Tadiran Telecom TAD2U18MOU, TAD4U36MOU, TAD3U24MOU Installation Manual

Installation Manual
Ductless Multi Zone with Highwall Indoor Unit
Design may vary by model number.
TABLE OF CONTENTS
IMPORTANT SAFETY INFORMATION .................................................................................4
INSTALLATION INSTRUCTIONS ......................................................................................6
Step 1 ...........................................................................................................9
Step 2 ..........................................................................................................11
Step 3 ..........................................................................................................13
Step 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
LIMITED WARRANTY .............................................................................................. 18
OPERATING RANGE
The following information lists the operating range specific to each model.
TAD2U18MOU / TAD3U24MOU / TAD4U36MOU
Cooling: 14F -115F Heating: 5F-75F
ENGLISH
NOTES:
When the outdoor temperature drops below -22°F
(-30°C), the unit will stop running. The unit will turn back on automatically when the temperature rises above the lowest limit.
It is recommended to have a secondary heating source(s)
available in case the temperature drops below the operating range.
RECORD KEEPING
Thank you for purchasing this Haier product. This installation manual will help you get the best performance from your new heat pump.
Staple your proof of purchase to this manual to aid in obtaining warranty service if needed.
_______________________________________ Model number
_______________________________________ Serial number
_______________________________________ Date of purchase
31-5000001 Rev. 1
3
ENGLISH
IMPORTANT SAFETY INFORMATION
WARNING
electric shock, or personal injury.
• Use this equipment only for its intended purpose as described in this manual.
• This heat pump must be properly installed in accordance with these instructions before it is used.
• All wiring should be rated for the amperage value listed on the rating plate. Use only copper wiring.
• All electrical work must be completed by a qualified electrician and completed in accordance with local and national building codes.
• Any servicing must be performed by a qualified individual.
WARNING
• An adequate ground is essential before connecting the power supply.
• Disconnect all connected electric power supplies before servicing.
For your safety, the information in this manual must be followed to minimize the risk of fire,
RISK OF ELECTRIC SHOCK. Could cause injury or death.
For any service which requires entry into the refrigerant sealed system, Federal regulations require that the work is performed by a technician having a Class II or Universal certification.
• All air conditioners contain refrigerants, which under federal law must be removed prior to product disposal. If you are getting rid of an old product with refrigerants, check with the company handling disposal.
• These R-410A heat pumps systems require that contractors and technicians use tools, equipment and safety standards approved for use with this refrigerant. DO NOT use equipment certified for R22 refrigerant only.
• Repair or replace immediately all electrical wiring that has become frayed or otherwise damaged. Do not use wiring that shows cracks or abrasion damage along its length or at either end.
WARNING
Do not store or use combustible materials, gasoline or other flammable vapors or liquids in the vicinity of this or any other appliance.
RISK OF FIRE. Could cause injury or death.
WARNING
This appliance is not intended for use by persons (including children) with reduced physical,Sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.
To avoid danger of suffocation, keep the plastic bag or thin film used as the packaging material away from young children.
Be careful that foreign matter (oil, water, etc.) does not enter the piping than with refrigerant models. Also, when storing the piping, securely seal the openings by pinching, taping, etc.
For installation purposes, be sure to use the parts supplied by the manufacturer or other prescribed parts. The use of non-prescribed parts can cause serious accidents such as the unit falling, water leakage, electric shock, or fire.
The rated voltage of this product is 208/230 V A.C. 60 Hz. Before turning on verify that the voltage is within the 187
V to 264 V range. Always use a special branch circuit and install a special
receptacle to supply power to the air conditioner. Use a special branch circuit breaker and receptacle
matched to the capacity of the air conditioner. (Install in accordance with standard.)
Do not extend the power cord. Perform wiring work in accordance with standards so that
the air conditioner can be operated safely and positively. Install a leakage special branch circuit breaker in
accordance with the related laws and regulations and electric company standards.
4
31-5000001 Rev. 1
CAUTION
CAUTION
IMPORTANT SAFETY INFORMATION
Use pipes that have clean external and intermal sides
It is highly recommended that you do not open or close the stop valves when the outdoor temperature is below
-5°F (-21°C) as this may cause refrigerant leakage. After a long period of disuse in an environment 32 °F (0° C)
or lower, supply power to the unit at least 12 hours before re-starting the unit.
Do not touch the fins of the heat exchanger. Touching the heat exchanger fins could result in damage to the fins or personal injury such as skin rupture.
