Takagi TH3JOSNG Part List

ATH3
OFF
1 2 3 4 5 6
OFF
1 2 3 4 5 62 3 4 5 6
OFF
1 2 3 4 5 6
1 2 3 4 5 6
OFF
1 2 3 4 5 6
OFF
1 2 3 4 5 6
OFF
1 2 3 4 5 6
OFF
1 2 3 4 5 6
OFF
1 2 3 4 5 6
OFF
1 2 3 4 5 6
OFF
1 2 3 4 5 6
OFF
1 2 3 4 5 6
OFF
1 2 3 4 5 6
OFF
1 2 3 4 5 6 7 8
OFF
1 2 3 4 5 6 7 8
OFF
1 2 3 4 5 6 7 8
OFF
ON
1 2 3 4 5
OFF
ON
1 2 3 4 5
OFF
ON
1 2 3 4 5 6
OFF
ON
1 2 3 4 5 6
Maintenance sheet
68A166-1
A. Troubleshooting
If the error code is indicated on the green LED (Refer to Section C) on the PCB (Part #701) of the water heater (and/or the remote controller), refer to Section B.
<< It takes long time to get hot water at the fixtures >>
The time it takes to deliver hot water from the water heater to your fixtures depends
on the length of piping between the two. The longer the distance or the bigger the pipes, the longer it will take to get hot water.
If you would like to receive hot water to your fixtures quicker, you may want to
consider a hot water recirculation system.
<< The water is not hot enough or turns cold and stays cold >>
Compare the flow and temperature. Refer to the “Output temperature chart” of the
Installation manual.
Check cross plumbing between cold water lines and hot water lines.
Check if the gas supply valve is fully open, the gas line is sized properly and the gas
supplies enough pressure. Refer to the “Gas supply and gas pipe sizing” of the Installation manual.
Check the set temperature, and change the set temperature with the remote controller
or the DIPswitch setting. Refer to Section D.
Refer to the “Water circuit” in this section.
<<The water is too hot>>
Check the set temperature, lower setting temperature.
<<The hot water is not available when a fixture is opened>>
Refer to the “Power supply circuit” and “Water circuit” in this section.
<<Fluctuation in hot water temperature>>
Check if the filter on the cold water inlet is cleaned. (Part #406)
Check if the gas line is sized properly and the supply gas pressure is sufficient.
Check for cross connection between cold water lines and hot water lines.
Refer to the “Water circuit” in this section.
<<Unit does not ignite when water goes through the water heater>>
Refer to the “Power supply circuit” and “Water circuit” in this section.
If you use the remote controller, turn the power button on and then check if the
STAND BY LED will light up.
Check if the filter on the cold water inlet is cleaned (Part #406).
Refer to the “Water circuit” in this section.
B. Error codes
031: Incorrect DIPswitch setting
Check the DIPswitch settings on the PCB. Refer to Section D.
101: Warning for the “991” error code
Check the gas type of the house (and/or the building).
Instructions” of the Installation manual.
If the water heater is installed as a direct-vent system, check whether there is enough
distance between the intake air terminal and the exhaust terminal. Refer to the “Vent termination clearances” of the Installation manual.
Check the total vent length. Refer to the "Venting instructions" of the Installation manual.
Check the altitude/elevation of area of where the water heater is installed. Refer to the
“High-altitude function” of Section D. And change the DIPswitch settings.
Check if there is grease and/or dirt in the burner (Part #101) and the fan motor
(Part #103), especially if the water heater has been installed in a contaminated area.
Check if there is dust and lint in the heat exchanger.
Check the manifold pressure of the water heater. Refer to the Installation manual of the water heater.
111: Ignition failure
1. Check the gas supply and inlet gas pressure.
2. Check if the Hi-limit switch (Part #412) is properly functioning.
3. Check for connection/breakage of wires (Part #413, 708, 709, 710, 712), and/or soot on the flame rod (Part #108). And then if the O.H.C.F (Part #413) has a breakage, Consult the manufacturer.
4. Check if there is a buzzing spark ignition sound coming from the burner (Part #101) when water heater prepares for combustion.
5. Listen for the double “clunk” sound coming from the gas valve assembly (Part #102) when water heater goes into combustion.
