 to recognize the ISO Module(s)
a.
Re view Sec tion 7 on Pro gramming and Sec tion 8 on Pa ram e ters.
b. De pending on which slot the ISO Mod ule was in stalled, se lect one of the fol low ing pa ram e ters to edit:
c.
TMPSRC: Tem per a ture Source.
d.
APRSRC: Ab so lute Pres sure Source.
e.
Use the INC or DEC but tons to scroll to ‘1=EXT’ (1 = EX Ter nal)
f. Press the EDIT key to save this change to memory.
D. Calibrating the ISO Module
a. Ex ter nal Ab so lute Pres sure Trans mit ter ISO Mod ule . Re view the Pro gram Pa ram e ters in sec tion 8.
i. Con nect a 4-20 mA source to the Ab so lute Pres sure Trans mit ter ISO Mod ule in put ter mi nals
(marked EXTIN 1). See ter mi nal block draw ing on page 7.
ii.
Make sure pa ram e ter aprSRC (Ab so lute Pres sure Zero Source) is set to 1 (1 = EX Ter nal).
iii.
Set the EX_APZ (Ab so lute Pres sure Zero) pa ram e ter.
iv.
Set the APZCAL (Ab so lute Pres sure Zero Cal i bra tion) pa ram e ter:
.
.! Ap ply 4.0 milliamps. Press the Edit Key to read and store the 4 milliamp cal i bra tion value.
.
.! Ap ply 20.0 milliamps. Press the Edit Key to read and store the 20 milliamp cal i bra tion value.
! Press the Edit key. Dis play will change to read IN4mA.
v.
Set the EX_ABS (Ab so lute Pres sure Span) pa ram e ter.
vi.
Set the APSCAL (Ab so lute Pres sure Span Cal i bra tion) pa ram e ter.
! Press the Edit key. Dis play will change to read IN20mA.
þ NOTE: For those MST2400 with the Integral Absolute Pressure Transmitter option installed , the ISO
Module has been calibrated at the factory.
Page 24MST2000 Multivariable SMARTFLOW® TransmitterBrandt Instruments, Inc.
OPERATION MANUALOPTIONAL MODULE INSTALLATION
b. Ex ter nal Tem per a ture Trans mit ter ISO Mod ule . Re view the Pro gram Pa ram e ters in sec tion 8.
i. Con nect a 4-20 mA source to the Ex ter nal Tem per a ture Trans mit ter ISO Mod ule in put ter mi nals
(marked EXTIN 2). See ter mi nal block draw ing on page 7.
ii.
Make sure pa ram e terTMPSRC (Tem per a ture Source) is set to 1 (1 = EX Ter nal).
iii.
Set the EX_TPZ (Tem per a ture Zero) pa ram e ter.
iv.
Set the TPZCAL (Tem per a ture Zero Cal i bra tion) pa ram e ter.
.
.! Ap ply 4.0 milliamps. Press the Edit Key to read and store the 4 milliamp cal i bra tion value.
.
.! Ap ply 20.0 milliamps. Press the Edit Key to read and store the 20 milliamp cal i bra tion value.
! Press the Edit key. Dis play will change to read IN4mA.
v.
Set the EX_TPS (Tem per a ture Span) pa ram e ter.
vi.
Set the TPSCAL(Tem per a ture Span Cal i bra tion) pa ram e ter.
! Press the Edit key. Dis play will change to read IN20mA.
12.2 Dig i tal In put / Out put Mod ule In stal la tion
A. Thermo Brandt Part Number FP37-OPTN-DIO
a. The Dig i tal I/O mod ule al lows the MST2000 to ac cept one (1) dig i tal in put and out put (1) dig i tal out -
puts.
b. The Dig i tal I/O mod ule must be in stalled on the right most con nec tor. See pho to graph and draw ings
in this sec tion.
c. The Dig i tal I/O module will be shipped in a sealed bag along with stand offs (2) and in struc ti on sheet.