The power source capacity must be the sum of the air conditioner current and the current of other electrical appliances. When the current contracted capacity is insufficient, change the contracted capacity.
When the voltage is low and it is difficult to start the air conditioner, contact the power company to have the voltage raised.
Be sure to install a breaker of the specified capacity. Regulation of cables and breaker differs from each
locality, refer in accordance with local rules. Do not use existing pipes.
without any contamination which may cause trouble during use, such an sulphur, oxide, dust, cutting waste, oil, or water.
It is necessary to use seamless copper pipes. Material: Phosphor deoxidized seamless copper pipes. It is desirable that the amount of residual oil is less than 40 mg/10 m.
Do not use copper pipes that have a collapsed, deformed, or discolored portion (especially on the interior surface). Otherwise, the expansion valve or capillary tube may become blocked with contaminants.
Improper pipe selection will dearade performance. As an air conditioner using R410A incurs pressure higher than when using conventional refrigerant, it is necessary to choose adequate materials.
To prevent breaking of the pipe, avoid sharp bends. Bend the pipe with a radius of curvature of 4 in. (100 mm ) or more.
If the pipe is bent repeatedly at the same place, it will break.
ENGLISH
READ AND SAVE THESE INSTRUCTIONS
FOR MORE HELP, VISIT HAIERAPPLIANCES.COM OR CALL THE CONSUMER HELP LINE AT 877-337-3639.
BEFORE YOU BEGIN
Read these instructions completely and carefully.
IMPORTANT – Save these instructions
for local inspector’s use.
IMPORTANT – Observe all governing
codes and ordinances.
• Note to installer – Be sure to leave these instructions
with the Consumer.
• Note to consumer – Keep these instructions for
future reference.
• Skill level – A licensed certified technician (to handle
refrigerant R-410A, recovery, etc) and a qualified electrician are required for installation and service of this split heat pump system.
• Proper installation is the responsibility of the installer.
• Product failure due to improper installation is not covered under the limited warranty.
• For personal safety, this system must be properly grounded.
• Protective devices (fuses or circuit breakers) acceptable for installation are specified on the nameplate of each unit.
• Make sure to avoid wiring or plumbing inside the wall when installing.
• Aluminum building wiring may present special problems - consult a qualified electrician.
• When the unit is in the STOP position, there is still voltage to the electrical controls.
31-5000001 Rev. 1
5
ENGLISH
INSTALLATION INSTRUCTIONS
Required Tools for Installation
• 14/4 AWG stranded wire
• 5/8” (16mm), 7/8” (22mm), 1” (25mm) or Adjustable Wrench
• R-410A Refrigerant*
• Adhesive tape*
• Conduit cable clamp 1/2”*
• Copper line set (for size, see table on page 15)
• #2 phillips screwdriver
• Drill
• R-410A flaring tool
• Hex wrench
• Hole saw 2 1/4”
• Insulation*
• Refrigerant scale
• Level
• Manifold gauge set
• Measuring tape
• Micron gauge
• Mini-split adapter (5/16”F to 1/4”M)
• Nitrogen*
• Pipe cutter
• PVC pipe
• Razor knife
• Reamer
• Saddle clamp (L.S.) w/ screws
• Sealant, non-expanding (for lineset hole)
• Soap/water solution* or gas leakage detector
• Stud finder
• Torque wrench
• Vacuum pump
• Wire strippers
• All usual and customary HVAC hand and power tools, meters, and testing devices
* consumable
6
31-5000001 Rev. 1
INSTALLATION INSTRUCTIONS
COMPATIBILITY MATRIX FOR MULTI ZONE DUCTLESS SYSYTEM
FlexFit Mult
Outdoor Indoor
Model Rated
TAD2U18MOU
TAD3U24MOU
( * ) For 3U24EH2VHA, please follow these combinations.
