Taie FA Series, FU series, FY series, FY400, FY600 Operation Manual

...
0
1
CONTENT
1. Notice before start-up ..................................................................................................3
2. FU Series.....................................................................................................................4
2.1 Specifications......................................................................................................4
2.2 Outer Dimension.................................................................................................5
2.4 Assembly & Wiring .............................................................................................7
3 FY Series .................................................................................................................... 8
4. Terminal arrangement................................................................................................ 11
4.1 FY400 / FU48 Terminals ( 48mm x 48mm , DIN 1/16 ) .....................................11
4.3 FY700 / FU72 Terminals ( 72mm x 72mm).......................................................13
4.6 FY100 Terminals ( 175mm x 110mm ) ..............................................................16
4.7 FY101 Terminals ( 90mm x 90mm )..................................................................17
5. External dimension and panel cutout〈Unit:mm〉 .................................................18
5.1 FY100...............................................................................................................18
5.2 FY101...............................................................................................................18
5.3 FY400~900 & FU48~96.................................................................................... 19
6. Parts description........................................................................................................ 20
7. Operations .................................................................................................................21
7.1 Power On..........................................................................................................21
7.2 Change the Set Value (SV)...............................................................................21
7.3 Change the Alarm Value...................................................................................21
7.4 Autotuning (AT).................................................................................................22
7.5 Programmable RAMP / SOAK (Only available for PFY model) ........................23
8. Operation levels.........................................................................................................24
8.1 Levels diagram .................................................................................................24
8.2 Lock function ....................................................................................................24
9. Parameters ................................................................................................................25
9.1 Level 1 (User Level) .........................................................................................25
9.2 Level 2 (PID Level) ...........................................................................................26
9.2.1 Level 2 parameters display / hiding condition ......................................26
9.2.2 Description of parameters....................................................................27
9.3 Level 3 (Input Level) .........................................................................................28
9.4 Level 4 (SET level) ...........................................................................................30
9.4.1 How to hide parameters (Use SET1~SET7)........................................ 30
9.4.2 Special functions (Use SET8 / SET9 / SET0) ......................................31
9.4.3 Remote SV type selection ...................................................................32
9.4.4 Output mode selection (Use OUTY) ....................................................32
9.4.5 Modify caution .....................................................................................32
9.5 Program Level (Only displayed in programmable controller) .........................33
9.5.1 Description of parameters....................................................................33
2
9.5.2 Description of operation.......................................................................34
10. Input type table (INP1 selection)..............................................................................35
11. Alarm .......................................................................................................................37
11.1 Alarm time (ALT1/ALT2/ALT3) ........................................................................37
11.2 SETA...............................................................................................................37
11.3 Alarm mode (ALD1 / ALD2 / ALD3).................................................................38
12 Heater Break Alarm (HBA)........................................................................................39
12.1 HBA Wiring Example ......................................................................................39
12.2 HBA Function Description...............................................................................39
12.3 HBA setting procedure....................................................................................40
12.4 Parameters for HBA function ..........................................................................40
12.5 Activated conditions of HBA ...........................................................................41
12.6 Remarks .........................................................................................................41
12.7 CT specifications ............................................................................................42
12.7.1 SC-80T Specifications ..........................................................................42
12.7.2 SC-100T Specifications ........................................................................42
11.7.3 SC-80T Linear Diagram ........................................................................ 43
13. Error codes ..............................................................................................................44
14. Modify input type (“TC” “RTD”)......................................................................45
14.1 FY400~FY900 ................................................................................................45
14.2 FU48~96.........................................................................................................46
14.3 FY100~FY101 ................................................................................................46
15. Modify input type : Linear Input (mA ,V)...................................................................48
15.2 FY100/101 Hardware:.................................................................................. 49
15.3 Calibration:...................................................................................................50
16. Modify Output type : Relay , SSR , 4~20mA............................................................ 51
17. Modify output mode: OUT1/ALARM, OUT1/OUT2 ..................................................51
18. Applications .............................................................................................................52
18.1 RAMP & SOAK...............................................................................................52
18.2 TTL CommunicationSV output and RATE function .....................................53
18.4 1ψ Phase angle control (By TRIAC) ...............................................................55
18.7 1ψZero crossing control (By TRIAC) ..............................................................58
18.9 3ψZero crossing control (By TRIAC) ..............................................................60
18.10 3 wires proportional motor valve control .......................................................61
18.11 Wiring diagram of PC communication...........................................................62
3
1. Notice before start-up
FY series controller has got the CE approvals as below:
LVD D/N EN61010-1 EMC EN 55 022 1994 /A11995/ A21997
EN 61 000-3-2 1995 / -3-3 1995 EN 61 000-4-2 1995 / -4-3 1996 / -4-5 1995 / -4-6 1996 / -4-8 1993 / -4-11:1996/ EN 50 204: 1995
Please confirm the specification of controller is to totally with your requirement before using it, also read this manual in detail.
Danger
1. Danger! Electric Shock!
DON'T touch AC power wiring terminals when controller has been
powered!
Keep the power off until all of the wirings are completed!
Warning
1. Please confirm the AC power wiring to controller is correct, otherwise it would be
caused aggravated damage on controller. ( FY400 connecting with Pin 1 and 6,
FY100/FY101/FY600/700/800/900 with Pin 1 and 2).
2. Be sure to use the rated power supply (AC85~265V or DC24V), otherwise it would be
caused aggravated damage on controller.
3. Please confirm wires are connected with correct terminal (Input, Output).
4. Use M3 screw-compatible crimp-on terminals with an insulation sleeve, as shown
below
3.2mm
3.2mm
Torque : 0.4 N.m (4kgf.cm)
5. Avoid installing controller in following spaces:
I. A place where the ambient temperature may reach beyond the range
from 0 to 50
II. A place where the ambient humidity may reach beyond the range
from 20 to 90% RH.
III. A place where the controller likely to come into contact with water, oil,
chemicals, steam and vapor.
IV. A place where the controller is subject to interface with static
electricity, magnetism and noise.
6. For thermocouple (TC) input, use shield compensating lead wire.
7. For RTD input, use shield wires which have low resistance and no
resistance difference between the 3 wires.
4
2. FA Series
2.1 Specifications
z Standard Spec.
z General Spec.
5
z Control Features
z Input Features
z Output Features
z Communication
z Alarms
2.2 Outer Dimension
6
2.3 Terminal Wiring Diagram
7
2.4 Assembly & Wiring
plug-in-out terminal M2.0 using “”screwdriver fix terminal M2.6 using “”screwdriver
Selecting suitable electric wire of AWG 16 ~ AWG22 Lock Screw torque: 0.3 N.m (3 kgf.cm)
8
3 FY / FU Series
z Standard spec.
