read completely prior to installation of the
equipment. A copy of these instructions
should be retained on file for future reference.
WARNING: Electrical shock hazard. Disconnect ALL power sources when installing or
servicing this equipment to prevent electrical
shock or equipment damage.
This pump is intended for the circulation of water or other
suitable HVAC media. It is not intended for hazardous,
corrosive, or flammable liquids.
Pump must not be operated until all piping and/or electrical connections are in place.
Proper care and suitable equipment should be used to
move and install this heavy equipment.
Care should be taken when installing pipe systems to
avoid placing an excessive load on the pump unions.
Refer to motor installation instructions to determine
proper terminal connections in order to obtain correct
pump rotation.
When the system piping is used as an earth bonding path
for the building electrical services (check local codes),
the pump should not be relied upon as part of the circuit.
A properly installed bridging connection should be provided.
If electrical connection is to be made using any means
other than rigid conduit, proper strain relief must be provided (min 100N tension).
Pump should be installed according to local electrical and
safety codes using appropriate size wire and suitable
over current protection. It should use a lockable isolator
or circuit breaker conforming to applicable electrical
codes.
It is recommended that the pump be fitted with a suitable
“emergency stop” per the requirements of applicable
electrical codes.
2 GENERAL INSTALLATION
REQUIREMENTS
2.1 Receiving Pump
Inspect for shipping damage. If a shortage or damage
occurs, contact carrier immediately.
2.2 Location
Install vertically with motor up. Consult factory for horizontal mounting.
Pump should be accessible for inspection and repair
work, head room must be provided for the use of hoist or
tackle as necessary.
Lift pump by slinging through motor eye bolts and securing through pump adapter.
NOTE: In no case should any part of motor
be covered with insulation.
2.3 Foundation
The pump must always be supported.
Pumps with smaller motors may be suspended in the piping, provided the piping is supported adjacent to the
pump.
For pumps with larger motors, the pump should be
attached to a support utilizing the tapped hole or holes in
the bottom of the pump casing.
NOTE: Piping loads shall not be applied to
the pump.
Pump must be allowed to move with piping movement.
Expansion of piping must be taken into account
when piping and suitable devices should be employed.
NOTE: The pump should not be rigidly attached to the
mmmmbase/pad structure unless flexible couplings are used.
NOTE: Provide vibration isolation pads
under floor mounted supports. Do not support unit by the motor eye-bolts.
3 MAINTENANCE
3.1 Routine Inspections
Routine inspections should be made on a regular basis.
Inspections made while pump is running should reveal
potential failures.
• Inspect motor bearings for any sign of temperature
rise. Temperature should not exceed 160°F. Temperature rise may indicate the early stages of bearing
problems.
• Listen for any unusual noise:
1.Air trapped in pump.
2.Hydraulic noise.
3.Mechanical noise in motor and/or pump.
• Check suction gauge reading and confirm that it is
normal.
• Check discharge gauge reading and confirm that it is
normal. If gauge readings are abnormal find out why.
NOTE: Suction and discharge gauges
should read the same with pump stopped.
3.2 Close Coupled Pumps
The pump section is attached directly to the motor shaft
and does not contain bearings.
3.3 Close Coupled Motors
The motor must be lubricated in accordance with the
manufacturer’s recommendations. Do not over lubricate
the motor bearings as this could cause premature bearing failure.
3.4 Mechanical Seal
The mechanical seal is the “John Crane” Type 21 General Purpose Seal for the 175 psig pressure rating.
A “John Crane” Type 2 General Purpose Seal is used for
the 300 psig pressure rating.
4 DIS-ASSEMBLY AND REASSEMBLY
4.1 General
If the pump has been maintained and serviced properly,
breakdowns requiring pump disassembly should occur
only rarely.
• If a problem occurs, the cause should be determined,
if possible, before dis-assembling. (See “Problem
Analysis”)
• If the pump is being dis-assembled, all parts must be
carefully handled, avoid heavy blows and shocks.
• All parts must be carefully cleaned and inspected for
wear. Recondition or replace parts where necessary.
4.2 Dis-Assembly
Drain liquid from casing by removing drain plug.
CAUTION: Allow pump to cool and secure
suction and discharge valves before working
on pump!
Remove re-circulation line.
Remove bolts holding cover/adapter to casing, pry cover/
adapter and motor assembly from casing.
Remove impeller bolt in a counterclockwise direction.
Remove impeller and key.