B. Installing the Digital I/O Module Option.
a. Dis con nect all power from the MST2000.
b. Take off the MST2000 Cover by re mov ing the 4 flat head screws. It is not nec es sary to re move the
Main Board from the hous ing.
c. Lo cate the slot, con nec tor and two mount ing holes for the Dig i tal I/O module on the Main Board.
d. Re move the Dig i tal I/O module and two (2) stand offs from the bag.
e. Snap the standoffs into the two holes lo cated on the Main Board as shown in the draw ing. Note the
ori en ta tion of the stand offs.
f. Align the Dig i tal I/O mod ule such that con nec tor will be on the bot tom of the board. Snap the module
into the stand offs while mak ing sure the con nec tor and header are prop erly aligned.
g. Re place the cover.
h. Hook up the MST2000 as per the ter mi nal block wir ing di a gram on page 7.
i. Ap ply Power to the MST2000.
C. For Dig i tal I/O wiring con fig u ra tions see sec tion 14.
12.3 HART® Com mu ni ca tions Mod ule
A. Thermo Brandt Part Number FP37-OPTN-HART
a. The HART® Com mu ni ca tion mod ule al lows the MST2000 to com mu ni cate with stan dard HART® In -
ter faces.
b. The HART® Com mu ni ca tion mod ule must be in stalled on the up per left most con nec tor. See pho to -
graph and draw ings in this sec tion.
c. The HART® Com mu ni ca tion mod ule will be shipped in a sealed bag along with stand offs (2) and in -
struc tion sheet.
B. In stalling the HART® Com mu ni ca tion Mod ule Op tion.
a. Dis con nect all power from the MST2000.
b. Take off the MST2000 Cover by re mov ing the 4 flat head screws. It is not nec es sary to re move the
Main Board from the hous ing.
c. Lo cate the slot, con nec tor and two mount ing holes for the HART® mod ule on the Main Board.
d. Re move the HART® mod ule and two (2) stand offs from the bag.
e. Snap the Stand offs into the two holes lo cated on the Main Board as shown in the draw ing. Note the
Align the HART® mod ule such that con nec tor will be on the bot tom of the board. Snap the mod ule
into the stand offs while mak ing sure the con nec tor and header are prop erly aligned.
g. Re place the cover.
h. Hook up the MST2000 as per the ter mi nal block wir ing di a gram on page 7.
i. Ap ply Power to the MST2000.
13. MST2000 HART® Communications Information
13.1 Power and Loop Con di tions
The MST2000 Multivariable differential pressure transmitter is a HART® conforming loop-powered
4-20 milliamp transmitter. Power connection is made at the two left terminal positions marked LOOP+
and LOOP-. Nominal power supply voltage is 24 volts DC which allows up to 600 ohms series
resistance in the loop circuit. Higher loop resistance can be used with higher power supply voltages as
required. See the loop resistance-voltage graph below in determining the minimum loop voltage
required.
Note: For HART® communication applications, minimum loop resistance is 250 ohms.
13.2 HART® Con nec tions
Maximum resistance
versus DC loop voltage
All electrical connections are per standard HART® connections. Refer to HART® Communication
Foundation Document HCF_SPEC-54 (HART® FSK Physical Layer Specification, Revision 8.0) for
additional information. The current sense resistor may be connected in either the high or low side of the
field loop wiring. HART® communication devices must be connected in accordance with
HCF_SPEC-54 for proper operation. Typical connection methods are shown in the following diagrams.
13.3 Ca bling Re quire ments
The field wiring of a HART® based system should use shielded twisted pair cable. When using cable
with multiple twisted pairs, it is important not to use the other pairs for signals that might interfere with
the HART® communication signals.
Typical multi-drop
connection with digital
communications.
Page 26MST2000 Multivariable SMARTFLOW® TransmitterBrandt Instruments, Inc.
OPERATION MANUALMST2000 HART® Communications Information
Typical Point to Point
Connection with
analog signaling.