Capacity (BTUh)
18K
24K
No. of Zones
TWO
TWO
THREE
Total Indoor Capacity
Unit B Unit A 14K 7K 7K 16K 9K 7K 19K 12K 7K 18K 9K 9K 21K 12K 9K 24K 12K 12K
Unit C Unit B Unit A *14K 7K 7K --­*16K 9K 7K --­*19K 12K 7K --­*25K 18K 7K --­*18K 9K 9K --­*21K 12K 9K --­*27K 18K 9K --­*24K 12K 12K --­*30K 18K 12K --­*21K 7K 7K 7K *23K 9K 7K 7K *26K 12K 7K 7K 32K 18K 7K 7K *25K 9K 9K 7K *28K 12K 9K 7K 31K 12K 12K 7K *27K 9K 9K 9K *30K 12K 9K 9K 33K 12K 12K 9K
TAD4U36MOU
FlexFit Mult (table continued)
TWO
THREE
36K
FOUR
ENGLISH
Unit D Unit C Unit B Unit A 31K 24K 7K --- --­27K 18K 9K --- --­33K 24K 9K --- --­30K 18K 12K --- --­36K 24K 12K --- --­36K 18K 18K --- --­42K 18K 24K --- --­48K 24K 24K --- --­32K 18K 7K 7K --­38K 24K 7K 7K --­28K 12K 9K 7K --­34K 18K 9K 7K --­40K 24K 9K 7K --­31K 12K 12K 7K --­37K 18K 12K 7K --­43K 24K 12K 7K --­27K 9K 9K 9K --­30K 12K 9K 9K --­36K 18K 9K 9K --­42K 24K 9K 9K --­33K 12K 12K 9K --­39K 18K 12K 9K --­45K 24K 12K 9K --­36K 12K 12K 12K --­42K 18K 12K 12K --­48K 24K 12K 12K --­48K 18K 18K 12K --­28K 7K 7K 7K 7K 30K 9K 7K 7K 7K 33K 12K 7K 7K 7K 39K 18K 7K 7K 7K 45K 24K 7K 7K 7K 32K 9K 9K 7K 7K 35K 12K 9K 7K 7K 41K 18K 9K 7K 7K 47K 24K 9K 7K 7K 38K 12K 12K 7K 7K 44K 18K 12K 7K 7K 34K 9K 9K 9K 7K 37K 12K 9K 9K 7K 43K 18K 9K 9K 7K 40K 12K 12K 9K 7K 43K 12K 12K 12K 7K 36K 9K 9K 9K 9K 39K 12K 9K 9K 9K 42K 12K 12K 9K 9K 48K 18K 12K 9K 9K 45K 12K 12K 12K 9K 48K 12K 12K 12K 12K
31-5000001 Rev. 1
7
ENGLISH
Sea
Protection walls
INSTALLATION INSTRUCTIONS
INDOOR CLEARANCES
(Appearance may vary)
This picture is for reference only. Your product may look different.
More than 4 inches
More than 4 inches
Wrap the insulation pipe with
the �nishing tape from the bottom to top.
Cut thermal insulation pipe to an
appropriate length and wrap it with
tape, making sure that no gap is left in the insulation pipe’s cut line.
Arrangement of
piping directions
Rear left
Left
Below
Condensate piping
must have a
downward slope of at least 1/4" per foot for
proper drainage.
Rear right Right
SALTWATER COAST INSTALL
• The outdoor unit should be installed at least ½ mile away from the salt water, including seacoasts and inland waterways. If the unit installed from ½ mile to 5 miles away from the salt water, including seacoasts and inland waterways, please follow the installation instruction below.
• Install the outdoor unit in a place (such as near buildings etc.) where it can be protected from sea breeze which can damage the outdoor unit.
ODU
Sea breeze
Sea
ODU
• If you cannot avoid installing the outdoor unit by the seashore, construct a protection wall around it to block the sea breeze.
• A protection wall should be constructed with a solid material to block the sea breeze. The height and the width of the wall should be 1.5 times larger than the size of the outdoor unit. Also, allow at least 28” (700mm) between the protection wall and the outdoor unit for air circulation to ventilate.
• Install the outdoor unit in a place where water can drain.
• If the above conditions cannot be met, contact for assistance.
Sea breeze
ODU
Sea
ODU
Sea breeze
ODU
8
31-5000001 Rev. 1
INSTALLATION INSTRUCTIONS
Step 1 - Preparation
Outdoor Unit Clearances
NOTE: If there is danger that the unit will fall or turn over,
fix the unit by inserting bolts, wire or other foundation options. NOTE: Place the unit on a level mounting base (or a plastic pedestal) for proper drainage.
(3) Installation and maintenance space
Selection of installation location of outdoor
ENGLISH
NOTE: Install the outdoor unit in a level position. Failure to do so may result in water leakage or accumulation.
8
Select the Outdoor location:
• Choose a level place solid enough to bear the weight and vibration of the OD unit and where the operation noise will not be amplified.
• Choose a location where the hot air discharge and/or noise will not create a nuisance for neighbors.