In all cases of mechanical seal arrangement, after
removing the sleeve and its seal assembly, the seal rotating element may be drawn off the shaft sleeve.
NOTE: Apply silicone grease on the OD of
the sleeve in the area between the seal and
the end of the sleeve. This will help removal
of the old seal. The stationary element is to
be removed from the cover.
All parts must be cleaned and inspected for wear.
Replace parts where necessary.
4.3 Re-Assembly
Be certain that all parts to be replaced are free from
burrs, with screw threads and connecting faces clear and
free from damage.
Insert stationary element of seal into cover adapter, slip
cover-adapter over shaft and engage rabbit of motor.
Note: Do not touch the seal surfaces
because this may result in leakage. Do not
contaminate seal faces with fingerprints.
Lubricate smaller OD of shaft sleeve with silicone grease.
Do not use petroleum oil or grease.
Place spring on shaft sleeve to abut against sleeve
shoulder. Slide rotary seal on sleeve until it contacts
spring.
Slide the shaft sleeve on the shaft, larger bore first. Be
certain the O-ring is correctly seated in the groove.
Assemble impeller key and impeller on shaft. Refit with
new impeller washer on impeller bolt and tighten carefully. Be certain that the impeller rotates freely by hand.
Apply a few spots of gasket adhesive to gasket surface of
cover. Place a new casing gasket against gasket surface
and press against adhesive.
Assemble cover-adapter complete with motor into casing. Insure that gasket is seated correctly. Install hexheaded cap screws into casing tapings and tighten uniformly.
piping, unless extra care is taken to measure
and align the piping flanges well. Always
start piping from pump. Use as few bends as
possible and preferably long radius elbows.
Do not use flexible connectors on the suction or discharge of a vertical in-line pump, unless the pump is rigidly mounted to a foundation. Ensure piping exerts no
strain on pump as this could distort the casing causing
breakage or early failure due to pump misalignment. All
connecting pipe flanges must be square to the pipe work
and parallel to the pump flanges.
Suction and discharge pipes may be increased or
decreased at pump nozzle to suit pump capacity and particular conditions of installation. Use eccentric reducers
on suction connection with flat side uppermost.
Lay out the suction line with a continual rise towards the
pump without high points, thus eliminating possibility of
air pockets that may prevent the pump from operating
effectively.
Airflow into the motor and/or motor fan should not be
obstructed.
7.2 VFD Mounting to Pump
For instructions on mounting the VFD directly to the
pump, see the diagrams and notes on the following page.
6 APPLICATION
Working Pressure:175 psig
Optional Working Pressure:300 psig
Temperature:250°F Standard
300°F Hi Temperature
7 MECHANICAL INSTALLATION
7.1 Location
In open systems, locate the unit as close as practical to
the liquid supply source, with a short, direct suction pipe.
Ensure adequate space is left above and around the unit
for operation, maintenance, service and inspection of
parts.
In closed systems, where possible, the pumps should be
installed immediately downstream of the expansion tank/
make-up connection. This is the point of zero pressure
change and is necessary for effective pump operation.
Do not install more than one expansion tank connection
into any closed hydronic system.
Electric motor driven pumps should not be located in
damp or dusty location without special protection.
1.Items specified on this drawing are specifically for the SKV or SKS product series.
2.Assemble safety strap onto isolation mount stud to produce orientation shown in the assembly drawing.
3.Apply 'Loctite' to isolation mount stud threads (1 place) on all 4x parts.
4.Assemble threaded stud with 'Loctite' into bar bracket until surfaces are in contact without gaps.
5.Use strap wrench for isolation mounts. Screw mount into bar bracket (#2) until the rubber face is flush against the
bar. Torque the mount 1/4 of a full turn.
• Check the weight of the unit to determine a safe lifting method.
• Ensure that the lifting device is suitable for the task.
• If necessary, plan for a hoist, crane, or forklift with the
appropriate rating to move the unit.
• For lifting, use hoist rings on the unit, when provided.
7.3.2 Mounting
• Mount the unit vertically.
• The frequency converter allows side by side installation.
• Ensure that the strength of the mounting location will
support the unit weight.
• Mount the unit to a solid flat surface or to the optional
back plate to provide cooling airflow (see Figure 7-2
and Figure 7-3).
• Improper mounting can result in overheating and
reduced performance.
• Use the slotted mounting holes on the unit for wall
mounting, when provided.