6. (Only if sparking and/or kick sound) Check the voltage on each wire to gas valve assembly (Part #102) and/or the igniter assembly (Part #711). Refer to “Appendix A” in Section C. *No sparking sound >>>>> Refer to #1 at “Appendix A” in Section C. *No kick sound >>>>> Refer to #2 at “Appendix A” in Section C.
7. Check if there is leaking from the heat exchanger (Part #401).
8. Check if there is dust and lint in nozzles of the manifold (Part #102).
9. Check the current on the flame rod (Part #108). Refer to #3 at “Appendix A” in Section C.
121: Loss of flame
1. Check the gas supply and inlet gas pressure.
2. Check if the Hi-limit switch (Part #412) is properly functioning.
3. Check for connection/breakage of wires (Part #413, 708, 709, 712), burn marks on the computer board (Part #701), and/or soot on the flame rod (Part #108). And then if the O.H.C.F (Part #413) has a breakage, Consult the manufacturer.
4. Check if there is leaking from the heat exchanger (Part #401).
5. Check if there is dust and lint in nozzles of the manifold (Part #102).
6. Check the current on the flame rod (Part #108). Refer to #3 at “Appendix A” in Section C.
311,321,331,341*: Disconnected/short-circuited thermistor
Check for connection/breakage of wires and/or debris on the thermistor (Part #407, 408, 411, 715, 718).
Check the thermistor resistance. Refer to “Appendix D” in Section C.
391: Air-fuel ratio rod failure
Check for connection/breakage of wires (Part #709) and/or soot on the flame rod (Part #108).
441: Flow sensor failure (Only Easy-Link system)
Check for connection/breakage of wires and/or debris on the flow sensor impeller (Part #402).
*The 341, 751 and 941 error codes are applied to the 540 (T-H3) Indoor models only.
<<The fan motor is still spinning after operation has stopped>>
This is normal. After operation has stopped, the fan motor keeps running from 15 to 70
seconds in order to re-ignite quickly, as well as purge all the exhaust gas out of the flue.
<<Abnormal sound from water heater>>
An abnormal sound from the water heaters is caused by not enough air supply or wrong
installations. The water heater needs more combustion air. Refer to the “101” error code in the section B.
<<Power supply circuit>>
1. If the remote controller is installed, press the “ON/OFF” button of the remote controller, and make sure that the STAND BY LED next to the “ON/OFF” button of the remote controller is lit. Restart the water heater.
2. Check if the green LED on the PCB (Part #701) of the water heater is lit. If so, the power supply circuit of the water heater is under normal condition. Next, refer to the “Water circuit” in this section.
3. Check the fuse on the surge box (Part #703), and if it has a brown spot, need to replace it.
4. Check the power supply, and make sure that the water heater has 120 VAC.
5. If the green LED on the PCB (Part #701) isn’t lit, some electrical parts can be broken. Consult
the manufacturer.
<<Water circuit>>
1. If you use the remote controller, turn the power button on and then check if the STAND BY LED will light up.
2. Open all hot water faucets, and make sure that there is enough water flow. This water heater needs at least 0.5 GPM water flow (at the default set temperature) to operate.
3. Check for reverse connection and cross connection.
4. Check if the filter on the cold water inlet is cleaned (Part #406).
5. Check if there is no debris or obstruction on the fixtures.
6. Check if water ways in the water heater are frozen. If so, unfreeze them. And refer to the Installation manual to protect your water heater from freezing.
7. Check if the inlet water pressure is higher than 40 psi. And if it’s lower than 40 psi, need to increase the pressure.
8. Check for connections and breakage of wires (Part #402).
9. Check if the motor drive of the flow adjustment valve (Part #402) is locked due to scale buildup, and/or water leakage. If so, Consult the manufacturer.
510,551: Abnormal main gas solenoid valve and gas solenoid valve
Check for connection/breakage of wires (Part #708) and/or burn marks on the computer board (Part #701).
Reset power supply of the water heater.
Check the voltage of each valve on the gas valve assembly (Part #102). Refer to “Appendix C” in Section C.
611: Fan motor fault
Check for connection/breakage of wires, dust buildup in the fan motor (Part #103) and/or
burn marks on the computer board (Part #701).
Check for frozen/corrosion of connectors of the fan motor (Part #103).
Check the voltage between blue wire and each wire of the fan motor (Part #103). Refer to
“Appendix B” in Section C.
