tae FM 2000 Instruction & Operation Manual

Page 1
Pikatron GmbH – division TAE Antriebstechnik – Raiffeisenstrasse 10 – 61250 Usingen – http://www.tae-antriebstechnik.de
EFM2000.DOC HS 03/98 V3.260298.GB.002 The german text applies in cases of doubt
Frequency Meter
Instruction- & Operation Manual
Caution:
As with any form of electrical equipment there is always a risk involved in the handling of electrical
machinery. The greatest care must always be exercised during installation and maintenance, and it
is recommended this be carried out by authorized personnel.
Page 2
Misprints as well as technic al changes reserved
EFM2000.DOC HS 03/98 V3.260298.GB.002
2
Table of contents
1.0 Technical Data ................................................................................................... 3
1.1 General information .................................................................................... 3
1.2 Frequency Meter ........................................................................................ 3
1.3 Period Time Meter ...................................................................................... 3
1.4 Impulse Counter ......................................................................................... 3
2.0 Drawing of Dimensions / Connect i ons ............................................................ 4
3.0 Test Mode ........................................................................................................... 6
4.0 Algorithmical Adjustments ............................................................................... 6
5.0 Multiplier Adjustment ........................................................................................ 7
6.0 Operating Mode / MODE Selection / Decimal Pl ace ........................................ 8
6.1 Operating Mode .......................................................................................... 8
6.2 MODE Selection ......................................................................................... 9
6.3 Decimal Point ........................................................................................... 13
7.0 Measurement Display ...................................................................................... 13
8.0 Example ............................................................................................................ 13
Manufactures Declaration ............................................................................... 14
Page 3
Misprints as well as technic al c hanges reserved
EFM2000.DOC HS 03/98 V3.260298.GB.002
3
1.0 Technical Data
1.1 General
Line voltage
refer to name plate
Power consumption
max. 6VA
Display
5 digits, 7-segment LED, decimal point, parameter display
Weight
approx. 400g
Dimensions
W 96 x H 48 x D 158 mm (including terminals)
Panel cut dimensions
W 92 x H 44mm
Installation position
horizontal
Spacing
min. 10mm
Ambient temperature
0 - 40°C
Input voltage
0 corresponds to 0V..4,5V
1 corresponds to 6V...20V
max. voltage = 32V
1.2 Frequency meter
Input frequency
0 to 100kHz
Accuracy
0,01% ± 1 digit
1.3 Periode time meter
Input frequency
0,1 to 100Hz
Accuracy
0,1% ± 1 Digit
1.4 Impulse counter
Input frequency
0 to 100kHz
Page 4
Misprints as well as technic al changes reserved
EFM2000.DOC HS 03/98 V3.260298.GB.002
4
2.0 Dimensions / Connections
Terminal 1 - Line voltage (L1) Terminal 2 - Line voltage (N) Terminal 3 - Input measuring sig nal ( ⊥) Terminal 4 - Input measuring sig nal (+ )
Page 5
Misprints as well as technic al c hanges reserved
EFM2000.DOC HS 03/98 V3.260298.GB.002
5
Pikatron GmbH
division TAE Antriebstechnik
Raiffeisenstrasse 10
D-61250 Usingen Tel.: -49/ 6081 583 445 Fax: -49/ 6081 583 123
MANUFACTURERS DECLARATION
The EMC-law of November 9th 1992 concerning the electromagnetic compatibility with reference to the EMC-directive EMCD 89/336/EWG is a national law. This directive distinguishes between two criteria: product components and product distribution.
According to these criteria our products are classified as follows:
-Product components: parts from suppliers which are inoperative on their own.
-Product distribution: not commonly available, sold to qualified persons. The law states, that an EG-declaration of conformity as well as a CE-marking is not requested for
such components.
In order to meet the requirements of the EMC-directive we supply the following:
- Product related documents which describe the interference radiation of our products. This information will enable the user to provide all necessary steps to meet the EMC- requirements during planning and installation.
- EMC-specific components such as filters, chokes, shielded wiring, metal enclosures and others are available from TAE. TAE will furthermore provide specific technical information concerning the proper use of such components for their products in order to meet the requirements of the harmonised standards.
It is the users responsibility to carry out our instrutions and to induce adequate provisions. The user is also responsible that his machine and installation meets the requirements of the EMC-standards.
Based on the EMC-law and its corresponding standards we have carried out extensive measurements at our premises. These tests have included our complete product line. With the use of
filters and proper wiring all our products meet the requirements of standard EN 50081-2 (sweep radiation) and standard EN 55011 class A for industrial use.
The extent of the necessary modification depends on the individual product line. Our pamphlet "TAE PRODUCTS AND EMC" provides information of the minimum requirements for our products in order
to meet the standard EN 50081-2. Our "GUIDE LINES FOR EMC-CONFORMAL INSTALLATION" provide information for a properly and EMC-conformal installation.