Figure 7-2: Proper Mounting with Back Plate
Item A is a back plate properly installed for required airflow to cool the unit.
7.3.3 Tightening Torques
See “17.2 Connection Tightening Torques” on page 77
for proper tightening specifications.
7.4 Pump Piping – Detailed
In order to achieve the full added value of the Vertical InLine pump design, it is important that you ensure the
pump is affixed to the system piping by the pump flanges
and the pump and motor assembly is allowed to float
freely with the expansion and contraction of the piping
system. Should any vertical in-line pump use supports to
the structure, it is imperative that no pipe strain is
imposed on the pump flanges. Compliant mounts such
as springs or “waffle”-style isolation pads should be used
under the pipe supports if the pump is not truly pipe
mounted.
Various installation arrangements are detailed in the figures that follow.
Figure 7-4: Hanger Supported, Pipe Mounted
NOTE: Back plate is required when mounted
on railings.
NOTE: The pump should not be rigidly attached to the base/pad structure unless flexible couplings are used.
Vertical In-Line pumps may be installed directly in the
system piping with no additional support. Pipe hangers
are simply sized for the additional weight of the pumping
unit. Many pumps are installed in this manner and are
mounted at sufficient height to take zero floor space.
A similar arrangement to Figure 7-5 with additional floor
mounted pipe-stools isolated from the structure by 'waffle' style isolation pads under the Suction Diffuser (RSP)
and Plus Two Multi-Purpose Valve is illustrated in
(Figure 7-7).
(Figure 7-4)
Piping for smaller in-line pumps (typically 15 hp and
below) is hung close to the ceiling in many mechanical
rooms. Larger pumps are often mounted near ground
level for ease of maintenance. Figure 7-5 illustrates such
an arrangement with the piping supported at the ceiling
and the vertical pump installed with a Taco Suction Diffuser (RSP) and Plus Two Multi-Purpose Valve.
Figure 7-5: Pipe Mounted, Supported at Ceiling
Floor mounted saddle supports (Figure 7-8) are typical
for condenser water pumps where cooling tower base is
near mechanical room elevation.
Figure 7-7: With Additional Pipe Supports
Figure 7-8: Floor Saddle Support
Should additional space saving be required, the discharge spool piece and Plus Two Multi-Purpose Valve
may be replaced by a long-radius elbow and the Plus
Two Multi-Purpose Valve field converted to a straight pattern configuration and installed in the vertical discharge
pipe (Figure 7-6).
Figure 7-6: Discharge Elbow for Minimum
Footprint
Where required, additional floor support may be used as
shown in Figure 7-9. Install a “waffle” isolation pad under
the pump. NOTE: The pump should not be rigidly
attached to the base/pad structure.
Figure 7-9: Additional Floor Support
Stanchion plates at the pump suction and discharge ports
may be supplied for installation convenience. Isolation
pads must be used under the legs and monitored as pipe
hangers are adjusted to ensure the pump flanges are not
supporting the piping. Bolting to the floor or housekeeping pad is not recommended. If the stanchions are bolted
down the bolts must be isolated from the stanchion or
inertia base and flexible pipe connectors used (Figure 7-
10).
Figure 7-10: With Stanchion Plates
An installation with stanchion plates for seismically active
regions is illustrated in Figure 7-11. Seismically rated isolation pads or snubbers with bolts isolated from the stanchion plates are installed to restrain the pump during a
seismic event. Pipe hangers carry the weight of the
equipment as seismic components are designed only to
restrain the equipment during a seismic event.
Figure 7-11: Installation in Seismically Active
Region
Figure 7-12: Mounting in Grooved Pipe Systems
DO NOT support the unit by the motor eye bolts
(Figure 7-13) or by any other part of the motor.
Figure 7-13: Motor Lifting Hook Supported
Connecting the pump to a permanent rigid base
(Figure 7-14) is not recommended unless isolated from
the piping by flexible connectors and the base isolated
from the building structure on an inertia base. (Figure 714 is generally acceptable when using plastic piping.)
Figure 7-14: Mounted on Rigid Base without
Flexible Connectors
In systems utilizing grooved pipe, flange adapter locking
devices or welded flanges at the pump should be used to
prevent the possibility of pipe mounted pumps rotating in
the piping (Figure 7-12).
NOTE: The pump should not be rigidly attached to the base/pad structure unless flexible couplings are used.