Model FY400 /
FU48
FY600 FY700 /
FU72
FY800 /
FU86
FY900 /
FU96
FY100 FY101
Dimension
48X48mm 96X48mm 72X72mm 48X96mm 96X96mm 175X110mm 90X90mm
Supply voltage
AC 85~265VDC 15~50V (Option)
AC 85~265V
Frequency
50 / 60 HZ
Power
consumption
approx
3VA
approx
4VA
approx
3VA
approx
4VA
approx
4VA
approx
4VA
approx
3VA
Accuracy
0.2 % FS ± 1digit
Sample time
250ms
TC
K , J , R , S , B , E , N , T , W5Re/W26Re , PLII , U , L
RTD
PT100,JPT100,JPT50
mA dc
4~20mA ,0~20mA
mV / V dc
0~1V,0~5V,0~10V,1~5V,2~10V
-10~10mV,0~10mV,0~20mV,0~50mV,10~50mV
Input
Decimal point
position
0000 , 000.0 , 00.00 , 0.000
Available for linear input (mA / mV / V)
SPST type SPDT type SPST type SPDT type SPDT type SPDT type SPDT type
Relay
3A , 220V , electrical life:100,000 times or more (under rated load)
Voltage pulse
For SSR drive. ON : 24V , OFF : 0V , max load current : 20mA
mA dc
4~20mA, 0~20mA. Maximum load resistance:560
Output 1
Voltage dc
0~5V , 0~10V , 1~5V , 2~10V . Max load current:20mA
Alarm 1
3A , 220V , electrical life:100,000 times or more (under rated load)
Control algorithm
PIDPIPD,P,ON / OFF(P=0)FUZZY
PID range
P: 0.0 ~ 200.0 %I: 0~3600sD: 0~900s
Isolation
Output terminals(control output , alarm , transmission) and input
terminals are isolated separately
Isolated resistance
10M or more between input and case (ground) at DC 500 V
10M or more between output and case (ground) at DC 500 V
Dielectric strength
1000V AC for 1 minute between input terminal and case (ground)
1500V AC for 1 minute between output terminal and case (ground)
Operating
temperature
0~50
Humidity range
20~90%RH
Weight
150g 225g 225g 225g 300g 130g 80g
Display Height
PV:7mm
SV:7mm
PV:7mm
SV:7mm
PV:14mm
SV:10mm
PV:7mm
SV:7mm
PV:14mm
SV:10mm
9
z Optional Spec.
Model FY400 /
FU48
FY600 FY700 /
FU72
FY800 /
FU86
FY900 /
FU96
FY100 FY101
Output 2
For heating and cooling control use.
Relay , SSR , 4~20mA , 0~20mA , 0~5V , 0~10V , 1~5V , 2~10V
Available Available Available Available Available Available
SPST type SPDT type SPST type SPDT type SPDT type SPDT type
Not
available
Alarm 2
3A , 220V , electrical life:100,000 times or more (under rated load)
Available Available Available Available Available Not
available
SPST type SPST type SPST type SPST type SPST type
Not
available
Alarm 3
3A , 220V , electrical life:100,000 times or more (under rated load)
Display range of heater current : 0.0~99.9A , Accuracy : 1%FS
Included CT : SC-80-T (5.8mm dia , 0.0~80.0A)
or SC-100-T (12mm dia , 0.0~99.9A)
Heater Break Alarm
(HBA)
Alarm relay : AL1
Available for PV or SV transmission
Transmission
4~20mA , 0~20mA , 0~1V , 0~5V , 0~10V , 1~5V , 2~10V
Remote SV
4~20mA , 0~20mA , 0~1V , 0~5V , 0~10V , 1~5V , 2~10V
Protocol : MODBUS RTU , MODBUS ASCII , TAIE
RS232 , RS485 , TTL
Baud rate: 2400 , 4800 , 9600 , 19200 , 38400 bps.
Communication
Data bits : 8 , Stop bit : 1 or 2bit , Odd or Even parity.
Water/Dust proof
IP65
z
Special control output (OUT1)
Model FY400 /
FU48
FY600 FY700 /
FU72
FY800 /
FU86
FY900 /
FU96
FY100 FY101
1φ zero crossing
control(1φSSR)
Available Not
available
Available Not
available
Available Not
available
Not
available
3φ zero crossing
control(3φSSR)
Not
available
Available Not
available
Not
available
Motor valve control
Available
1φ phase angle
control(1φSCR)
Not
available
Available Available Not
available
3φ phase angle
control(3φSCR)
Not available Available Not
available
Not
available
10
z Programmable RAMP/SOAK
Model
PFY400 PFY600 PFY700 PFY800 PFY900 PFY100 PFY101
Programmable
RAMP/SOAK
2 patterns with 8 segment each.
The 2 patterns can be linked together as 16 segments use.
11
4. Terminal arrangement
4.1 FY400 / FU48 Terminals ( 48mm x 48mm , DIN 1/16 )
AC 85~265V DC 15 ~50V(Option)
A.Power Supply
Relay SSR mA,V
OUT1
G1
K1
G2
K2
OUT1
(1ΦZero Cross Control)
Relay SSR mA,V
OUT2
2
3
CLOSE
OPEN
COM
OUT1
(Proportional Motor
Valve Control)
B.Control Output
mA,V RTD
TC,mV
C.Input
2
3
AL 1
11
12
AL 1
13
14
AL 2
D.Alarm
TRS
E.Transmission
RS232
F.Communication
11
12
13
RD
SD
SG
RS485
11
12
Dx-
Dx+
TTL
11
12
13
RD
SD
SG
(Option)
(Use OUT1 & OUT2)
(Proportional Motor
Valve Control)
H.CT Input
CT
11
12
12
4.2 FY600 Terminals ( 96mm x 48mm , DIN 1/8 )
AC 85~265V DC 15 ~50V(Option)
A.Power Supply
Relay SSR mA,V
OUT1
K2
G2
K1
G1
OUT1
(1ΦPhase Angle Control)
Relay SSR mA,V
OUT2
6
7
CLOSE
OPEN
OUT1
(Proportional Motor
Valve Control)
B.Control Output
mA,V RTD
TC,mV
C.Input
AL 1
6
7
AL 2
D.Alarm
TRS
E.Transmission
RS232
G.Communication
14
15
16
RD
SD
SG
RS485
14
15
Dx-
Dx+
TTL
14
15
16
RD
SD
SG
(Option)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
7
8
9
10
COM
6
7
8
9
10
17
18
19
20
17
18
19
20
17
18
19
20
AL 3
12
13
Remote SV
F.Remote
14
15
H.CT Input
CT
14
15
13
4.3 FY700 / FU72 Terminals ( 72mm x 72mm)
AC 85~265V DC 15 ~50V(Option)
A.Power Supply
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
Relay SSR mA,V
OUT1
G1
K1
G2
K2
OUT1
Relay SSR mA,V
OUT2
3
4
CLOSE
OPEN
OUT1
B.Control Output
mA,V RTD
TC,mV
C.Input
3
4
AL 2
D.Alarm
TRS
E.Transmission
RS232
G.Communication
15
16
17
RD
SD
SG
RS485
15
16
Dx-
Dx+
TTL
15
16
17
RD
SD
SG
(Option)
COM
3
4
5
6
7
11
12
13
14
11
12
13
14
11
12
13
14
AL 1
18
19
Remote SV
F.Remote
9
10
5
6
7
21
15
16
17
18
20
PROT
G1
G2
OUT1
20
15
17
19
PROT
8
9
10
COM