If the ca ble is lon ger than sev eral me ters, it’s re sis tance and ca pac i tance may be come sig nif i cant in the
HART® RC time-constant lim i ta tion ® x C [ 65 mi cro sec onds). When us ing a sin gle field de vice and a
host with a 250 ohm load and no other sig nif i cant re sis tance, the 65 mi cro sec ond lim i ta t ion would al low
0.26 uF of ca pac i tance for the sys tem. Al lowing 0.01 uF (10,000 pF) for the host and field de vice (each
hav ing a CN=1), the to tal ca ble ca pac i tance could be up to 0.25 uF. How ever, if the ca ble re sis tance
was 110 ohms, the sys tem re sis tance be comes 360 ohms, which then al lows for a to tal per mit t ed ca ble
ca pac i tance of 0.18 uF. This cor re sponds to a nom i nal ca ble length of 900 me ters for a ca ble with a rat ing of 200 pF/me ter. If the ca ble needs to be ex tended up ward to wards the max i mum HART® ca ble
length of 1500 me ters, a ca ble with a lower ca pac i tance rat ing must be se lected.
• In a multi-dropped sys tem, the ad di tional ca pac i tance from each net worked trans mit ter must
also be con sid ered. Each trans mit ter has an es tab lished CN value. A CN value of 1 in di cates
that the trans mit ter rep re sents 5000 pF of load ca pac i tance.
• The MST2000 trans mit ter has a CN Value of 1 ( 5000pF).
• The in ter nal re sis tance of the MST2000 trans mit ter is in ex cess of 100,000 ohms and can be ig -
nored in the ca ble length cal cu la tions.
13.4 HART® Com mu ni ca tion Dis tance
Up to 1.5 km (1 mile) when using multiple twisted pair cables. Communication distance varies
depending on type of cable used.
Use the following formula to determine cable length for specific applications:
6
C
+
10000
×
65 10
L
=
R C
×
()
Where:
L = Length in Meters or Feet
R = Resistance in Ohms (Ω ) including barrier resistance.
C = Cable capacitance in pF/m or pF/ft
Cf = Maximum shunt capacitance of receiving devices in pF/m or pF/ft.
13.5 Power Sup ply Re quire ments
To minimize signal degradation of the HART® communication signals, the following power supply
specifications are required.
• Volt age: .......................24 V DC (typ i cal)
• Max i mum rip ple (47 to 125 Hz): ..........0.2 V (peak to peak)
• Max i mum noise (500 Hz to 10 kHz): ........1.2 mV
• Max i mum se ries im ped ance (500 Hz to 10 kHz):..10 ohms
Intrinsic safety approvals for the MST2000 are pending. Contact the factory for additional information
involving hazardous applications with the use of safety barriers.
13.7 HART® Com mand In for ma tion
The MST2000 transmitter is compliant with HART® Command Revision 5.1. The following commands
are supported. Reference HART® Document HCF_LIT-20 (HART® Technical Overview) for additional
information.
COMMANDHART® Command SetDescription
0UniversalRead Unique Identifier
1UniversalRead Primary Variable (pv)
2UniversalRead (pv) current and percent of range
3UniversalRead (pv) current and four predefined variables
6UniversalWrite Polling Address
11UniversalRead Unique Identifier associated with Tag
12UniversalRead Message
13UniversalRead Tag, Descriptor, Date
14UniversalRead sensor information
15UniversalRead output information
16UniversalRead final assembly number
17UniversalWrite message
18UniversalWrite tag, descriptor, date
19UniversalWrite final assembly number
35Common PracticeWrite (pv) range values
50Common PracticeRead dynamic variable assignments
51Common PracticeWrite dynamic variable assignments
59Common PracticeWrite number of response preambles
pv = primary vari able
13.8 Thermo Brandt In stru ments HART® Man u fac turer Iden ti fi ca tion Code = 96 Hex, 150 Dec i mal
13.9 MST2000 HART® Trans mit ter Vari able Code As sign ments.
Vari able CodeENGLISH UNIT VERSIONMETRIC UNIT VERSION
0 or 1DP in Inches of W.C.D.P. In Mil li me ters of W.C.