DANGER: EQUIPMENT HAZARD! Rotating shafts and electrical equipment can be hazardous. All electrical work must conform to national and local electrical codes. It is strongly recommended that installation,
start-up, and maintenance be performed only by trained and qualified personnel. Failure to follow these
guidelines could result in death or serious injury.
CAUTION:WIRING ISOLATION! Run input power, motor wiring and control wiring in three separate
metallic conduits or use separated shielded cable for high frequency noise isolation. Failure to isolate
power, motor and control wiring could result in less than optimum adjustable frequency drive and associated equipment performance.
For your safety, comply with the following requirements:
• Electronic controls equipment is connected to hazardous AC line voltage. Extreme care should be
taken to protect against electrical hazards when
applying power to the unit.
• Run motor cables from multiple adjustable frequency
drives separately. Induced voltage from output motor
cables run together can charge equipment capacitors
even with the equipment turned off and locked out.
8.2.1 Overload and Equipment Protection
• An electronically activated function within the adjustable frequency drive provides overload protection for
the motor. The overload calculates the level of
increase to activate timing for the trip (controller output stop) function. The higher the current draw, the
quicker the trip response. The overload provides
Class 20 motor protection. See “14 Warnings and
Alarms” on page 61 for details on the trip function.
• Because the motor wiring carries high frequency current, it is important that wiring for line power, motor
power, and control is run separately. Use metallic
conduit or separated shielded wire. Failure to isolate
power, motor, and control wiring could result in less
than optimum equipment performance. See Figure 8-
4.
Figure 8-4: Proper Electrical Installation Using
Flexible Conduit
All adjustable frequency drives must be provided with
short-circuit and overcurrent protection. Input fusing is
required to provide this protection, see Figure 9.2.3. If not
factory supplied, fuses must be provided by the installer
as part of installation.
Figure 8-5: Adjustable Frequency Drive Fuses
Wire Type and Ratings
• All wiring must comply with local and national regulations regarding cross-section and ambient temperature requirements.
• Danfoss recommends that all power connections be
made with a minimum 167°F [75 °C] rated copper
wire.
8.3 Grounding Requirements
DANGER: GROUNDING HAZARD! For
operator safety, it is important to ground
adjustable frequency drive properly in accordance with national and local electrical
codes as well as instructions contained
within these instructions. Ground currents
are higher than 3.5 mA. Failure to ground the
adjustable frequency drive properly could
result in death or serious injury.
NOTE: It is the responsibility of the user or certified electrical installer to ensure correct grounding of the equipment in accordance with national and local electrical
codes and standards.
• Follow all local and national electrical codes to
ground electrical equipment properly.
• Proper protective grounding for equipment with
ground currents higher than 3.5 mA must be established, see Leakage Current (>3.5 mA).
• A dedicated ground wire is required for input power,
motor power and control wiring.
• Use the clamps provided with on the equipment for
proper ground connections.
• Do not ground one adjustable frequency drive to
another in a “daisy chain” fashion.
• Keep the ground wire connections as short as possible.
• Use of high-strand wire to reduce electrical noise is
recommended.
• Follow the motor manufacturer wiring requirements.
8.3.1 Leakage Current (>3.5 mA)
Follow national and local codes regarding protective
grounding of equipment with a leakage current > 3.5 mA.
Adjustable frequency drive technology implies high frequency switching at high power. This will generate a leakage current in the ground connection. A fault current in
the adjustable frequency drive at the output power terminals might contain a DC component which can charge
the filter capacitors and cause a transient ground
current. The ground leakage current depends on
various system con"gurations including RFI filtering,
shielded motor cables, and adjustable frequency drive
power.
EN/IEC61800-5-1 (Power Drive System Product Standard)
requires special care if the leakage current exceeds
3.5mA.
Grounding must be reinforced in one of the following
ways:
• Ground wire of at least 0.0155 in2 [10mm2]
• Two separate ground wires both complying with the
dimensioning rules
See EN/IEC61800-5-1 and EN50178 for further information.
8.3.3 Grounding Using Shielded Cable
Grounding clamps are provided for motor wiring (see
Figure 8-6).
Figure 8-6:
Grounding with Shielded Cable
8.3.4 Grounding Using Conduit
DANGER: GROUNDING HAZARD! Do not
use conduit connected to the adjustable frequency drive as a replacement for proper
grounding. Ground currents are higher than
3.5 mA. Improper grounding can result in
personal injury or electrical shorts.
Dedicated grounding clamps are provided (See Figure 8-
7).