NO
NC
(Proportional Motor
Valve Control)
(1ΦZero Cross Control)
(1ΦPhase Angle Control)
H.CT Input
CT
15
16
14
4.4 FY800 / FU86 Terminals ( 48mm x 96mm , DIN 1/8 )
AC 85~265V DC 15 ~50V(Option)
A.Power Supply
Relay SSR mA,V
OUT1
K2
G2
K1
G1
OUT1
(1ΦPhase Angle Control)
Relay SSR mA,V
OUT2
6
7
CLOSE
OPEN
OUT1
(Proportional Motor
Valve Control)
B.Control Output
mA,V RTD
TC,mV
C.Input
AL 1
6
7
AL 2
D.Alarm
TRS
E.Transmission
RS232
G.Communication
14
15
16
RD
SD
SG
RS485
14
15
Dx-
Dx+
TTL
14
15
16
RD
SD
SG
(Option)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
7
8
9
10
COM
6
7
8
9
10
17
18
19
20
17
18
19
20
17
18
19
20
AL 3
12
13
Remote SV
F.Remote
14
15
H.CT Input
CT
14
15
15
4.5 FY900 / FU96 Terminals ( 96mm x 96mm , DIN 1/4 )
AC 85~265V DC 15 ~50V(Option)
A.Power Supply
Relay SSR mA,V
OUT1
Relay SSR mA,V
OUT2
6
7
B.Control Output
mA,V RTD
TC,mV
C.Input
AL 1
6
7
AL 2
D.Alarm
TRS
E.Transmission
RS232
G.Communication
14
15
16
RD
SD
SG
RS485
14
15
Dx-
Dx+
TTL
14
15
16
RD
SD
SG
1
2
3
4
5
6
7
8
9
10
21
22
23
24
25
26
27
28
29
30
17
18
19
20
17
18
19
20
17
18
19
20
AL 3
39
40
Remote SV
F.Remote
14
15
G1
G2
OUT1
(1ΦZero Cross Control)
40
31
33
39
PROT
G1
K1
G2
K2
OUT1
(1ΦPhase Angle Control)
CLOSE
OPEN
OUT1
COM
6
7
8
9
10
36
31
32
33
34
35
PROT
RG1
RG2
TG1
TG2
OUT1
(3ΦZero Cross Control)
40
31
33
35
37
39
PROT
G1
K1
G2
K2
OUT1
(3ΦPhase Angle Control)
40
31
32
33
34
39
PROT
G3
K3
35
36
RS232
31
32
33
RD
SD
SG
RS485
31
32
Dx-
Dx+
( Remote SV )
11
12
13
14
15
16
17
18
19
20
31
32
33
34
35
36
37
38
39
40
(Proportional Motor
Valve Control)
H.CT Input
14
15
CT
16
4.6 FY100 Terminals ( 175mm x 110mm )
17
4.7 FY101 Terminals ( 90mm x 90mm )
18
5. External dimension and panel cutoutUnitmm
5.1 FY100
5.2 FY101
19
5.3 FY400~900 & FU48~96
FY400/
FU48
Y1
Y2
AT
AL
AL
PRO
1
2
50
50
44.5+0.5
44.5+0.5
65
70
FY600
96
50
90.5+0.5
44.5+0.5
111
70
FY700/
FU72
74
74
68.5+0.5
68.5+0.5
89
94
FY800/
FU86
96
50
44.5+0.5
90.5+0.5
65
116
FY900/
FU96
96
96
90.5+0.5
90.5+0.5
111
116
20
6. Parts description
FY400/FU48
Y1
Y2
AT
AL
AL
PRO
1
2
1
2
3 5 6
7
10
11
12
15
9
8
FY600
1 2
13 10 15 14
11 8 9 12 16 5
7
4 3 6
FY800/FU86
1 2
9
8
12
4
3 5 6
7
13
16
14
15
11
10
FY700/FY900/FU72/FU96
FY100/101 External
Interface Unit
1
2
16
3 4 5
6 7
8 9
10 11 12 13 14 15
SYMBOL NAME FUNCTION
PV
1
Measured value
(PV) display
Displays PV or various parameter symbols
(Red)
SV
2
Set value
(SV) display
Displays SV or various parameter set values
(Green)
SET
3
Set key Used for parameter calling up and set value
registration
A/M
4
Auto/Manual key Switches between Auto(PID) output mode and
Manual output mode.
5
Shift key Shift digits when settings are changed
6
Down key
*Program hold
Decrease numbers (-1000,-100,-10,-1)
* Program hold
Programmable controller
7
Up key
*Program run
Decrease numbers (+1000,+100,+10,+1)
* Program run
Programmable controller
OUT1
8
OUT1 lamp Lights when OUT1 is activated (Green)
OUT2
9
OUT2 lamp
Lights when OUT2 is activated (Green)
AT
10
Auto tuning lamp Lights when Auto tuning is activated (Orange)
AL1
11
Alarm 1 lamp Lights when Alarm 1 is activated (Red)
AL2
12
Alarm 2 lamp Lights when Alarm 2 is activated (Red)
AL3
13
Alarm 3 lamp Lights when Alarm 3 is activated (Red)
MAN
14
Manual output lamp Lights when manual output is activated
(Orange)
PRO
15
*Program running
lamp
*Flashes when program is running
Programmable controller
〉。
OUT1%
16
OUT% bar-graph
display
Output% is displayed on 10-dot LED.
21
7. Operations
7.1 Power On
Controller will display as below
Display input type
(K2)
Display range
(0.0~400.0)
Ready for use
All LED and 7 segment
displays will be lighted
7.2 Change the Set Value (SV)
Change SV from 0.0 to 100.0
Press key. The SV number started to flash. The flashing digit indicates which digit can be set.
Press key to select the hundreds digit.
Press key to change the number to 1
Press key to store the new set value.
SET
7.3 Change the Alarm Value
Change AL1 value to “5.0” (AL1 active, if PV exceeds SV over 5.0)
Press key to display parameter AL1
Press key to change AL1 value
Press key increase AL1 value
Press key store the new value of AL1
SET
SET
* The are total 16 alarm mode types, please referred with “alarm mode” in page 30
* To change alarm mode, press
SET
+ key 3 seconds to enter Level 3 (Input
Level) and then change ALD1/ALD2/ALD3 value.
22
7.4 Autotuning (AT)
Use AT function to automatically calculate and set the optimize PID value for your system.
23
7.5 Programmable RAMP / SOAK (Only available for PFY model)
*For detail of the programmable instruction, please refer with page 25.
Press key to display SV_1
Set SV_1 to 200.0
Set TM_1 to 01.00 (1 hour)
Set OUT1 to 100.0
SET
Assume the temperature profile is as below (use total 4 segments )
TIME
SV
RAMP SOAK
RAMP SOAK
1 hour
30
minutes50minutes
1 hour and 20 minutes
200
120
Set SV_2 to 200.0
Set TM_2 to 00.30 (30 minutes)
Set OUT2 to 100.0
Set SV_3 to 120.0
Set TM_3 to 00.50 (50 minutes)
Set OUT3 to 100.0
Set SV_4 to 120.0
Set TM_4 to 01.20 (1 hour and 20 minutes)
Set OUT4 to 100.0
Press key to run program (PRO LED start lighting)
Please operate conroller as following steps:
24
8. Operation levels
8.1 Levels diagram
8.2 Lock function
To use lock function, please set parameter “LCK” in level 2.