651: Flow adjustment valve fault (Only Easy-Link system)
Inspect the flow adjustment valve (Part #402), for connection/breakage of wires, locked
motor drive due to scale buildup, and/or water leakage.
Check the voltage between black wire and red wire. Refer to “Appendix F” in Section C.
661: Bypass valve fault
Inspect the bypass valve (Part #403), for connection/breakage of wires, locked motor drive
due to scale buildup, and/or water leakage.
Check the voltage between brown wire and red wire. Refer to “Appendix F” in Section C.
701: Computer board fault
Check for connection/breakage of wires (Part #714), and check the resistance between
white wire and red wire. Refer to “Appendix A” in Section C.
711: Gas solenoid valve drive circuit failure
Refer to the “111” and “121” error codes in this section.
721: False flame detection
1. Clean the flame rod (Part #108).
2. Check if there is leaking from the heat exchanger (Part #401).
741: Miscommunication between water heater and remote controller
1. Check the model type of the remote controller. Model No. 9008172005 (TM-RE40) is the correct one.
2. Inspect the connections between the water heater and remote controller. Refer to the “Remote controller connections” of the Installation manual.
3. Check the power supply of the water heater.
4. If this error code appears only on the green LED in the PCB (Part #701), check the voltage on the remote controller terminal on the PCB. Refer to “Appendix E” in Section C.
5. If this error code appears only on the remote controller, replace the PCB (Part #701). 6 . If this error code appears on both the PCB (Part #701) and the remote controller, replace the remote controller.
751*: Miscommunication between water heater and temperature controller
1. Check the power supply of the water heater.
2. If this error code appears only on the green LED in the PCB (Part #701), check the voltage on the remote controller terminal on the PCB. Refer to “Appendix E” in Section C.
3. If this error code appears only on the temperature controller, replace the PCB (Part #701).
4. If this error code appears on both the PCB (Part #701) and the temperature controller, replace the temperature controller.
761: Miscommunication between Parent unit and Child units for Easy-link system
Check if the connections between the parent unit and the child units are correct. Refer to
the “Easy-Link system” section in the Installation manual.
941*: Abnormal exhaust temperature (Only 540 (T-H3) Indoor models)
Check for connection/breakage of wires, dust buildup in the fan motor (Part #103) and/or
burn marks on the computer board (Part #701).
Check the exhaust thermistor resistance. Refer to "Appendix D" in Section C.
991: Imperfect combustion
Refer to the “101” error code in this section.
C. Wiring diagram and check point of the water heater
W: WHITE
R: RED G: GREEN
FM
Flame rod
Ground
Gas
Propor-
onal
Val ve
Bypass
Valve
DIPswitches
Appendix A (For error code 111)
Check the following points during ignition stage.
# 1. Refer to check point “B” on the wiring diagram above. Check the voltage between purple wires. (Normal: 108 to 132 VAC)
This check point is normal? Yes >> Replace the igniter assembly (Part #711). No >> Go to Next.
# 2. Refer to check points “C” and “H1” on the wiring diagram above. Check the voltages below: C: Between blue wire and light blue wire (#3). (Normal: 93 to 120 VDC) C: Between blue wire and orange wire (#53). (Normal: 93 to 120 VDC) H1: Check the voltage between white wire and red wire. (Normal: 1 to 15 VDC)
These check points are normal? Yes >> Replace the gas valve assembly (Part #102). No >> Replace the PCB (Part #701).
# 3. Check the current through the yellow flame rod wire (Part #709).
(Normal: more than 5 μA)
This check point is normal during operation? Yes >> Replace the PCB (Part #701). No >> Replace the flame rod (Part #108).
Appendix F (For error code 651 and 661)
Error code 651 : Refer to check point “J” on the wiring diagram above. Check the voltage between black wire and red wire. (Normal: 7 to 16 VDC) Error code 661 : Refer to check point “J1” on the wiring diagram above. Check the voltage between brown wire and red wire. (Normal: 3 to 11 VDC)
This check point is normal? Yes >> Error code 651: Replace the Flow adjustment valve (Part #402). / Error code 661: Replace the Bypass valve (Part #403). No >> Replace the PCB (Part #701).