• Ensure there is sufficient space to maneuver the OD unit into place.
• Ensure there is sufficient space and no obstructions for the air inlet and outlet.
31-5000001 Rev. 1
• I nstall the unit’s power/communication wiring at least 10 feet away from television and radio sets to prevent interference.
• Ensure any moisture sensitive items are kept away from the
condensate drain path of the OD unit.
• Choose a location not affected by heavy snowfall or wind.
• To prevent wind exposure, install a wind baffle.
9
ENGLISH
INSTALLATION INSTRUCTIONS
Step 1 - Preparation Cont.
NOTES:
• OD unit cannot hang from a ceiling or be stacked.
• If installing the OD unit with a fence or rail guard around it, ensure that accumulated snow, debris, etc… will not block the air inlet or the coil exchanger.
• Ensure ventilation in case of refrigerant leakage. R-410A is a safe, nontoxic, and nonflammable refrigerant.
• Avoid installing the OD unit where corrosive gases, such as sulfur oxides, ammonia, and sulfurous gas are produced. If unavoidable, consult with an installation specialist about using a corrosion-proof or anti-rust additive to protect the unit coils.
• Do not install the outdoor unit near the edge of a balcony. Otherwise, children may climb onto the outdoor unit and fall off of the balcony.
• Do not install the outdoor unit in thw following areas: Area filled with mineral oil or containing a large amout of splashed oil or steam, such as a kitchen. It will deterorate plastic partic parts, causing the parts to fail or the unit to leak water.
• Area that can cause combustible gas to ledk, contains suspended carbon fibers or flammable dust, or volatile inflammables such as pain thinner or gasoline. If gas leaks and settles around the unit, it can cause a fire.
• Area where small animals may live. It may cause failure, smoke or fire if small animals enter and touch inernal electrical parts.
• Area where animals may urinate on the unit or ammonia may be generated.
• If the outdoor unit must be installed in an area within easy reach of the general public,Install as necessary a protective fence or the like to prevent their access.
• If the outdoor unit is installed in a cold region that is affected by snow accumulation, snow fall, or freezing, take
appropriate measures to protect it from those elements. To ensure a stable operating, install inlet and outlet ducts.
• Make sure the outdoor unit is installed level and is stable. Install snow protection hood as necessary.
• Avoid salty places such as the seaside for installation where air conditioner trouble is liable to occur.
• Install the outdoor unit in a location that is away from exhaust or the vent ports that discharge vapor, soot, dust, or debris.
• Install the unit where it will not be tilted by more than 3°. However, do not install the unit with it tilted towards the side containing the compressor.
• When installing the outdoor unit where it may exposed to strong wind, fasten it securely.
• It is recommended that unit be installed under a canopy or elevated on a high stand.
• In places where the outdoor temperature drops to 32°F (0°C) or lower, the drain water may freeze and may stop up the drain or cause other outdoor unit trouble. Therefore take measures so that the drain water will not freeze and clog the drain.
• Please set up the outdoor unit in a high place and pleade do not arrange the frame of installed stand under the drain port, because the water dropped from the drain port repeats freezing and accumulating, and may block the drain port.
• Do not use mineral oil on a flaredf part. Precent mineral oil from getting into the syetem as this would reduce the lifetiome of the units.
• While welding the pipes, be sure to blow dry nitrogen gas through them.
• The maximum lengths of this product are shown in the table. If the units are further apart than this , correct operation cannot be guaranteed.
Step 2 - Installation of the Indoor Unit
A. Select the Indoor location:
• Do not allow any heat or steam near the unit.
• Select a location where there are no obstacles in front of the unit.
• Make sure that condensate drainage can be conveniently routed away.
• Do not install near a doorway.
• Ensure that the space around the left and right of the unit is more than 4”. The unit should be installed as high on the wall as possible but allow a minimum of 4” from the ceiling.
• Use a stud finder to locate and mark stud locations for mounting and to prevent unnecessary damage to the wall.
• Install in a location that is strong enough to withstand the full weight and vibration of the unit.
• Leave enough space to allow access for routine maintenance.
• Select a location that gives easy access to removing and cleaning air filters.
• Install in a location that is 3 ft. or more away from other electrical appliances, such as televisions and audio devices.
10
B. Install the Mounting Plate
• Remove plastic bag, tape, and mounting plate from the back of the indoor unit.
• Place the mounting plate on the wall in the desired location taking into account the minimum clearances necessary for proper operation.