These guidelines and recommendation for the use of electronic equipment are based on the following standards:
DIN EN-50178 (VDE 0160:1994-11) Electronic equipment for use in electrical power installations DIN VDE 0100 Erection of power installations DIN VDE 0110 Dimensioni ng of cl earance and c reepage distances DIN 40050 IP-Protections DIN 50081/50082 EMC Basic Standards
Page 6
Misprints as well as technic al changes reserved
EFM2000.DOC HS 03/98 V3.260298.GB.002
6
3.0 Test Mode
Figure 1: Front view of the Frequency Meter FM 2000
In order to start the test mode of the FM 2000 key T1 must be pressed and be held while key T2 is pressed at the s am e t im e. Not e: The test mode cannot be started during the configuration function.
During the test mode all display functions are individually tested and each single digital display will show one after the other the numbers 0 to 9 and the decimal point.
4.0 Algorithmical Adjustments
The Frequency Meter FM 2000 is being configurated with two keys T1 and T2 and with the parameter counter P.
The algorithmical adjustment is act ivated by pressing key T2. T he parameter count er P will now indicate the number 1 and the decimal point of the parameter count er will also light up. This indicates that the paramet er counter can be increased by a repeated pressing of k ey T2. The other f ive digital display units will show the value which has been recalled by the parameter counter P.
P
T1
lights up
T2
Figure 2: Display of the paramter counter during the algorithmical adjustment.
Page 7
Misprints as well as technic al c hanges reserved
EFM2000.DOC HS 03/98 V3.260298.GB.002
7
In order to change the indicated paramet er the decimal point must be moved to the individual display unit by pressing key T1. The indicated number of this display can now be altered by pressing key T2.
If key T1 is pressed again the system retur ns t o the parameter counter P. Pressing now key T2 again will increase the parameter counter to the next parameter. At
the end of the algorithmical adjustment the parameter counter will return to t he opterating mode and the new values of the parameters are stored. The FM 2000 will now operate with the set new parameters.
NOTE: This newly set parameter cannot be cancelled if t he line voltage is int er r upt ed! All parameters can be changed as often as r equested and any parameter which is not to
be changed can be scipped with the parameter counter by selecting t he next par am et er .
5.0 Multiplier Adjustment
When the param et er c ount er P shows the number 1 it is possible to set a multiplier for the actual measuring value. The standard value is 01000.
This standard value corresponds to the multiplier 1.0. I f for instance the fac t or 0.5 is requested the parameter mus t then be adjusted to 00500.
P
T1
lights up
T2
Figure 3: Display of the FM 2000 for multiplier adjustment
The requested segments ( 1 t o 5) c an be activated with key T1. The decimal point of the activated segment lights up. The figures can now be selected with key T2. Activating key T1 will return the system to the parameter counter P after the parameter 1 has been completely adjusted.
Page 8
Misprints as well as technic al changes reserved
EFM2000.DOC HS 03/98 V3.260298.GB.002
8
6.0 Operating Mode / MODE Selection / Decimal Place
The operating mode, the mode select ion and t he decim al place can be adj usted by setting the parameter counter to number 2.
P
T1
l
ig
h
ts
up
T2
Figure 4: Display of the parameter counter for setting the Operating Mode / MODE
Selection and Decimal Place
6.1 Operating Mode
The Frequency Meter FM 2000 offers a selection between three operat ing modes:
• Frequency Meter
• Period time Meter
• Impulse Counter The first digit display (right side) indicates t he oper ating mode when the parameter
coungter is set to number 2:
0: Frequency Meter The operating mode is set
for frequency measurement
1: Periode Time Met er The operating mode is set
for measuring the period time (very exactly frequency display in the range of 0,1 to 100Hz)
2: Impulse Counter
Page 9
Misprints as well as technic al c hanges reserved
EFM2000.DOC HS 03/98 V3.260298.GB.002
9
The operating mode is set for impulse counting
Procedure: a) Paramet er counter is set to number 2 b) Activate with key T1 the first digit display c) Select with key T2 one of the above mentioned modes d) After complete set t ing of parameter 2 return t he parameter counter by pressing key T1 again.