Levels entering available LCK
Level 1
(User)
Level 2
(PID)
Level 3
(Input)
Level 4
(SET)
Parameters which can be
changed
------ All parameters
(Factory set value)
◎ ------ ◎ All parameters
------ ------ All parameters except level 3
------ ------ Parameters in level 1
------ ------ “SV” and “LCK”
◎ ------ ------ Only “LCK”
25
9. Parameters
9.1 Level 1 (User Level)
Process Value Set Value
Output Limt
Autotuning
Alarm 1 set value
Alarm 2 set value
Set
Set
Set
Set
Set
Alarm 3 set value
PV SV
Set
()
Heater current display HBA set value
26
9.2 LEVEL 2 (PID Level)
To enter level 2, press SET key 3 seconds in level 1
9.2.1 Level 2 parameters display / hiding condition
27
9.2.2 Description of parameters
Set
Set
Set
Set
Set
Set
Set
Set
Set
Set
Set
Set
Set
Set
Proportional band 1 (For output 1)
Range:0.0~200.0% ON/OFF control if set to 0 (0.0)
Reserved
Auto tuning offset value
Output 1 cycle time
Hysteresis for output 1 ON/OFF control
Proportional band 2 (For output 2)
Integral time 2 (For output 2)
Derivative time 2 (For output 2)
Output 2 Cycle time
Hysteresis for output 2 ON/OFF control
Control gap 1 (For output 1)
Control gap 2 (For output 2)
Function lock
Range:0~3600 seconds PD control if set to 0
Range:0~900 seconds PI control if set to 0
Reserved
Range:0~USPL
Range:0~150 seconds Relay output : 10 Voltage pulse output : 1 , mA output: 0
Range:0~1000
The same with P1
The same with I1
The same with D1
The same with CYT1
The same with HYS1
Set point of output 1 (Heating side) =SV - GAP1
=SV + GAP2
Return to “P1"
If P2=0.0
Display
Display if output2 is provided
Integral time 1 (For output 1)
Derivative time 1 (For output 1)
If P1=0.0
Display
Levels entering available LCK
Level 1
(User)
Level 2
(PID)
Level 3
(Input)
Level 4
(SET)
Parameters which can be
changed
------ All parameters (default value)
◎ ------ ◎ All parameters
------ ------ All parameters except level 3
------ ------ Parameters in level 1
------ ------ “SV” and “LCK”
◎ ------ ------ Only “LCK”
28
9.3 LEVEL 3 (Input Level)
To enter level 3 , set LCK to ”0000”and then press SET key + Shift( ) key 3 seconds.
Set
Set
Set
Set
Set
Set
Set
Set
Set
Set
Set
Set
Set
Set
Input type selection
Analog input low limit calibration (Used for mA and V input)
Decimal point position
Lower Set-Point Limit
Alarm mode of AL1
Range:-1999 ~ 9999
Range:0 ~ 9999
0000,000.0,00.00,0.000
Range:00~19 Refer to “Alarm mode type"
Range:0~99 Min 59 Secs 0=Flicker Alarm,99:59=Continued Others=On delay time (If ALD=07 , ALT means alarm on time)
The same with ALD1
Set
Hysteresis of all Alarm Range:0~1000
Range:0 ~ 9999
Set
Analog input high limit calibration (Used for mA and V input)
(Available for mA and V input)
Upper Set-Point Limit
Scaling Low Limit
Scaling High Limit
Remote input low limit calibration Range:-1999 ~ 9999
Remote input high limit calibration Range:0 ~ 9999
Alarm time of AL1
Alarm mode of AL2
Alarm time of AL2
Alarm mode of AL3
Alarm time of AL3
The same with ALT1
The same with ALD1
The same with ALT1
Output 1 low limit calibration (Used for mA and V output)
Set
Range:0 ~ 9999
Output 1 low limit calibration (Used for mA and V output)
29
Set
Set
Set
Set
Set
Full run time of proportional motor
Used for programmable controller to wait continued operation
PV Filter
The same with CLO1
Range:5~200 seconds
0=Not wait
Others=Wait value
Set
Retransmission low limit calibration
Return to “INP1"
Output 2 low limit calibration (Used for mA and V output)
Output 2 high limit calibration (Used for mA and V output)
The same with CHO1
The same with CLO1
The same with CHO1
Retransmission high limit calibration
( Used for proportional motor valve control output)
Set
Set
Set
Set
Set
Set
Set
Set
Set
Set
Control mode
Heat / Cool
Control algorithm
PID / Fuzzy
Frequency
50 / 60HZ
ID number
Baudrate
SV compensation
PV compensation
Unit of PV & SV
Range:0 ~ 255
2400 / 4800 / 9600 / 19200 / 38400 bps
Range:-1000~1000
Range:-100.0~500.0
C(℃) / F(℉) / A(Analog)
Reserved
Set
Set
Set
Communication Protocol Selection
Communication Bits Configuration
MODBUS RTU / MODBUS ASCII / TAIE
O_81 /O_82/E_81/ E_82
PV will responese faster if PVFT is smaller.
30
9.4 Level 4 (SET level)
To ent e r l e v e l 4 , s e t L C K t o ” 1111 ” and then press SET key + Shift( ) key 3 seconds.
Remote SV
Setting
Output mode
selection
Special functionsDisplay/hiding
parameters
SET
Press Key
SET
Press Key
SET
SET
SET SETSET
9.4.1 How to hide parameters (Use SET1~SET7)
SET 1_ 1 SET 1_ 2 SET 1_ 3 SET 1_ 4
0
:Hide this parameter
1
:Display this parameter
PV
SV
*For the description of Level 1 parameters, please refer with page 17.
*For the description of Level 3 parameters, please refer with page 20.
SET Display / hiding Level SET Display / hiding Level
1_ 1
Level 1 5_ 1
,
Level 3
1_ 2
Level 1 5_ 2
,
Level 3
1_ 3
Level 1 5_ 3
, ,
Level 3
1_ 4
Level 1 5_ 4
, , ,
Level 3
2_ 1
Level 1 6_ 1
Level 3
2_ 2
, ,
Level 3 6_ 2
Level 3
2_ 3
,
Level 3 6_ 3
Level 3
2_ 4
,
Level 3 6_ 4
Level 3
3_ 1
Level 3 7_ 1
Level 3
3_ 2
Level 3 7_ 2
Level 3
3_ 3
Level 3 7_ 3
Level 3
3_ 4
Level 3 7_ 4
Level 3
4_ 1
Level 3
4_ 2
Level 3
4_ 3
Level 3
4_ 4
,
Level 3
31
9.4.2 Special functions (Use SET8 / SET9 / SET0)
SET 8 Remark
0 : Program not repeat 8_ 1
1 : Program repeat
0 : No power failure option 8_ 2
1 : With power failure option
0 : Program starts from 0 8_ 3
1 : Program starts from PV
Only available for
programmable
controller
8_ 4 0 : Reserved (Don’t change it)
SET 9 Remark
9_ 1 0 : Reserved (Don’t change it)
0 : Timer Unit = “Hour : Minute” 9_ 2
1 : Timer Unit = “Minute : Second”
Only available for
programmable
controller
0 : Disable transmission 9_ 3
1 : SV Transmission
0 : Disable transmission 9_ 4
1 : PV Transmission
Used for transmission
output
SET 0 Remark
0 : TTL Communication (Slave) 0_ 1
1 : TTL Communication (Master)
Used for TTL
communication
0 : Hide parameter “RATE” 0_ 2
1 : Display parameter “RATE” AL3 will be replaced
by “RATE”
0 : Disable Remote SV function 0_ 3
1 : Enable Remote SV function
Used for Remote SV
function
0 : use output relay “b” contact when
motor valve closed
0_ 4
1 : use output relay “a” contact when
motor valve closed
Used for 3 wire
proportional motor
valve control
32
Please don't operate SET 8_4otherwise the controller's process will be in confusion.
