Electronic sensing of room temperatur e at wall locations.
SPECIFICATIONS
Sens ing Ele m ent: Temperature sensitive Balco resistance.
TS-8101 Series, 1000 ohms ±0.1% at 70°F (21°C);
changes 2.2 ohms per 1°F (0.5°C at 70°F (21°C).
TS-811 Series, 1000 ohms when control dial is set to
sensed temperature.
Control Dial Range: See Table 1.
Environment:
Ambient Temperature Limi ts,
Shipping and Storage -40 to 160°F (-40 to 71°C).
Operating 40 to 140°F (4 to 60°C).
Humidity, 5 to 95% RH, non-condensing.
Locations, NEMA Type 1 indoor only.
Connections: Coded screw terminal s.
Cover: Beige plastic.
Mounting: Wall.
Dimensions: 4-3/8" high x 2-3/4" wide x 1- 5/8" deep
(111 mm x 70 mm x 43 mm).
STANDARD
TS-8111 °F
TS-8111-116 °C
TS-8111-770 °F only
TS-8101, TS-8101-770
TS-8111, TS-8111-116
TS-8111-770
Electronic Room Temperature Sensors
General Instructions
ACCESSORIES
AT-61 Series Brushed bronze cover pla tes
AT-70 Series Brushed bronz e cover pla tes (TS-8 1XX-770)
AT-82 Series Digital thermometer cover kit
AT-82-770 Digital thermometer cover kit (TS-81XX-770)
AT-101 Lock cover kit
AT-104 Dial stop pins
AT-504 Plaster hole cove r kit (small)
AT-505 Surface mounting base
AT-546 Auxiliary moun ting plat e
AT-602 Selector switch sub-base DP4T
AT-1103 Wire guard
AT-1104 Cast aluminum guard
AT-1105 Plastic guard
AT-1155 Plastic guard
AT-1165 Plastic guard
PKG-1093 Digital therm om e ter batte r y repla c emen t kit
OPTIONS (TS-8111 & TS-8111-116 only)
(for quantities of 24 or more of each part number)
Add “dash-number” (-XXX) suffix to base part no. for desired option.
Inspect the car ton for damage. If damaged, notify the
appropriate carrier immediately. If undamaged, open the
carton and inspec t the device for obvious damag e. Ret urn
damaged products.
Required Installation Items
• Wiring diagrams
• Tools (not provided):
DVM (digital volt-ohm meter)
Appropriate screwdriver for mounting screws and termi-
nal connections
• Appropriate accessories
• Mounting screws, two (2) provided for securing to a 2 x 4
conduit box
INSTALLATION
Caution:
• Installer must be a qualified, experi enced technician.
• Make all connections in accordance with the wiring
diagram, and in accordance with national and local
electrical codes. Use copper conductors only.
• Do not exceed ratin gs of t he de vice.
Figure-3 TS-8101 Series Mounti ng (Cover Removed) and
Part Identifi cation.
Mounting
LOCATION
Locate the sensor on a wall where it will be exposed to
unrestricted air circulati on, at a minimum of 15 ft ./min., which
represents the average temperature of the sensed space.
Normally, the se nsor is lo cated 5- 1/2 to 6- 1/2 f t. (1. 7 to 2. 0 m)
from floor level.
Caution:
cold, such as lamps, motors, sunlight or concealed ducts or
pipes. Avoid location where excessive vibration, moistu re,
corrosive f um es or vapors are present. NEMA Type 1 covers
are intended for indoor use primarily to provide a degree of
protection against contact with the enclosed equipment.
Do not locate the sensor n ear sources of heat or
Figure-4 TS-8111 Series Mounti ng (Cover Removed) and
Part Identifi cation.
Wiring
Two conductor twisted pai r wires (six turns per f oot), Class I I,
low volta ge, ar e suita ble f or t he sensor leads ex cept a s sta ted
below.
Caution:
to install the sen sor lead in the same conduit with power
wiring, or when it is known that high RFI/EMI generating
devices are near. System ground the shield at the controller
only on the COM (-) terminal or Blu e (-) lead. Do not use an
earth ground.
Do not use inside of the cover as a junction box for other
contro l circuits.
Restrict element lead to shortest length practical (see
Table 2).
Figure-5 Wiring for TS-8111 Series with Remote Sensor.
ADJUSTMENTS
Turn the control dial knob to required setting on TS-8111
adjustable mode ls. No adjustments are possible on TS-8101.
CHECKOUT
Measure the resistance between terminals 7 and 8 (see
Figure 1).
TS-8101 Series: 100 ohms ±0.1% at 70°F (21°C); changes
2.2 ohms per 1°F (0.5°C) at 70°F (21°C).
TS-8111 Series (see Figure 5 ): 1000 ohms when control dial
is set to sensed tempe rature.
LIMIT CONTROL DIAL RANGE
Dial Sto p Pi n I nser ti on - Included wi th Mo unting
Plate
See Figure 7.
1. Remove sensor cover.
2. Secure the control dial with hand so that the dial will not
rotate.
3. Place a dial stop pin in the j aws of a needl e nose pliers.
4. Insert the dial stop pin in the appropriate hole on either (or
both) side(s) of the control dial to restri ct di al rotation.
CONCEALED CONTROL DIAL
ADJUSTMENT
Knurled Dial Removal
See Figure 6.
1. Remove sensor cover.
2. Secure the control dial with hand so that the dial will not
rotate.
3. Place needle nose pliers at knu rled rin g of the control dial
at the points where the knurled ring is attache d to th e
control dial.
4. Twist the pliers at each knurled ring at tachment point until
the entire knurled ring of the control dial i s removed.
Figure-7 Dial Stop Pin Insertion.
Cover Insert Installation (See Figure 8)
1. Select appropriate cover insert.
Note:
If blank insert i s used, The knurled ring must be
removed from the setpoint dial. See Knurled Dial Removal
above. Also, remove dial wi ndow by sliding and/or pressi ng
window from front of cover.
2. Remove prot ective ba cking and pr otectiv e skin on f ace of
cover insert.
3. Press insert uniformly on the thermostat with company
logo in lower left-hand corner.
Regular maintenance of the total system is needed to assure
sustained optim um performance. Sensors should be periodically
inspected for dirt or blockage of air over the elements.
FIELD REPAIR
These sensors ar e not fi eld repai rable. Replace a defecti ve sensor
with a functional unit.
Copyright 2008, TAC
All brand names, trademarks and registered
trademarks are the property of their respective
owners. Information contained within this
document is subject to change without notice.
F-22633-5