• Using a level, verify that the mounting plate is horizontal and mark the screw locations.
• Attach the mounting plate to the wall with the supplied screws.
• If not able to align all screw holes with studs, wall anchors are supplied.
• Be sure that the mounting plate has been attached firmly and that applied weight is evenly distributed by each screw. (At least one screw in wall stud, others can use wall anchors.)
• The piping for the indoor unit may be routed to and from the unit in one of several directions: left, left rear, right, right rear, or right below. See Illustration on page 7.
31-5000001 Rev. 1
Outdoor unit
Power Wiring
3
2
1
)
(N)
(L
)
(
C
2
1
)
(
N
)
(
L
Indoor unit
Control Wiring
4 Wire - 14 AWG
Stranded
1 2 3
=White =Black =Red =Green
Sugested Colors
Strain Relief
Brackets
INSTALLATION INSTRUCTIONS
Step 2 - Installation of the Indoor Unit (Cont.)
C. Install the Tubing
• Always use new clean copper tubing. Never reuse tubing if replacing an existing system.
• Measure and mark the location where the piping hole is to be drilled.
• If pipe location will be on the left side of the unit, follow these steps to move the drain pipe.
1. Remove the stopper in the left drain hole and
knockout the molded plug inside the port.
2. Transfer the corrugate drain hose from the right side
to the left side.
3. Insert stopper into right side drain port. Using soap
as a lubricant and a small screwdriver will allow for easier seating of the stopper.
• Drill the lineset hole using a 2 1/4” hole saw. Angle the drill with a downward pitch to the outside wall so that the outside wall hole will be at least a ¼” lower than the inside hole. This allows for proper drainage of condensate.
• Install the lineset hole flange at the hole opening on the inside wall.
NOTE: The flange is prescored. It may be necessary to modify the flange to fit properly behind the wall unit housing.
D. Electrical Connections for the Indoor Unit
NOTE: Be certain all wiring complies with local building
codes and NEC and that the supply voltage for this system is correct.
• Place the indoor unit on a solid work surface before making electrical connections.
• To make the electrical connections for the indoor unit, both the outer plastic and inner galvanized steel cover plate must be removed.
• Raise the front cover to access the screws for removing these covers.
• Rout the 14/4 AWG wiring through the slot in the back of the unit and into the front access panel.
ENGLISH
E. Mount Indoor Unit to Mounting Plate
• Bundle the refrigerant piping, drain piping, and wiring with tape and carefully rout the bundle through the piping hole.
• With the top of the indoor unit closer to the wall, hang the indoor unit on the upper hooks of the mounting plate. Slide the unit slightly side to side to verify proper placement.
• Rotate the lower portion of the indoor unit to the mounting plate, and lower the unit onto the lower hooks of the mounting plate. (see illustration)
• Verify the unit is secured and flush to the wall.
• Indoor Unit installation is finished at this time.
mounting plate
F. Condensate Drainage Pipe
• Verify the condensate drain line has a constant pitch downward for proper water flow. There should be no kinks or rises in the tubing which may cause a trapping effect of the water (see illustration).
Optional: Can use PVC pipe by connecting a 1” ID
PVC pipe to the drain line coming out of the wall and running to desired location.
31-5000001 Rev. 1
• Using a wire stripper, remove the insulation and separate the 4 wires.
• Make wiring connections at each terminal according to wiring diagram. (Take note of the color of the wire at each terminal and ensure the wires are connected to the outdoor unit accordingly.)
• Ensure each wire is under the screw terminal plate and the plate is tightened.
• Ensure the 14/4 cable is secured under the strain relief bracket.
• After the terminal block wiring is completed, replace both cover plates and lower the front casing.
Less than
5cm
It becomes
high midway.
The end is imm­ersed in water.
It waves.
The gap with the
ground is too small
There is the bad smell from a sewer
G. To Remove the Indoor Unit
• Slightly raise the entire unit.
• Pull the lower portion of the unit off the lower hooks and pull slightly away from the wall.
• Lift the upper portion of the unit off the upper hooks.