BK: BLACK BL: BLUE
O: ORANGE
Igniter rod
R
BL
Y
O
W
O
G
Y
AFR rod
R
W
R
Y
W
1
BL
2 3 4
BR
65
87
1 2 3
654
Green LED
MAX buon
MIN buon
Increase buon
Decrease buon
H1 J1
ON
ON
LB: LIGHT BLUE
Y: YELLOW
BR: BROWN
IG
I
BK
BK
E3 E2
E1
P P
540
Indoor
Only
BK
BK BK
B
P: PURPLE
540 Outdoor Only
Heater Heater Heater
PCB
A G
3 9
53
C
73
J
H2
540
Indoor
Only
exchanger Heat
thermistor Inlet thermistor
Outlet thermistor
G
C1
C2
D1
L
Y
Y
W
BK
G
Ground
Hi-
BL
limit
BL
switch
BL
BL
BL
BL
O.H.C.F
BL
LB
O
R R BK
Flow
R
W
Sensor
BK
W
D2
W
BL
Temperature controller
R
BK
W
BK
K1
W
W
K2
540 Indoor Only
Heater Heater Heater
Heater
Thermostat
BK
SW
MV
SV1
SV2
A2
SV3
Flow
Adjust-
Ground
ment
Valve
BK
W
BK
F
Remote controller
W
W
thermistor
Exhaust Hi-limit switch
for exhaust
W
Surge box
W
BK
120 VAC
G
1 2
Parent
Appendix B (For error code 611)
Refer to check point “G” in the diagram to the left and the following.
Check the voltage between red wire and blue wire (Normal: 132 to 192 VDC).
Y
Check the voltage between yellow wire and blue wire (Normal: 13 to 17 VDC).
Check the voltage between orange wire and blue wire (Normal: 2.0 to 6.5 VDC).
Y
All check points are normal?
Y
Yes >> Replace the fan motor (Part #103).
B1
No >> Replace the PCB (Part #701).
Y
BK
Appendix C (For error code 510 and 551)
Refer to check point “C” in the diagram to the left and the following. Check the voltage on each valve on the gas valve assembly.
W
BK
Between blue wire and light blue wire (#3) (Normal: 93 to 120 VDC).
Between blue wire and green wire (#9) (Normal: 93 to 120 VDC).
A1
Between blue wire and orange wire (#53) (Normal: 93 to 120 VDC).
Between blue wire and red wire (#73) (Normal: 93 to 120 VDC).
All check points are normal? Yes >> Replace the gas valve assembly (Part #102). No >> Replace the PCB (Part #701).
Appendix D (For error code 311, 321, 331, 341, and 941)
Outlet thermistor (Find the marking of No.113 on the connector)
Check point “E1”
Inlet thermistor (Find the marking of No.42 on the connector)
Check point “E2”
Heat exchanger thermistor (Find the marking of No.12 on the connector)
Check point “E3”
Check the resistance between black wire and black wire.
Temperature
Resistance 15.4 12.6 10.3 8.5 7.0 5.9
• Exhaust thermistor
Check point “K1”
Check the resistance between white wire and white wire.
Temperature
Resistance 19.5 15.9 13.0 10.7 8.9 7.4
All check points are normal?
Yes >> Replace the PCB (Part #701). No >> Replace the thermistor (Part #407, 408, 411, 718).
Appendix E (For error code 741 and 751)
Error code 741: Refer to check point “F” on the wiring diagram above.
Error code 751 : Refer to check point “L” on the wiring diagram above. Check the voltage on the remote controller and/or temperature controller on the PCB. • Between black wire and white wire. (Normal: 11 to 25 VDC)
This check point is normal? Yes >> Replace the remote controller and/or temperature controller. No >> Replace the PCB (Part #701).
°F 50 59 68 77 86 95
°C 10 15 20 25 30 35
°F 50 59 68 77 86 95
°C 10 15 20 25 30 35
D. DIPswitch settings on the computer board of the water heater
Locate the bank of DIPswitches at the bottom left of the computer board of the unit. Change the DIPswitch settings when the power supply is turned off. The dark square is the direction the DIPswitch should be set to. DEFAULT is the factory setting.
<Upper bank of DIPswitches>
Vent settings (Indoor models only)
3" venting 4" venting
Set DIPswitches shown in the table above depending on the vent length.