If SET8.4 is set to “1”, the controller will enter into “Single Display” mode, the PV LED will
not display any values. The SV LED will display both the parameter value and the setting
value alternately as shown in the diagram below.
PV
SV
EMPTY
Displayed alternately
To rectify the problem please press the SHIFT KEY ( ) and change the setting value to
“0000”.
9.4.3 Remote SV type selection
INP2=0 None
INP2=1 10~50mV / 4~20mA / 1~5V / 2~10V
INP2=2 0~50mV / 0~20mA / 0~5V / 0~10V
INP2=4 CT input Remote SV function is not available for programmable controller
9.4.4 Output mode selection (Use OUTY)
OUTY=0 Single output (OUT1)
OUTY=1 Dual output (OUT1 / OUT2)
OUTY=2 Reserved
OUTY=3 3 wire proportional motor valve control
OUTY=4 1ψPhase angle control (1ψSCR)
OUTY=5 3ψPhase angle control (3ψSCR)
9.4.5 Modify caution
If change parameter “BAUD”, “BITS”, “RUCY”, “OUTY” the power must be reset
33
9.5 Program Level (Only displayed in programmable controller)
9.5.1 Description of parameters
Set
Set
Set
Set
Set
Set
Set
Set
Set
Set
Set
Set
Set
Set
Program Pattern Range:0~2
Program Segment display
Program countdown display Range:0~99 hour 59 min
Setting value of Seg.1 Range:LSPL~USPL
Set time for Seg.1 Range:0~99 hour 59 min
Output Limit of Seg.1 Range:0~100% If OUT=0,program will end.
Setting value of Seg.2
Set time for Seg.2
Output Limit of Seg.2
Setting value of Seg.3
Set time for Seg.3
Output Limit of Seg.3
Setting value of Seg.4
Set time for Seg.4
Output Limit of Seg.4
LEVEL 1
Set
Set
Set
Set
Set
Set
Set
Set
Set
Set
Set
Set
Setting value of Seg.5
Set time for Seg.5
Output Limit of Seg.5
Setting value of Seg.6
Set time for Seg.6
Output Limit of Seg.6
Setting value of Seg.7
Set time for Seg.7
Output Limit of Seg.7
Setting value of Seg.8
Set time for Seg.8
Output Limit of Seg.8
Set
Set
Return LEVEL 1
( Pattern _ Segment )
34
9.5.2 Description of operation
1. There are 2 patterns can be usedeach pattern contains 8 segments.
2. Terminologies
Pattern A program consists of some steps. Ramp statusThe status with changing SV. Soak status The status with fixed SV.
3. Operating
I. "KEY" function (no changing parameter)
(RUN) Start program procedurePRO LED in panel start flicking.
(HOLD) Suspend program procedurePRO LED in panel will stop
flicker but still light on.
+ SET(JUMP) Jump to previous segment.
+ SET (RESET)Reset program procedurePRO LED in panel will off.
II. Alarm Function
ALD1 = “07”(Segment end alarm) AL1 =“2”(It means when segment 2 end,AL1 will act)
ALT1 =“00:10” (Relay on time is 10 seconds).
In this casewhen program proceeds to segment 2 endthe relay of AL1 will
be on 10 seconds.
III. END function
The Controller doesn’t have END order, so if program procedure is less than 8
segments, please set the last segments OUT to “0”. Program will end in this segment. Otherwiseit will proceed 8 or 16 segments.
IV. Linking Function
PTN=1 proceed pattern 1contains 8 segments. PTN=2 proceed pattern 2contains 8 segments.
PTN=0 linking proceed pattern 1 and 2 totally 16 segments.
(Please set PTN1 and PTN2 at firstand then set PTN to 0)
V. Other function(refer to LEVEL 4)
SET 8_1=1 Program repeats.
SET 8_2=0 No power failure function.
SET 8_2=1 Enable power failure function.
(When power shut down and on again,the controller will start from the
segment which is near PV)
SET 8_3=0 Program starts from 0.
SET 8_3=1 Program starts from PV.
SET 9_2=0 Timer Unit = “Hour: Minute”
SET 9_2=1 Timer Unit = “Minute: Second”
35
10. Input type table (INP1 selection)
TYPE CODE RANGE
0.0 ~ 200.0 / 0.0 ~392.0
0.0 ~ 400.0 / 0.0 ~752.0
0 ~ 600 / 0 ~1112
0 ~ 800 / 0 ~1472
0 ~ 1000 / 0 ~1832
K
0 ~ 1200 / 0 ~2192
0.0 ~ 200.0 / 0.0 ~392.0
0.0 ~ 400.0 / 0.0 ~752.0
0 ~ 600 / 0 ~1112
0 ~ 800 / 0 ~1472
0 ~ 1000 / 0 ~1832
J
0 ~ 1200 / 0 ~2192
0 ~ 1600 / 0 ~2912
R
0 ~ 1769 / 0 ~3216
0 ~ 1600 / 0 ~2912
S
0 ~ 1769 / 0 ~3216
B
0 ~ 1820 / 0 ~3308
0 ~ 800 / 0 ~1472
E
0 ~ 900 / 0 ~1652
0 ~ 1200 / 0 ~2192
N
0 ~ 1300 / 0 ~2372
-199.9 ~ 400.0 /-199.9 ~752.0
-199.9 ~ 200.0 / -199.9 ~392.0
T
0.0 ~ 350.0 / 0.0 ~662.0
0 ~ 2000 / 0 ~3632
W5Re/W26Re
0 ~ 2320 / 0 ~4208
0 ~ 1300 / 0 ~2372
PL
0 ~ 1390 / 0 ~2534
-199.9 ~ 600.0 / -199.9 ~999.9
-199.9 ~ 200.0 / -199.9 ~392.0
U
0.0 ~ 400.0 / 0.0 ~752.0
0 ~ 400 / 0 ~752
L
0 ~ 800 / 0 ~1472
36
TYPE CODE RANGE
-199.9 ~ 600.0 / -199.9 ~999.9
-199.9 ~ 400.0 / -199.9 ~752.0
-199.9 ~ 200.0 / -199.9 ~392.0
0 ~ 200 / 0 ~392
0 ~ 400 / 0 ~752
JIS
PT100
0 ~ 600 / 0 ~1112
-199.9 ~ 600.0 / -199.9 ~999.9
-199.9 ~ 400.0 / -199.9 ~752.0
-199.9 ~ 200.0 / -199.9 ~392.0
0 ~ 200 / 0 ~392
0 ~ 400 / 0 ~752
DIN
PT100
0 ~ 600 / 0 ~1112
-199.9 ~ 600.0 / -199.9 ~999.9
-199.9 ~ 400.0 / -199.9 ~752.0
-199.9 ~ 200.0 / -199.9 ~392.0
0 ~ 200 / 0 ~392
0 ~ 400 / 0 ~752
JIS
PT50
0 ~ 600 / 0 ~1112
AN1
-10 ~ 10mV / -1999~9999
AN2
0 ~ 10mV / -1999~9999
AN3
0 ~ 20mV / -1999~9999
AN4
0 ~ 50mV / -1999~9999
AN5
10 ~ 50mV /-1999~9999
The initial setting in factory is “K2”.