6.2 MODE Selection
The FM 2000 offers the selection between seven diff er ent MODES in order to adapt the display of the measured values to the individual requirements. The selected MODE applies to the display only and is independent from the selected multiplier. The following MODE selection is indicated in the parameter 2 on the second digit segment (second from rig ht ) and refers to the operating m odes: frequency meter and period-t im e m et er :
MODE 0: Standard display ( no changes) This mode provides the display of the measured value without any change.
example:
operating mode 0
Frequency meter
operating mode 1
Period time meter
Frequency to be measured
567,8Hz
67,358Hz
Display indicates
567
6735
MODE 1: last digit shows 0 This mode is used if the measuring pr ocedur e with 10 times m easuring accuracy is too
slow and the flickering of the last digit should be eliminated.
example:
operating mode 0
Frequency meter
operating mode 1
Period Time meter
Frequency to be measured
567,8Hz
67,358Hz
Display indicates
560
6730
MODE 2: 10-times measuring ac cur ac y
Page 10
Misprints as well as technic al changes reserved
EFM2000.DOC HS 03/98 V3.260298.GB.002
10
The FM 2000 offers a new measuring method which allows to measure with a 10-times accuracy without a substandial increase of the measuring t ime. However the last two digits will need about 10 seconds before the correct value is indicated.
example:
operating mode 0
Frequency meter
operating mode 1
Period Time meter
Frequency to be measured
567,8Hz
67,358Hz
Display indicates
5678
67358
MODE 3: Shifting of the display with additional 0 For lower frequencies it may become necessary to abtain a larg er indicat ion on t he display
without the delay of 10 seconds for the measuring t im e. In this case the display is shifted one digit to the left and a zero is added at the end.
example:
operating mode 0
Frequency meter
operating mode 1
Period Time meter
Frequency to be measured
567,8Hz
67,358Hz
Display indicates
5670
67350
MODE 4: Steady Display Due to different measuring methods most instruments show a flickering of the last digit in
their display.The measuring method of m ode 4 is t he s am e as it is used for mode 2 but with the intention to eliminate the flicker ing of the last digit.
example:
operating mode 0
Frequency meter
operating mode 1
Period Time meter
Frequency to be measured
567,8Hz
67,358Hz
Display indicates
567
6735
Page 11
Misprints as well as technic al c hanges reserved
EFM2000.DOC HS 03/98 V3.260298.GB.002
11
MODE 5: Steady display, Indication is shifted 1 digit to the right. The indication on the display is shifted 1 digit to the r ig ht.
example:
operating mode 0
Frequency meter
operating mode 1
Period Time meter
Frequency to be measured
567,8Hz
67,358Hz
Display indicates
56
673
MODE 6: Steady display. Indication is shifted two digits t o the right. example:
operating mode 0
Frequency meter
operating mode 1
Period Time meter
Frequency to be measured
567,8Hz
67,358Hz
Display indicates
5
67
The assignment for t he m ode selection in the operating mode 2 ''Impulse Counter '' is as follows:
The shown examples relate to 1234 counted pulses.
MODE 0: Indication without any change
MODE-selection Display indication MODE 1: Additional zero on the last digit
MODE-selection Display indication
Page 12
Misprints as well as technic al changes reserved
EFM2000.DOC HS 03/98 V3.260298.GB.002
12
MODE 2: is not used
MODE 3: Shift of t he indicat ion one dig it t o t he left and addition of one zero
MODE-selection Display indication
MODE 4: is not used
MODE 5: Shift of t he indicat ion one dig it t o t he right
MODE-selection Display indication
MODE 6: Shift of t he indicat ion t wo digit t o t he r ight MODE-selection Display indication
The segment 2 can be activated with key T1. T he dec imal point of the activated segment lights up. The place of the MODE can now be selected with key T2. Activating key T1 will return the system to the paramet er c ount er P after the parameter 2 has been com plet ely adjusted.
Page 13
Misprints as well as technic al c hanges reserved
EFM2000.DOC HS 03/98 V3.260298.GB.002
13
6.3 Decimal Point
The decimal point can be placed on four different positions of the display. Number 3 of the parameter 2 shows the position of the decimal point:
Example:
Indication 3 of parameter 2
Display indication
0
12345 (no point)
1
1234.5
2
123.45
3
12.345
4
1.2345
The requested segment c an be act ivated with key T1. The decimal point of the activated segment lights up. The place of the decimal point can now be selected with key T2. Activating key T1 will return the system to the param eter counter P after the par am et er 2 has been completely adjusted.
7.0 Measurement Display
In the operating conditon it is possible to measure the input frequency to the FM 2000 without reference to the preset mult iplier by keeping the key T1 pressed.
8.0 Example
This example refers to the connection of the FM 2000 to the DC-Brushless-Control Series ''TA-BL...'' from TAE and can serve as a sample for any other application. The speed (rpm ) of the brushless motor is to be indicated on t he FM 2000 by using the frequency output.
Assumption: The output frequency of t he c ont r ol is t wice as high as the motor speed. Adjustment: The above mentioned assumption requires a multiplication fact or at 0,5.
As previously indicated under point 3 the parameter 1 must be set to 00500. The parameter 2 should be adjusted for 000, that m eans the operating mode, the mode selection and the place of the decimal point are set to 0.
The result from these adj us t m ents is that for instance for an output frequency of 3456Hz the display will indicate 1728 which corresponds to the actual motor speed.