Figure 8-7: Grounding with Conduit
8.3.2 Using RCDs
Where residual current devices (RCDs), also known as
ground leakage circuit breakers (ELCBs), are used, comply with the following:
• Use RCDs of type B only which are capable of
detecting AC and DC currents
• Use RCDs with an inrush delay to prevent faults due
to transient ground currents
• Dimension RCDs according to the system configuration and environmental considerations
1.Use a wire stripper to remove the insulation for
proper grounding.
2.Secure the grounding clamp to the stripped portion
of the wire with the screws provided.
3.Secure the grounding wire to the grounding clamp
provided.
13
Taco® SKV
8.3.5 Motor Connection
DANGER: INDUCED VOLTAGE! Run out-
put motor cables from multiple adjustable
frequency drives separately. Induced voltage
from output motor cables run together can
charge equipment capacitors even with the
equipment turned off and locked out. Failure
to run output motor cables separately could
result in death or serious injury.
• For maximum wire sizes, see “17.1 Power-dependent Specifications” on page 75.
• Comply with local and national electrical codes for
cable sizes.
• Motor wiring knockouts or access panels are provided at the base of IP21 and higher (NEMA1/12)
units
• Do not install power factor correction capacitors
between the adjustable frequency drive and the
motor
• Do not wire a starting or pole-changing device
between the adjustable frequency drive and the
motor.
• Connect the 3-phase motor wiring to terminals 96
(U), 97 (V), and 98 (W).
• Ground the cable in accordance with grounding
instructions provided.
• Follow the motor manufacturer wiring requirements
The three following figures represent line power input,
motor, and grounding for basic adjustable frequency
drives. Actual configurations vary with unit types and
optional equipment.
Figure 8-8: Motor, Line Power and Ground Wiring
for A-Frame Sizes
Figure 8-9: Motor, Line Power and Ground Wiring
for B-Frame Sizes and Above Using Shielded
Cable
Figure 8-10: Motor, Line Power and Ground
Wiring B-Frame Sizes and Above Using
Shielded Cable or Conduit
14
8.3.6 AC Line Power Connection
Size wiring based upon the input current of the adjustable
frequency drive.
• Comply with local and national electrical codes for
cable sizes.
• Connect 3-phase AC input power wiring to terminals
L1, L2, and L3 (see Figure 8-11).
• Depending on the configuration of the equipment,
input power will be connected to the line power input
terminals or the input disconnect.
Figure 8-11: Connecting to AC Line Power
• Ground the cable in accordance with grounding
instructions provided in “8.3 Grounding Requirements” on page 12.
• All adjustable frequency drives may be used with an
isolated input source as well as with ground reference power lines. When supplied from an isolated
line power source (IT line power or floating delta) or
TT/TN-S line power with a grounded leg (grounded
delta), set 14-50 RFI 1 to OFF. When off, the internal
RFI filter capacitors between the chassis and the
intermediate circuit are isolated to avoid damage to
the intermediate circuit and to reduce ground capacity currents in accordance with IEC 61800-3.
Figure 8-12: Control Wiring Access for A2, A3,
B3, B4, C3 and C4 Enclosures
Figure 8-13: Control Wiring Access for A4, A5,
B1, B2, C1 and C2 Enclosures
8.3.7 Control Wiring
Isolate control wiring from high power components in the
adjustable frequency drive.
If the adjustable frequency drive is connected to a thermistor, for PELV isolation, optional thermistor control wiring
must be reinforced/ double insulated. A 24 VDC supply
voltage is recommended.
Access
Remove access coverplate with a screwdriver. See “Figure 8-12: Control Wiring Access for A2, A3, B3, B4, C3
and C4 Enclosures” on page 15.
Or remove front cover by loosening attaching screws.
See “Figure 8-13: Control Wiring Access for A4, A5, B1,
B2, C1 and C2 Enclosures” on page 15.
Figure 8-14 shows the removable adjustable frequency
drive connectors.
Figure 8-14: Control Terminal Locations
Figure 8-15: Unplugging Control Terminals
1.Open the contact by inserting a small screwdriver
into the slot above or below the contact, as shown
in Figure 8-16.
2.Insert the bared control wire into the contact.
3.Remove the screwdriver to fasten the control wire
into the contact.
4.Ensure the contact is firmly established and not
loose. Loose control wiring can be the source of
equipment faults or less than optimal operation.