37
11. Alarm
11.1 Alarm time (ALT1/ALT2/ALT3)
ALT1=0 Flicker alarm
ALT1=99.59 Continued alarm
ALT1=00.01 ~ 99.58 Alarm on delay time
11.2 SETA
*SETA is in Level 3 (Input level)
If SETA_1=1,AL1 relay will be action reversely
If SETA_4=0,program run alarm If SETA_4=1,program end alarm
When "b" contact (normal close) is needed
}
Only available for programmable controller
If SETA_2=1,AL2 relay will be action reversely
If SETA_3=1,AL3 relay will be action reversely
}
38
11.3 Alarm mode (ALD1 / ALD2 / ALD3)
15
05
04 14
03
02
00 10
01
HIGH
ONOFF
11
HIGH
ONOFF
HIGH
ON OFF
HIGH
ON
OFF
LOW
ON
HIGH
OFF
ON
LOW
OFF
HIGHLOW
ONOFF
HIGHLOW
ONOFF
16
HIGHLOW
OFFON
07
(1) ALD1~3 , set 07
(2) ALD1~3=Alarm Segment
0 =flicker alarm
99.59 =continued alarm others =alarm ON time
17
ON OFF
Run
Stop
08
OFF ON
Normal
Failed
18
ON OFF
AL
AL
AL
HIGHLOW
OFFON
06
HIGH
ON OFF
12
13
HIGH
ON
OFF
LOW
ON
Normal
Failed
( :SV :Alarm set value)
Deviation high alarm with hold action*
Deviation high alarm
Deviation low alarm with hold action*
Deviation low alarm
Deviation high/low alarm with hold action*
Deviation high/low alarm
PV
PV
PV
PV
PV
PV
PV
PV
PV
PV
PV
Band alarm
Process high alarm with hold action*
Process high alarm
Process low alarm with hold action*
Process low alarm
No alarm
Segment End alarm (Only for Programmable controller)
(3) ALT1~3 defines as follows:
Program Run alarm (Only for Programmable controller)
System failed alarm* (ON)
System failed alarm* (OFF)
09
(HBA)
Heater Break Alarm
Please refer with HBA function description in page 31.
*Hold action:
When Hold action is ON ,the alarm action is suppressed at start-up until the measured
value(PV) enters the non-alarm range.
*System failed:
It means that the controller display error message with one of following :
”UUU1” or “NNN1” or “CJCE”
Heater Break Alarm
(HBA)
Please refer with HBA Function Description in Page39
RAMP & SOAK
If PV=SV, Alarm will delay for a
while then (alarm set value) action.
Range: 00.00~99.59(hr.min.)
39
12 Heater Break Alarm (HBA)
12.1 HBA Wiring Example
SSR
+
-
AC POWER
CT
Heater
Sensor
OUT1
AL1
(HBA Relay)
(CT Input)
(Sensor Input)
12.2 HBA Function Description
HBA function detects the AC current flowing through the heater by a Current Transformer
(CT), and compares the CT input value and HBA set value. When OUT1 is ON and CT
input value is less than HBA set value during 5 seconds, AL1 is activated. Otherwise, AL1
is not activated.
The AC current flowing through heater can also be monitored in HBA setting mode.
40
12.3 HBA setting procedure
SV
Press Key
SET
SV
Means current
Press Key
SET
Press Key
SET
HBA Set Value
Heater Current
Press Key
SET
Press Key
Press Key
(HBA Setting Mode)
To select HBA set value
To adjust HBA set value
Press Key
SET
To store new HBA set value
12.4 Parameters for HBA function
Name Value Operation Level
AL1 HBA Set Value Level 1
ALD1 9 Level 3
SET0 X1XX Level 4
INP2 4 Level 4
¾ How to enter Level 3:Set parameter “LCK” to 0000 in Level 2 , and then press “SET”
key + “Shift” key 5 seconds to enter operation Level 3.
¾ How to enter Level 4:Set parameter “LCK” to 1111 in Level 2 , and then press “SET”
key + “Shift” key 5 seconds to enter operation Level 4.
¾ ‘X’ value available 0 or 1
41
12.5 Activated conditions of HBA
Condition
1. OUT1 is ON
2. Heater current is less the HBA set value
3. Condition1 and 2 continued more than 5 seconds
AL1 will be activated, if condition 1&2&3 are all “true”.
12.6 Remarks
¾ Available output(OUT1) type for HBA
I. Relay
II. Voltage pulse (SSR drive)
¾ Since HBA function uses AL1 as alarm relay, please set temperature alarms in AL2 or
AL3.
42
12.7 CT specifications
12.7.1 SC-80T Specifications
Rated Primary Current (Amp.):0.1A~80.0A Turns Ratio 8001 D.C.Resistance Max.at 20 ℃()45 Accuracy ( Linearity )3% Dielectric Withstanding Voltage(Hi-pot)2500Vrms / 1 minute Approx.Weight12g
5.9
15.0
30.0
40.0
6.0
Epoxy
b
Vout
K
L
SC-80T Mechanical Dimensions (mm) Test Circuit
12.7.2 SC-100T Specifications
Rated Primary Current (Amp.):0.1A~100.0A Turns Ratio 10001 D.C.Resistance Max.at 20 ℃()150 Accuracy ( Linearity )3% Dielectric Withstanding Voltage(Hi-pot)4000Vrms / 1 minute Approx.Weight55g
25 .2±0.3
38 MA X
32 .8±0.3
Front view
Bottom view
1
4
3
15MAX
39.5MAX
1.0
13±0.3
6.0
+1
0
Side vie w
2
Ep oxy
Epoxy
1 00ohm
SC-100T Mechanical Dimensions (mm) Test Circuit
43
11.7.3 SC-80T Linear Diagram
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
5 101520253035404550556065707580
Current Generator(A)
FY900 Controller Current Value(A)
Japan CTL-6-S
TAIE-1
TAIE-2
TAIE-3
TAIE-4
TAIE-5
44
13. Error codes
DISPLAY DESCRIPTION
Open circuit of main control sensor.(INP1)
A/D convert failed.