2Stan dard Cu bic Feet Per Min ute (SCFM)Nor mal Cu bic Me ters Per Hour (NM3-HR)
3Ac tual Cu bic Feet per Min ute (ACFM)Cu bic Me ters per Hour (M3-HR)
4Mass in Pounds per Hour (LB/HR)Mass in Ki lo grams per Hour (KG-HR)
5Ex ter nal Tem per a ture in Degree Fahr en heitEx ter nal Tem per a ture in De gree Cel sius
6Ex ter nal Ab so lute Pres sure in PSIAEx ter nal Ab so lute Pres sure in BAR
Page 28MST2000 Multivariable SMARTFLOW® TransmitterBrandt Instruments, Inc.
OPERATION MANUALWiring Diagrams
14. Wiring Diagrams
Four Wire Con nec tion with Ab so lute Pres sure Trans mit ter
The MST2000 with a Ab so lute Pres sure Trans mit ter can be wired to re -
place your ex ist ing four wire trans mit ter
Dual 2 Wire Con nec tion with Ab so lute Pres sure Trans mit ter
The MST2000 with Ab so lute Pres sure Trans mit ter can be wired to re place
your ex ist ing four wire trans mit ter. Re quires two 24Vdc power sources.
Three Wire Con nec tion with Ab so lute Pres sure Trans mit ter.
The MST2000 with Ab so lute Pres sure Trans mit ter can be wired to re place
Power Sup ply & Ab so lute Pres sure Trans mit ter
The MST2000 with Ab so lute Pres sure Trans mit ter can be sup plied with a
power sup ply to power the MST2000 and Ab so lute Pres sure Trans mit ter.
Wiring DiagramsOPERATION MANUAL
Power Sup ply and Ab so lute Pres sure Trans mit ter
The MST2000 with Ab so lute Pres sure Trans mit ter can be sup plied with a
power sup ply to power the Ab so lute Pres sure only. The MST2000 will be
pow ered by a 24Vdc, 4-20mA loop.
2 Wire RTD Connection
3 Wire RTD Connection4 Wire RTD Connection
Page 30MST2000 Multivariable SMARTFLOW® TransmitterBrandt Instruments, Inc.
OPERATION MANUALMST2000 Haz ard ous Area In stal la tion
Dig i tal I/O Con nec tions for In te gral Blowdown System
15. MST2000 Haz ard ous Area In stal la tion
The MST2000 Multivariable SMARTFLOW
so ci a tion ap proved for the fol low ing haz ard ous area clas si fi ca tions.
15.1 In trin sically Safe In stal la tions
A. Model MST2100 (NEMA 1): In trin sically Safe for CL. I, Grps. C & D
B. Model MST2400 (NEMA 4X): In trin sically Safe for CL. I, Grps. C & D. CL. II, Grps.
E, F & G
• For In trin sically Safe ap pli ca tions, unit must be in stalled per Thermo Brandt in stal la tion draw ing num ber
SC37-4000-00. See Page 29.
• In trin sically safe en tity pa ram e ters: Vmax = 40 VDC, Imax = 165mA, Ci = 0uf, Li = 240uH.
• Max i mum op er at ing am bi ent tem per a ture: 66 De grees C ( 151 De grees F)
15.2 Di vi sion 2 And Other In stal la tions:
A. Model MST2100 (NEMA 1): CL I, Div. 2, Grps. C & D
B. Model MST2400 (NEMA 4X): CL I, Div. 2 Grps. C & D. CL II, Div. 2 Grps. E, F & G. CL. III, Div. 2
• For Di vi sion 2 ap pli ca tions, unit must be in stalled per Ca na dian and/or Na tional Elec tri cal Code re quire -
ments for Di vi sion 2 ar eas. In trin sic safety bar ri ers are not re quired.
• Di vi sion 2 power rat ings: Vmax = 40 VDC, Imax = 165mA.