Figure 8-16: Connecting Control Wiring
• Connector 1 provides four programmable digital
inputs terminals, two additional digital terminals programmable as either input or output, a 24V DC terminal supply voltage, and a common for optional
customer supplied 24V DC voltage.
• Connector 2 terminals (+)68 and (-)69 are for an RS485 serial communications connection.
• Connector 3 provides two analog inputs, one analog
output, 10V DC supply voltage, and commons for the
inputs and output.
• Connector 4 is a USB port available for use with the
MCT-10 Set-up Software.
• Also provided are two Form C relay outputs that are
in various locations depending upon the adjustable
frequency drive configuration and size.
Wiring to Control Terminals
Control terminal connectors can be unplugged from the
adjustable frequency drive for ease of installation, as
shown in Figure 8-15.
Using Shielded Control Cables
Correct Shielding
The preferred method in most cases is to secure control
and serial communication cables with shielding clamps
provided at both ends to ensure best possible high frequency cable contact.
With very long control cables, ground loops may occur.
To eliminate ground loops, connect one end of the shieldtoground with a 100 nF capacitor (keeping leads short).
Avoid EMC noise on serial communication
To eliminate low-frequency noise between adjustable frequency drives, connect one end of the shield to terminal
61. This terminal is connected to ground via an internal
RC link. Use twisted-pair cables to reduce interference
between conductors.
Control Terminal Functions
Adjustable frequency drive functions are commanded by
receiving control input signals.
• Each terminal must be programmed for the function it
will be supporting in the parameters associated with
that terminal.
• It is important to confirm that the control terminal is
programmed for the correct function. See “9 User
Interface” on page 28for details on accessing parameters..
• The default terminal programming is intended to initiate adjustable frequency drive functioning in a typical
operational mode.
Jumper Terminals 12 and 27
A jumper wire may be required between terminal 12 (or
13) and terminal 27 for the adjustable frequency drive to
operate when using factory default programming values.
• Digital input terminal 27 is designed to receive an
24VDC external interlock command. In many applications, the user wires an external interlock device to
terminal 27.
• When no interlock device is used, wire a jumper
between control terminal 12 (recommended) or 13 to
terminal 27. This provides an internal 24 V signal on
terminal 27.
• No signal present prevents the unit from operating.
• When the status line at the bottom of the LCP reads
“AUTO REMOTE COASTING” or “Alarm 60 External
Interlock” is displayed, this indicates that the unit is
ready to operate but is missing an input signal on terminal 27.
• When factory installed optional equipment is wired to
terminal 27, do not remove that wiring.
Terminal 53 and 54 Switches
• Analog input terminals 53 and 54 can select either
voltage (0 to 10V) or current (0/4–20mA) input signals
• Remove power to the adjustable frequency drive
before changing switch positions.
• Set switches A53 and A54 to select the signal type. U
selects voltage, I selects current.
• The switches are accessible when the LCP has been
removed (see Figure 8-17). Note that some option
cards available for the unit may cover these switches
and must be removed to change switch settings.
Always remove power to the unit before removing
option cards.
• Terminal 53 default is for a speed reference signal in
open-loop set in 16-61 Terminal 53 Switch Setting
• Terminal 54 default is for a feedback signal in closedloop set in 16-63 Terminal 54 Switch Setting
The unit connection blocks are shown in “Figure 8-14: Control Terminal Locations” on page 16.
Table 2: Control Terminal Information
Terminal
number
Relay Outputs 01, 02, 03 5-40 Relay 1[160] No AlarmForm C Relay Output. Used for AC or DC voltages and either
04, 05, 06 5-40 Relay 2[5] Running
Connector 112, 13 - +24 V DC24 V DC supply voltage. Maximum output current is 200 mA
18 5-10[8] StartStart/Stop digital input signal for the drive. Connect input to 24
19 5-11[0] No OperationDigital input (not used)
27 5-12[0] No OperationDigital input (not used)
29 5-13[0] No OperationDigital input (not used)
32 5-14[0] No OperationDigital input (not used)
33 5-15[0] No OperationDigital input (not used)
20 - Common Common for digital inputs and reference for 24 V supply
Connector 261 - Shield Connection Integrated RC filter for cable shield. ONLY for connecting the
Connector 339 - AO Common Common for analog output
42 6-504-20mA Motor
50 - +10 V DC10 V DC analog supply voltage. 15mA max.
53 6-1[0] No OperationAnalog input 53.