Upper bank
5 to 20 ft (DEFAULT) 21 to 40 ft 41 to 70 ft
5 to 50 ft (DEFAULT) 51 to 100 ft N/A
ON
ON
<Lower bank of DIPswitches>
ON
Temperature set
120 °F (49 °C)
DEFAULT
140 °F (60 °C)
Easy-Link system
ON
ON
OFF
Lower bank
Parent Unit
Child Unit (DEFAULT)
Single unit is the same as the child unit.
Gas type*
Propane
Natural Gas
*Factory setting
High-altitude function
ON
ON
Indoor models
DEFAULT DEFAULT
Up to 2,500 ft Up to 2,000 ft
Up to 5,000 ft Up to 4,000 ft
Up to 7,500 ft Up to 6,000 ft
Up to 10,100 ft Over 6,000 ft
FM speed is increased automatically.
ON
ON
ON
ON
ON
Model type*
Indoor model
Outdoor model
Outdoor models
ON
ON
ON
ON
Consult the manufacturer
E. Components diagram / Parts list
Case assembly
052
003
007
050
717
713
052
008
702
704
052
002
050
Temperature remote controller
Burner assembly
Burner assembly
053
053
107
108
709
110
062
109
102
121
711
106
111
707
062
711
055
114
063
104
115
112
053
150
057
117
719
714
101
113
Manifold assembly
055
004
001
708
065
116
117
119
151
118
051
105
724
052
053
103
004
054
Outdoor modelsIndoor models
702
006
005
002
052
Bypass section
403
456
460
462
B
Temperature contoller
Indoor models
056
401
Item #
540 models T-H3 models
001 N/A
002 319143-507
003 004 005 006 007
008 009
050 051 052 053 054
055 056 057 058 059
060 061 062 063 064 065
N/A
319143-508
319143-509
N/A 319143-510 319143-511 319143-512
319143-513 319143-018
319143-025 319143-325 319143-026 319143-060 319143-326
319143-063
N/A 319143-201 319143-087 319143-328
319143-438
N/A 319143-059 319143-048
N/A 319143-330
704
458
001
A
Part #
467
451
462
451
414
722
EK159 EK164
EK158 EK174
EK170 EK162 EK190 EK171 EK161
EK160 EKH23
EW000 EW001 EW002 EW003 EW004
EW005 EW018
EKK31 EW00A EW009
EKK37
EK191 EW00D EM167
EK230 EW00B
Water way assembly
453
F
412
058
473
064
462
468
473
468
462
064
E
415
A
466
723
Case assembly for Indoor models
Case assembly for Outdoor models
Front cover for Indoor models
Front cover for Outdoor models
Intake air port assembly
Power supply cord assembly
Chamber fixing plate
Condensate drain port
Screw M4×12 (W/Washer) Screw M4×10 (W/Washer)
Screw M4×10 (Coated)
Hex head screw M4×12 (W/Washer)
Hex head screw M4x8
Pan screw M4x20
Tap tight screw M4x12 FEZN
Screw M3x6 SUS3
B
451
D
Description
Bracket
Junction box
Back guard panel
Screw M4x10
Screw M3x6 Screw M4x6
Screw M4x12
Screw M3x6
Pan screw M4x8
Wire clamp 60
Screw M4x10
414
E
463
052
465
418
413
452
472
418
152
153
456
D
460
458
052
406
457
405
402
461
454
404
417
059
407
Water intlet secon
471
718
415
470
053
F
401
459
454
411
Water outlet secon
455
C
463
464
455
469
Item #
101 102
103 319143-443
104 105 106 107 108
109 110 111 112
113 114 115 116 117
118 119 121
150 151 152 153
401 402 403 404
416
450
414
703
009
052
Part #
540 models T-H3 models
319143-514 319143-515 319143-516
319143-043 319143-031
319143-282 319143-033 319143-034 319143-517
319143-037 319143-036 319143-038 319143-518 319143-519
319143-044 319143-045 319143-032 319143-042 319143-520
319143-455 319143-342 319143-522
319143-350 319143-057 319143-523 319143-524
319143-548 319143-463 319143-464 319143-193
EK192 EK181 EK182
EK109 EKK25
EKK2X
EM381
EKK2V
EKK2W
EK193
EKK0F EKK32 EKN61 EK183 EK169
EKK2Y EKK2K EKK0G EKK2D EX019
EK117 EX00D EK163
EZP18 EK042 EK157 EK177
EK250 EK129 EKD58 EKK1U
Surge box
703
706
Manifold with gas valve assembly LP
Manifold with gas valve assembly NA