11
ENGLISH
35
N
1.84in (46mm)
0.236in (6mm)
Ø 2 1/4in (57mm)
3.150in (80mm)
1.85in (47mm)
35 T
Ø 2 1/4in (57mm)
INSTALLATION INSTRUCTIONS
Wall Brackets
2.795in (71mm) Ø 2 1/4in (57mm)
0.472in (12mm)
40 N
50 N
50 T
100 N
4.961in (126 mm) Ø 2 1/4in (57mm)
1.417in (36mm)
5.906in (150mm) Ø 2 1/4in (57mm)
1.417in (36mm)
4.961in (126mm) Ø 2 1/4in (57mm)
1.614in (41mm)
70 T
70 N
4.882in (124mm) Ø 2 1/4in (57mm)
1.417in (36mm)
4.882in (124mm) Ø 2 1/4in (57mm)
1.614in (41mm)
Capacity (BTUh) Bracket Style Part Number Factory Reference Number 07K/09K/12K 35N/35T/40N WJ65X23038/WJ65X23240/WJ65X23038 10101275/10103071/10101275 15K/18K 50N/50T/70N WJ65X23251/WJ65X23251/WJ65X23056 10102598/10102598/10102740 24K 70N/70T WJ65X23056/WJ65X23056 10102740/10102740 30K/36K 100N WJ65X22785 10103059
12
31-5000001 Rev. 1
INSTALLATION INSTRUCTIONS
Step 3 - Installation of the Outdoor Unit
A. Prepare the Outdoor Unit for Installation
• Remove all packaging.
• Place supplied vibration pads onto outdoor unit’s feet.
• Place the unit on a solid foundation, 8” above
the average snowfall.
ENGLISH
B Attaching Drain Elbow to Outdoor Unit
• If required, attach the supplied drain elbow to the outdoor unit. Connect extension piping as needed (not supplied). (see illustration)
NOTE: The drain elbow is designed with an air gap and will not sit flush to bottom of the outdoor unit.
NOTE: Arctic Multi models will not use a drain elbow. If condensate management is required by code, a 3rd party pan is needed.
31-5000001 Rev. 1
13
ENGLISH
Outdoor unit
Power Wiring
3
2
1
)
(N)
(L
)
(
C
3
2
1
)
(N)
(L
)
(
C
Indoor unit 2
Control Wiring
4 Wire - 14 AWG
Stranded
To Service Disconnect
1 2 3
=White =Black =Red =Green
Sugested Colors
230 Volt Supply. 1 to L1, 2 to L2.
Indoor unit 1
2
1
)
(
N
)
(
L
Strain Relief
Brackets
INSTALLATION INSTRUCTIONS
Step 3 - Installation of the Outdoor Unit (Cont.)
C. Electrical Connections for the Outdoor Unit
• Using a wire stripper, remove the insulation and separate the wires.
WARNING
RISK OF ELECTRIC SHOCK.
Could cause injury or death. Make sure power is off before touching wires.
NOTE: Be certain all wiring complies with local
building codes and NEC and that the supply voltage for this system is correct.
• Connect the wiring for both the power source
• Verify that the wiring connections match the indoor connections wire for wire.
• Ensure each wire is under the screw terminal plate and the plate is tightened.
• Ensure the 14/4 wire cable is secured under the strain relief bracket.
• Verify that all connections are secured
and the indoor wiring using a conduit cable bracket on the side of the outdoor unit
NOTE: Failure to follow the wiring guidelines can result in control board damage and communication issues (E7 error code). This includes improper wire size, use of solid core wire, midline splicing and poor terminal connections.
Models:
TAD3U24MOU TAD4U36MOU
Power Wiring
To Service Disconnect
230 Volt Supply. 1 to L1, 2 to L2.
Outdoor unit
Only on FlexFit 3U & 4U
and Arctic 2U & 3U
Diagnostic and Control
Only on FlexFit 4U and Arctic 2U & 3U
43
)
(
1
N
Only on FlexFit 3U
)
(
L
2
43
Models: TAD2U18MOU
14
Indoor unit A
)
(
)
(N)
(L
C
1
3
2
A B C D
Strain Relief
Indoor unit B Indoor unit C Indoor unit D
Brackets
(N)
1
)
2
(
(L
3
)
(N)
C
1
Control Wiring
4 Wire - 14 AWG
Stranded
)
(L
2
)
(
C
3
)
(
)
(N)
(L
C
1
3
2
Sugested Colors
=White
1
=Black
2
=Red
3
=Green
31-5000001 Rev. 1
INSTALLATION INSTRUCTIONS
Step 3 - Installation of the Outdoor Unit (Cont.)
D. Wiring Error Check
• This unit is capable of automatically checking for wiring errors between the indoor and outdoor units.