Cold junction compensation failed.
Open circuit of sub control sensor.(Remote SV)
PV exceeds USPL.
PV under LSPL.
Input signal of sub control exceeds the upper limit.
(Remote SV)
Input signal of sub control under the lower limit.
(Remote SV)
RAM failed.
Interface failed.
Auto tuning failed.
NOTEIf the “*” marked error comes upthe controller needs to be repaired.
Please send it to the nearest sales office or retail dealer.
FY400 TC_Pt100 Switch Jumper Site Plan
*Note : Please change the input type at the display menu when you finished the jumper switch.
1. Keep controller flat, LED display forwards
2. Pull out controllerjumper is below the CPU
3. Turn the Power board up
4. Sensor Input TC. Jumper insert the right site
5. Change Sensor input, pull the Jumper out
6. Sensor Input Pt100. Jumper insert the left site
CPU
Thermal couple
CPU
Jumper
K. J. R. S. B. E. N. T. W. PL. U. L.
Pt100
Pt100
TC
45 A
FY600/700/800/900 TC_Pt100 Switch Jumper Site Plan
*Note : Please change the input type at the display menu when you finished the jumper switch.
1. Keep controller flat, LED display forwards
2. Pull out controllerjumper is below the CPU
3. Turn the Power board up
4. Sensor Input TC. Jumper insert the right site
5. Change Sensor input, pull the Jumper out
6. Sensor Input Pt100. Jumper insert the left site
CPU
Jumper
TC
CPU
Thermal couple
K. J. R. S. B. E. N. T. W. PL. U. L.
Pt100
Pt100
TC
45 B
46
14.2 FU48~96
1. Take out the main body from outer case: adjust the jumper to the correct place.
2. Start power after setting jumper to the correct place.
3. Amend the input type from the front membrane to enter in Level 3 to set.
4. Please be sure to cut off power and start again after amending input type so that the
new parameters could be effective.
5. To change input type of TC or RTD is available but linear input is unavailable.
Please ask our local distributor for help.
14.3 FY100~FY101
If the controller needs to modify input type from TC or mV to RTD please make PAD
short on the back side of PC board as following diagram and change input selection(INP1). On the contrarymodify from RTD to TC or mVmake PAD open.
FY100
No short Pin is TC(mV)
47
RTD TC or mV
Short pin insert to left Short pin insert to right or remove
If the controller needs to modify input type from TC or mV to RTD please make PAD
short on the back side of PC board as following diagram and change input selection(INP1). On the contrarymodify from RTD to TC or mVmake PAD open.
FY101
TC or mV RTD
48
15. Modify input type : Linear Input (mA ,V)
15.1 FY400~900 & FU48~96 Hardware
FY900FY600FY800
FU86FU96
FY700
FU72
FY400
FU48
INPUT ( + )
PIN 17 PIN 11 PIN 7
INPUT ( - )
PIN 20 PIN 14 PIN 10
0~20mA (INP1=AN4)(R3 use 100R5 use 2.4 S3 S5 SHORT) 4~20mA (INP1=AN5)(R3 use 100R5 use 2.4 S3 S5 SHORT) 0 ~ 1V (INP1=AN4)(R1 use 2KR4 use 100S1 S4 SHORT) 0 ~ 5V (INP1=AN4)(R2 use 10KR4 use 100S2 S4 SHORT) 1 ~ 5V (INP1=AN5)(R2 use 10KR4 use 100S2 S4 SHORT) 0 ~ 10V (INP1=AN4)(R3 use 22KR4 use 100S3 S4 SHORT) 2 ~ 10V (INP1=AN5)(R3 use 22KR4 use 100S3 S4 SHORT)
49
15.2 FY100/101 Hardware
FY100 FY101
INPUT ( + )
PIN 14 PIN 10
INPUT ( - )
PIN 11 PIN 8
0~20mA (INP1=AN4)(R3 use 100R5 use 2.4 S3S5 SHORT) 4~20mA (INP1=AN5)(R3 use 100R5 use 2.4 S3S5 SHORT) 0 ~ 1V (INP1=AN4)(R1 use 2KR4 use 100S1S4 SHORT) 0 ~ 5V (INP1=AN4)(R2 use 10KR4 use 100S2S4 SHORT) 1 ~ 5V (INP1=AN5)(R2 use 10KR4 use 100S2S4 SHORT) 0 ~ 10V (INP1=AN4)(R3 use 22KR4 use 100S3S4 SHORT) 2 ~ 10V (INP1=AN5)(R3 use 22KR4 use 100S3S4 SHORT)
50
15.3 Calibration
SET 2.2 = 1
ANL1=0
ANH1=5000
LSPL=0
USPL=5000
Adjusts "ANL1" until PV Display = 0
Inputs 4mA
Inputs 20mA
Adjusts "ANH1" until PV Display = 5000
Inputs 4mA to CHECK LOW
Inputs 20mA to CHECK HIGH
OK ?
Set the range you want LOW =LSPL HIGH =USPL
ExLow = -20.0High = 50.0 SET LSPL = -20.0USPL = 50.0DP000.0
To display ANL1 & ANH1
at INPUT Level
Return User Level to view the changing of PV
YES
NO
51
16. Modify Output type: Relay, SSR, 4~20mA
It just needs to change a module at the same positionand modify parameter CYT1 in
LEVEL 2 .
ÎRelay: CYT1=10, Voltage pulse: CYT1=1, 4~20mA:CYT1=0
17. Modify output mode: OUT1/ALARM, OUT1/OUT2
12 13 14 15 16 17 18 19 20
( CPU Board )
96×9648×9696×48
11
PAD of AL3:SHORT
PAD of OUT2:OPEN
12 13 14 15 16 17 18 19 20
( CPU Board )
96×9648×9696×48
11
PAD of AL3:OPEN
PAD of OUT2
SHORT
8 9 10 11 12 13 14
( CPU Board )
6 7 8 9 10
( CPU Board )
48×48
72×72
PAD of OUT2 OPEN
PAD AL1 SHORT
8 9 10 11 12 13 14
( CPU Board )
72×72
PAD of OUT2 SHORT
PAD of AL1 OPEN
PAD of OUT2 OPEN
PAD of AL1 SHORT
6 7 8 9 10
( CPU Board )
48×48
PAD of OUT2 SHORT
PAD of AL1 OPEN
OUT1 / ALARM OUT1 /OUT2
FY600 , FY800 , FY900 FY600 , FY800 , FY900
FY700 FY700
FY400 FY400
52
18. Applications
18.1 RAMP & SOAK
z RAMP
I. SET2.1=1ÎTo display AL3
II. SET4.1=1ÎTo display ALD3
III. ALD3=9ÎOpen RAMP option
IV. Then, AL3 will not display. It was replaced by RAMP.
RAMP 0 0.0 0
Range00.00 ~ 99.99(/ min) (If RAMP is not usedplease set ALD3 to 0)
z SOAK
I. ALD1 / ALD2=19
Î To use Sock Timer.