Fan motor for Indoor models
Fan motor for Outdoor models
Fan damper for Indoor models
Burner damper NA
Burner holder gasket
Combustion chamber tube
O-ring P18 NBR (Black) O-ring P20 NBR (Black)
Silicon ring for Outdoor models
Exhaust port for Outdoor models
Primary heat exchanger assembly
Flow adjustment valve / Flow sensor
C
458
462
409
052
Description
Burner assembly
Burner gasket
Burner window
Rod holder gasket
Flame rod
Igniter rod Rod holder
Rod cap
Burner damper LP
Manifold gasket A Manifold gasket B
Pressure port
Gas inlet
Gas inlet ring
Surge box plate
Bypass valve
Water inlet
053
455
121
709
454
408
410
063
417
713
Item #
405 406 407 408 409 410
411 412 413 414 415
416 417 418
450 451 452 453 454
455 456 457 458 459
460 461 462 463 464
465 466 467 468 469
470 471 472 473
701 702 703 704
706 707 708 709
711 713
714 715
716 717 718 719
721 722 723
724 319143-485 ER014 Temperature remote controller
Computer board assembly
701
714
403
716
715
Part #
540 models T-H3 models
319143-197 319143-198 319143-465 319143-190 319143-530 319143-199
319143-096 319143-095 319143-149 319143-531 319143-532 319143-533
319143-534 319143-468 319143-549 319143-550
319143-088 319143-125 319143-066 319143-146 319143-082
319143-080 319143-100 319143-091 319143-083 319143-097
319143-105 319143-226 319143-205 319143-112 319143-535
319143-536 319143-538 319143-539 319143-540 319143-541
319143-106 319143-111 319143-104 319143-542
319143-545 319143-334 320273-128 319143-427 319143-546
319143-141 319143-491 319143-492 319143-493
319143-479 319143-496 319143-497 319143-498 319143-499
319143-191 319143-500 319143-131 319143-484
319143-501 319143-502 319143-503
EKK2B EKK2C EK137 EKK1A EK208 EKK2E
EKK2T EKN34 EK333 EK209 EK210 EK211
EK231 EK105 EK251 EK256
EKK27 EK031 EKK26 EK029
EZM04 EZM06
EZM14 EZM15 EZM16
EKH30 EKK24
EM192
EKK39 EX12K EK217
EK218 EK220 EK222 EK226 EK228
EX13H EX13L
EKH6G
EK229 EK176
EX00B EK280 EK146 EK143
EKK4V EK165 EK168 EK166
EK153 EK184 EK185 EK167 EK179
EKK1M
EX13C EKH6E EK152
EK180 EK173 EK178
Secondary heat exchanger for Indoor models Secondary heat exchanger for Outdoor models
Switch wire with thermostat for Indoor models Switch wire with thermostat for Outdoor models
Exhaust thermistor for Indoor models
Temperature controller for Indoor models
709
711
708
715
722
721
707
Description
Inlet drain plug
Inlet water filter
Inlet thermistor
Outlet thermistor
Water outlet
Outlet drain plug
Heat exchanger thermistor
Hi-Limit switch
Overheat-cut-off fuse
Inlet heater for Indoor models
Inlet heater for Outdoor models
Stainless heat exchanger out pipe
120 VAC wire for Indoor models
120 VAC wire for Outdoor models
120 VAC Power ON-OFF switch
Cable clamp for Indoor models
Pipe heater
Drain tube
Inlet heater
Pipe heater fixing plate
Heater fixing plate 16
Fuse fixing plate 18 Fuse fixing plate 14
O-ring P4 FKM
O-ring P6 FKM O-ring P14 FKM O-ring P15 FKM O-ring P16 FKM Fastener “4-11”
Fastener “14-22”
Fastener “16A”
Fastener “16-25A”
Fastener “6-15”
Flat heater
Drain pipe
Cold pipe
Header connection
Drain port
Thermistor fixing plate
Exhaust thermistor gasket
Hi-limit switch for exhaust
Gasket
Computer board
Rubber grommet
Surge box
Remote controller wire
Gas valve wire
Flame rod wire
Igniter assembly
Proportional gas valve wire
24V cables
Computer board cover
Remote fixing plate
Exhaust Hi-limit switch wire
Fixing plate
713
103
402
402
Loading...