Takex PB-30TK, PB-60TK, PB-100TK Instruction Manual

PHOTOELECTRIC BEAM SENSOR
INSTRUCTION MANUAL
We appreciate your purchase of our photoelectric beam sensor. This sensor will provide long and dependable service when properly installed. Please read this Instruction Manual carefully for correct and effective use.
Please note: This sensor is designed to detect intrusion and to initiate an alarm ; it is not a burglary-preventing device.
We are not responsible for damage, injury or losses caused by accident, theft, Acts of God (including inductive surge by lightning), abuse, misuse, abnormal usage, faulty installation or improper maintenance.
[TRANSMITTER]
COVER
COVER
Terminals
Operational
LED
Lens
Lens
View finder
Terminals
Alarm LED
Attenuation
LED
Lens
Lens
View finder
Horizontal adjustment
Vertical adjustment screw
Response time adjustment
Monitor jack
Horizontal adjustment
Vertical adjustment screw
MOUNTING PLATE
MOUNTING PLATE
[OPTION PARTS]
Pole mounting plate: 2
Pole bracket: 2
[RECEIVER]
Attenuation sheet: 1
Tapping screw: 4
DO’S AND DONT’S
Remove all obstructions (trees, clothes lines, etc.) between Transmitter and Receiver.
Do not install the unit on places where it may be splashed by dirty water or direct sea spray.
Avoid strong light from the sun, automobile headlights etc. directly shining on Transmitter / Receiver. When strong light stays in optical axis for a long time, it does not cause malfunction but will affect the product life.
Do not install the unit on unsteady surfaces.
The protection distance (between Transmitter / Receiver)
should be placed in the rated range.
PB-30TK : Outdoor : 100’ (30m) / indoor : 200’ (60m) PB-60TK : Outdoor : 200’ (60m) / indoor : 400’ (120m) PB-100TK : Outdoor : 330’ (100m) / indoor : 660’ (200m)
Expansion of beam
Expansion of beam can be calculated as follows: A=0.03 x l
l A
66’ (20m) 2’(0.6m) 135’ (40m) 4’ (1.2m) 200’ (60m) 6’ (1.8m)
330’ (100m) 10’ (3.0m)
Transmitter
Receiver
Protection distance
POINTS OF INSTALLATION
Heights of installation
Install the sensor at a height of 31" to 39" (80 to 100cm) to catch human pattern.
Position of installation
Using the adjustments, the lens can move horizontally ( ±90 degrees) and vertically (±10 degrees) allowing the unit to work in all directions. ( example 1 to 3)
Vertical
adjustment
screw
±10˚
±90˚
Horizontal adjustment
Exemple 1 Exemple 2 Exemple 3
CAUTIONS ON INSTALLATION
Avoid overhead wiring
When installing indoors, wiring procedures similar to those for telephones or intercoms are acceptable. Outdoor wires should be placed inside pipes, or underground cable / metal shielded cable should be used.
Terminal configuration
Connection
Power
10V to 30VDC (non-polarity)
Power
10V to 30VDC
(non-polarity)
[Receiver]
[Transmitter]
Alarm
NC NC
COM NO
Alarm output Dry contact relay Output 1c 30V (AC/DC) 0.5A
When cover attached
Tamper output Dry contact relay Output N/C 30V (AC/DC) 0.5A
Wiring distance
model PB-30TK PB-60TK, PB-100TK
voltage 12V 24V 12V 24V
wire size
AWG22 720’ 6200’ 490’ 4200’
(Dia 0.65mm) (220m) (1890m) (150m) (1280m)
AWG20 1200’ 10500’ 830’ 7200’
(Dia 0.8mm) (366m) (3200m) (250m) (2200m)
AWG18 1800’ 16000’ 1200’ 10500’
(Dia 1.0mm) (549m) (4880m) (366m) (3200m)
AWG17 2200’ 20000’ 1450’ 13500’
(Dia 1.1mm) (670m) (6000m) (442m) (4000m)
Note 1) Maximum wiring distance when two or more sets are connected
is the value above divided by the number of sets.
2) The signal line can be wired to a distance of up to 3,300 ft. (1,000m) with AWG22 (dia 0.65mm) telephone wire.
Example connection 1
Example connection 2
Example connection 3
Transmitter Receiver
Control panel
(12VDC)
Power
Alarm signal
TR. RE. TR. RE.
TR. RE. TR. RE.
Control panel
(12VDC)
Power
Alarm signal
Control panel
(12VDC)
Power
Alarm (1ch.)
Alarm (2ch.)
31" to 39"
(80 to 100cm)