• Max i mum op er at ing am bi ent tem per a ture: 66 de grees C (151 De grees F).
MST2000 Haz ard ous Area In stal la tionOPERATION MANUAL
15.3 Ap proved Op tions.
See the chart be low and re view the Model Num ber De scrip tion on Page 2.
MST2100MST2400
OPTION
HART COMMUNICATIONSXXXXXX
4 Wire RTDXXXXXX
ISO 4-20mA Tem per a ture In put ModuleXXXXXX
ISO 4-20mA Pres sure In put ModuleXXXXXX
Dig i tal I/O CardXXXX
High Pres sure Blow DownN/AX
In te gral 120VAC Power SupplyN/AX
Ab so lute Pres sure TransmitterN/AX
HeaterN/AX
Con tin u ous PurgeN/AXXX
Test JacksXX
Ter mi nal Block 4XX
In trin sically
Safe
Di vi sion 2
Not
Cer tified
In trin sically
Safe
Di vi sion 2
Not
Cer tified
15.4 MST2000 I.S. In stal la tion Draw ing SC37-4000-00
See Notes for Draw ing SC37-4000-00 on next page:
Page 32MST2000 Multivariable SMARTFLOW® TransmitterBrandt Instruments, Inc.
OPERATION MANUALCal i bra tion of the MST2000
15.5 Notes for MST2000 I.S. In stal la tion Draw ing SC37-4000-00
For I.S. In stal la tions, field wir ing shall be in stalled in ac cor dance with Ca na dian Elec t ri cal Code and/or Na tional
1.
Elec tri cal code ANSI/NFPA 70, Ar ti cle 504-30
Wiring ca ble shall be 24 AWG or heavier, sep a rate shielded pairs.
2.
The ground ing con nec tion be tween the safety bar rier and earth ground must be less than 1 ohm.
3.
Con trol room equip ment must not gen er ate more than 250 Volts rms.
4.
Safety Bar riers must be of ap proved types and used in an ap proved con fig u ra tion where the trans mit ter Vmax
5.
value is greater than the bar rier Voc rat ing and the trans mit ter Imax value is greater than the Bar rier Isc rat ing.
The trans mit ter in put ca pac i tance (Ci) plus the to tal ca ble ca pac i tance for each loop must not ex ceed the bar rier
6.
Ca rat ing.
The trans mit ter in put in duc tance (Li) plus the to tal ca ble in duc tance for each loop must not ex ceed the bar rier La rat ing.
7.
Trans mit ter en clo sure must be grounded to earth ground us ing the pro vided ground lug on the en clo sure.
8.
The MST2000 Trans mit ter is In trin sically Safe for:
9.
! Class I, Di vi sion 1, Groups C and D
! Class II, Di vi sion 1 Groups E, F and G.
Loop en tity pa ram e ters per cir cuit are:
10.
! Vmax = 40 VDC
! Imax = 165mA
! Ci = 0uF
! Li = 240uH
Use only CSA ap proved I.S. Pres sure trans mit ters where the Vmax and Imax of the trans mit ter is greater than the Voc and Isc of the bar rier.
11.
The Ci and Li of the trans mit ter must be in cluded in sys tem to tal ca pac i tance and in duc tance cal cu la tion and must be less than bar rier Ca
and La Rat ings.
Ap proved meth ods for sep a ra tion of each loop are:
12.
! Run ning Loops in sep a rate ca bles
! Run ning Loops in sep a rate shields
When con nect ing HART com mu ni ca tor the Vmax and Imax of the com mu ni ca tor must be greater than the Voc and Isc of the bar rier. Voc of
13.
com mu ni ca tor plus Voc of bar rier must be less than Vmax of trans mit ter, ISC of Com mu ni ca tor plus Isc of Bar rier must be less than Imax of
Trans mit ter. Li of Trans mit ter plus Li of Com mu ni ca tor must be less than La of Bar rier, Ci of trans mit ter plus Ci of Com mu ni ca tor must be
less than Ca of Bar rier.