• To enter the wiring error check test, place all 4 DIP switches of the test board to the ON position. (Illustration 6) Remove and reapply power to the unit, the system will enter the operation of “Wiring Error Check”.
• The numeric display will initialize and begin to alternate between the compressor working frequency (a number representing the Hz value) and “CH” (Checking).
• As the check is being performed, all units that are properly
connected will be indicated by the corresponding LED for that circuit being lit constantly. (LED 1 = piping circuit A, LED 2 = piping circuit B, ...)
• After the check has completed, if all wiring is correct,
the numeric display will indicate “0” and the single LEDs representing the individual circuits for the connected indoor units will be lit constantly.
• If there are any miswired units, the numeric display will flash
“EC” (error connection), and th corresponding LED for the miswired circuit will flash. Check and correct the wiring as needed.
LED 1 2 3 4 5 Message
OFF Unit not connected
ALL Flashing Automatic chekcing impossible, all units connected wrong
Status
ON Flashing Flashing ON Flashing ON: unit connected correctly
ON Flashing Flashing ON ON ON: unit connected correctly
ALL ON All units connected correctly
Only one LED flashing
• Refer to the chart shown below. (Table 2)
• When the test is complete, remove power to the system and return the 4 DIP switches to the OFF position. Reapply power to the the system. The test is complete.
• If the self-check is not possible, check the indoor unit wiring and piping in the usual manner.
Flashing: unit connected wrong, need to change the wiring manually between 2, 3, and 5
Flashing: unit connected wrong, need to change the wiring manually between 2 and 3
ENGLISH
Connections Cautions
Model TAD4U36MOU TAD3U24MOU TAD2U18MOU Connection priority
between indoor and service valve higher from down to up.
A
B
A
B
C
When there are 2 indoors, the prior service valves are
When there are 3 indoors, the prior service valves are
When there are 4 indoors, the prior service valves are
NOTE: For better oil return and more reliable system, please execute as the above when connecting indoor unit.
31-5000001 Rev. 1
D C C B B A
D C B C B A /
D C B A / /
15
ENGLISH
Forced fastening without careful centering may damage the threads and cause a refrigerant leak.
Pipe Diameter(ǿ) Fastening torque
Liquid side6.35mm(1/4") 18N.m/13.3Ft.lbs
Liquid/Gas side9.52mm(3/8") 42 N.m/30.1Ft.lbs
Gas side 12.7mm(1/2") 55N.m/40.6Ft.lbs
Gas side 15.88mm(5/8") 60 N.m/44.3Ft.lbs
Half union
Flare nut
h
Forced fastening without careful centering may damage the threads and cause a refrigerant leak.
Pipe Diameter(ǿ) Fastening torque
Liquid side6.35mm(1/4") 18N.m/13.3Ft.lbs
Liquid/Gas side9.52mm(3/8") 42 N.m/30.1Ft.lbs
Gas side 12.7mm(1/2") 55N.m/40.6Ft.lbs
Gas side 15.88mm(5/8") 60 N.m/44.3Ft.lbs
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
A
B
Outdoor unit
Indoor unit
Oil trap
CAUTION
Max. Elevation: A Max = 33ft / 10m (09k / 12k) = 50ft / 15m (18k / 24k) In case the height of A is more than 15ft / 5m, an oil trap should be installed every 16-23ft /5-7m Max. Length: B Max = 50ft / 15m (09k / 12k) = 83ft / 25m (18k / 24k)
INSTALLATION INSTRUCTIONS
Step 3 - Installation of the Outdoor Unit (Cont.)
E. Install Copper Lineset
• The standard line set length is 25 feet. If the installation length is different, adjust the refrigerant charge by 0.2 oz/ft if the liquid line is 1/4”, or 0.5 oz/ft if the liquid line is 3/8”.
• See table on page 15.
• Cut the line set to length.
• Place nut over the pipe and then flare with the R-410A flaring tool.
NOTE: Follow standard practices for creating pipe flares. When cutting and reaming the tubing, use caution to prevent dirt or debris from entering the tubing. Remember to place nut over the tubing before flaring.
• To join the line set, directly align the tubing flare to the fitting on the other pipe. Slide the nut onto the fitting and hand tighten.
• Torque the fittings according to the specifications shown in the torque chart below.
• Two wrenches are required to join the flare connection; one standard wrench and one torque wrench adjusted to the proper settings.
• Repeat the process for attaching the other end of the line set.