54 6-2[0] No OperationAnalog input 54.
55 - AI Common Common for analog input.
Parameter Default setting Description
resistive or inductive loads. see the following section on relay
wiring for contact current and voltage ratings.
total for all 24 V loads. Intended for digital inputs, external
transducers.
V to start. Open the input to stop the drive.
shield when experiencing EMC problems.
Analog output. Default setting is 4-20mA signal (500 ohms
This configuration makes use of the controller factory default settings for input/output. The factory default settings are
configured for Set-up 1, SelfSensing system curve control without an external transducer. No parameters need to be
changed to use this configuration. Set-up 3, SelfSensing constant flow control, uses the same default settings.
Set-ups can be changed by modifying the parameter 0-10 Active Set-up.
NOTE: The factory default settings require a start signal wired to DI18 (see below).
As shown above, each unit has two form C programmable relay outputs. The relay terminals can be found on the controller in various locations according to the frame size.
Figure 8-19: Wiring the Relay Terminals
Relay 1
01
02NO03
COM
COM
Unit Receiving
Output from
Relay 1
[5-40.0]
[160] No Alarm*
No Alarm: Comm=NO
Alarm: Comm = NC
NO
NC
NC
Relay 2
04
05NO06
COM
COM
Unit Receiving
Output from
Relay 2
[5-40.1]
[5] Running*
Running: Comm=NO
Off: Comm = NC
NO
NC
NC
* Factory Default Settings
Table 3: Relay Terminal Specifications
Programmable relay outputs 2
Relay 01 Terminal number 1–3 (break), 1–2 (make)
Maximum terminal load (AC-1) on 1–3 (NC), 1–2 (NO) (Resistive load) 240 V AC, 2A
Maximum terminal load (AC-15) (Inductive load @ cos 0.4) 240 V AC, 0.2A
Maximum terminal load (DC-1) on 1–2 (NO), 1–3 (NC) (Resistive load) 60 V DC, 1A
Maximum terminal load (DC-13) (Inductive load) 24 V DC, 0.1A
Relay 02 Terminal number 4–6 (break), 4–5 (make)
Maximum terminal load (AC-2) on 4–5 (NO) (resistive load) 400 V AC, 2A
Maximum terminal load (AC-15) (Inductive load @ cos 0.4) 240 V AC, 0.2A
Maximum terminal load (DC-1) on 4–5 (NO) (Resistive load) 80 V DC, 2A
Maximum terminal load (DC-13) on 4–5 (NO) (Inductive load) 24 V DC, 0.1A
Maximum terminal load (AC-1) on 4–6 (NC) (Resistive load) 240 V AC, 2A
Maximum terminal load (AC-15) on 4–6 (NC) (Inductive load @ cos 0.4)240 V AC, 0.2A
Maximum terminal load (DC-1) on 4–6 (NC) (Resistive load) 50 V DC, 2A
Maximum terminal load (DC-13) on 4–6 (NC) (Inductive load) 24 V DC, 0.1A
Minimum terminal load on 1–3 (NC), 1–2 (NO), 4–6 (NC), 4–5 (NO) 24 V DC 10mA, 24 V AC 20mA
Environment according to EN 60664–1 overvoltage category III/pollution degree 2
This configuration adds a transducer for closed loop control or external monitoring. Use Set-up 4 for pressure control
(Delta P) using a wired pressure transducer.
NOTE: Analog input configuration switches must be set before using the analog input, as shown in
Figure 8-21.
Figure 8-20: Terminal Wiring for 4–20mA Sensor Sensor
To configure the controller for closed loop control based on the input from an external transducer, use the following
parameters:
Table 4: Settings for a Wired Sensor for Input
Parameter
number
0–10 Active Set-up For wired pressure transducer, choose Set-up 4.
6-24* Terminal 54 Low Ref./Feedb.
Value
6-25* Terminal 54 High Ref./Feedb.
Value
6-27*Terminal 54 Live Zero Enabled
20-00Feedback 1 Source Analog Input 54*
20-12Reference/Feedback Set as appropriate for application. For example, set to PSI when using a pressure
20–13 Minimum Reference/Feed-
back
20–14 Maximum Reference/Feed-
back
Description Set to
Minimum transducer input value. For example, for a 0–100 PSI transducer, set to
0. For live 0 function set feedback to 1V or 10 PSI. Note: Live 0 does not work if
minimum is set to 0.