II. AL1 / AL2 will display as below:
AL1
0 0 . 0 0
Range00.00 ~ 99.59(Hour.Minute)
z Example
SV=100RAMP=10.00 ( /min) ,AL1=00.10 min,PV=25
100
PV=25℃
5 seccons(Start RAMP function)
Time on
if PV > = SV(100℃)
Time up AL1 on
SV=PV (When start RAMP function)
SV=SV+RAMP
AL1
00.10
00.01
00.10
Sock Timer
counts
1sec.
Power on
53
18.2 TTL CommunicationSV output and RATE function
z Open RATE function (use for slave controller)
Display AL3 :SET2.1=1 Display ALD3:SET4.1=1
Display RATE(AL3 will be replaced)
:SET0.2=1
Set ALD3 to 0. (In Level 3)
Slave SV = (
RATE÷9999)×master SV
z Example
SD
SG
PFY900
Master
RD
SG
FY900
Slave 1
RD
SG
FY900
Slave 2
SV OUT (SET0.1=1) IDNO=0 (SET5.4=1) BAUD=2400(SET5.4=1)
IDNO=1 (SET5.4=1) BAUD=2400
(SET5.4=1) open RATE function
IDNO=1 (SET5.4=1) BAUD=2400
(SET5.4=1) open RATE function
Connection Diagram
Time Chart
Time
1 hour
1000
SV_1=1000 TM_1=01:00 OUT_1=100%
Time
1 hour
900
RATE = 9000 SV=900
Time
1 hour
800
RATE =8000 SV=800
( Three controllers reach to the max value at the same time )
SV
SV SV
Master Slave 1 Slave 2
54
18.3 1ψ Phase angle control (By SCR module)
z Available ModelsFY900 / PFY900FY700 / PFY700FY800 / PFY800
FY100 / PFY100
z OUT1: 1ψSCR phase angle control z Parameter setting OUTY=4
CLO1=0CHO1=4500 if use for resistance load CLO1=0CHO1=4000 if use for inductor load
Short
CONTROLLER
G 1
G 2
K 1
K 2
PROT
K1
K 2
G 1
S
R
G 2
FAST FUSE
UV
SCR
Module
** Controller source phase must be same as load source phase
LOAD
55
18.4 1ψ Phase angle control (By TRIAC)
z Available ModelsFY900 / PFY900FY700 / PFY700FY800 / PFY800
FY100 / PFY100
z OUT1: 1ψSCR phase angle control z Parameter setting OUTY=4
CLO1=0CHO1=4500 if use for resistance load CLO1=0CHO1=4000 if use for inductor load
Short
CONTROLLER
G1
G2
K1
K2
PROT
T1
G1
SR
FAST FUSE
UV
TRIAC
Module
T2
M
M
VU
1/2W
100Ω
0.1uf/630V
A C
** Controller source phase must be same as load source phase
LOAD
56
18.5 3ψ Phase angle control (By DIODE/SCR module)
z Available ModelsFY900 / PFY900 z OUT1: 3ψSCR phase angle control z Parameter setting OUTY=5
CLO1=0CHO1=4500 only if use for resistance load CLO1=0CHO1=4000 if use for inductor load
CONTROLLER
Short
K 1 G 1
K 2 G 2
K 3 G 3
TS
R
FAST FUSE
U
V
DIODE/SCR
Module
W
K 2
G 2
K 3
PROT
G 3
G 1
3φ LOAD
K 1
57
18.6 1ψZero crossing control (By SCR module)
z Available Models FY900 / PFY900FY700 / PFY700
FY400 / PFY400
z OUT1: 1ψSCR zero cross control z Parameter setting OUTY=0
CYT1=1
Short
G 2
CONTROLLER
G 1
G 2
PROT
R
S
G 1
FAST
FUSE
UV
SCR
Module
CYCLE TIME = 200 mSEC.
OFF
ON
TIME CHART:
58
18.7 1ψZero crossing control (By TRIAC)
z Available Models FY900 / PFY900FY700 / PFY700
FY400 / PFY400
z OUT1: 1ψSCR zero cross control z Data Change OUTY=0
CYT1=1
Short
Controller
G1
G2
PROT
T1
G1
S
R
UV
TRIAC
T2
Load
Fast Fuse
59
18.8 3ψZero crossing control (By SCR module)
z Available ModelsFY900 / PFY900 z OUT1: 3ψSCR zero cross control z Data Change OUTY=0
CYT1=1
RG 1
Short
CONTROLLER
WE CAN SUPPLY
HEATER SINK
RG 1
TG 1
RG 2
TG 2
PROT
TG 2
TG 1
S
R
FAST FUSE
U
V
SCR
Module
RG 2
T
W
CYCLE TIME = 200 mSEC.
OFF
ON
TIME CHART:
60
18.9 3ψZero crossing control (By TRIAC)
z Available ModelsFY900 / PFY900 z OUT1: 3ψSCR zero cross control z Data Change OUTY=0
CYT1=1
Short
Controller
(RG 1)
(TG 1)
(RG 2)
(TG 2)
PROT
S
R
U
V
T
W
Fast Fuse
T2
(TG 1)
G1
T1
(TG 2)
T2
G1
T1
(RG 1)
(RG 2)
61
18.10 3 wires proportional motor valve control
z Available Models FY900 / PFY900FY700 / PFY700
FY800 / PFY800FY600 / PFY600 FY400 / PFY400FY100 / PFY100
FY101 / PFY101
z Data Change OUTY=3
CYT1=1 ~ 100sec.
(Manufacturing default setting “5” seconds.)
RUCY=5 ~ 200 seconds.
After change “RUCY” the controller must be reset
1. CYT1 is the cycle time of Open / Close
2. RUCY is the 0 ~ 100% running time of motor valve
MOTOR VALVE
CONTROLLER
CLOSE
OPEN
COM
OPEN
CLOSE
COM
OUT1
Relay
OUT2 Relay
R
S
62
18.11 Wiring diagram of PC communication
PC
COM PORT :
9PIN
( DTE )
SD
SG
RD
Pin 3 (T)
Pin 2 (R)
Pin 5 (G)
RS232 Connection Diagram
PC
COM PORT :
25PIN
( DTE )
Pin 2 (T)
Pin 3 (R)
Pin 7 (G)
NOTE:
1.The length of cable be connected between controller and PC can't exceed 15 meter.
2.One Com Port can only be connected to one controller. If more than one controller is connected to one Com Port,communication will be failed.
3.Ensure that the controller's IDNO and BAUD settings are the same with PC software's settings.
4.For the software communication format please refer to communication manual.
SD
SG
RD
Controller
Controller
RS485 Connection Diagram
NOTE:
1.The length of cable be connected between Converter and Controller can't exceed 1.2 KM. Suggestion:choose "Shielded Cable".
2.One Com Port can be connected up to a maximum of 30 Controllers.
3.Ensure that the Controller's IDNO and BAUD settings are the same with PC software's settings.
4.For the software communication format ,please refer to communication manual.
PC
Com Port
(Cable)
Converter
DCE
TxON
RxO
N
Controller
1 2 3 4
DX +
DX -
(R-)
(T-)
(T+)
(R+)
Cable
63
19. Order Information
19.1 FA Series
64
Loading...