Taco iWorX HPU2, iWorX HPU3 Installation Manual

Installation Guide
HPU2 Water Source Heat Pump Controller
Self-Contained Interoperable Controller Model UCP-1
502-025
SUPERSEDES: New
Plant ID: 001-3982
HPU2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Purpose of This Guide . . . . . . . . . . . . . . . . . . . . . . . . . 2
Representations and Warranties . . . . . . . . . . . . . . . . . 2
Applicable Documentation . . . . . . . . . . . . . . . . . . . . . . 3
Installation Instructions . . . . . . . . . . . . . . . . . . . . . . 3
Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Static Electricity . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
FCC Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Before Installing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
About this Document . . . . . . . . . . . . . . . . . . . . . . . . 4
Inspecting the Equipment . . . . . . . . . . . . . . . . . . . . 4
What is Not Included with this Equipment . . . . . . . . 4
Equipment Location . . . . . . . . . . . . . . . . . . . . . . . . . 5
Selecting a Power Source . . . . . . . . . . . . . . . . . . . . 5
EFFECTIVE: April 12, 2011
Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Mounting the Device. . . . . . . . . . . . . . . . . . . . . . . . .5
Routing Cabling to the Device . . . . . . . . . . . . . . . . .6
Grounding the Device. . . . . . . . . . . . . . . . . . . . . . . .7
Wiring Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Connecting Input Devices. . . . . . . . . . . . . . . . . . . . .9
Connecting Output Devices . . . . . . . . . . . . . . . . . .10
Other Connections . . . . . . . . . . . . . . . . . . . . . . . . .10
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Mechanical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Diagnostic LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Troubleshooting Tips . . . . . . . . . . . . . . . . . . . . . . .13
© 2011 Taco Electronic Solutions, Inc. 1
iWorx® HPU2

HPU2

The HPU2 heat pump controller is a stand-alone microprocessor-based controller for liquid source heat pump units. The application includes liquid source heat pump units with two-stage compressor, reversing valve and fan.

Overview

A digital input is provided to monitor equipment status. A two-wire serial interface is provided for the thermostat. The HPU2 incorporates digital outputs in the form of triacs for fan start/stop, two compressor stages, and a reversing valve.
The controller is based on LONWORKS® networking technology. The controller can be networked to a higher-level control system for monitoring and control applications.

Features

• Two stage compressor heating/cooling control
• Reversing valve control
• Local backup schedule
• Individual temperature setpoints for occupied/unoccupied heat and cool
•LONWORKS interface to building automation systems
• Equipment status input for additional safety interlocks
• Thermostat with space temperature, setpoint adjust, fan override, occupancy override
• Fan control energized on call for heating or cooling
• Automatic heat/cool changeover
• Global unit enable for main plant synchronization
• Remote sensor capabilities
• Automatic configuration with the LCI
• Real Time Clock
• Alarm/Event reporting

PURPOSE OF THIS GUIDE

The iWorx® HPU2 Installation Guide provides installation information for the HPU2 Controller.
The reader should understand basic HVAC concepts, intelligent environmental control automation, and basic LON- WORKS networking and communications. This application manual is written for:
• Users who engineer control logic
• Users who set up hardware configuration
• Users who change hardware or control logic
• Technicians and field engineers

REPRESENTATIONS AND WARRANTIES

This Document is subject to change from time to time at the sole discretion of Taco Electronic Solutions, Inc. All updates to the Document are available at www.taco-hvac.com. When installing this product, it is the reader’s responsi­bility to ensure that the latest version of the Document is being used.
iWorx® products shall only be used for the applications identified in the product specifications and for no other pur­poses. For example, iWorx® products are not intended for use to support fire suppression systems, life support sys­tems, critical care applications, commercial aviation, nuclear facilities or any other applications where product failure could lead to injury to person, loss of life, or catastrophic property damage and should not be used for such purposes.
2 502-025, Effective: April 12, 2011
© 2011 Taco Electronic Solutions, Inc.
iWorx® HPU2
Taco Electronic Solutions, Inc. will not be responsible for any product or part not installed or operated in conformity with the Document and instructions or which has been subject to accident, disaster, neglect, misuse, misapplication, inade­quate operating environment, repair, attempted repair, modification or alteration, or other abuse. For further informa­tion, please refer to the last page of this Document for the company’s Limited Warranty Statement, which is also issued with the product or available at www.taco-hvac.com.