Use only listed and ap proved dust tight seal for Class II and Class III Haz ard ous Lo ca tions.
14.
Other wire ter mi nals not avail able for use on In trin sically Safe ver sion
15.
No re vi sions shall be made with out no ti fi ca tion of Ap proval Agency(s).
16.
16. Cal i bra tion of the MST2000
Ba sic cal i bra tion of the MST2000 Se ries trans mit ters is done in two parts: 1) set ting the 4-20 mA out put
from the dig i tal to an a log con verter and 2) set ting the 0 & 100% val ues of the dis played DP . Both parts
are done by the set ting of pa ram e ters, en tered via the in te gral key pad.
16.1 OUTPUT mA CALIBRATION
A. ZERO and SPAN of the mA out put are set by the OUTPTO and OUTPTG pa ram e ters, re spec tively.
You do not need to ap ply any DP sig nal for the mA cal i bra tion, only an ac cu rate mA test me t er is re quired.
B. Fol low ing the pro ce dures of Sec tion 7, en ter the PROGRAMMING Mode and se lect the OUTPTO
pa ram e ter. The ex ist ing value of OUTPUT OFFSET will be dis played.
C. Press the EDIT/SAVE key once to force the dig i tal to an a log con verter to its 0% out put value and to
al low you to ad just the out put to ex actly 4.00mA as read on a mA test me ter. Use the INCREMENT
& DECREMENT keys as needed.
D. Press the EDIT/SAVE key to exit the edit mode and save the OUTPUT OFFSET value (even if there
was no ad just ment made). Now step to the OUTPTG pa ram e ter to dis play the ex ist ing value of
OUTPUT GAIN.
E. Press the EDIT/SAVE key once to force the dig i tal to an a log con verter out put to its 100% value and
to al low you to ad just the out put to ex actly 20.00mA as read on a mA test me ter. Use the
INCREMENT & DECREMENT keys as needed.
F.Press the EDIT/SAVE key to exit the edit mode and save the OUTPUT GAIN value. This com pletes
the out put mA cal i bra tion.
G. Exit the PROGRAMMING Mode, by press ing the MODE key, or con tinue with the DP cal i bra tion.
þ NOTE: For MST2000 Trans mit ters with CONTINUOUS PURGE OPTION. Do not use a hand pump, or com -
pres sion cyl in der type of pres sure source for the DP test sig nals. You must use a vented source to per mit con tin u ous flow of purge air. Con tact the fac tory for ad di tional in for ma tion on cal i brat ing
trans mit ters with con tin u ous purge.
þ NOTE: Do not turn off the purge air sup ply to use the trans mit ter as though it does not have the purge
op tion; this will cause er rors.
A. Con nect an ac cu rate test DP sig nal to the MST2000, equal to the 0% min i mum range value.
B. While in the PROGRAMMING MODE, step to the INPUTO pa ram e ter to dis play the ex ist ing value
of INPUT OFFSET.
C. Press the EDIT/SAVE key once to dis play the DP read ing. Use the INCREMENT/DECREMENT
keys as needed to ad just the dis play to match the test DP sig nal value.
D. Press the EDIT/SAVE key to exit the edit mode and to save the INPUT OFFSET value, (even if it
was not changed).
E. Ad just the test DP sig nal to the 100% max i mum range value. Step to the INPUTG pa ram e ter to dis -
play the ex ist ing value of INPUT GAIN.
F.Press the EDIT/SAVE key once to dis play the DP read ing. Use the INCREMENT/DECREMENT
keys as needed to ad just the dis play to match the test DP sig nal value.
G. Press the EDIT/SAVE key to exit the edit mode and to save the INPUT GAIN value.
þ NOTE: Changes to INPUTO or INPUTG will af fect both the dis play & the mA for any ap plied DP value.
Ad justing OUTPTO or OUTPTG will af fect only the mA value for any ap plied DP value.
Page 34MST2000 Multivariable SMARTFLOW® TransmitterBrandt Instruments, Inc.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.