Maximum transducer input value. For example, for a 0–100 PSI transducer, set to
100.
transducer. The default value for this setting is PSI.
Minimum transducer input value. For example, for a 0–100 PSI transducer, set to
0 PSI.
Maximum transducer input value. For example, for a 100 PSI transducer, set to
100 PSI.
* To use AI 53, set parameters 6–14, 6–15, 6–17 and set 20–00 to “Analog Input 53.”
To set up the controller with a transducer that is intended for external monitoring, as opposed to feedback to the controller, set the following parameters:
Table 5: Settings for a Wired Sensor for External Monitoring
Parameter
number
Description Set to
0-24Display Line 3 Large Ext. 1 Feedback [Unit]
21-14Ext. 1 Feedback Source Analog Input 54*
21–10 Ext. 1 Ref./Feedback Unit Select as appropriate for application. For example, set to PSI when using a
pressure transducer.
21–11 Ext. 1 Minimum Reference Minimum transducer input value. For example, for a 0–60 PSI transducer,
set to 0 PSI.
21–12 Ext. 1 Maximum Reference Maximum transducer input value. For example, for a 60 PSI transducer,
set to 60 PSI.
6–24* Terminal 54 Low Ref./Feedb. Value Minimum transducer input value. For example, for a 0–60 PSI transducer,
set to 0 PSI.
6–25* Terminal 54 High Ref./Feedb. Value Maximum transducer input value. For example, for a 60 PSI transducer,
set to 60 PSI.
6–27* Terminal 54 Live Zero Disabled
* To use AI 53, set parameters 6–14, 6–15, 6–17 and set 20-00 to “Analog Input 53.”
This configuration allows an external potentiometer to control the speed of the motor.To use this set-up, the analog
input must be configured as a voltage input.
The following wiring scheme is used with Set-up 2 as shown in “10.1 SelfSensing Description” on page 34.
Figure 8-23: Terminal Wiring for Potentiometer used as External Speed Reference
To set up the controller for speed control with an external potentiometer, set the following parameters:
Parameter
number
1-00Configuration Mode Open Loop
3-15Reference 1 Source Analog Input 54
6-20Terminal 54 Low Voltage* 0 V
6-21Terminal 54 High Voltage* 10 V
6-24Terminal 54 Low Ref./Feedb. Value 0
6-25Terminal 54 High Ref./Feedb. Value Maximum motor speed. For example, 2950 Hz.
6-27Terminal 54 Live Zero Disabled.
20-00Feedback 1 Source No Function
8.4.5 Control from external PLC/BMS through Analog Input
This set-up allows an external control source such as a PLC or BMS controller to provide: a) the process variable, b)
the setpoint or c) a speed reference. The output from the external control device can be either a voltage or current signal. The analog input configuration switches must be set to the correct type of output signal. The drawing below shows
the connections for this configuration.
This wiring scheme is used with Set-up 2, as shown in “10.1 SelfSensing Description” on page 34.
Figure 8-24: Terminal Wiring for External Control Source
Table 6: Parameter Configuration for Use of an External Control Signal
Parameter
Number
1-00Configuration Mode Closed Loop Closed Loop Open Loop
3-15Reference 1 Source No Function Analog Input 54* Analog Input 54*
6-24Terminal 54 Low Ref./
6-25Terminal 54 High
6-27 Terminal 54 Live Zero EnabledEnabledDisabled
20-00Feedback 1 Source Analog Input 54 Select as appropriate for applica-
20-12 Reference/Feedback
20-14Maximum Reference/
Parameter
Description
Feedb. Value
Ref./Feedb. Value
Unit
Feedback
For process variable from
BMS/PLC*
Minimum value of process variable. For example, for a 0-60PSI
transducer, set to 0.
Maximum value of process variable. For example, for a 60PSI
transducer, set to 60.
Select as appropriate for application. For example, set to PSI
when using pressure feedback.
Maximum transducer feedback
value. For example, for a 60PSI
transducer, set to 60 PSI.
For setpoint from BMS/ PLC**
Minimum reference/setpoint
value. For example, for a 060PSI DP transducer, set to 0.
Maximum reference/setpoint
value. For example, for a 60PSI
DP transducer, set to 60.
tion. This can be any selection
except the setting of parameter
3-15.
Select as appropriate for application. For example, set to PSI
when using pressure reference.
Maximum reference/setpoint
value. For example, for a 60PSI
transducer, set to 60 PSI.