APPLICABLE DOCUMENTATION

See the table below for additional documentation that may be applicable to this controller.
Description Audience Purpose
iWorx® HPU2 Application Guide, Document No. 505-025
iWorx® LCI2 Application Guide, Doc­ument No. 505-002
iWorx® LHP2 Application Guide, Doc­ument No.505-024
http://iWorxWizard.taco-hvac.com – Application Engineers
Additional Documentation
– Application Engineers – Installers – Service Personnel – Start-up Technicians – End user
– Application Engineers – Installers – Service Personnel – Start-up Technicians – End user
– Application Engineers – Installers – Service Personnel – Start-up Technicians – End user
– Wholesalers – Contractors
LonWorks FTT-10A Free Topology Transceiver User’s Guide, published by Echelon Corpo­ration. It provides specifications and user instructions for the FTT-10A Free Topology Trans­ceiver. See also: www.echelon.com/support/documentation/manuals/transceivers.
Provides complete instructions for setting up and using the iWorx® HPU2 controller.
Provides instructions for setting up and using the iWorx® Local Control Interface.
These controllers may operate in conjunction with the HPU2. Application manuals provide specific application information about these con­trollers, including sequence of operation and configuration information.
An on-line configuration and submittal package generator based on user input. Automatically generates bill of materials, sequence of opera­tions, flow diagrams, wiring diagrams, points and specifications.

INSTALLATION INSTRUCTIONS

Precautions

General

This symbol is intended to alert the user to the presence of important installation and maintenance (servic­ing) instructions in the literature accompanying the equipment.
WARNING: Electrical shock hazard. Disconnect ALL power sources when installing or servicing this equipment to prevent electrical shock or equipment damage.
Make all wiring connections in accordance with these instructions and in accordance with pertinent national and local electrical codes. Use only copper conductors.
502-025, Effective: April 12, 2011 3 © 2011 Taco Electronic Solutions, Inc.
iWorx® HPU2

Static Electricity

Static charges produce voltages that can damage this equipment. Follow these static electricity precautions when han­dling this equipment.
• Work in a static free area.
• Touch a known, securely grounded object to discharge any charge you may have accumulated.
• Use a wrist strap when handling printed circuit boards. The strap must be secured to earth ground.

Location

Avoid locations where corrosive fumes, excessive moisture, vibration or explosive vapors are present.
Avoid electrical noise interference. Do not install near large contactors, electrical machinery, or welding equipment.
This equipment is suitable for indoor use only. Preferably, or as required by National Electrical Code, the unit is intended to be installed within an electrical control enclosure. Operate where ambient temperatures do not exceed 140 °F (60 °C) or fall below 32 °F (0 °C) and relative humidity does not exceed 90%, non-condensing.

FCC Compliance

This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference. This equip­ment can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a par­ticular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and the receiver.
• Connect the equipment to a power source different from that to which the receiver is connected.
• Consult the equipment supplier or an experienced radio/TV technician for help.
You are cautioned that any changes or modifications to this equipment not expressly approved in these instructions could void your authority to operate this equipment in the United States.

BEFORE INSTALLING

About this Document

The instructions in this manual are for the HPU2 module which supports a liquid source heat pump.

Inspecting the Equipment

Inspect the shipping carton for damage. If damaged, notify the carrier immediately. Inspect the equipment for damage. Return damaged equipment to the supplier.

What is Not Included with this Equipment

• A power source for the equipment electronics and peripheral devices.
• Tools necessary to install, troubleshoot and service the equipment.
• The screws or DIN rail needed to mount the device.
4 502-025, Effective: April 12, 2011
© 2011 Taco Electronic Solutions, Inc.
iWorx® HPU2
• Peripheral devices, such as sensors, actuators, etc.
• Cabling, cabling raceway, and fittings necessary to connect this equipment to the power source, FTT-10A network and peripheral devices.

Equipment Location

Abide by all warnings regarding equipment location provided earlier in this document.
Optimally, the equipment should be installed within a secure enclosure.
If the equipment is to be installed outdoors, it must be contained within a protective enclosure. The enclosure must maintain internal temperature and humidity within the ranges specified for this equipment.
The equipment must be installed within 500 feet of all input peripherals (smoke detectors, sensors, etc.) that will be connected to the equipment.

Selecting a Power Source

This equipment requires a UL recognized Class 2 external power source (not supplied) to operate. The controller power input requires a voltage of 24 Volts AC.
To calculate power source current requirements, add the power consumption of all peripheral devices to that of the controller.
The controller and sensor power supplies can use the same power source. If both are using the same power source, the loads must have EMF protection. This protection can be integral to the load, or installed in the 24 VAC wiring across the load’s coil.
To provide necessary RFI and transient protection, the controller’s ground (GND) pin (T40) must be connected to earth ground or the earth ground of the packaged unit’s enclosure ground. Failure to properly ground the controller may cause it to exceed FCC limits. Excessive noise could also produce inaccurate sensor data. The power source must be capable of operating with this connection to ground.

INSTALLATION

Warning: Electrical shock hazard. To prevent electrical shock or equipment damage, disconnect ALL
power sources to controllers and loads before installing or servicing this equipment or modifying any wir­ing.

Mounting the Device

1.Select a mounting location. Enclosure mounting is recommended.
2.Hold the controller on the panel you wish to mount it on. With a marker or pencil mark the mounting locations on
the panel.
3.Using a small drill bit pre-drill the mounting holes.
4.Using two #6 pan head screws, mount the controller to the panel.
5.Wire the controller (See Routing Cabling to the Device).
502-025, Effective: April 12, 2011 5 © 2011 Taco Electronic Solutions, Inc.