16
F. Leak Test
FlexFit multi-zone models 2U18MS and 3U24MS do not have master service valves. Perform the following steps for EACH line set.
The FlexFit multi-zone model 4U36MS and Arctic multi models 2U20EH and 3U24EH have a master service valve. Performing the following steps will test ALL line sets.
• Remove the cap on the service valve.
• Using a tank of dry nitrogen and approved regulator, charge the system with 150 psig of dry nitrogen using mini-split adapter to connect the valve.
• Check for leaks at the flare fittings using soap bubbles or another detection device. If a leak is detected, make repairs to the fittings and recheck. If no leaks are detected within 3 minutes, proceed.
• Using the same tank/regulator, charge the system to 300 psig.
• Check for leaks as earlier. If no leaks are detected within 3 minutes, proceed.
• Using the same tank/regulator, charge the system to 500 psig.
• Check for leaks as earlier. Keep system pressurized for at least 20 minutes.
WARNING
Do not use acetylene, oxygen or
compressed air or mixtures containing them for pressure testing. Do not use mixtures of hydrogen containing refrigerant and air above atmospheric pressure for pressure testing as they may become flammable and could result in an explosion. Refrigerant, when used as a trace gas, should only be mixed with dry nitrogen for pressurizing units. Failure to follow these recommendations could result in death or serious injury as well as equipment or property damage.
G. System Evacuation
Spanner
Torque wrenc
NOTE– Do not open service valve.
• Remove the suction line cap and attach a manifold
gauge, micron gauge, and vacuum pump to the suction line port using adapter AD-87 (see illustration).
• Evacuate the system to at least 350 microns.
• Close the vacuum pump valve and check the micron
gauge. If the gauge rises above 150 microns in 60 seconds, the evacuation is incomplete or there is a leak in the system. If the gauge does not rise above 150 microns in 60 seconds, the evacuation is complete.
• Once evacuation is complete, remove the adapter
and hose connection from the suction line port and replaced the cap.
31-5000001 Rev. 1
INSTALLATION INSTRUCTIONS
Step 3 - Installation of the Outdoor Unit (Cont.)
H. Refrigerant Charging
• Add any additional refrigerant after evacuation using a digital scale.
NOTE: Charge liquid only.
• Fill out the refrigerant charge label using indelible ink.
• Place the factory refrigerant charge found in table on page 15 in the box number 1.
• Place the amount of additional refrigerant added in box number 2.
• Add boxes 1 and 2 together and place the value in the sum box (D).
• Adhere the filled out label in the proximity of the product charging port and under the outside unit valve cover.
• If no sticker found, write amounts on outdoor unit with permanent marker above the charging port.
• Remove the cap from the liquid line valve. Using a hex wrench, open the valve, then replace and tighten the cap securly to avoid leaks.
• Remove the cap from the suction line valve. Using a hex wrench, open the valve, then replace and tighten the cap securly to avoid leaks.
• Wrap the line set, drain line, and 14/4 AWG wiring
Step 4 - Final Check
starting at the bottom of the bundle with an overlap type wrap until you reach the piping hole.
• Use a sealant to seal the piping hole opening on both sides of the wall in order to prevent drafts, weather, or pests from entering the building.
This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. Do not vent into the atmosphere.
Contains fluorinated greenhouse gases covered by the Kyoto Protocol
R410A
2
1
F E
Refrigerant type: R-410A GWP* value: 1975 GWP = global warming potential
1=
2=
1+2=
oz
oz
oz
A
B
C
D
ENGLISH
System Test
Please explain to the customer how to operate the system by using the Owner’s Manual found with the indoor unit.
Explaining Operation To the End User
• Using the User Manual, explain to the user how to use the air conditioner/heat pump, (the remote controller, adding/removing the air filters, placing or removing the remote controller from the remote control holder, cleaning methods, precautions for operation, etc.)
• Review precautions for operation.
• Recommend that the user read the Operating Instructions carefully.
Check Items for Test Run
No gas leak from linesets? Are the linesets insulated properly? Are the connecting wirings of indoor and outdoor firmly
inserted to the terminal block? Is the connecting wiring of indoor and outdoor fixed? Is condensate draining correctly? Is the ground wire securely connected? Is the indoor
unit securely fixed? Is power source voltage correct according to local
code? Is there any odd noise? Does the cooling temperature drop between 20-30°F? Does the heating temperature raise between 35-40°F? Is the room temperature display accurate?
31-5000001 Rev. 1
17
Loading...